Protecting High-Voltage Motors Against Switching Overvoltages
Protecting High-Voltage Motors Against Switching Overvoltages
OVERVOLTAGES
I. INTRODUCTION
II. TYPES OF OVERVOLTAGES ASSOCIATED WITH
In a desalinization plant equipped with 32 HV motors (11 SWITCHING
kV), several severe stator failures occurred. At least 3 motors
have developed stator failures during commissioning tests, The subject of switching surge overvoltages associated with
then one failed during operation in spite of the installation of vacuum circuit breakers has been discussed in many technical
MOA (metal-oxide arrester) surge arresters. papers [1]-[3]. Therefore the aim of this chapter is to clarify
All of these motors were switched with vacuum circuit only the involved phenomena leading to the most severe
breakers, and thus the first assumption was that the stator transients and to describe them in some detail.
faults were a result of exposure to steep fronted switching
surges. These surges cause severe stress on the stator A. Current Chopping (opening)
windings insulation because of the non-uniform distribution of
the voltage across the windings. Both opening and closing Current chopping (I0) refers to the premature suppression of
operations could generate switching overvoltages with large the power frequency current before normal current-zero in the
amplitude and high frequencies. If the switching overvoltage vacuum circuit breaker. Depending on the load 's inductance
amplitude exceeds the basic insulation level (BIL) of the motor, (Lb), a magnetic energy remains trapped in the load circuit.
overvoltage protection must be installed. The maximum voltage at the load level can be estimated
The purpose of this paper is to demonstrate, in the case of with the approximation that the trapped magnetic energy (1/2
this desalinization plant, the necessity of complementary LbI0²) will be converted into electrical energy in the parasitic
protection against overvoltages by adding C-R surge capacitance (Cb). So the estimation of the maximum chopping
1 1 1 2 Lb
CbUˆm = LbI 0 + CbU pf ⇒ Uˆm = U pf + I 0
2 2 2
2 2 2 Cb (1)
where
Upf the power frequency voltage at interruption.
For vacuum circuit breakers, the chopping current is Fig. 1. Circuit demonstrating how the high frequency current
determined mostly by the contact material and is typically 2 to resulting from a reignition in one phase couples into the other
10 A. Data published in [2] indicates that the maximum phases to produce the conditions for virtual current chopping.
overvoltage created by current chopping never exceeds the
IEEE motor impulse voltage withstand recommendation [5].
Compared with normal current chopping, the virtual current
Therefore, in general, overvoltages at current chopping do not
chopping can be much higher and also the overvoltages
need surge protection (see chapter V.A).
between phases B and C can be up to twice the overvoltage
from phase to ground on these phases.
B. Voltage Escalation (opening)
B. Cable Data
i(t) MODELS
Open/
close u2(t)
u1(t) signal
125.0 20
62.5
10
0.0
-62.5 0
-125.0
-10
-187.5
-250.0
-20
0 4 8 12 16 [m s ] 20
(f ile RB12b.pl4; x-var t) c:CABLEA-W6BBCA c:CA BLEB-W6BBCB c:CABLEC-W6BBCC
4
-30
[A] 0 4 8 12 16 [m s] 20
2
(file RB23.pl4; x-var t) v:MOTORA v:MOTORB v:MOTORC
-2
-4
Vpeak
-6
-8
The phase to neutral voltage at motor terminal is given by
-10
-12
Fig. 9, the maximum value is about 24 kV peak.
7.60 7.69 7.78 7.87 7.96 [ms] 8.05
(file RB12b.pl4; x-var t) c:CABLEA-W6BBCA c:CABLEB-W6BBCB c:CABLEC-W6BBCC 30
Fig. 7. Current in the motor circuit breaker – current [kV]
chopping = 8 Amps 20
B. Voltage Escalation (opening) Fig. 9. Voltage across the motor winding (phase to neutral
voltage): 24k Vpeak
In these simulations, we have modelled current chopping
with reignition : the switch model simulates the multiple re- So, if these overvoltages are compared only with magnitude
ignitions of the arc in the vacuum circuit breaker. criteria, it can be said that the motor protection is correct. But if
a graphical check for time rise is made taking into account the
1) Without Any MOA Surge Arrester: When there is no envelope defined by IEC 60 034-15, the conclusion can be
MOA surge arrester connected, the overvoltage due to different. Fig. 10 gives the two latest re-ignitions for the single
multiple re-ignitions is well over the withstand level of phase voltage and Fig. 11 shows the comparison between the
the motor insulation. simulated overvoltage and the envelope defined by IEC 60
2) With MOA Surge Arrester At Load Terminal Of The 034-15.
Vacuum Circuit Breaker: When there is only one MOA
surge arrester connected at the load terminal of the
vacuum circuit breaker, the overvoltage at the arrester
0
0
-10 -5
-20 -10
-30 -15
6.48 6.51 6.54 6.57 6.60 6.63 [ms] 6.66
(file RB23.pl4; x-var t) v:MOTORA v:MOTORB v:MOTORC -20
0 4 8 12 16 20
Fig. 10. Voltage at motor terminal (single phase voltage): (file RB25.pl4; x-var t) v:MOTORA-XX0308 v:MOTORB-XX0308 v:MOTORC-XX0308
[ms ]
Zoom on the two latest re-ignitions Fig. 13. Voltage across the motor winding (phase to neutral)
15k Vpeak with a frequency around 1kHz
VII. CONCLUSIONS
-20
Additional studies are carried out in order to provide an Caroline Vollet received her Electrical Engineering degree
application guide. This guide will give the necessary protection from the National Polytechnic Institute of Grenoble in 1988.
as a function of cable length, motor power and network She joined Merlin Gerin (now Schneider Electric) in 1989. She
configuration and exploitation. is currently working on electrical network analyses such as
stability, harmonic and overvoltage studies. She has been
VIII. REFERENCES personally involved in several instances of equipment failure or
malfunctioning in different kind of industrial plants.
Benoit de Metz Noblat received his Electrical Engineering
[1] J. F. Perkins, "Evaluation of switching overvoltages on degree from the Ecole Supérieure d'Electricité (France) in
medium voltage power systems," IEEE Trans. Power 1974. He worked first for Saint Gobain as electrical new
Apparatus and Systems, vol. PAS-101, pp. 1727-1734, projects & maintenance manager. He joined Merlin Gerin (now
June. 1982. Schneider Electric) in 1986. He is a member of the Electrical
[2] S. H. Telander, M. R. Wilhelm, K. B. Stump, "Surge Network competence group that studies electrical phenomena
limiters for vacuum circuit breakers," IEEE Trans. concerning the operation of networks and their interaction with
Industry Applications, vol. 24, pp. 554-559, July. 1988. devices and equipment.
[3] S. M. Wong, L. A. Snider, "Overvoltages and reignition
behavior of vacuum circuit breaker," in Proc. 2003