OUTER SHEATH: FRLS-PVC

INSULATION: PVC
BINDER: NON-WOVEN TAPE
CONDUCTOR: FLEXIBLE COPPER

FIGURE: 1C 240 mm2 (NYYF-FRLS/YYF-FRLS) 0.6/1.0 (1.2)kV Cables


Note: This Drawing is not in Scale. This is for Reference Only.

GUARANTEED TECHNICAL PARTICULARS FOR


1.2kV 1C 240 mm² CU/PVC/FRLS-PVC CABLES
Sl. No. Description Particulars Unit Manufacturer’s Particulars
A.General Parameter
1 Name of the Manufacture and Country of Origin - Poly Cable Industries Limited, Bangladesh
2 Reference Standard - BS 6360, IEC 60228, IEC 60502–1
3 Rated Voltage: U0/U (Um) V 600/1000 (1200)
4 No. of Cores & Conductor Cross–Sectional Area No.xmm2 1C 240 mm2
5 Type / Model of the Cable - NYYF/YYF
B.Construction Parameter
1 CONDUCTOR: ▼
i. Conductor Material - Plain Annealed Stranded Copper, Class 5
ii. Number of Wire and Each Wire Diameter No./mm 1221/0.50 (Before Stranding)
iii. Shape of Conductor - Round Circular
vi. Approx. Conductor Diameter mm 23.00 [BS 6360, IEC 60228]
2 BINDER OVER CONDUCTOR: ▼
i. Binder Material Non-Hygroscopic Polypropylene Tape
ii. Approx. Thickness of Binder Tape - 0.20 mm (Approx. 25% Overlap)
3 INSULATION: ▼
i. Insulation Material - Extruded Polyvinyl Chloride (PVC), Type A
ii. Nominal Thickness of Insulation mm 2.20 mm (Nom); 1.88 mm (Min) [IEC 60502-1]
iii. Approx. Diameter over Insulation mm 28.00
iv. Core Identification Color - Black
4 OUTER SHEATH / JACKET: ▼
i. Outer Sheath / Jacket Material - Extruded Flame Reterdant Low Smoke (FRLS-PVC), Type ST1
ii. Nominal Thickness of Outer Sheath mm 2.00 mm (Nom); 1.40 mm (Min) [IEC 60502-1]
iii. Color of Outer Sheath / Jacket - Black
C. COMPLETE CABLES DETAILS:
1 Approx. Overall Diameter of Cable mm 32.00 ± 2.0
2 Approx. Weight of Complete Cable kg/km 2750
D. ELECTRICAL PARAMETER:
1 Max. DC Resistance of Conductor at 20ºC Ω/km 0.0817
2 Max. AC Resistance of Conductor at 70ºC Ω/km 0.1005
3 Max. Reactance of Cable at Operating Frequency Ω/km 0.0876
4 Max. Capacitance of Cable at Operating Frequency µF/km 1.5640
5 Max. Impedance of Cable of Conductor at 70ºC Ω/km 0.1278
6 CONTINUOUS CURRENT RATING:
i. In Air at 35ºC Amps 580
Sl. No. Description Particulars Unit Manufacturer’s Particulars
7 MAXIMUM CONDUCTOR TEMPERATURE:
i. Condition: Normal Operation ºC 70
ii. Condition: Short–Circuit ºC 1600 (5 Second Maximum Duration)
8 Short–Circuit
Circuit Withstand Capacity of Conductor kA 27.601 (for 1 second duration)
9 Minimum Insulation Resistance at 220ºC MΩ-km 2.786 (Calculated) [IEC 60502-1]
60502
10 Minimum Bending Radius for Fixed Installation mm 15 Times of Overall Diameter of Cable
11 Applied High Voltage Withstand Test kV 3.5 kV, 5 Minutes
E. OTHER PARAMETER:
i. Standard Drum Length Meter Should be in Single Length as per Capacity
ii. Drum Type and Drum Size (Flange x Width) - Wooden Drum, Drum Size: Depends on Customer
iii. Gross Weight of Complete Drum Length ((±5%) kg ---
iv. EMBOSSING OR PRINTING - Printing and Sequential Meter Marking