TECHNICAL DATA SHEET FOR CABLES:
B-ELECTRICAL DATA
L.V 50 – 80
M.V 80 - 100
Page 5 of 17
IEC STANDERD FOR CABLES.
Page 6 of 17
Page 7 of 17
Technical Data for Power Transformer
Page 8 of 17
ACCESSORIES:
Factory Test
Type: ser. No. :
Page 9 of 17
1-separate source (power frequency) voltage-withstand test:
Test result:
Object under test has withstood the separate source voltage-withstand test.
Test-result:
Object under test has withstood the separate source voltage-withstand test.
Resultants
Page 10 of 17
Time S 15 30 45 60
HV—LV M
Ohm
HV-- M
TANK Ohm
LV-- M
TANK Ohm
Curves:
M ohm
S
Insulating liquid:
Mineral oil – synthetic insulating liquid average break down voltage according to
(60/2.5) KV/ mm.
3 – induced over voltage withstand test
Page 11 of 17
120 * (50 / 100) = 60 Sec.
The test voltage developed between line terminals of the high-voltage
winding of uniformly-insulated windings in accordance with IEC is given
with 22 KV, provided that the voltage between the different parts of the
winding does not exceed twice the voltage, which appears when rated
voltage is applied to the line terminals.
In this test we measure the transformer ratio for single, three phase
transformers by Appling voltage on primary winding and measured it on
secondary winding (or you can reverse it)
Measured it by DIGITAL TRANSFORMER RATIO METER instrument.
Description
This instrument has four (two black & two red) clamps.
Screen to show the ratio and another information
Knob to adjustment the construct
We put (1 red xx) on the low tension phase that , want to measure it and
other (2 black xx) in the neutral if it is founded
And we put (red HH) cable in the phase , and so
Note this connection to reading positive
We take reading for each phase and for one phase take for each tap
We coordinate the value that , reading it by the standard value
Page 12 of 17
Calculation.
Tolerance.
Test result:
Object under test has the calculated voltage ratio. The deviation is within
tolerance in accordance IEC.
Page 13 of 17
MEASUREMENT PRESSES IN ACCORDANCE WITH IEC.
Description
This instrument have a two clamp , and screen to indicate the current rang
,the knob to adjust the range of resistance are measure it (20-200-2000-
micro ohm- 20-200-2000-m ohm)
we must adjust the current indicator to 100 %,
View the construct of screen
It must be the tape changer on no. 1 (i.e. over all winding are under
measure process )
The resistance is line to line.
The average oil temperature was 20 ºC that can be assumed the average
winding temperature, since the transformer was not loaded the last 24
hours.
Time for the measuring current to become steady 60 S.
u2 - v2
LV v2 - w2
w2 - u2
Page 14 of 17
• In this test we measured I(NO.L) , Pi for each phase
• Connection
• Connect the source to low tension winding on three winding and measure
the voltage, current, power by tow watt meter method
• Let the H.T terminals is open.
• You can reverse the connection (but it preferred the connection (1) because
the sours is more available in low tension)
• After you had connected you will increase the applied voltage to rated
value in tank and(.25% active part )
• After testing current you can connect the instruments and reading
(W1,W2,V1,V2,I1,I2) if you measured by tow wattmeter method ,(if another
method u can take W1,W2,W3, and so on )
This instrument have four channel, 600 v, 16A , and for one of them I can
measure voltage, current, power, and many function can I uses it.
No load test I V P
CH ( )
CH ( )
CH ( )
CH ( )
Potential transformer
ratio
Current transformer
ratio
Page 15 of 17
V (KV)
• Connection
This instrument has four channel, 600 v, 16v, and for one of them I can
measure voltage, current, power and many function.