Transformer Protection
Scott R. Secrest, PE
Director of Engineering
2. Factors Affecting Transformer Protection
a. Cost of Repair
b. Cost of Down Time
Cost of Down Time
c. Affects on the Rest of the System
d. Potential to Damage Adjacent Equipment
e Length of Time to Repair or Replace
e. Length of Time to Repair or Replace
4. Applicable Standards
a C57.12.00
a. C57 12 00 – IEEE Standard General Requirements for Liquid‐Immersed
IEEE Standard General Requirements for Liquid‐Immersed
Distribution, Power, and Regulating Transformers
b. C57.12.80 – IEEE Standard Terminology for Power and Distribution
Transformers
c. C57.109 ‐ IEEE Guide for Liquid‐Immersed Transformer Through‐Fault‐
Current Duration
d.
d C37 91 IEEE Guide for Protecting Power Transformers
C37.91 – IEEE Guide for Protecting Power Transformers
e. C62.22 – IEEE Guide for the Application of Metal‐Oxide Surge Arresters for
Alternating‐Current Systems
Types of Over Voltages
f l
1. Temporary
a. Power Frequency
b. Relatively Long Duration (seconds to hours)
c. Attributable to Ground Faults, Load Rejection, Low
, j ,
Frequency Resonance
2
2. Transient
a. Fast Rate of Rise
b. Short Duration (microseconds to milliseconds)
c Attributable to Lightning, Switching, Flashover and
c. Attributable to Lightning Switching Flashover and
Restrike Phenomena
Temporary Overvoltage Levels and Duration
Equipment BIL
System Grounding
115kV
66.4kV
3
13.8kV
7.97 kV
3
Inrush Current
12x Rated Current for 0.1 sec
Transformer Damage
g Curve
Calculated per C57.109
3750000
520 A
3 * 4160
T
Transformer
f Inrush
I h Current:
C t
i 2t 1250
12 0
i 2t K
2
K 2
ZT
13800V If
4160V
0.58*If*Vs/Vp
High Speed,
Speed Sensitive Protection for Internal Faults
Looks at current flowing into and out of zone
Unequal currents means fault in the zone
300-5A 2500-5A
33/44/55 MVA
115kV – 13.8Y/7.97kV
300-5A 2500-5A
33/44/55 MVA
115kV – 13.8Y/7.97kV
55000000 55000000
IP 276.1A IS 2301A
115000 * 3 13800 * 3
For Wye Connected CT’s
5 5
I PRel 276.1A * 4.61A I SRel 2301A * 4.60 A
300 2500
For Delta Connected CT’s
5
I SRel 2301A * * 3 7.97 A
2500
LTC Controls
LTC Position
LTC Malfunction
Fan/Pump Controls
Fan/Pump Operating Stages
Fan/Pump Malfunction
On-Line
On Line Acoustical and Partial Discharge Monitoring