Sl. No. Description Particulars Unit Manufacturer’s Particulars
A. General Parameter
1 Name of the Manufacture and Cou Country of Origin - Poly Cable Industries Limited, Bangladesh
2 Reference Standard - IEC 60228, IEC 60502–1
60502
3 Rated Voltage: U0/U (Um) V 600
00/1000 (1200)
4 No. of Cores & Conductor Cross
Cross–Sectional Area No.xmm2 1 500 mm2
1C
5 Type / Model of the Cable - LV Power
Po Cable / 2xY
B. Construction Parameter
1 CONDUCTOR: ▼
i. Conductor Material - Plain Annealed Stranded Copper,
Copper Class 2
ii. Number of Wire and Each Wire Diameter No./mm 61/3.39 (Before Stranding)
iii. Shape of Conductor - Compacted Circular
vi. Approx. Conductor Diameter mm 25.30 – 27.60 [IEC 60228]
2 INSULATION: ▼
i. Insulation Material - Extruded Cross–Linked
Linked Polyethylene (XLPE)
ii. Nominal Thickness of Insulation mm 2.20 mm (Nom); 1.88 mm (Min) [IEC 60502-1]
iii. Approx. Diameter overer Insulation mm 31.00
iv. Core Identification Color - Natural
3 OUTER SHEATH / JACKET JACKET: ▼
i. Outer Sheath / Jacket Material - Extruded Polyvinyl Chloride (PVC), Type ST1
ii. Nominal Thickness of Outer Sheath mm 2.20
0 mm (Nom); 1.56 mm (Min) [IEC 60502-1]
iii. Color of Outer Sheath / Jacket - Black
C. COMPLETE CABLES DETAILS:
1 Approx. Overall Diameter of Cable mm 35.40 ± 2.0
2 Approx. Weight of Complete Cable kg/km 5134
D. ELECTRICAL PARAMETER:
1 Max. DC Resistance of Conductor at 20 20ºC Ω/km 0.0366
2 Max. AC Resistance of Conductor at 990ºC Ω/km 0.0468
3 Max. Reactance of Cable at Operating Frequency Ω/km 0.0835
4 Max. Capacitance of Cable at Operating Frequency µF/km 0.8570
5 Max. Impedance of Cable of Conductor at 990ºC Ω/km 0.0957
6 CONTINUOUS CURRENT RATI RATING:
i. Direct Buried in Ground at 30
30ºC Amps 800
ii. In Air at 35ºC Amps 1030
7 MAXIMUM CONDUCTOR TEMPERATURE:
i. Condition: Normal Operation ºC 90
ii. Condition: Short–Circuit ºC 250 (5 Second Maximum Duration)
8 Short–Circuit
Circuit Withstand Capacity of Conductor kA 71.542 (for 1 second duration)
9 Minimum Insulation Resistance at 27 27ºC MΩ-km 24.962 (Calculated) [IEC 60502-1]
60502
10 Minimum Bending Radius for Fixed Installation mm 15 Times of Overall Diameter of Cable
11 Appliedd High Voltage Withstand Test kV 3.5 kV, 5 Minutes
E. OTHER PARAMETER:
i. Standard Drum Length Meter Should be in Single Length as per Capacity
ii. Drum Type and Drum Size (Flange x Width) - Wooden Drum, Drum Size: Depends on Customer
iii. Gross Weight of Complete Drum Length ((±5%) kg ---
iv. EMBOSSING OR PRINTING - Printing and Sequential Meter Marking

Engr. Anamul Kabir


Manager

www.polycables.com.bd
Corporate Office: Madina Heights, 32, Shiddheswari
P LY CABLE IND. LTD. New Circular Road, 3rd & 4th Floor, Shantinagar More
Dhaka–1217. Tel: (+88 02) 4831 1856–60,
1856 Fax: 4831 1861
Email: info@polycables.com.bd
@polycables.com.bd, Web: www.polycables.com.bd
Factory: Bhitikandi, Bhober Char, Gazaria, Munshigonj

DRAWING AND TECHNICAL PARTICULARS FOR


SINGLE CORE, 500 mm2 XLPE INSULATED AND PVC SHEATHED COPPER CABLE
As P
Per IEC 60228, IEC 60502-1

PVC Sheath Thickness: 2.220 mm

XLPE Insulation Thickness: 2.20 mm

Number of Wires: Min. 61 Wires

Figure: 1C 500 mm2 (2xY)


C 50

Nominal X- No. of Wire & Nominal Nominal Approx. Maximum D.C. Approx
Sectional area Each Wire Thickness of Thickness of Overall Resistance of Weight of
of conductor Diameter Insulation Sheath Diameter Conductor at 20°C
2 Cable
mm2 No./mm mm mm mm Ohm/km kg/km
As Per IEC/
500 Min. 53 Wires 2.20 2.20 35.40 0.0366 5134
BS/BDS/VDE
Guaranteed
500 Min. 61 Wires 2.20 2.20 35.40 0.0366 5134
Particulars