Professional Documents
Culture Documents
Coordination and Protection of Busbar Distribution PDF
Coordination and Protection of Busbar Distribution PDF
Coordination
and protection
of busbar
distribution
Low voltage
expert guides n° 1
YFJYVIIVGIT
6FKQHLGHU(OHFWULF )55(9$
Content
Busbar distribution
Busbar distribution, with its highly flexible design, fully covers these requirements.
3. Dependability
Dependable electrical distribution is optimized as a means of guaranteeing:
b safety of persons and equipment
b continuity of service (choice of grounding system, implementation of
discrimination techniques, breaking not required when making changes to the
installation....)
b reliability (reliable switchgear, factory-mounted subassemblies...)
b easy maintenance (simple, rapid modifications).
Dependability also guarantees an economic operating solution.
Busbar distribution
TØ transmission
DB125336
MSB
workwhop 1 Isc 30 to 80 kA
T1 transmission supply workshop 2 supply
with a small 1000 to 5000 A
quantity of
tap points
hall 2 hall 3 hall 1
supply supply supply
Isc 20 to 50 kA Isc 20 to 70 kA
distribution
with a large y 400 A i 800 A
quantity of tap
points bay 1 bay 2
supply supply
100 to 250 A
Isc 10 to 40 kA
Isc 10 to
automation socket 15 kA automation
enclosure enclosure lighting enclosure
y 25 A y 160 A
y 5 to y 40/ (40 A) 15 to 25 kA
y 40 A 10 kA 63 A y 10 to 16 kA y 400 A
y 400 A
20 to 70 kA
M M
M
NB. right next to the machine or use
built into the machine
Busbar distribution
Level A
DB125337
Transmission and
distribution with a small
quantity of tap points. 400 A
Note : does not concern
“medium-sized and small sites“.
15 kA
10 to 15 kA
warehouse storage
y 5 kA
< 63 A
10 to 15 kA
Level C 25 to 40 A
ID63 s
Energy utilisation. 60 A
10 kA
30 mA
PC
homogeneous load,
offices M
Busbar distribution
1.2. Functions
BBT in transmission and distribution with
a small quantity of tap points
Level A: transmission and distribution with a
b High current ratings from 1000 A to small quantity of tap points
5000 A
b High short-circuit withstand up to Requirements
150 kA This level corresponds to Transformer/Main Switchboard (MSB) supply and main
b Technological continuity distribution downstream from the Main Switchboard (MSB).
b Flexibility The requirements of this level as far as performance criteria are concerned (see p. 3)
are summarized in the table below:
BBT in Distribution with a large quantity
of tap points: Performance criteria Requirement Comments
b numerous tap off sockets Upgradeability bb modifications at this level of the
b box positioning flexibility installation although rare are
important; new layouts do not
b safe, easy handling affect main distribution
Final distribution: Simplicity bbb Power is available at all points of
b on-load opening (emergency breaking) the installation as from the
design stage.
b local disconnection. Implementation simplified by the
factory-built BBT concept.
Dependability
b continuity of service bbb Distribution is entirely placed
downstream. Maintenance is
performed with power on.
Requirements
Two types of loads must be supplied downstream from the distribution BBTs:
b workshops and large machines (automation cubicle). In this case the short-circuit
and current levels may still be high (20 to 70 kA respectively and up to 800 A)
(see large sites on page 4).
b bays and small machines (switchboard, automation enclosure, lighting circuit...).
Short-circuit and power levels are lower, 10 to 40 kA respectively and up to 400 A.
Busbar distribution
Requirements
Downstream final distribution is often linked to the load. The performance criteria
requirements are:
Busbar distribution
DB125338
DB125339
BBT BBT
connecting
cable connecting
cable
industrial
control final
circuit breaker distribution
circuit breaker
Busbar distribution
Construction arrangements
Busbar trunkings must be designed as type tested LV switchgear assemblies (TTA).
According to the manufacturer’s instructions, BBTs are designed to withstand
mechanical loads.
For safety reasons, an BBT equipped with tap off points must be designed
in such a way as to prevent incorrect connection of the tap off parts.
If three-phase ac is used, phase order must be constant throughout the BBT.
Temperature rise limits are defined on the enclosures and connection terminals.
Test specifications
Type tests are designed to check compliance with the specifications laid down for a
given BBT type.
Type tests are carried out on a copy of an BBT or on an BBT type produced using the
same or similar drawings.
Type tests consist of:
b checking temperature rise limits, dielectric properties, short-circuit withstand,
electrical continuity of the protection circuit, clearances and creepage distances,
mechanical operation, degree of protection, resistance, reactance and impedance,
and sturdiness of the construction.
The standard describes all the conditions and provisions of the tests laid down and, if
necessary, the results to be obtained.
For extension purposes, busbar trunking is normally protected for its rated current
In I lnc (or for their permissible current lz if the temperature factor f1 is applied).
Iz = 1.1 In 1.45 Iz
Iz = Inc if fz = 1 In order to take account of busbar trunking thermal overload protection, the various
Fuse. protection switchgear technologies and the maximum opening currents for
protection devices in overload conditions must be considered.
DB125341
In I
Iz = In 1.45 Iz
Circuit breaker.
Busbar distribution
10
Busbar distribution
Applications
■ Two cases must be considered :
v directely protected busbar trunking
circuit breaker lcu u assumed Isc at point A
BBT peak l u asymmetrical assumed or limited Isc at point A
BBT thermal withstand in lcw u thermal stress passing through the BBT
This coordination depends on the type of circuit breaker protecting the busbar
I1 trunking.
DB125344
11
Busbar distribution
250
Isc: assumed symmetrical short-circuit Assymetric factor
200 kA (rms value) k
4.5 y I y 6 1.5
150 6 < I y 10 1.7
105 kA 10 < I y 20 2.0
100 20 < I y 50 2.1
50 50 < I 2.2
rms Isc
0 For example: for a circuit with a assumed short-circuit current of 50 kA rms, the first
4,5 6 10 20 50 100 peak reaches 105 kA (50 kA x 2.1): see figure opposite.
Transcient and steady states of a short-term short-circuit. b The short-term short-circuit current, lcw, of the BBT, must be greater than the
current flowing through the installation for the duration of the short-circuit Isc
(duration T - total breaking time - including the time delay if any -).
For example: a KTA16 BBT has an lcw characteristic of 60 kA for T = 1 second, i.e.
a thermal stress withstand expressed in A2s equal to 3.6x109 A2s.
If one of these relationships is not verified, a suitable higher rating must be chosen
for the BBT.
non-limiting Isc
peak current
Ipeak
maximum current
permissible to the
busbar trunking IL current limitation
curve
peak current
limited in the
busbar trunking
Icc
assumed short-circuit
current
thermal stress
permissible to the
busbar
thermal stress
thermal stress limitation curve
limited in the
busbar trunking
Icc
assumed short-circuit
current
If either of these conditions is not met, oversizing of the BBT will be required.
12
Busbar distribution
DB125343
circuit breaker
circuit breaker
Isc at point A
A 'A
cable
BBT
BBT
b The busbar trunking short-circuit protection level can be either total or partial:
v total protection: the busbar trunking is protected up to the ultimate breaking
capacity of the circuit breaker
v partial protection: the busbar trunking is protected up to a high short-circuit
current level (e.g. 55 kA) but less than circuit breaker ultimate breaking capacity (lcu)
(e.g. lcu = 70 kA).
DB125349
BBT 1 BBT 1
partial partial
protection protection
BBT 2 BBT 2
circuit breaker
curve
limiting
circuit breaker
curve
I (12 kA) Icu (25 kA) Isc I (25 kA) Icu Isc
BBT2 BBT2 (150 kA)
protection protection
limit limit
13
Busbar distribution
14
The Schneider Electic busbar distribution System
15
The Schneider Electic busbar distribution System
In large sites
Buildings in excess of 5 000 m²
DB125174
DB125364
KTA20
push
to
trip
push
to
trip
KSA40
Level A
KTA20
.1
.2
.4
push
to
trip
KSA16
Level B
push
to
trip
KBB
.1
.2
.4
Level C
16
The Schneider Electic busbar distribution System
DB125365
push
to
trip
KSA16
push
to
trip
Level B
KNA63
KBA
T
OFF
Level C
Example:of a supermarket.
17
The Schneider Electic busbar distribution System
The diagram opposite shows a T1 transmission BBT and a KTA16 distribution BBT
(1600 A) protected by a Masterpact M16 circuit-breaker with a 0.5 s time delay.
b At point A, at the supply end of the KTA16 distribution BBT, the Isc is 55 kA.
The following table lists the various constraints and characteristics of the circuit
breaker and busbar trunking.
Network characteristics at point A
Isc ������������
= 55 kA in A
Circuit breaker characteristics / short-circuit constraints
Icu = 65 kA u 55 kA in A
BTT characteristics / short-circuit constraints
Peak I = 130 kA Icw = 66 kA for 1s A 2s
BBT withstand Permissible short-term Instantaneous
at peak current current thermal withstand
k kA rms x f(T) kA2s
Non-limiting circuit breaker 130 kA u 55 kA x 2,2 66 kA u 55 kA
fot 1s
Naturally verified characteristics.
DB125194
DB125350
Limiting capacity
The circuit breakers in the Compact NSX range are limiting circuit breakers with a
high limiting capacity.
A circuit breaker’s limiting capacity expresses its ability only to let a limited current IL
lower than the assumed Isc asymmetrical peak short-circuit current, through on a
short-circuit.
The consequence is a considerable reduction in electrodynamic and thermal
stresses in the installation requiring protection.
18
The Schneider Electic busbar distribution System
This fault current limitation means that BBT protection level is extremely high.
NSX400N With Compact NSX circuit breakers, a 10% limitation (IL/asymmetrical Isc) reduces
to less than 1% the fault current flowing through the installation.
The diagram opposite shows protection of the KSA40 distribution busbar trunking by
an NSX400N limiting circuit breaker. In this diagram:
b the Isc is 45 kA at point A.
assumed Isc A study of the various limitation curves shows that:
at "A" 45 kA b in B, the limited Isc is only 26 kA (instead of nearly 84 kA without limitation)
b the energy limited in A2s is far lower than BBT withstand.
kA peak
DB125352
assumed Isc KSA40
at "B" 40 kA 48 kÂ
Isc
40 kA
a. current limitation
A2s
DB125353
354 x 106
1.6 x 106
Isc
40 kA
b. energy limitation
The following table lists the various constraints and characteristics of the circuit
breaker and BBT.
Network characteristics
Isc ������������������
= 45 kA at point A Isc ������������������
= 40 kA at point B
Circuit breaker characteristics / Short-circuit constraints
Icu = 45 kA u 45 kA at point A
BBT characteristics / Short-circuit constraints (at point B)
Peak I = 48 kA Icw = 66 kA for Ts "A2s" = 354 x 106 A2s
BBT withstand Permissible short-term Instantaneous
at peak current current thermical withstand
k kA rms x f(T) kA2s
Limiting circuit breaker 48 k u IL = 28 k 354 x 106 u 1,6 x 106 A2s
Unapplicable characteristics.
This table shows that the limitation performance of the Compact NSX is vital to
reduce the stresses to which the busbar trunkings are subjected and in particular the
thermal stress.
19
The Schneider Electic busbar distribution System
The exceptional limitation of the peak current means that monitoring of the BBT
thermal stress criterion can be “ignored” (limited I2t << BBT withstand I2t).
The following limitation curves immediately show the coordination characteristics.
DB125354
DB125355
106 x A2s
KSA63 (630 A)
1100
Ipeak
k KSA40 (400 A)
354
KSA25 (250 A)
KSA63
67.5 100
NSX630
49.2
KSA40 NSX400 KSA16 (160 A)
KSA25 20.2
28 NSX250 KSA10 (100 A)
NSX160 6.8
22 N H L NSX630
KSA16 NSX100
L NSX400
H N H L
13.6 1
KSA10 N NSX250
0.55 NSX160
Isc N H L NSX100
25 70100 150 Isc
Limited î and Canalis. Limited A s and Canalis.
2
These diagrams show that protection is provided in excess of the maximum Isc
encountered on installations.
20
The Schneider Electic busbar distribution System
Isc = 35 kA Isc = 45 kA
Peak I = 22 k IL = 19 k IL = 20 kÂ
A2s = 20,2 106 A2s = 0,52 106 A2s = 0,6 106
The following diagrams optimize all the functions required for all industrial and
commercial building applications.
Protection
b switchboard overcurrent protection is provided by the protection circuit breaker
(DD) installed in the tap off box.
b feeder protection is provided by the circuit-breakers (DCI) installed at each feeder.
Continuity of service is optimum at feeder level:
b thanks to enhanced total discrimination between the protection devices
b thanks to easy access and resetting of the protection devices.
Maintenance
The switchboard incoming switch (IS) guarantees disconnection and thus safety for
maintenance, servicing and upgrading of the installation.
21
The Schneider Electic busbar distribution System
On-load opening
This function is performed by a switch. The incoming switch places the installation
out of operation should a problem arise, either by manual control or automatically
using an emergency punch button. This safety function requires a high degree of
reliability should a fault occur on the electrical installation.
DB125356
DB125357
Canalis Canalis
connecting
cable
connecting
cable
isolating isolating
switch IS switch
The Schneider Electric Canalis tap off boxes satisfy operators’ needs in terms of:
b installation upgradeability without production downtimes
b continuity of service
b safety.
Tap off box. The tap off boxes:
b can be connected and disconnected with power on without risk to the operator
b are designed for installation at one-meter intervals on the distribution BBTs.
22
The Schneider Electic busbar distribution System
Final distribution
DB125207
DB125216
The protection switchgear optimizes switchboard functions.
b Coordination of upstream protection devices is provided and guaranteed by
Schneider Electric:
v for distribution applications between Masterpact, Compact C, Compact NSX
circuit breakers and Multi 9 circuit breakers.
v for industrial control applications between circuit breakers and control
(motor circuit breaker, Integral,...).
The coordination tables are available in the relevant product catalogs.
The Schneider Electric switches comply with the IEC 60947-3 standard, and are
designed to ensure AC23 on-load breaking and disconnection. Their protection is
guaranteed by coordination with the upstream circuit breakers.
Prisma enclosure.
Automation enclosure.
DB125217
Switch.
23
The Schneider Electic busbar distribution System
Summarizing table
Level A Level B Level C
Transmission and Distribution with Final distribution
distribution with a small a large quantity
Criteria Relevant functions quantity of tap points of tap points
Upgradeability One tap off connection every meter BBT
24
YFJYVIIVGIT
6FKQHLGHU(OHFWULF )55(9$
2009 - Schneider Electric - ��������������������
© ���������������������������� All rights reserved.
Schneider Electric Industries SAS As standards, specifications and designs change from time to time, please ask for confirmation
35, rue Joseph Monier of the information given in this publication.
CS 30323
F- 92506 Rueil Malmaison Cedex This document has been printed on ecological paper
DBTP118EN 06-2009