You are on page 1of 2

No : E18-LOC-371

TECHNICAL Issue :2
Date : 18-09-2018
SPECIFICATION Pages : 17 of 18

CONSTRUCTION
Cable Type : PVC-FR
Voltage : 600/1000V
Design Standard : IEC 60502-1
Conductor Standard : IEC 60228, BSEN 60228
Flame Propagation : IEC 60332-3-22

CABLE DESCRIPTION:

1
2

Part Description No.


Conductor Cu Plain annealed stranded circular copper conductor, Class 2 1
Insulation PVC- Flame retardant polyvinyl chloride compound.
FR 2

CABLE MARKING:
DRAKA ELECTRIC CABLE 600/1000V PVC RFP_MM2 IEC60502-1, IEC 60332-3-22 YR-
Wording
YYYY
Min. 2 mm for size 6mm² and below
Height of text
Min. 3 mm for size 10mm² and above
Type of Marking Ink-jet
Length marking Sequential length marking at 1 metre interval printed on outermost surface

CORE IDENTIFICATION:
1-core : Green/Yellow

This information contained in this data sheet is subject to normal manufacturing and internal standard practice.The data and properties may be changed as
a result of our efforts to improve the quality of our products.
No : E18-LOC-371

TECHNICAL Issue :2
Date : 18-09-2018
SPECIFICATION Pages : 18 of 18

TECHNICAL DATA TABLE

PVC-FR 600/1000V

DIMENSIONAL DATA LV LV

Voltage Uo/U KV 0.6/1


Size Nominal mm2 1Cx25
Conductor Type (Phase) Non Compact
Conductor Diameter Approx mm 6.33
Insulation Thickness Min.Ave mm 1.2
Min.Spot mm 0.98
External diameter of cable Approx mm 8.8
Diameter Tolerance ±0.5 mm
Mass of cable Approx Kg/Km 273
Standard Length Nominal M 2000
Drum Size mm 800
Bending Radius Minimum mm 54
Pulling Tension
Eye on Conductor Maximum Kgf 175

ELECTRICAL DATA
DC Resistance at 20 ºC (Phase) Maximum Ω/km 0.727
AC Resistance at 90 ºC Maximum Ω/km 0.928
Reactance at 50 Hz Approx Ω/km 0.06
Capacitance Approx µF/km 1.363
Impedance Approx Ω/Km 0.93
Inductance Approx mH/km 0.192
Conductor Fault at 1s [Phase] kA 2.9
Current rating in Ground *) A 128
Current Rating in Air *) A 114
Voltage Drop mV/A/m 1.611
Insulation Resistance MΩ.km 5
Conductor Operating Temperature Maximum °C 90
AC Voltage Test for 5 minute KV 3.5

*) Air Temp.=30°C ,Ground Temp.= 30°C,Soil Thermal Resistivity =1.0K.m/W,Depth of Laying =500mm

This information contained in this data sheet is subject to normal manufacturing and internal standard practice.The data and properties may be changed as