You are on page 1of 1

A B C D E F G H I J K L M N O P Q R S

1 Fill data only in coloured areas


2 Project Name : Building No. one West wing Altitude 600 Mt Latitude 30
Estimated by Ghaleb Abu
3 Date July 28, 2000
Saa'
4 Reference Dimensions Space used for Lb H2O/Lb dry air
5 Unit L W H Area Volume Office Outside Room
6 Office two Ft 17 22 10 376 3,696 Special conditions 0.0122 0.0104
7 Mt 5.25 6.65 3.00 34.91 104.74 Temp. not to exceed 74 oF Grains/Lb H2O 6000
8 Summer Cooling Load NOTES
9 Condition Unit DB WB %RH Gr/Lb SUN LIGHT GAIN
10 oF 115 84 29% 126 1 For rooms or zones having more than one exposure, use north
Outside
11 oC 46 28.9 29% 126 values for all exposures except the one having the largest solar
12 oF 70 50.0 50 38 gain. Usually greatest solar area.
Inside
13 oC 21 10.0 50 38 2 Figures shown are based on an average of 17 Hrs operation.
14 oF 45 88 3 Multiply by factor 1.2for very light construction, 0.9 for very
Difference
15 oC 25 88 heavy construction & 1.25 for hotels to allow for pull-down &
16 Outside Air/Fresh air data individual rooms preference on outside air temperature.
17 Variable Qty Total Air changes per % to A/C TRANSMISSION GAIN
18 Persons 2 CFM Hr CFM 1 Ceiling type one is under finished room
19 CFM/Person 15 30 0.49 4.05% 2 Ceiling type two is un-insulated frame or heavy masonary with ceiling
20 Room heat load 3 Ceiling type three is un-insulated frame or heavey masonery
21 Sensible heat load without ceiling
22 Sun light gain BTUH 1,824 4 Ceiling type four is un-insulated light masonary with ceiling
23 Sourse Sq Ft Factor BTUH W1 5 Ceiling type five is un-insulated light masonary without ceiling
24 Glass N 0 23 0 169 6 Ceiling type six is insulated all kinds with ceiling
25 Glass E 0 80 0 7 Ceiling type seven is insulated all kinds without ceiling
26 Glass S 0 68 0 8 Floor type one is over finished floor
27 Glass W 19.4 94 1823.6 W3 215 215 W4 9 Floor type two is over basement with finished ceiling
28 Glass NE 0 66 0 10 Floor type three is on ground.
29 Glass SE 0 70 0 W3 Safety Factors
30 Glass SW 0 81 0 W2 Glass SAFETY FACTOR "A" 5%
31 Glass NW 0 74 0 169 19.4 Re-heat supply duct heat gain 5%
32 Transmission heat gain BTUH 10,357 1 Supply duct leakage loss 2%
33 type Sq Ft u To-Ti BTU/Hr Fan factor 3%
34 Sunlit walls 150 0.3 45 2,026 Safety factor used 5%
35 Shaded wall 0 0.2 0 0 SAFETY FACTOR "B" 2%
36 Partition 169 0.2 45 1,525 2 Supply duct leakage loss 2%
37 Ceiling type one 0 0.24 0 0 Safety factor used 2%
38 Ceiling type two 0 1.07 0 0 SAFETY FACTOR "C" 0%
39 Ceiling type three 0 1.2 0 0 Return duct heat gain 2%
40 Ceiling type four 0 1.6 0 0 Return duct leakage gain 3%
3
41 Ceiling type five 0 1.7 0 0 Pump Hp 2%
42 Ceiling type six 376 0.2 45 3,380 Dehumidufication & piping loss 3%
43 Ceiling type seven 0 0.9 0 0 Safety factor used 0%
44 Floor type one 376 0.24 38 3,425 Latent heat load
45 Floor type two 0 0.2 0 0 Sourse No. Factor BTU/Hr
46 Floor type three 0 0 0 0 people seated at rest 0 150 0
People seated, very light
47 Internal heat gain BTUH 1,663 2 155 310
work
48 Sourse No. Factor BTU/Hr People moderately active 0 250 0
Standing light work/walking
49 people seated at rest 0 180 0 0 300 0
slowly
Sedentary & light bench
50 People seated, very light work 2 193 386 0 330 0
work.
51 People moderately active 0 200 0 Moderate & heavy work. 0 980 0
52 Standing light work/walking slowly 0 200 0 Steam rate in Lb/Hr 0 1000 0
53 Sedentary & light bench work. 0 220 0 Room latent heat sub total 310
54 Moderate & heavy work. 0 450 0 Safety factor "B" 1.02%
55 Motors in KW 0 3412 0 Room latent heat 316
56 Lights in Watt 376 3.4 1,277 Outside air heat load
57 Room sensible heat sub total 13,843 Sensible heat CFM Delta "T" Factor BTU/Hr
58 Safety factor "A" 1.05% 30 45.0 1.08 1,458
59 Room sensible heat 14,535 Latent CFM "Gr/Lb" Factor BTU/Hr
60 Grand total sensible heat 15,993 30 88 0.67 1,769
61 Room total heat load BTUH 18,078 Safety factor "C" 1.00%
62 Q = mCpDelta"T" Tons 1.51 Out side air total sensible heat load 1,458
63 (1.2*2.2/35)*60*0.24*Delta "T" KW 5.30 Out side air total latent heat load 1,769
64 1.077 Kcal/Hr 4,535 Grand total latent heat 2,085
Assume delta "t" (temperature difference between room temperature & air off coil dry bulb temperature to
65 oF 20
be :-
66 Room supply air C.F.M. = room sensible heat divided over (1.08*delta "t") = 740

You might also like