Designers, contractors and site supervisory staff should understand the common defects and their related
causes to prevent them. It is also essential to use some recommended details to better manage the defects
and implement necessary remedial actions. Figure 10.1 shows the common defects, possible causes and
their remedial actions.
Common Defects /
Possible Causes Recommendations
Bad Practices
10.1.2 Stud cutting for switch • Insufficient planning • Stud placement must be
casing installation according to shop drawing
• Last minute changes (inclusive of M&E services
layout)
• Insufficient training
• Stud realigned to
avoid switch casing or
alternatively, additional stud
is required
52
COMMON DEFECTS AND REMEDIES
Common Defects /
Possible Causes Recommendations
Bad Practices
10.1.3 Poor cutting of • No provision of right tools • Panel must be cut according
plasterboard to shop drawing
• Insufficient training
• Over cut / slanting / Rough
cut is not allowed
10.1.5 Gaps between different • Insufficient planning • All gaps are to be sealed
materials using Fire Rated Sealant or
• Insufficient training relevant sealant
• No gap allowed
• Lack of supervision
• Gap was filled by mortar
filling instead of flexible
sealant.
53
COMMON DEFECTS AND REMEDIES
Common Defects /
Possible Causes Recommendations
Bad Practices
10.1.7 Studs not fastened to • Lack of supervision • All Studs and Bracing must
bottom track be riveted/ screwed
• Insufficient training
• Poor workmanship
54
COMMON DEFECTS AND REMEDIES
Common Defects /
Possible Causes Recommendations
Bad Practices
10.1.8 M&E Services not • Insufficient planning • All Electrical Services must
within drywall setting out be within drywall setting out
• Insufficient training
• Poor workmanship
10.1.9 Small cut pieces • Insufficient planning • Full piece & proper joint.
installed and torn board
• Insufficient training
• Poor workmanship and
supervision
10.1.10 Bottom track cut to • Insufficient planning • Services Holes was created
accommodate M&E services without cutting track
• Insufficient training
• Poor workmanship and
supervision
55
COMMON DEFECTS AND REMEDIES
Common Defects /
Possible Causes Recommendations
Bad Practices
10.2.2a Wall alignment and evenness • Square-ness less than 4mm over 300mm
56
COMMON DEFECTS AND REMEDIES
10.2.2b Wall alignment and evenness • Less than 3mm over 1.2m length
10.2.3 M&E and wall alignment • No uneven gap between FCU and Drywall
10.2.4 Wall jointing, crack and damages • Drywall should be visually straight
• No chips , roughness and scratches
allowed
57