RIYADH CABLES GROUP COMPANY

P.O. Box 26862, Riyadh 11496 Saudi Arabia


DIMENSIONAL DATA FOR
3x25mm² CU/PVC/PVC 1 kV

DESCRIPTION UNIT DETAILS


Reference Standard IEC 60502-1
Rated voltage of cable Uo/U kV 0.6/1
Number of cores (Ph) No. 3
Nominal conductor cross-sectional area (Ph) mm² 25
Shape of conductors (Ph) Flexible(Class 5)
Conductor material Copper
Number of strands (Ph) No. 178
Approximate diameter of conductor (Ph) mm 6.0
Insulation material PVC
Nominal thickness of PVC insulation(Ph) mm 1.2
Approximate diameter over insulation(Ph) mm 8.4
Approximate diameter over Laid up cores mm 18.2
Material of inner sheath PVC
Nominal thickness of PVC inner sheath mm 1.0
Approximate diameter over inner sheath mm 20.7
Material of outer sheath Extruded PVC-ST2
Nominal thickness of PVC outer sheath mm 1.8
Approximate overall diameter of cable mm 24
Approximate weight of complete cable kg/km 1170
Colour of insulation RED, YELLOW, BLUE
Colour of outer sheath BLACK
Ph: Phase
Printed by: Eng. EYAD Reviewed By: S.Eng. A.Darweesh Approved by: G.M. M.Al-Shmoury
17-Jul-2019

FORM# TE/A/F/07 Issue no.00 08.12.1998 Page 1 of 2


RIYADH CABLES GROUP COMPANY
P.O. Box 26862, Riyadh 11496 Saudi Arabia
CABLE'S PARAMETERS FOR
3x25mm² CU/PVC/PVC 1 kV

DESCRIPTION UNIT DETAILS


Rated voltage of cable Uo/U kV 0.6/1
Highest operating voltage Umax kV 1.2
Phase conductor DC resistance at 20°C Ω/km 0.7800
Phase conductor AC resistance at 70°C Ω/km 0.9337
3-phase inductance mH/km 0.255
3-phase reactance at 60 Hz Ω/km 0.096
3-phase impedance at 70°C Ω/km 0.939
3-phase capacitance µF/km 0.434
Minimum insulation resistance at 20°C MΩ.km 5.3
Minimum bending radius (during installation) mm 288
Maximum pulling tension through conductor kN 3.75
Max. permissible short circuit current through Phase
kA 2.88
Conductor for 1 second
Max. permissible continuous conductor temp. °C 70
Max. permissible short circuit conductor temp. °C 160
3-phase voltage drop factor V/A/km 1.394
Continuous current rating: (for Phase conductor)
Single circuit in ground: Amps 74
- Soil thermal resistivity 2 °Cm/W,
- Soil temperature 40 °C
- Direct burial at 700 mm depth
- Free air & shaded area at 55 °C ambient temp. Amps 56

Printed by: Eng. EYAD Reviewed By: S.Eng. A.Darweesh Approved by: G.M. M.Al-Shmoury
17-Jul-2019

FORM# TE/A/F/07 Issue no.00 08.12.1998 Page 2 of 2