You are on page 1of 88

Operation

Maintenance Manual
Gear-Driven Centrifugal
Water-Cooled Liquid
Chillers with CH530
Controls

Unit Model
CVGF 400-1000 Ton Units
(50 and 60 Hz)

X39640691020 CVGF-SVU02B-E4
Warnings and
Cautions

Warnings and Cautions designed to alert personnel to


Notice that warnings and conditions that could result in
cautions appear at appropriate equipment damage.
intervals throughout this Your personal safety and the
manual. Warnings are provided proper operation of this machine
to alert installing contractors to depend upon the strict
potential hazards that could observance of these precautions.
result in personal injury or
death, while cautions are

NOTICE: Warnings and Cautions appear at appropriate sections throughout this manual.
Read these carefully.

WARNING – Indicates a potentially hazardous situation which, if not avoided, could result
in death or serious injury.

CAUTION – Indicates a potentially hazardous situation which, if not avoided, may result in
minor or moderate injury. It may also be used to alert against unsafe practices.

CAUTION – Indicates a situation that may result in equipment or property-damage-only


accidents.

© 2005 American Standard Inc. All rights reserved. CVGF-SVU02B-E4


Contents

Warnings and Cautions 2


General Information 4
Unit Control Panel (UCP) 22
Base Loading Control Algorithm 44
Control System Components 47
Machine Protection and Adaptive 62
Unit Startup 73
Unit Shutdown 76

Periodic Maintenance 77

CVGF-SVU02B-E4 3
General
Information

Literature History Model Number


CVGF-SVU02A-E4 Refer to the Installation Manual.
(November 2002)
This is a new manual. Product Description Block
A typical Product Description
About this manual Block is shown in the Installation
Manual.
Operation and maintenance
information for models CVGF Unit Nameplate
are covered in this manual. This
includes both 50 and 60 Hz. The unit nameplate is located on
CVGF centrifugal chillers the left side of the unit control
equipped with the Tracer CH530 panel.
Chiller Controller system. Note: Trane starters are
Carefully review this information identified by a separate model
and follow the instructions given number found on the starter.
to successfully operate and
maintain a CVGF unit.
If mechanical problems do
occur, contact a qualified service
organization to ensure proper
diagnosis and repair of the unit.

4 CVGF-SVU02B-E4
General
Information

Commonly Used DTFL = Design Delta-T at Full LLID = Low Level Intelligent
Abbreviations Load (for example, the Device (Sensor, Pressure
difference between entering and Transducer, or Input/output UCP
For convenience, a number of leaving chilled water module)
abbreviations are used temperatures)
throughout this manual. These MAR = Machine Shutdown Auto
are listed alphabetically below, DV = DynaView™ Clear Language Restart (Non-Latching where
along with a translation of each: Display, also know as the Main chiller will restart when
Processor (MP) condition corrects itself.)
ASME = American Society of
Mechanical Engineers ELWT = Evaporator Leaving MMR = Machine Shutdown
Water Temperature Manual Restart (Latching where
ASHRAE = American Society of chiller must be manually reset.)
Heating, Refrigerating and Air ENT = Entering Chilled Water
Conditioning Engineers Temperature MP = Main Processor
BAS = Building Automation EXOP = Extended Operation PFCC = Power Factor Correction
System GBAS = Generic Building Capacitor
CDBS = Condenser Bundle Size Automation Interface PID = Proportional Integral
GPM = Gallons-per-minute Derivative
CDSZ = Condenser Shell Size
HLUV = High Lift Unloading PSID = Pounds-per-Square-Inch
CH530 = Tracer CH530 Controller. (differential pressure)
Valve.
CWR = Chilled Water Reset PSIG = Pounds-per-Square-Inch
Hp = Horsepower
CWR’ = Chilled Water Reset (gauge pressure)
Prime HVAC = Heating, Ventilating, and
Air Conditioning ODT = Outdoor Temperature
IE = Internally-Enhanced Tubes OPST = Operating Status
Control
IPC = Interprocessor
Communication RLA = Rated Load Amps
LCD = Liquid Crystal Display RTD = Resistive Temperature
Device Tracer CH530= Controls
LED = Light Emitting Diode Platform used on this Chiller
TRMM = Tracer
Communications
UCP = Unit Control Panel

CVGF-SVU02B-E4 5
General
Information

Figure 1. General CVGF unit component


Unit-Mounted Starter (Optional)

Two-Stage Compressor

Condenser

Relief Valves

Evaporator

Oil Pump

Control Panel CH530

Unit Nameplate

Figure 2. Component location for typical CVGF unit (back view)

Motor

Unit nameplate

Relief valves

Oil cooler

Economizer

6 CVGF-SVU02B-E4
General
Information

Cooling Cycle Evaporator - A liquid vapor Compressor first stage -


refrigerant mixture enters the Refrigerant vapor is drawn from
The refrigeration cycle of the
evaporator at state point 1. the evaporator into the first
CVGF chiller can be described
Liquid refrigerant is vaporized to stage compressor. The first stage
using the pressure-enthalpy
state point 2 as it absorbs heat impeller accelerates the vapor
diagram shown in Figure 3. Key
from the system cooling load. increasing its temperature and
state points are indicated and
The vaporized refrigerant flows pressure to state point 3.
will be referred to in the
into the compressor first stage.
following discussion. A
schematic of the system
showing refrigerant flow is given
in Figure 4.
Figure 3. P-H chart

Pc Condenser
5 4
Compressor
2nd stage

P1 Economizer 3
8
Compressor
1st stage

1 Evaporator 2
Pe
RE

1
RE

CVGF-SVU02B-E4 7
General
Information

Compressor second stage - Economizer and refrigerant To complete the operating cycle,
Refrigerant vapor leaving the orifice system - Liquid liquid refrigerant leaving the
first stage compressor is mixed refrigerant leaving the economizer at state point 8
with cooler refrigerant vapor condenser at state point 5 flows flows through a second orifice.
from the economizer. This through the first orifice and Here refrigerant pressure and
mixing lowers the enthalpy of enters the economizer to flash a temperature are reduced to
the vapor entering the second small amount of refrigerant at evaporator conditions at state
stage. The second stage an intermediate pressure point 1.
impeller accelerates the vapor, labeled P1. Flashing some liquid An innovative design feature of
further increasing its refrigerant cools the remaining the CVGF chiller is maximizing
temperature and pressure to liquid to state point 8. the evaporator heat transfer
state point 4. Another benefit of flashing performance while minimizing
Condenser - Refrigerant vapor refrigerant is to increase the refrigerant charge requirements.
enters the condenser where the total evaporator Refrigeration This is accomplished by the
system cooling load and heat of Effect from RE’ to RE. The Trane-patented falling film
compression are rejected to the economizer provides around 4 evaporator design. The amount
condenser water circuit. This percent energy savings of refrigerant charge required in
heat rejection cools and compared to chillers with no CVGF is less than that in
condenses the refrigerant vapor economizer. comparably sized chillers of
to a liquid at state point 5. flooded evaporator design.

8 CVGF-SVU02B-E4
General
Information

Figure 4. Refrigerant flow diagram

Starter
Internal filter
F
Compressor
Inlet
High lift Gears ST vanes
ST
unloading Motor 2 1
valve Bearings
Condenser
(HLUV)
Fixed
Oil cooler orifice

Condenser
sump S
Strainer

Economizer Oil sump


Fixed
orifice Pump

Fixed
orifice

Distributor
Refrigerant Flow

Evaporator

CVGF-SVU02B-E4 9
General
Information

Compressor Description Compressor


The centrifugal compressor is
The CVGF compressor consists
two-stage with high-strength
of three distinct sections: the
aluminum alloy fully shrouded
two-stage centrifugal
impellers. The impellers are
compressor, the motor, and the
tested at 25 percent over design
gear box with integral oil sump.
operating speed. The rotating
See Figure 5.
assembly is dynamically
balanced for vibration of less
than 5.1 mm/sec (0.2 ips peak
velocities) at nominal operating
speeds. The control system
affords 20 to 100 percent
capacity modulation by
electrically actuated guide vanes
upstream of each impeller.

10 CVGF-SVU02B-E4
General
Information

Figure 5. Compressor cross-section view

Motor rotor

Motor shaft

Discharge end
Bull gear

Motor Motor terminal


housing

Motor stator

Pinion shaft
Gear housing

2nd stage
impeller

1st stage
impeller

Suction Oil pump


end

Oil
sump

CVGF-SVU02B-E4 11
General
Information

Drive Train When servicing a chiller, you TechView™ Chiller


The drive train consists of need different information and a For the service technician or
helical bull and pinion gears. lot more of it such as historic advanced operator all chiller
Gear tooth surfaces are case and active diagnostics, status, machine configuration
hardened and precision ground. configuration settings, and settings, customizable limits,
The one-piece impeller shaft is customizable control and up to 60 active or historic
supported by hydrodynamic algorithms, as well as operation diagnostics are displayed
thrust and radial bearings. settings. through the TechView™
Motor By providing two different tools, interface. Using TechView™, a
The motor is a hermetic, liquid one for daily operation and one technician can interact with an
refrigerant cooled, two-pole, for periodic service, appropriate individual device or a group of
low-slip squirrel cage induction information is readily devices for advanced
motor. A radial hydrodynamic accessible. troubleshooting. LED lights and
bearing and duplex angular their respective TechView™
DynaView™ Human Interface indicators visually confirm the
contact ball bearings support For the operator, day-to-day
the rotor assembly. Winding- viability of each device. Any PC
operational information is that meets the system
embedded sensors provide presented at the panel. Up to
positive thermal protection. requirements may download the
seven lines of data (English or SI service interface software and
units) are simultaneously Tracer CH530 updates. For more
Controls Overview displayed on the touch-sensitive information on TechView™ visit
Controls Operator Interface screen. Logically organized your local Trane Service
Information is tailored to groups of information such as company, or The Trane
operators, service technicians chiller modes of operation, Company’s website at
and owners. When operating a active diagnostics, settings and www.trane.com.
chiller, there is specific reports put information
information you need on a day- conveniently at your fingertips.
to-day basis such as setpoints, See Operator Interface Section
limits, diagnostic information, for details.
and reports.

12 CVGF-SVU02B-E4
General
Information

Figure 6. CVGF sequence of operation overview

Stopped
Power Up
Stopped
Run Inhibit

n
w

St
do

ar
ut

tC
Sh

om
ia
ed

gn

m
irm

os

an
tic

d
nf
Co

Re
se
t
Stopping Starting
Fast Restart or Satisfied Setpoint Auto
Preparing to Shut Waiting to Start
Down Shutting Starting
Down Stop Command or Diagnostic Compressor
St
op

t
ar
Co

St
m
D

ed
m
ia

irm
an
gn

d
os

nf
Co
tic

Running
Running
Running - Limit

CVGF-SVU02B-E4 13
General
Information

Figure 7. Sequence of operation: power up


Apply
Control
Power

Self Test
Completing Self Test
(12 Seconds)

Starting Application
(20-30 Seconds*) Application
Starting

Last Mode
Such as
Auto or
Stopped
as shown

*Note: The variation in DynaView Power Up time is dependent on the number of


installed options.

14 CVGF-SVU02B-E4
General
Information

Figure 8. Sequence of operation: running

Starter Status is Limit Mode Exit Limit Mode


“Running”

Starting
Running - Limit Running Running Running
Compressor

Modulate IGV for Modulate IGV for Modulate IGV for


LWT control Limit control LWT control

CVGF-SVU02B-E4 15
General
Information

Figure 9. Immediate shutdown to stopped or run inhibit

Immediate shutdown non-latching diagnostic Run Inhibit


Immediate shutdown latching diagnostic
Stopped
Panic stop

Post lube complete

Run Inhibit or
Running Shutting down Shutting down Shutting down
Stopped

Post lube and evaporator


pump off delay complete
Close IGV
(0-50 seconds)

Post Lube: De-energize oil pump


(1 minute)

Confirm no oil pressure*


5 minutes after oil pump is de-energized

De-energize evaporator
Evaporator pump off water pump relay
delay not performed for
immediate shutdown

De-energize
compressor

Confirm no compressor currents 8


seconds after compressor is de-
energized

De-energize condenser
water pump
*Note: No oil pressure when oil differential pressure switch is open.

16 CVGF-SVU02B-E4
General
Information

Figure 10. CVFG sequence of operation: satisfaction setpoint

Satisfied setpoint

Running Preparing shutdown Shutting down Shutting down Auto

Close IGV De-energize oil pump


Post lube
(0-50 seconds) (1 minute)

Command IGV closed De-energize compressor Confirm no oil pressure*


5 minutes after oil pump
is de-energized

Confirm no compressor
currents within 30 seconds

De-energize condenser
water pump relay

Enforce all running mode


diagnostics
*Note: No oil pressure when oil differential pressure switch is open.

CVGF-SVU02B-E4 17
General
Information

Oil Management Low Oil Temperature Start This mode is indicated to the
Inhibit Setpoint default is: 95° F. user.
The primary purpose of Oil
Management is to ensure When enhanced oil protection is 2. Idle: The oil pump is off. The
appropriate and sufficient enabled, the low oil temperature oil temperature is maintained
lubrication to the bearings start inhibit is the saturated by the heater, at the control-
during compressor operation evaporator at 30°F (16.6°C) or temperature setpoint +/- 2.5°F
and to minimize refrigerant 105°F (40.5°C), whichever is (1.4°C).
dilution in the oil. higher. 3. Pre-lube: The oil pump
The Oil Management system When enhanced oil temperature lubricates the bearing for 30
performs safety checks and protection is enabled, the oil seconds before the
manages the operation of the Oil temperature setpoint is fixed at compressor starts.
Pump and the Oil Heater. The 136°F (57.8°C). This mode is indicated to the
sensor inputs used for these The oil temperature control user.
purposes are the Differential Oil setpoint range is settable from:
Switch, and the Oil Temperature. 4. Running: The oil pump
100 to 160°F (37.8 to 71.1°C) continues to lubricate the
Two oil heater outputs exist, that bearings when the compressor
should always operate Essential Modes is running.
simultaneously, for example, The Oil-Management has the
both on or both off. following modes:
Note: The Oil Pump and the Oil 1. Low Temperature Start Inhibit:
Heater are never energized at the
same time. The oil temperature is at or
below the low oil temperature
start inhibit setpoint. The heater
is energized to raise the oil
temperature. See Low
Temperature Start Inhibit section
for information about Enhanced
Oil Temp Protection.

18 CVGF-SVU02B-E4
General
Information

5. Post-lube: The oil pump Oil Temperature Control Here are the details:
lubricates the bearings for 60 The oil heater is used to
seconds after the compressor maintain the oil temperature
• CH530 verifies that the
pressure switch is reading no
is stopped to ensure bearings within +/- 2.5°F (4.5°C) of the oil differential pressure with the
remain lubricated as the temperature control setpoint. oil pump off before proceeding
compressor coasts to a stop. The oil heater is commanded off with pre-lube.
If a start command is issued when the oil pump is
while in post-lube, a quick restart commanded on. • CH530 displays a mode
Waiting for Low Oil Differential
will be performed. Press.
Oil Differential Pressure
The post-lube mode is indicated
to the user on DynaView™ and
Check • The check is made if oil pump
is off and before it is turned on.
TechView™. The Oil Differential Pressure
6. Manual: The oil pump can be
Check validates the oil • CH530 allows five minutes for
differential pressure before the the differential oil pressure
commanded on and off in a oil pump is turned on. This check switch to open.
manual mode. in necessary in case the
differential pressure switch is
• This check is performed on
power up or reset also. If a
not operational. Without this MPL occurred or power up was
check, the differential oil within the post-lube time, oil
pressure feedback is gone. This pump is running so do not do
check is made after post-lube is the check.
complete to verify that the
differential pressure has
dropped to indicate no oil flow.

CVGF-SVU02B-E4 19
General
Information

Protective Diagnostics and Low Differential Pressure Cutout Once oil flow has been
their description is a latching diagnostic that can established, if the differential
come up while the unit is pressure switch indicates there
Differential Oil Pressure Overdue running. Oil pressure is is not oil pressure for 2 seconds,
is a latching diagnostic that can indicative of oil flow and active this diagnostic will be issued.
come up while the unit is in pre- oil pump operation. Significant
lube. Unexpected Differential Oil
fall in oil pressure is indicative of Pressure is a latching diagnostic
The differential pressure switch failure of the oil pump, oil that can come up while the unit
status is used instead of the Low leakage, or other blockage in the is idle and is implemented to
Differential Oil Pressure Cutout oil circuit. recognize and ensure that the
setpoint. pressure switch is operational
and that it is open for a period of
five minutes.

20 CVGF-SVU02B-E4
General
Information

Figure 11. Oil circuit diagram

Starter
Internal Filter
F Compressor

Gears
Motor ST 2 ST 1
High Lift Condenser Bearings
Unloading
Valve (HLUV)
Oil Cooler

Condenser
Sump S
Strainer

Economizer Oil Sump


Fixed Orifice Pump

Fixed Orifice

Refrigerant
Distributor
Oil

Evaporator

CVGF-SVU02B-E4 21
Unit Control
Panel (UCP)

Control Panel Devices and The UCP houses several other and the main processor. Unit
Unit Mounted Devices controls modules called panel mounted devices are called
mounted LLID (Low Level frame mounted LLID’s and can
Unit Control Panel (UCP) Intelligent Device), power be temperature sensors or
Safety and operating controls supply, terminal block, fuse, pressure transducers. These and
are housed in the unit control circuit breakers, and transformer. other functional switches
panel, and the starter panel. The The IPC (Interprocessor provide analog and binary inputs
UCP ‘s operator interface and communication) bus allows the to the control system.
main processor is called the communications between LLID’s
DynaView™ and is located on the
UCP door. (See Operators
interface section for detailed
information)
Figure 12. Control panel

22 CVGF-SVU02B-E4
Unit Control
Panel (UCP)

Tracer CH530 Chiller Whenever the controller senses Variable water flow through the
Controller a situation that might trigger a evaporator
protective shutdown, it focuses Chilled water systems that vary
Tracer CH530’s Main Processor, on bringing the critical water flow through chiller
DynaView™, is fast and keeps parameter back into control. evaporators have caught the
the chiller online whenever When the parameter is no longer attention of engineers,
possible. Smart sensors collect critical, the controller switches contractors, building owners,
three rounds of data per second, its objective back to controlling and operators. Varying the water
55 times the data collection the chilled water temperature, or flow reduces the energy
speed of its predecessor. Each to another more critical consumed by pumps, while
device (a sensor) has its own parameter should it exist. requiring no extra energy for the
microprocessor that chiller. This strategy can be a
simultaneously converts and significant source of energy
accurately calibrates its own savings, depending on the
readings from analog to digital. application. With its faster and
Because all devices are more intelligent response to
communicating digitally with changing conditions, Tracer
the DynaView™, there is no need CH530 reliably accommodates
for the main processor to variable evaporator water flow
convert each analog signal one and its effect on the chilled water
at a time. This distributed logic temperature. These
allows the main processor to improvements keep chilled
focus on responding to water flowing at a temperature
changing conditions in the load, closer to its setpoint.
the machine, its ancillary
equipment, or its power supply.
Tracer CH530 constantly
receives information about key
data parameters, temperatures
and currents. Every five seconds
a multiple objective algorithm
compares each parameter to its
programmed limit. The chiller’s
Adaptive Control™ capabilities
maintain overall system
performance by keeping its peak
efficiency.

CVGF-SVU02B-E4 23
Unit Control
Panel (UCP)

The DynaView™ (DV) Operator The MP contains non-volatile DynaView™ presents three menu
Interface contains the Main memory both checking for valid tabs across the top which are
Processor (MP) which set points and retaining them on labeled “MAIN, REPORTS, and
communicates commands to any power loss. System data SETTINGS”.
other modules, collecting data, from modules (LLID) can be The Main screen provides an
status and diagnostic viewed at the DynaView™ overall high level chiller status
information from the other operator interface. Such as so the operator can quickly
modules over the IPC (Inter evaporator and condenser water understand the mode of
Processor Communications) temperatures, outdoor air operation of the chiller.
link. The Main Processor temperature, evaporator and
software controls water flows by condenser water pump control, The Chiller Operating Mode will
starting pumps and sensing status and alarm relays, external present a top level indication of
flow inputs, establishes a need auto-stop, emergency stop, and the chiller mode (Auto, Running,
to heat or cool, performs pre- evaporator and condenser water Inhibit, Run Inhibit, and so forth)
lube, performs post-lube, starts flow switches. The “additional info” icon will
the compressor, performs water present a subscreen that lists in
temperature control, establishes further detail the subsystem
limits, and pre-positions the modes.
inlet guide-vanes.

Figure 13. DynaView™ main processor

24 CVGF-SVU02B-E4
Unit Control
Panel (UCP)

Main screen content can be Touch screen key functions are Action buttons are buttons that
viewed by selecting the up or determined completely in the appear temporarily and provide
down arrow icons. The Main software and change depending the operator with a choice such
screen is the default screen.After upon the subject matter as Enter or Cancel. The operator
an idle time of 30 minutes. currently being displayed. The indicates his choice by touching
DynaView™ (DV) is the operator user operates the touch sensitive the button of choice. The system
interface of the Tracer CH530 buttons by touching the button then takes the appropriate action
control system utilized on the of choice. The selected button is and the button typically
CTV machines. The DynaView™ darkened to indicate it is the disappears.
enclosure is 9.75" (24.8 cm) selected choice. The advantage DynaView™ consists of various
wide, 8” (20.3 cm) high and 1.6” of touch sensitive buttons is that screens, each meant to serve a
(4.1 cm) deep. The DynaView™ the full range of possible choices unique purpose of the machine
display is approximately 4” (10.2 as well as the current choice is being served. Tabs are shown
cm) wide by 3” (7.6) high. always in view. row across the top of the display.
Features of the display include a Up or down arrow buttons are The user selects a screen of
touch screen and long life LED used to allow a continuously information by touching the
backlight. This device is capable variable setpoint, such as appropriate tab. The folder that
of operating in 0 - 95 percent leaving water setpoint. The value is selected will be brought to the
relative humidity (non- changes by touching the up or front so it’s contents are visible
condensing). The enclosure down arrows.
includes a weather tight
connection means for the RS232
TechView™ connection.

CVGF-SVU02B-E4 25
Unit Control
Panel (UCP)

The main body of the screen is The bottom of the screen is the Persistent keys, horizontal at the
used for description text, data, persistent area. It is present in all bottom of the display, are those
setpoints, or keys (touch screens and performs the keys that must be available for
sensitive areas) The double up following functions. The left operation regardless of the
arrows cause a page by page circular area is used to reduce screen currently being displayed.
scroll either up or down. The the contrast and viewing angle These keys are critical for
single arrow causes a line by of the display. The right circular machine operation. The Auto
line scroll to occur. At the end of area is used to increase the and Stop keys will be presented
the screen, the appropriate scroll contrast and viewing angle of as radio buttons within the
buttons will disappear. the display. The contrast control persistent key display area. The
will be limited to avoid complete selected key will be dark. The
“light” or complete “dark”, chiller will stop when the Stop
which would potentially confuse key is touched, entering the stop
an unfamiliar user to thinking sequence. Pressing the
the display was malfunctioning. “Immediate Stop” button will
cause the chiller to stop right
away.
The AUTO and STOP, take
precedence over the ENTER and
CANCEL keys. (While a setting is
being changed, AUTO and STOP
keys are recognized even if
ENTER or CANCEL has not been
pressed. Selecting the Auto key
will enable the chiller for active
cooling.

26 CVGF-SVU02B-E4
Unit Control
Panel (UCP)

The machine-operating mode The TOP LEVEL MODE is the text The BAS CODE is the code that
indicates the operational status seen on the single top level will be sent via COMM4/5 to the
of the chiller. A subscreen with chiller system operating mode Tracer Summit system as the
additional mode summary line. The SUB LEVEL MODE is chiller system mode. Note that
information will be provided. the text seen on the operating each top level mode may contain
When the user scrolls down the mode sub-menu. The operating multiple sub level modes. In
screen the Machine Operation mode sub-menu may have up to general, the BAS CODE will
Mode will remain stationary six (6) lines of text displayed. reflect the top level mode and
On DynaView™, the user will be not the sub level mode.
presented with a single line of
text that represents the ‘top-
level’ operating state of the
machine. These top-level modes
are shown in the Table 1.
Additional information (if it
exists) regarding the machine Figure 14.
operating state will be available
to the user by selecting the
“additional information” button
(double right arrow) next to the
top-level operating mode. These
sub-level modes are shown
Table 1.

CVGF-SVU02B-E4 27
Unit Control
Panel (UCP)

Table 1. A general description of the top level modes is show in the following table.
Top Level Mode Description
Stopped Unit inhibited from running and will require user action to go to Auto.
Run Inhibit Unit inhibited from running by Tracer, External BAS, or an Auto Reset diagnostic.
Auto Unit determining if there is a need to run.
Waiting To Start Unit waiting for tasks required prior to compressor start to be completed.
Starting Compressor Unit is starting compressor.
Running Compressor is running with no limits in effect.
Running – Limit Compressor is running with limit in effect.
Preparing To Shutdown Unit is closing inlet guide vanes prior to compressor shutdown.
Shutting Down Compressor has been stopped and unit is performing shutdown tasks.

Figure 15.

28 CVGF-SVU02B-E4
Unit Control
Panel (UCP)

Reference
Top Level Mode Sub Level Mode BAS Code
SYSTEM RESET Boot & Application software part number, self-test, and
configuration validity screens will be present. NA
Stopped Local Stop 00
Stopped Panic Stop 00
Stopped Diagnostic Shutdown – Manual Reset 00
Run Inhibit Tracer Inhibit 100
Run Inhibit External Source Inhibit 100
Run Inhibit Diagnostic Shutdown – Auto Reset 100
Auto Waiting For Evaporator Water Flow 58
Auto Waiting For A Need To Cool 58
Auto Waiting For A Need To Heat 58
Auto Power Up Delay Inhibit: MIN:SEC 58
Waiting To Start Waiting For Condenser Water Flow 70
Waiting To Start Establishing Oil Pressure 70
Waiting To Start Pre-Lubrication Time: MIN:SEC 70
Waiting To Start Motor Temperature Inhibit: 70
Motor Temperature / Inhibit Temperature
Waiting To Start Restart Time Inhibit: MIN:SEC 70
Waiting To Start Low Oil Temperature Inhibit: 70
Oil Temperature / Inhibit Temperature
Waiting To Start Waiting For Starter To Start: MIN:SEC 70
Starting Compressor There is no sub mode displayed 72
Running There is no sub mode displayed 74
Running Surge 74
Running Base Loaded 74
Running Current Control Soft Loading 74
Running Capacity Control Soft Loading 74
Running – Limit Current Limit 75
Running – Limit Phase Unbalance Limit 75
Running – Limit Condenser Pressure Limit 75
Running – Limit Evaporator Temperature Limit 75
Running – Limit Minimum Capacity Limit 75
Running – Limit Maximum Capacity Limit 75
Preparing To Shutdown Closing IGV IGV Position % 7E
Shutting Down Post-Lubrication Time: MIN:SEC 7E
Shutting Down Evaporator Pump Off Delay: MIN:SEC 7E
Shutting Down Condenser Pump Off Delay: MIN:SEC 7E

CVGF-SVU02B-E4 29
Unit Control
Panel (UCP)

Main Screen
The main screen provides an
overall view of the chiller
performance in addition to the
main and sub operating modes.
The table below indicates other
items found , when specified by
options, that can be scrolled to
via the up or down arrows.

Description
Chiller Operating Mode (>>sub modes)
Evaporator Entering and Leaving Water Temperature
Condenser Entering and Leaving Water Temperature
Active Chilled Water Setpoint (>>source)
Active Current Limit Setpoint (>>source), If enabled
Active Base Loading Setpoint (>>source), If enabled
Average Line Current
Approximate Chiller Capacity, If option installed
Software Version

30 CVGF-SVU02B-E4
Unit Control
Panel (UCP)

Diagnostic Screen Up to ten active diagnostics can A Manual Override indicator


The diagnostic screen is be displayed if required. (shares space with the Alarms
accessible by touching the The reason for all diagnostics key) alerts the operator to the
Alarms enunciator. must be determined and presence of a manual override.
When an alarm is present, the corrected. Do not reset and An Alarm will take precedence
alarm enunciator is present next restart the chiller as this can over the manual override, until
to the Stop key. A flashing cause a repeat failure. Contact the reset of active alarms. The
“alarm” indicates a machine local Trane Service for assistance manual override indicator would
shutdown and a non flashing as necessary. reappear if such an override
“alarm” indicates an exists.
After corrective action, the chiller
informational message. can be reset or restarted. In the Temperature settings can be
Machine shutdowns can be of case of a diagnostic type, the expressed in F or C, depending
two types: chiller will have to be manually on Display Units settings.
Latching (MMR) require reset through the Diagnostics Dashes (“- - - -”) appearing in a
corrective action and manual alarm menu. temperature or pressure report,
reset. When reset they become historic indicates that the value is invalid
and viewable via the TechView™. or not applicable.
Non-Latching (MAR) will restart
automatically when condition Performing a Reset All Active The languages for DynaView™
corrects itself. Diagnostics will reset all active will reside in the main processor.
diagnostics regardless of type, The main processor will hold
machine or refrigerant circuit. three languages, English, and
two alternate languages. The
TechView™ will load the main
processor with user selected
languages from a list of available
translations. Whenever possible,
complete words will be used on
the persistent keys as described.

CVGF-SVU02B-E4 31
Unit Control
Panel (UCP)

The active chilled water setpoint The chilled water reset status, in
is the setpoint that is currently in the right most column, will
use. It will be displayed to 0.1 display one of the following
degrees Fahrenheit or Celsius. messages: Return, Constant
Touching the double arrow to Return, Outdoor, None
the left of the Active Chilled The left column text “Front
Water Setpoint will take the user Panel”, “BAS”, “External”,
to the active chilled water Chilled Water Reset, and “Active
setpoint arbitration sub-screen. Chilled Water Setpoint” will
The Active Chilled Water always be present regardless of
Setpoint the result of arbitration installation or enabling those
between the front panel, BAS, optional items. In the second
and external setpoints. column “- - - -” will be shown if
that option is Not Installed,
otherwise the current setpoint
from that source will be shown.
The “Back” button provides
navigation back to the chiller
screen.

32 CVGF-SVU02B-E4
Unit Control
Panel (UCP)

The active current limit setpoint


is the current limit setpoint that
is currently in use. It will be
displayed in percent RLA.
Touching the double arrow to
the left of the Active Current
Limit Setpoint will take the user
to the active current limit
setpoint sub-screen. The active
current limit setpoint is that
setpoint to which the unit is
currently controlling. It is the
result of arbitration between the
front panel, BAS, and external
setpoints.

CVGF-SVU02B-E4 33
Unit Control
Panel (UCP)

Reports

Reports Evaporator Report Items Units


Evaporator Entering Water Temperature °C or °F
Evaporator Leaving Water Temperature °C or °F
Evaporator Saturated Refrigerant Temperature °C or °F
Evaporator Refrigerant Pressure Psia or kPa
Evaporator Approach °C or °F
Evaporator Water Flow Switch Status Flow or No Flow

Condenser Report Items Units


Condenser Entering Water Temperature °C or °F
Condenser Leaving Water Temperature °C or °F
Condenser Saturated Refrigerant Temperature °C or °F
Evaporator Refrigerant Pressure Temperature °C or °F
Condenser Refrigerant Pressure Psia or kPa
Condenser Approach Temperature °C or °F
Condenser Water Flow Switch Status Flow or No Flow
Outdoor Air Temperature, If installed °C or °F

34 CVGF-SVU02B-E4
Unit Control
Panel (UCP)

Compressor Report Items Units


Compressor Starts: ###
Compressor Running Time: Hour and minute
Oil Differential Pressure Switch Open or Closed
Oil Tank Temperature °C or °F
Vanes Position Percent open
Vanes Position Steps Steps

Motor Report Items Units


Percent RLA L1 L2 L3 Percent RLA
Amps L1 L2 L3 Amps
Volts AB, BC, CA Vac
Power Consumption, If installed xxx kW
Load Power Factor, If installed xx
Winding Temperature A °C or °F
Winding Temperature B °C or °F
Winding Temperature C °C or °F

ASHRAE Chiller Log Units


1. Current Time / Date HH:MM AM / PM MMM DD YYYY
2. Chiller Mode Stopped / Running
3. Amps L1 L2 L3 Amps
4. Volts AB BC CA Volts
5. Active Chiller Water Set Point F/ C
6. Active Current Limit Set Point %
7. Refrigerant Type 134a
8. Compressor Starts 0
9. Compressor Running Time 0:00
10. Oil Tank Temperature F/ C
11. Evaporator Entering Water Temperature F/ C
12. Evaporator Leaving Water Temperature F/ C
13. Evaporator Saturated Refrigerant Temperature F/ C
14. Evaporator Saturated Refrigerant Pressure PSIG / kPa
15. Evaporator Approach Temperature F/ C
16. Evaporator Water Flow Switch Status Flow / No Flow
17. Condenser Entering Water Temperature F/ C
18. Condenser Leaving Water Temperature F/ C
19. Condenser Saturated Refrigerant Temperature F/ C
20. Condenser Refrigerant Pressure PSIG / kPa
21. Condenser Approach Temperature F/ C
22. Condenser Water Flow Switch Status Flow / No Flow

CVGF-SVU02B-E4 35
Unit Control
Panel (UCP)

Setting Tab screens provides a Settings screen for standard CVGF:


user the ability to adjust settings
justified to support daily tasks.
The layout provides a list of sub-
menus, organized by typical
subsystem.

36 CVGF-SVU02B-E4
Unit Control
Panel (UCP)

Chiller
Description Units notes
1. Front Panel Control Type (Chilled Water, Hot Water), Chilled Water default
2. Front Panel Chilled Water Setpoint Temperature 1
3. Front Panel Current Limit Setpoint Percent 2
4. Front Panel Base Load Command On or Auto
6. Front Panel Base Load Setpoint Percent
6. Differential to Start Temperature
7. Differential to Stop Temperature
8. Setpoint Source (none, use front panel, override BAS), none default

Feature Settings
Description Units
1. Chilled Water Reset (Constant, Outdoor, Return, Disable), Disable Percent
2. Return Reset Ratio Temperature
3. Return Start Reset Temperature
4. Return Maximum Reset Temperature
5. Outdoor Reset Ratio Percent
6. Outdoor Start Reset Temperature
7. Outdoor Maximum Reset Temperature
8. External Chilled Water Setpoint (Enable, Disable), Disable
9. External Current Limit Setpoint (Enable, Disable), Disable
10. External Base Loading Setpoint (Enable, Disable), Disable
Notes:
1. Temperatures will be adjustable to 0.1 degree F or C. The Main Processor provides the minimum and maximum allowable value.
2. Adjustable to the nearest whole number percent. The Main Processor provides the minimum and maximum allowable value.

CVGF-SVU02B-E4 37
Unit Control
Panel (UCP)

Mode Overrides
Description Units Default Monitor Value Notes
1. Compressor Control Signal (Auto, Manual) Auto Percent Vane Position
[0-100] )
Evaporator Leaving Water 7
Temperature
2. Evaporator Water Pump (Auto, On), Auto 1) Evaporator Flow status
2) Override Time Remaining 3
3. Condenser Water Pump (Auto, On), Auto 1) Condenser Flow status
2) Override Time Remaining 3
4. Oil Pump (Auto, On), Auto 1) Differential pressure
2) Override Time Remaining 3
5. Clear Restart Inhibit Timer

Display Settings
Description Units Notes
1. Date Format (“mmm dd, yyyy”, “dd-mmm-yyyy”),
2. Date “mmm dd, yyyy” 4
3. Time Format (12-hour, 24-hour), 12-hour
4. Time of Day HH:mm 4
5. Keypad and Display Lockout (Enable, Disable), Disable 5
6. Display Units (SI, English), English
7. Pressure Units Absolute / Guage
8. Language (English, Selection 2, Selection 3), English 6

Notes:
3. Terminates with 10 minutes if inactivity.
4. The Date and Time setup screen formats deviate slightly from the standard screens defined above. See the time and date section for further details.
5. Enables a DynaView™ Lockout screen. All other screens timeout in 30 minutes to this screen when enabled. The DynaView™ Lockout Screen displays
a 0-9 keypad to permit the user to exit the lockout with a fixed password (1x5 x 9 + Enter). See lockout section for further details.
6. Language choices are dependent on what has been setup in the Main Processor. Language selections will include English and two alternate as
loaded by TechView™. Language shall always be the last setting listed on the Display Settings menu. This will allow a user to find language selection
if looking at an unrecognizable language.
7. Manual Compressor Control allows an operator to override the Auto Control and manually control the compressor while in operation. This is not
active during Stop mode.

38 CVGF-SVU02B-E4
Unit Control
Panel (UCP)

Each Settings subscreen consists


of a setpoints list and the current
value. The operator selects a
setpoint to change by touching
either the description or setpoint
value. Doing this causes the
screen to switch to the Analog
Settings subscreen shown
below.

{
Note: Spin buttons used to
change setpoint value.

CVGF-SVU02B-E4 39
Unit Control
Panel (UCP)

Settings with buttons only (screen has no cancel or enter key) do


accept the new selection immediately.

Note: Radio 1 and Radio 2 refer


to “touch sensitive buttons.” The
labels depend upon the setting
being controlled.

Mode Override for Enumerated Settings is shown below:

40 CVGF-SVU02B-E4
Unit Control
Panel (UCP)

The mode override analog setting subscreen is similar but offers an


Auto or Manual radio button and value setting. An Auto or Manual
selection is necessary set to the mode to override. An Enter and
Cancel Key will allow the user to Enter or Cancel the entry.
Mode Override for Analog Settings is shown below:

The date setpoint screen for setting up the is shown below: The user
must select Day, Month, or Year and then use the up or down arrows
to adjust.

CVGF-SVU02B-E4 41
Unit Control
Panel (UCP)

The time setpoint screen with a 12 hour format is shown below: The
user must select Hour, or Minute and then use the up or down
arrows to adjust. Adjusting hours will also adjust am and pm.

Note: The 24 hour format setpoint screen is similar with the am and
pm not shown.

42 CVGF-SVU02B-E4
Unit Control
Panel (UCP)

The DynaView™ Display Touch If the Display and Touch Screen


Screen Lock screen is shown Lock feature is disabled, the
below. This screen is used if the following screen will be
Display and Touch Screen Lock automatically shown if the MP
feature is enabled. 30 minutes temperature is below 32°F (0°C)
after the last key stroke this and it has been 30 minutes after
screen will be displayed and the the last key stroke. Note: the
Display and Touch Screen will be main processor is equipped with
locked out until “159 Enter” is an on-board temperature sensor
entered. which enables the ice protection
Until the proper password is feature.
entered there will be no access
to the DynaView™ screens
including all reports, all
setpoints, Auto, Stop, Alarms,
and Interlocks. The password
“159” is not programmable from
either DynaView™ or TechView™.

DISPLAY AND TOUCH SCREEN ARE LOCKED

ENTER “159 Enter” TO UNLOCK

1 2 3

4 5 6

7 8 9

Enter Cancel

CVGF-SVU02B-E4 43
Base Loading
Control Algorithm

Base Loading Control If the chiller approaches full If the current exceeds the
Algorithm current, the evaporator setpoint, the current limit
temperature drops too low, or algorithm unloads.
This feature allows an external the condenser pressure rises too
controller to directly modulate The “Capacity Limited By High
high, Tracer CH530 Adaptive.
the capacity of the chiller. It is Current” message normally
Control logic limits the loading
typically used in applications displayed while the current limit
of the chiller to prevent the
where virtually infinite sources routine is active is suppressed
chiller from shutting down on a
of evaporator load and while base loading.
safety limit. These limits may
condenser capacity are available prevent the chiller from reaching Base loading can occur using
and it is desirable to control the the load requested by the Base Tracer or an external signal.
loading of the chiller. Two Loading signal. Tracer or an external signal Base
examples are industrial process
Base Loading Control is basically Loading: Current Setpoint
applications and cogeneration
a variation of the current limit Range: (20 - 100) percent RLA.
plants.
algorithm. During base loading, Base Loading requires Tracer
Industrial process applications the leaving water control Summit and an optional Tracer
might use this feature to impose algorithm provides a load Communications Module (LLID)
a specific load on the facility’s command every 5 seconds. The
electrical system. current limit routine may limit
Cogeneration plants might use the loading when the current is
this feature to balance the below setpoint. When the
system’s heating, cooling and current is within the deadband of
electrical generation. All chiller the setpoint the current limit
safeties and adaptive control algorithm holds against this
functions are in full effect when loading command.
Base Loading control is enabled.

44 CVGF-SVU02B-E4
Base Loading
Control Algorithm

Tracer Base Loading External Base Base Loading An alternative and less radical
approach to Base Loading
The Tracer commands the chiller The CH530 accepts 2 inputs to
indirectly controls chiller
to enter the base load mode by work with external base loading.
capacity. Artificially load the
setting the base load mode The binary input is at 1A18
chiller by setting the chilled
request bit ON. If the chiller is Terminals J2-1 and J2-2
water setpoint lower than it is
not running, it will start (Ground) which acts as a switch
capable of achieving. Then,
regardless of the differential to closure input to enter the base
modify the chiller’s load by
start. While the unit is running in loading mode. The second input,
adjusting the current limit
base loading, it will report that an analog input, is at 1A17
setpoint. This method provides
status back to the Tracer. When terminals J2-2 and J2-3 (Ground)
greater safety and control
the Tracer removes the base which sets the external base
stability in the operation of the
load mode request, the unit will loading setpoint, and can be
chiller because it has the
continue to run, using the controlled by either a 2-10Vdc or
advantage of leaving the chilled
normal chilled water control 4-20mA Signal. At startup the
water temperature control logic
algorithm, and will turn off, only input type is configured.
in effect.
when the differential to stop has The graphs in Figure 16 show
been satisfied. The chilled water temperature
the relationship between input
control logic responds quicker to
and percent RLA. While in base
dramatic system changes, and
loading the active current limit
can limit the chiller loading prior
setpoint is set to the Tracer or
to reaching an Adaptive Control
external base load setpoint,
limit point.
providing that the base load
setpoint is not equal to 0 (or out
of range). If it is out of range, the
front panel current limit setpoint
is used. During base loading, all
limits are enforced with the
exception of current limit.
DynaView™ displays the
message “Unit is Running Base
Loaded.”

CVGF-SVU02B-E4 45
Base Loading
Control Algorithm

Figure 16. Base loading with external mA input and with external voltage input

Base Loading with External mA Input

100

90

80

70
%RLA

60 —— %RLA

50

40

30

20
4 6 8 10 12 14 16 18 20
mA

Base Loading using External Voltage Input

100

90

80

70
%RLA

60 —— %RLA

50

40

30

20
4 6 8 10 12 14 16 18 20
Volts

46 CVGF-SVU02B-E4
Control System
Components

Control System Components The Control Panel Devices table


corresponds to the same device
Control Panel Internally mounted
designators. Optional controls
devices
are present when a specific
For visual identification Internal optional controls package is
Control Panel mounted devices specified. Optional controls
are identified by their respective packages are: OPST Operating
schematic designation number. Status, GBAS Generic Building
Control panel items are marked Systems, EXOP Extended
on the inner back panel in the operation, and TRMM Tracer
control panel (Figure 17). communications. 1A1, 1A4, 1A5,
1A6, 1A9, 1A13, 1A19, 1A26 are
standard and present in all
configurations. Other modules
vary depending on machine
optional devices.
Figure 17. Control panel components layout

OPTIONAL

OPTIONAL

OPTIONAL

OPTIONAL

OPTIONAL

OPTIONAL

OPTIONAL

OPTIONAL

OPTIONAL

CVGF-SVU02B-E4 47
Control System
Components

Chilled and Condenser Water Head Relief Request Output Maximum Capacity Relay
Flow Interlock Circuits When the chiller is running in When the chiller has been
Condenser Limit Mode or in operating at maximum capacity
Proof of chilled water flow for Surge Mode, the head relief for over a 10 minute (TechView™
the evaporator is made by the request relay on the 1A9-J2-6 to adjustable) time period this relay
closure of flow switch 5S1 and J2-4 will be energized and can will activate. Also upon being
the closure of auxiliary contacts be used to control or signal for a less than maximum capacity for
5K1 on terminals 1X1-5 and 1A6- reduction in the entering 10 minutes, this relay will
J3-1 and J3-2. Proof of condenser water temperature. deactivate. This is located at
condenser water flow for the This is designed to prevent high LLID 1A9-J2-1 and J2-3.
condenser is made by the refrigerant pressure trip-outs
closure of flow switch 5S2 and Compressor Running Relay
during critical periods of chiller Relay activates while the
the closure of auxiliary contacts operation.
5K2 on terminals 1X1-6 and 1A6- compressor is running.
J2-1 and J2-2.

48 CVGF-SVU02B-E4
Control System
Components

Control Panel Devices


Standard Devices
Controls Field Connection
Description Package Purpose Point Terminals
1A1 Power Supply Standard #1 Converts 24 vac to 24 Vdc not for field use
1A4 Quad High Voltage Standard High Pressure Cutout not for field use
Input
1A5 Quad Relay Standard Relay #1 Chilled water pump J2-1 NO, J2-2 NC,
Output modules (Relay #1) J2-3 common
1A5 Quad Relay Standard Relay #2 Condenser water pump control J2-4 NO, J2-5 NC,
Output modules (Relay #2) J2-6 common
1A6 Dual High Voltage Standard Input 1 Condenser Flow Input J3-2 Condenser water
Input flow switch
1A6 Dual High Voltage Standard Input 2 Evaporator Flow Input J2-2 Chilled water
Input flow switch
1A9 Standard Quad Standard Relay #1 Maximum Capacity Relay J2-1 NO, J2-2 NC,
Relay Output Status J2-3 common
1A9 Standard Quad Standard Relay #2 Head Relief Request Relay J2-4 NO, J2-5 NC,
Relay Output Status J2-6 common
1A9 Standard Quad Standard Relay #3 Oil Pump J2-7 NO, J2-8 NC,
Relay Output Status J2-9 common
1A19 Standard Dual LV Standard Signal #1 Oil Differential Pressure J2-3 Binary Input Signal #1,
Binary input module Switch J2-4 Ground
1A13 Dual LV Binary Standard Signal #1 External Auto Stop, J2-1 Binary Input Signal #1,
input module J2-2 Ground
1A13 Dual LV Binary Standard Signal #2 Emergency stop J2-3 Binary Input Signal #2,
input module J2-4 Ground
1F1 Standard LLID Power Supply Transformer not for field use
Primary Circuit protection
1F2 Standard Oil Pump Motor Branch Circuit not for field use
protection
1T1 Standard Control Panel Power not for field use
Transformer ; 120:24Vac
1Q1 Standard Circuit Breaker Compressor not for field use
Motor Controller Control Power
Branch Circuit
1Q3 Standard Circuit Breaker – Module [- not for field use
LLID] Power Supply Branch
Circuit
1X1 Terminal Block Standard Control Panel Terminal Block, 1X1-5 Chilled water flow
Flow switch connections switch input
1X1-6 Condenser water flow
switch input

CVGF-SVU02B-E4 49
Control System
Components

OPST Operation Status Option


Relay output module 1A8 provide relay outs as shown:
1A8 Optional Quad Relay OPST Relay #1 MAR Alarm Relay, J2-1 NO, J2-2 NC,
Output Status (Non-Latching) J2-3 common
1A8 Optional Quad Relay OPST Relay #2 Limit Warning Relay, J2-4 NO, J2-5 NC,
Output Status J2-6 common
1A8 Optional Quad Relay OPST Relay #3 MMR Alarm Relay J2-7 NO, J2-8 NC,
Output Status (Latching) J2-9 common
1A8 Optional Quad Relay OPST Relay #4 Compressor running relay J2-10 NO, J2-11 NC,
Output Status J2-12 common

EXOP Extended Operation Option


The following modules (1A17, 1A18) are provide when this control package is specified.
1A17 Optional Dual Analog EXOP Signal #1 External Base Loading J2-2 Input #1,
Input/Output Module Setpoint input J2-3 Ground
1A17 Optional Dual Analog EXOP Signal #2 Refrigerant monitor inputs J2-5 Input #2,
Input/Output Module J2-6 Ground
1A18 Optional Dual LV Binary EXOP Signal #1 External Base Loading J2-1 Binary Input Signal #1,
input module Enable or Disable input, points J2-2 Ground
1A18 Optional Dual LV Binary EXOP Signal #2 External Hot Water Control J2-3 Binary Input Signal #2,
input module Enable or Disable input J2-4 Ground

Refrigerant Monitor Input 1A17


Analog type input 4-20ma input signal to the 1A17 J2-5 to J2-6 (ground). This represents 0-100 ppm.

TRMM TRM4 TRM5 (Tracer Comm 4, Comm 5 interface)


1A14 Optional TRM4 / TRM5 Tracer Communications J2-1 COMM+, J2-2 COMM -J2-3,
Communication COMM +J2-4, COMM -,
Interface Module

CDRP (Condenser Refrigerant Pressure Output) (1A15)


1A15 Optional Dual Analog CDRP Signal #2 Condenser Refrigerant J2-4 Output #2, J2-6 Ground
Input/output Module Pressure output
1A15 Optional Dual Analog CDRP Signal #1 Percent RLA Compressor J2-1 Output #1, J2-3 Ground
Input/output Module Output

50 CVGF-SVU02B-E4
Control System
Components

CDRP Refrigerant Pressure Temperature based


Output Option 1A15: On standard machines the
Percent Condenser Pressure
Refrigerant Pressure Output can Indication Output is based on the
be configured at commissioning Saturated Condenser Refrigerant
to correspond to either A) the and a temperature to pressure
absolute condenser pressure, or conversion is made.
B) the differential pressure of the
evaporator to condenser If the Condenser Saturated
pressures. Temperature goes out of range
due to an open or short, a
This output is located at 1A15- pressure sensor diagnostic will
J2-4(+) to J2-6 (ground) be called and the output will also
The Output can source a go to the respective out of range
maximum of 22 mA of current. value. That is, for an out of range
A) Condenser Pressure Output. low on the sensor, the output
2 to 10 Vdc corresponds to 0 will be limited to 2.0 Vdc. For an
Psia to the HPC (in Psia) setting. out of range high on the sensor,
the output will be limited to 10.0
Vdc.
Figure 18.

CAP
10 vdc

2 vdc

0 PSIA HPC in PSIA


0 Percent 100 Percent

CVGF-SVU02B-E4 51
Control System
Components

B) Refrigerant Differential Pressure The Minimum Delta Pressure


Indication Output: Calibration setting has a range of
A 2 to 10 Vdc analog output is 0-400 psid (0-2758 kPa) in
provided instead of the previous increments of 1 psid (1kPa). The
condenser pressure output Maximum Delta Pressure
signal. This 2 signal corresponds Calibration setting has a range of
to a predetermined minimum 1-400 psid (7-2758 kPa) in
and maximum pressure settings increments of 1 psid (1kPa). The
setup at commissioning of this condenser refrigerant pressure is
feature. This relationship can be based on the Condenser
altered using TechView™ if Refrigerant Temperature sensor.
required. The evaporator refrigerant
The “Minimum Delta Pressure“ pressure is based on the
is typically set to 0 psi and will Saturated Evaporator Refrigerant
then correspond to 2 Vdc. The Temperature Sensor.
“Maximum Delta Pressure “ is
typically set to 30 psi and
corresponds to 10 Vdc.

Figure 19. Delta pressure setting

10 vdc

2 vdc

Minimum Delta Maximum Delta


Pressure Setting Pressure Setting

52 CVGF-SVU02B-E4
Control System
Components

GBAS (Generic Building Automation System)


1A15 Optional Dual GBAS Signal #1 Percent RLA Compressor Output J2-1 Output #1, J2-3 Ground
Analog Input/output
Module
1A15 Optional Dual GBAS Signal #2 Condenser Rerigerant Pressure J2-4 Input #2, J2-6 Ground
Analog Input/output or Evaporator/Condenser
Module differential

1A16 Optional Dual GBAS Signal #1 Chilled Water Reset input, or J2-2 Input #1, J2-3 Ground
Analog Input/output External Chiller Water Setpoint
Module
1A16 Optional Dual GBAS Signal #2 External Current limit Setpoint J2-5 Input #2, J2-6 Ground
Analog Input/output
Module

Percent RLA Output Figure 20. Voltage versus percent RLA


2 to 10 Vdc corresponding to 0
to 120% RLA. With a resolution
Voltage versus Percent RLA
of 0.146%. The Percent RLA
Output is polarity sensitive.
The following graph illustrates
the output:
Percent RLA

Voltage

CVGF-SVU02B-E4 53
Control System
Components

External Chilled Water Setpoint Power Input Voltage: 23VRMS


(ECWS) minimum, 27VRMS Nominal,
The External Chilled Water 30VRMS maximum
Setpoint allows the chilled water Frequency: 50-60 Hz
setpoint to be changed from a
remote location. The External Current: Full load 27 Vac – 4.30 A
Chilled Water Setpoint is found (RMS)
on 1A16 J2-2 to J2-3 (ground). Inrush 27 Vac (RMS) ~ 30A
2-10 Vdc and 4-20 mA (RMS)
correspond to a 0 to 65°F (-17.8
Power Output: Class II Voltage 24
to 18.3°C) CWS range.
Vdc, Rated Current 2.44 Amps.
External Current Limit Setpoint
1A4, 1A6, Dual high Voltage
The External Current Limit is an
Binary input module:
option that allows the current
Binary Input Signal #1 J2-1 to 2
limit setpoint to be changed
from a remote location. The Binary Input Signal #2 J3-1 to 2
External Limit Setpoint is found High Voltage Binary Input: Off
on 1A16 J2-5 to J2-6 (ground), Voltage: 0 to 40 Vac RMS , On
2-10 Vdc and 4-20 mA each Voltage: 70 to 276 Vac RMS
correspond to a 40 to 120
percent RLA range. CH530 limits Input is not polarity sensitive
the maximum ECLS to 100 (Hot and neutral can be
percent. switched), Input impedance 130K
to 280K ohms
Module Characteristics
14-26 AWG with a maximum of
1A1, Power Supply : two 14 AWG
Unit Control Power Supply
Module Converts 27 Vac to 24 Power, 24 +/- 10 percent Vdc, 20
Vdc. mA maximum. Trane IPC3
protocol. J1-1 +24Vdc, J1-2
Ground, J1-3 COMM +, J1-4
COMM -

54 CVGF-SVU02B-E4
Control System
Components

1A5, 1A8, 1A9 Quad Relay Output 1A13, 1A18, 1A19, 1A24 Dual
Status: Binary input module:
Relay #1 J2-1 NO, J2-2 NC, J2-3 J2-1 Binary Input Signal #1, J2-2
common Ground, J2-3 Binary Input Signal
Relay #2 J2-4 NO, J2-5 NC, J2-6 #2, J2-4 Ground
common Binary Input: Looks for a dry
Relay #3 J2-7 NO, J2-8 NC, J2-9 contact closure. Low Voltage 24V
common 12 mA.
Relay #4 J2-10 NO, J2-11 NC, 14 - 26 AWG with a maximum of
J2-12 common two 14 AWG
Relay Outputs: at 120 Vac: 7.2 Power, 24 +/- 10 percent Vdc, 40
Amps resistive, 2.88 Amps pilot mA maximum Trane IPC3
duty, 1/3 HP, 7.2 FLA, at 240 Vac: protocol.
5 Amps general purpose 14-26 1A14 Communication interface
AWG, two 14 AWG Maximum Module
Power, 24 Power, 24 ± 10 percent Vdc, 50
±10 percent Vdc, 100 mA mA maximum. Trane IPC3
maximum. Trane IPC3 protocol. protocol.

1A14 Communication Polarity


J1-1 +24 Vdc J2-1 COMM +. J11-1+24 Vdc
J1-2 Ground J2-2 COMM - J11-2 Ground
J1-3 COMM + J2-3 COMM + J11-3 COMM +
J1-4 COMM - J2-4 COMM - J11-4 COMM

CVGF-SVU02B-E4 55
Control System
Components

1A15, 1A16, 1A17, Dual Analog Analog Input:


Input/output Module; The analog input can be
Analog Output: The Analog software switched between a
Output is a voltage only signal. voltage input or a current input.
2-10 Vdc at 22mA When used as a current input a
J2: 14 - 26 AWG with a 200 Ohm load resistor is
maximum of two 14 AWG switched in.
J2-1 Output #1 to J2-3 (ground), 0-12 Vdc or 0-24 mA Analog Inputs
J2-4 Output #2 to J2-6 (ground). CH530 accepts either a 2-10 Vdc
or 4-20 analog input suitable for
CH530 provides a 2-10 Vdc customer external control. The
analog signals as Outputs. The type is determined at unit
Output’s maximum source commissioning during feature
capability is 22mA. The installation.
maximum recommended length
to run this signal is included in J2: 14-26 AWG with a maximum
the table below. of two 14 AWG
J2-2 Input #1 to
J2-3 (ground).
J2-5 Input #2 to
J2-6 (ground).
Power, 24 +/- 10 percent Vdc, 60
mA maximum, Trane IPC3
protocol.

Maximum Length to Run external Output signals


Gauge Ohms per Foot Length (Feet) Length (Meters)
14 0.00 2823 1062.7 324
16 0.004489 668.3 203.8
18 0.007138 420.3 128.1
20 0.01135 264.3 80.6
22 0.01805 166.3 50.7
24 0.0287 104.5 31.9
26 0.04563 65.7 20
28 0.07255 41.4 12.6
Note: the above table is for copper conductors only.

56 CVGF-SVU02B-E4
Control System
Components

Note: If the chiller is operating in Temperature Sensors Starter Module


a limit mode (current limit, Evaporator entering 4R6 In the hierarchy of modules the
condenser limit, evaporator Evaporator leaving 4R7 Starter module 2A1 (1A23 when
limit, and so forth), the limit Condenser entering 4R8 customer-supplied starter
operation has priority over all Condenser leaving 4R9 specified) is second only to the
DynaView™ manual modes of Oil temperature 4R5 DynaView™.
operation. Outdoor air 4R13 The starter module is present in
On each CH530 power-up, the Evaporator saturated refrigerant all starter selections. This
inlet guide vanes are driven full 4R10 includes Wye Delta, Across the
closed to recalibrate the zero Condenser saturated refrigerant Line, and Solid State whether
position (steps) of the Stepper 4R11 remote unit mounted or supplied
motor vane actuator. Probe Operating Temperature by others. The starter module
Motor Temperature Sensor Range -40 to 121°C provides the logic to provide the
Module Accuracy± 0.250°C over the motor protection for current
The motor temperature module range - 20 to 50°C ± 0.50°C over overload, phase reversal, phase
1A26 connects using unit wiring the range -40 to 121°C loss, phase imbalance, and
to the three motor winding momentary power loss.
temperature sensors. This
module is located in the control
panel where the module is
connected to the IPC bus.

CVGF-SVU02B-E4 57
Control System
Components

Electrical Sequence With the supply power 2. Circuit Breaker 1Q3 which
This section will acquaint the disconnect switch or circuit provides power to
operator with the control logic breaker (2Q1 or 2K3) on, 115-volt Transformer (1T1) which steps
governing chillers equipped with control power transformer 2T5 down the 115 Vac to 24 Vac.
Tracer CH530 control systems. and a 15-amp starter panel fuse This 24 Vac then powers the
Note: The typical wiring (2F4 ) to terminal (2X1-1) starter 24 Vdc power supply 1A1, and
diagrams are representative of panel to terminal 1X1-1 in the 1A2 if present. The 24 Vdc is
standard units and are provided control panel. From this point, then connected to all modules
only for general reference. They control voltage flows to: using the IPC Bus providing
may not reflect the actual wiring 1. Circuit Breaker 1Q1 which module power. 1Q3 also
of your unit. For specific provides power to the starter provides power to the
electrical schematic and module (2A1) relay outputs external chiller water proof of
connection information, always and the High Pressure Cutout flow device connected
refer to the wiring diagrams that switch (4S1). between terminal block
shipped with the chiller. 1X1-5 to 1A6-J3-2, and
condenser water proof of flow
device connected at 1X1-6 to
1A6-J2-2.
3. The DynaView™ display
module 1A22, receives 24 Vdc
power from the IPC bus.

58 CVGF-SVU02B-E4
Control System
Components

CH530 and Wye-Delta Based on the restart inhibit 3. Close start contactor (2K1)
Starter Control Circuits function and the differential to and check for no current - 500
start setpoint, oil pump (4M3) msec. If currents are detected,
(Sequence of Operation) will be energized by 1A9 module the MMR diagnostic ‘‘Starter
Logic Circuits within the various (1A9-J2-7). The oil pressure Fault Type I’’ is generated and
modules will determine the switch must be closed for 30 closes for one second.
starting, running, and stopping continuous seconds and 4. Delay time - 200 msec.
operation of the chiller. When condenser water flow verified (Opens 2K1).
operation of the chiller is within 4 minutes 15 seconds for
required the chiller mode is set the compressor start sequence 5. Close shorting contactor,
at ‘‘Auto.” Using customer- to be initiated. (2K3) and check for no current
supplied power, the chilled water (1A23 or 2A1 J4-1) for one
When less than 5 seconds second. If currents are
pump relay (5K1) is energized by
remain before compressor start, detected the MMR diagnostic
the 1A5 Module output at 1A5-
a starter test is conducted to ‘‘Starter Fault Type II’’ is
J2-4, and chilled water flow must
verify contactor state prior to generated. (Starter Integrity
be verified within 4 minutes 15
starting the compressor. The test)
seconds by the 1A6 module. The
following test or start sequence
main processors logic decides to 6. If no diagnostics are
is conducted for “Wye-Delta”
start the chiller based on the generated in the above tests,
starters:
differential to start setpoint. With the stop relay (2A1- J10) is
the differential to start criteria 1. Test for transition complete closed for two seconds and
met module 1A5 then energizes contact open (1A23X or the start relay (2A1-J8) is
the condenser water pump relay 2A1-J12-2) –160 to 240 msec. closed to energize the start
(5K2) using customer-supplied An MMR diagnostic will be contactor (2K1).
power at 1A5 J2-1. generated if the contact is
closed.
2. Delay time - 20 msec.

CVGF-SVU02B-E4 59
Control System
Components

The shorting contactor (2K3) 10. The run contactor (2K2) is An MMR diagnostic will be
has already been energized closed through relay 2A1-J6, generated if the transition
from (F) above. The shorting out the transition complete contacts (2K2-AUX) do
compressor motor (4M1) starts resistors 260 milliseconds not close.
in the “Wye” configuration, an after the opening of the Now that the compressor motor
auxiliary contact (2K1-AUX) shorting relay 2A1-J4. This (4M1) is running in the “Delta”
locks in the start contactor places the compressor motor configuration, the inlet guide
(2K1) coil. in the “Delta” configuration vanes will modulate, opening
7.After the compressor motor and the starter module waits and closing to the chiller load
has accelerated and the to look for this transition for variation by operation of the
maximum phase current has 2.35 seconds through the stepper vane motor actuator
dropped below 85 percent of closure of the transition (4M2) to satisfy chilled water
the chiller nameplate RLA for complete contacts 2K2- AUX setpoint. The chiller continues to
1.5 seconds, the starter at module 2A1-J12 input. run in its appropriate mode of
transition to the “Delta” 11. The starter module must now operation: Normal, Softload,
configuration is initiated. confirm closure of the Limit Mode, and so forth
8.The transition contactor (2K4) transition complete contact
is closed through relay 2A1-J2, (2K2- AUX) within 2.32 to
placing the transition resistors 2.38 seconds after the run
(2R1, 2R2, and 2R3) in parallel relay (2A1-J6) is closed.
with the compressor motor Finally, the transition relay
windings. (2A1-J2) is opened de-
energizing the transition
9.The shorting contactor (2K3) is contactor (2K4) and the
opened through the opening compressor motor starting
of relay 2A1-J4 100 msec after sequence is complete.
the closure of the transition
relay 2A1-J2.

60 CVGF-SVU02B-E4
Control System
Components

If the chilled water temperature If the <STOP> key is pressed on


drops below the chilled water set the operator interface, the chiller
point by an amount set as the will follow the same stop
“differential to stop” setpoint, a sequence as above except the
normal chiller stop sequence is chilled water pump relay (1A5-
initiated as follows: J2) will also open and stop the
1. The inlet guide vanes are chilled water pump after the
driven closed for 50 seconds. chilled water pump delay timer
has timed out after compressor
2. After the 50 seconds has shut down.
elapsed, the stop relay (2A1-
J10) and the condenser water If the “Immediate Stop” is
pump relays (1A5-J2) open to initiated, a panic stop occurs
turn off. The oil pump motor which follows the same stop
(4B3) will continue to run for 1 sequence as pressing the
minute post-lube while the <STOP> key once except the
compressor coasts to a stop. inlet guide vanes are not
The chilled water pump will sequence closed and the
continue to run while the compressor motor is
Main processor module immediately turned off.
(1A22) monitors leaving
chilled water temperature
preparing for the next
compressor motor start based
on the “differential to start”
setpoint.

CVGF-SVU02B-E4 61
Machine Protection
and Adaptive

Machine Protection and The oil pump will be run for the
Adaptive Control post-lube time period when
power returns. The compressor
Momentary Power Loss (MPL) and compressor motor are
Protection protected from damage from
Momentary power loss detects large torques and inrush
the existence of a power loss to currents resulting from
the compressor motor and reconnecting the compressor
responds by initiating the motor to the power source
disconnection of the compressor following a momentary loss of
motor from the power source. power.
Power interruptions of less than MPLs greater than 2 or 3 cycles
30 line-cycles are defined as are detected resulting in unit
momentary power losses. Tests shut down. Disconnection from
have shown that these short- the line is initiated within 6 line-
term power interruptions can be cycles of the power loss. MPL
damaging to the motor and protection is active anytime the
compressor if the chiller is compressor is in the running
reconnected to the line while the mode. (The transition complete
motor and line phases do not input has been satisfied.)
match. The chiller will be shut
down when a MPL is detected Note: MPL is defaulted to
and will display a non-latching enabled however can be
diagnostic indicating the failure. disabled, if required using
TechView™.

62 CVGF-SVU02B-E4
Machine Protection and
Adaptive

Figure 21. CVGF sequence of operation: momentary power loss, (DynaView™ and starter module remain
powered)

Momentary Power Momentary Power Loss Cleared


Loss Detected and Need to Cool

Compressor
Starting
Running Shutting Down Waiting to Start

Enforce Power Up Delay Timer

Close IGV (0-50 Seconds) Establish Condenser Water Flow


(6 Second Minimum)

Command IGV Closed Energize Condenser


Water Pump Relay

Confirm Condenser Water Flow Within 4


minutes 15 seconds (6 Second Filter)

Enforce Restart Inhibit Timer (30 Minutes)

De-Energize
Compressor

Confirm No Compressor Currents


Within 0-30 Seconds

De-Energize Condenser
Water Pump Relay

CVGF-SVU02B-E4 63
Machine Protection and
Adaptive

Current Overload Running Overload Protection Overload Must Hold = 102


Protection In the run mode, a time trip Percent RLA.
curve is looked at to determine if Overload Must Trip in 20 (+0 -3)
Motor currents are continuously a diagnostic should be called.
monitored for over current seconds = 112 Percent RLA
The starter LLID continuously
protection and locked rotor monitors compressor line (Note the above gives a nominal
protection. This protects the currents to provide running 20 seconds must trip point of
chiller from damage due to overload and locked rotor 107 Percent RLA.)
current overload during starting protection. Overload Must Trip in 1.5
and running modes but is seconds = 140 Percent RLA
allowed to reach full load amps. Overload protection is based on
the line with the highest current. (Nominal)
This overload protection logic is
independent of the current limit. It triggers a manually resettable The time trip curve is as follows:
The overload protection will diagnostic shutting down the
ultimately shut the unit down compressor when the current
anytime the highest of the three exceeds the specified time trip
phase currents exceeds the time curve. The compressor overload
trip curve. A manual reset time trip curve is expressed as a
diagnostic describing the failure percent of the RLA of the
will be displayed. compressor and is not
adjustable:
Overload protection for the
motor starts based on the
maximum time to transition
permitted for a particular motor.

Figure 22. Overload time trip versus percent RLA

Nominal Triptime
(Sec)

Minimum Triptime
(Sec)

Maximum Triptime
(Sec)

64 CVGF-SVU02B-E4
Machine Protection and
Adaptive

Current Limit Protection Compressor motor current is Phase Loss Protection


continuously monitored and Loss of phase detection protects
Current Limit Protections exist to
current is controlled using a the chiller motor from damage
avoid motor current overload
limit function to prevent running due to a single-phasing
and damage to the compressor
into overload diagnostic trips. condition. The controls will shut
motor during starting and
The current limit control logic down the chiller if any of the
running.
attempts to prevent the motor three phase currents feeding the
The Current Limit Setpoint (CLS) from shutting down on a motor are lost. The shutdown
can be changed from: Front diagnostic trip by limiting will result in a latching
Panel, External Analog input compressor current draw diagnostic indicating the failure.
(with GBAS option), or Tracer relative to an adjustable current
(Tracer option). Tracer current limit DynaView™ CLS. Reverse Rotation
setpoint has the highest priority,
unless disabled in the
This setpoint can also be Protection
lowered to provide electrical This function protects the
DynaView™ Setpoint source
demand limiting on the unit as compressor from damage
override menu. The External CLS
required. This could also be set caused by being driven in the
has second priority, and will be
to allow the chiller to continue to reverse direction. Incorrect
used if Tracer is disabled or not
run at a lower load to avoid phase rotation detection results
installed. The Front Panel
tripping off using a diagnostic. in a manually resettable
Setpoint has the lowest priority,
and will be used if Tracer and the The Current Limit function uses diagnostic. Phase Reversal
External CLS are both disabled. a PID algorithm (similar to the protection default is set to
Leaving Water Temperature enable, however can be disabled
control) that allows the chiller to using TechView™.
run at the CLS. At machine
startup, or with any setpoint
change the new current limit
setpoint reached after the
filtered setpoint time elapses.
The minimum current limit
setpoint is default set to 40
percent RLA (20-100 percent).
The filtering time default is set
to 10 minutes (0-120 minutes);
however these can be altered
using the TechView™. This
filtered setpoint allows for stable
control if the Current Limit
setpoint is adjusted during a run.

CVGF-SVU02B-E4 65
Machine Protection and
Adaptive

Differential to Start or Stop There are three independent Minimum and Maximum
The Differential to Start setpoint Softload setpoints: Capacity Limit
is adjustable from 1 to 10°F (0.55 • Capacity Control Softload Time A Minimum Capacity can be set
to 5.5°C) and the Differential to default is to 10 minutes and to limit the unloading ability of
Stop setpoint adjustable from 1 settable from 0-120 minutes. the compressor forcing
to 10°F (0.55 to 5.5°C). Both This setting controls the time differential stop to be reached
setpoints are with respect to the constant of the Filtered Chilled cycling the chillers. Minimum
Active Chilled Water Setpoint. Water Setpoint. capacity limit will be displayed
When the chiller is running and when in this limit mode. This
the Leaving Water Temperature • Current Limit Control Softload
Time default is 10 minutes and indicates when the chiller is
(LWT) reaches the Differential to running fully unloaded. Similarly
Stop setpoint the chiller will go settable from 0-120 minutes.
This setting controls the time a maximum capacity can be set
through its shutdown sequence to limit normal chilled water
to Auto. Reference Figure 10. constant of the Filtered Current
Limit Setpoint. temperature control. The
maximum capacity relay is
SoftLoading • Current Limit Softload Starting energized which is a signal used
Softloading stabilizes the startup Percent default is 40 percent by generic BAS systems to start
control during the initial chiller RLA and settable from 20-100 another chiller.
pulldown. Soft loading is used to percent. This setting controls
bring the building loop the Starting point of the The minimum (default at 0
temperature from its start value Filtered Current Limit Setpoint. percent) and maximum (default
to the Chilled Water or Hot Water at 100 percent) capacity are
Note: TechView™ provides adjustable using TechView™.
Setpoint in a controlled manner.
access to these three setpoints.
Without soft loading, the chiller
controls will load the chiller
rapidly and use the full chiller
capacity to bring the loop
temperature to setpoint.
Although the start temperature
of loop may have been high, the
actual system load may be low.
Thus, when the setpoint is met
the chiller must unload quickly
to the system load value. If it is
not able to unload quickly
enough, the supply water
temperature will drop below
setpoint and may even cause the
chiller to cycle off. Soft loading
prevents the chiller from going
to full capacity during the
pulldown period. After the
compressor has been started,
the starting point of the filtered
setpoint is initialized to the value
of the Evaporator Leaving Water
temperature and the percent
RLA.

66 CVGF-SVU02B-E4
Machine Protection and
Adaptive

Evaporator Limit Evaporator Limit uses the The Leaving Water Temperature
Evaporator refrigerant Evaporator Refrigerant Cut-out Setpoint is
temperature is continuously Temperature sensor in a PID independently adjustable from
monitored to provide a limit algorithm (similar to the Leaving the chilled water setpoint.
function that prevents low Water Temperature control) that Shutdown of the compressor
refrigerant temperature trips. allows the chiller to run at the due to violation of the Leaving
This allows the chiller to LRTC + 2 degree F (1.1°C). Water Temperature Cut-out
continue to run at a reduced When actively limiting machine results in an automatically
load instead of tripping off at the control “Evaporator resettable diagnostic (MAR). The
Low Refrigerant Temperature Temperature Limit” will be DynaView™ Operating Mode
Cutout Setpoint (LRTC). displayed as a suboperating indicates when the Leaving
mode. Water Temperature Cut-out
Evaporator limit could occur
Setpoint conflicts with the
with an initial pulldown of a loop
Leaving Water Temperature chilled water temperature
temperature where the
setpoint by a message on the
condenser is colder than the Cut-out display. The Leaving Water
evaporator (inverted start), and Leaving water temperature Temperature Cutout Setpoint
the evaporator refrigerant cutout is a safety control that and chilled water setpoint, both
temperature may drop below the protects the chiller from damage active and front panel, are
LRTC. This limit prevents the caused by water freezing in the separated by a minimum of
unit from shutting down on a evaporator. The cutout setpoint 1.7°F (0.94°C). (See Cut-out
diagnostic during this type of is factory set at 36°F (2.2°C) Strategy Figure 23.) When either
pulldown. Another example is a however is adjustable with difference is violated, the CH530
chiller that is low on refrigerant TechView™. The cut-out strategy does not permit the above
charge. It will run with low is illustrated in Figure 23. differences to be violated and
evaporator refrigerant
the display exhibits a message
temperatures. This limit allows
to that effect and remains at the
the chiller to continue to run at a
last valid setpoint. After violation
reduced load.
of the Leaving Water
Temperature Cut-out Setpoint
for 30°F (16.7°C) seconds the
chiller will shutdown and
indicate a diagnostic.

Low Refrigerant
Temperature Cut-out
The purpose of the low
evaporator refrigerant
temperature protection is to
prevent water in the evaporator
from freezing. When the LRTC
trip point is violated, a latching
diagnostic indicating the
condition is displayed. The LRTC
Diagnostic is active in both the
Running and Stopped modes.

CVGF-SVU02B-E4 67
Machine Protection and
Adaptive

Figure 23. Cutout strategy

Chilled-Water Set Point

Differential to stop
adjustment range

X degrees minimum differential Y degrees minimum


differential
Evaporator leaving-water
temperature cutout 2°F (1.1°C)
0.5°F (0.28°C) 2.5°F (1.36°C)

Integrate to trip
Evaporator
Limit loading limit
Evaporator limit set point Hold

Unload

Evaporator refrigerant
temperature cutout

Condenser Limit The Condenser Limit will be


Condenser pressure is based on a pressure conversion
continuously monitored to from the Condenser Refrigerant
provide a limit function that Temperature sensor. When
prevents High Pressure Cutout limited by this action,
(HPC) trips. This protection is “Condenser Pressure Limit” will
called Condenser Refrigerant be displayed as a sub-operating
Pressure Limit, or High Pressure mode.
Limit. A fully loaded compressor, The Condenser Limit Setpoint is
operating at high Evaporator factory set (93 percent of HPC),
Leaving Water Temperature however can be changed using
(ELWT) and high condenser TechView™.
temperatures causes high
condenser pressures. The
purpose of this limit is to avoid
HPC trips by allowing the chiller
to continue to run at a lower
load instead of tripping off using
HPC.

68 CVGF-SVU02B-E4
Machine Protection and
Adaptive

Restart Inhibit Note: When the start is inhibited If enhanced oil temperature
This function provides short by the restart inhibit function, protection is disabled or below a
cycle protection for the motor, the time remaining will be given Low Oil Temperature
and indirectly also short cycling displayed along with the restart Inhibit setting (default 95°F/35°C)
protection for the starter since inhibit mode. There is no ‘free’ the compressor cannot be
the starter is designed to operate start on a power up of the MP started. This is an inhibit mode
the motor under all the since a real time clock is used to and will be reported to the
conditions of motor determine when the next start operator interface.
performance. will be allowed based on the
start time of the previous start. The oil heater is energized in an
Restart Inhibit Function Using attempt to raise the oil
Time Base Low Oil Temperature Start Inhibit temperature over this inhibit
This method uses straight start- When oil temperature is at or temperature setpoint. The
to-start timer to determine when below the low oil temperature compressor is inhibited from
to allow the next start. A Restart start inhibit setpoint (80- starting until the oil temperature
Inhibit Start-to-Start Time 140°F/26.7-60°C), the heater is is raised 5°F (2.7°C) or more
setpoint is used to set the energized to raise the oil degrees above this setpoint.
desired start-to-start time. temperature.
The Low Oil Temperature Start
Default is 20 minutes and can be Low oil temperature is indicative Inhibit is tested on every start
altered using the TechView™. A of refrigerant dilution in the oil. unless a quick restart is being
time based restart inhibit Oil temperature is used to performed during post-lube.
function is used if the Restart estimate this dilution since the
oil temperature directly If the Enhanced Oil Temperature
Inhibit Type is set to ‘Time’ using Protection setting is enabled, the
TechView™ or if the motor corresponds to amount of
refrigerant dilution in the oil. It is Low Oil Temperature Start
winding temperatures are Inhibit value is 136°F (57.8°C).
determined to be invalid. required that oil contains
minimal refrigerant in it. This is If the Enhanced Oil Temperature
accomplished by boiling the Protection setting is not enabled,
refrigerant out of the oil by the Low Oil Temperature Start
maintaining a high enough oil Inhibit value is settable with the
temperature. Low Oil Temperature Start
Inhibit Setpoint using the
TechView™.

CVGF-SVU02B-E4 69
Machine Protection and
Adaptive

Oil Temperature Control High Oil Temperature Cutout Controls Chilled Water Reset
The oil heater is used to This is a latching diagnostic
maintain the oil temperature
(CWR)
resulting in an immediate
within +/- 2.5°F (1.4°C) of the oil shutdown. Default Setpoint Chilled water reset is designed
temperature control setpoint. The value: 165°F (73.9°C) for those applications where the
oil heater is commanded off when Implemented to avoid design chilled water temperature
the oil pump is commanded on. overheating of the oil and the is not required at partial load. In
bearings. these cases, the leaving chilled
If the oil temperature is at or
water temperature setpoint can
below the Low Oil Temperature If the oil temperature is at or be reset upward using the CWR
Cutout setpoint, this diagnostic above the High Oil Temperature features.
will be issued and stops the Cut-out setpoint this diagnostic
compressor. This diagnostic is will be issued, which will stop When the CWR function is based
ignored for the first 10 minutes the compressor. If Oil on return water temperature, the
of compressor run. After that, if Temperature violates this CWR feature is standard. When
the oil temperature falls below temperature cut-out for more the CWR function is based on
this cutout temperature for more than 120 seconds, this diagnostic outdoor air temperature, the
than 60 consecutive seconds this is issued. CWR feature is an option
diagnostic is issued. requiring an outdoor
Manual Oil Pump Control temperature sensor.
Low Oil Temperature Cutout The oil pump control accepts
If the oil temperature is at or commands to turn on the oil The type of CWR is selected in
below the Low Oil Temperature pump. The manual oil pump the Operator Interface settings
Cutout, for more than 60 choices will be “Auto” or “On.” Menu along with the Reset Ratio,
consecutive seconds this When the oil pump is Start Reset Setpoint, and the
diagnostic will be issued commanded “On,” it will revert Maximum Reset Setpoint.
stopping the compressor. to “Auto” in 10 minutes, and is
This diagnostic does not take adjustable at DynaView™ or
affect during the first 10 minutes TechView™.
of compressor run.

70 CVGF-SVU02B-E4
Machine Protection and
Adaptive

High Lift Unloading (500 Ton The HLUV valve does not Note: There is noticeable noise,
Family Only) modulate the flow rate, but due to gas flow, when the high
rather is either open or closed. lift unloading valve is open.
High Lift Unloading Valve directs Further, the valve was sized to
discharge gases from the Functional Description
handle a mass flow sufficient to The following equation
condenser through a solenoid permit operation below 35% IGV
valve directly into the determines action of the high lift
position but not necessarily to unloading function:
economizer. From the 0%. The valve was sized to
economizer, this gas then flows permit substantial but Trigger IGV% = 0.98 * Lift + -
to the second stage compressor incomplete unloading and yet 0.065 * CPIM + C
where the economizer normally was kept as small as practicable Where Lift is defined as
is connected. The purpose of to minimize power requirements Condenser Saturated Refrigerant
HLUV is to increase the gas flow with HLUV operation. Temperature minus Evaporator
rate through the second stage Saturated Refrigerant
compressor. Bypass gas is Not all CVGF chillers require the
bypassing of condenser gas. In Temperature in °F. The CPIM is
allowed to occur using an inline the average impeller diameter in
normally closed solenoid valve. some tonnages, the High Lift
Unloading Valve and copper inches times 100.
The high lift unloading function
is dependent on the lift (where lines do not exist. The LLID (1A9)
lift is defined as the difference with the High Lift Unloading
between Condenser Saturated relay always exists.
Refrigerant Temperature and the
Evaporator Saturated Refrigerant
Temperature) and on chiller load.
When the high lift unloading
mode is entered, the High Lift
Unloading valve is opened and
the inlet guide vane close travel
is limited.

CVGF-SVU02B-E4 71
Machine Protection and
Adaptive

High Lift Unloading Solenoid


The normally open contact of a CH530 control relay powers the normally closed high lift unloading valve
solenoid with the following logic:

LLID Relay High Lift Unloading High Lift


State Valve Solenoid Unloading Valve Function
De-energized De-energized Closed No condenser gas bypass
Energized Energized Open Bypass condenser gas

The high lift unloading valve Compressor Start Up Chiller Shutdown


opens if the compressor is At compressor startup, the The high lift unloading valve is
running and the IGV position is chiller is initialized as to not be normally closed (de-energized).
at or below the Trigger IGV% line in high lift unloading. The rules There is no check performed to
– 5%. The high lift unloading to enter high lift unloading mode ensure the valve is closed without
valve closes when the IGV are as stated above. Also at using TechView™.
position reaches the Trigger startup, sufficient time should be
IGV% + 5% or the compressor allowed so that an accurate
shuts down. Trigger IGV% may be calculated.
Note that this 5% is of the full Here non-saturated conditions
IGV travel range of 100%. Also exist right away resulting in
note that operation of the high unstable temperature
lift unloading valve is measurements.
independent of the high lift
unloading limit mode as stated Manual Capacity Control
below. This is the Compressor Control
Signal mode override in
High Lift Unloading Limit Mode DynaView™. Here high lift
For a Gear Drive chiller, the unloading solenoid valve
minimum IGV position is 60% of operation, 60% of the Trigger
the Trigger IGV%. When the IGV IGV% and displaying of the high
movement is being limited to the lift unloading limit submode is
60% of the Trigger IGV% point, obeyed.
the high lift unloading limit
submode is displayed.

72 CVGF-SVU02B-E4
Unit
Startup

Pre-Commissioning Bump The following checks require 7. After three seconds, activate
Start Procedure TWO personnel to complete. the emergency stop by
During the bump start of the pressing the Immediate Stop
Note: The following procedure is compressor, one person will look button at the CH530 twice in
a requirement prior to the first at the rotor from the rear of the quick succession. During this
start of the chiller. Failure to motor through the sight glasses three second period, the rotor
complete may result in damage to determine correct direction. should be seen to rotate in a
to the compressor and void the Looking at the sight glass, the counter-clockwise direction.
warranty. direction will be counter- 8. If the direction is incorrect, the
Procedure clockwise. Do not check the 3 phases must be isolated
1. Complete all control settings. rotation of the motor after the from the power source and
start sequence has completed as two legs swapped to obtain
2. Ensure water flows in the the indication may be incorrect.
condenser and evaporator are the correct direction.
correct according to the pre- 5. With the voltage applied to the
commissioning procedures. mains on the starter, place the
chiller in Auto mode.
3. Ensure the unit has been
charged with the correct 6. After the pre-lube is complete,
amount of refrigerant and oil let the starter energize the
and that the oil is the proper motor, permitting a start.
operating temperature.
4. Complete a phase rotation test
if the voltage is less than 600
volts.

CVGF-SVU02B-E4 73
Unit
Startup

Unit Startup 4. Check the chilled water Oil pressure must be verified
setpoint and readjust it, if within 3 minutes or a MMR
Unit Start-Up Procedures
necessary, in the Chiller diagnostic is generated.
Daily Unit Start-Up Settings menu. When less than 5 seconds
1. Verify the chilled water pump 5. Check the current limit remain on the restart inhibit, the
and condenser water pump setpoint and readjust it, if pre-start test is conducted on Y-
starter are in “ON” or necessary, in the chiller Delta starters. If faults are
“AUTO.” settings menu. detected, the unit’s compressor
2. Verify the cooling tower is in 6. Press <AUTO>. will not start, and a MMR
“ON” or “AUTO.” Diagnostic will be generated.
Next, the CH530 checks the
3. Check the oil tank oil level; the leaving evaporator water Note: Whenever the CH530
level must be visible in or temperature and compares it to detects a MMR diagnostic
above the lower sight glass. the chilled water setpoint. If the condition during start-up, unit
Also be sure to check the oil tank difference between these values operation is locked out, and
temperature; normal oil tank is less than the start differential manual reset is required before
temperature before start-up is setpoint, cooling is not needed. the start-up sequence can begin
140°F to 145°F (60° to 63°C). again. If the fault condition has
If the CH530 determines that the not cleared, CH530 will not
Note: The oil heater is energized difference between the permit restart.
during the compressor off cycle. evaporator leaving water
During unit operation, the oil temperature and chilled water When the cooling requirement is
tank heater is de-energized. setpoint exceeds the start satisfied, the CH530 originates a
differential setpoint, the unit “Shutting down” signal. The
enters the initiate in the start inlet guide vanes are driven
mode, the oil pump and the closed for 50 seconds, and the
condenser water pump are unit enters a 1 minute post-lube
started. If condenser water flow period. The compressor motor
is not proven (flow switch 5S2 and condenser water pump
does not close) within 4 minutes starter are de-energized
15 seconds, the unit is locked out immediately, but the oil pump
on a MMR Diagnostic. continues to run during this 3
minute interval; the evaporator
pump will continue to run. Once
the post-lube cycle is done, the
unit returns to auto mode.

74 CVGF-SVU02B-E4
Unit
Startup

Seasonal Unit Start-Up 5. If the evaporator was  WARNING


previously drained, vent and
Note: The following procedure is
fill the evaporator and chilled Live Electrical
a requirement prior to the first
water circuit. When all air is
start of the chiller. Failure to
removed from the system Components!
complete may result in damage
(including each pass), close During installation, testing,
to the compressor and void the
the vent valves in the servicing and troubleshooting of
warranty.
evaporator water boxes. this product, it may be necessary
1. Close all drain valves, and to work with live electrical
6. Lubricate the external vane
reinstall the drain plugs in the components. Have a qualified
control linkage as needed.
evaporator and condenser licensed electrician or other
headers. 7. Check the adjustment and individual who has been properly
operation of each safety and trained in handling live electrical
2. Service the auxiliary
operating control. components performs these tasks.
equipment according to the
start-up and maintenance 8. Complete all control settings. Failure to follow all electrical safety
instructions provided by the 9. Ensure water flows in the precautions when exposed to live
respective equipment condenser and evaporator are electrical components could result
manufacturers. correct according to the pre- in death or serious injury.
3. Vent and fill the cooling tower, commissioning procedures.
if used, as well as the
CAUTION
10. Close all disconnect
condenser and piping. At this switches.
point, all air must be removed Refrigerant Loss May
from the system (including 11. Ensure the unit has been Occur:
each pass). Then close the charged with the correct
amount of refrigerant and oil To avoid excessive unit refrigerant
vents in the condenser water pressure above the relief valve
boxes. and that the oil is the proper
operating temperature. setting, follow these
4. Open all of the valves in the recommended procedures:
evaporator chilled water 12. Complete a phase rotation • Do not run the pump for more
circuit. test if the voltage is less than than 30 minutes after chiller shut-
600 volts. down.
13. Perform instructions listed in Failure to avoid excessive
“Unit Start-up” section operation of the evaporator
water pump with Chiller off
may cause loss of refrigerant
charge.
• If the chilled water loop is used
for heating.
• Ensure that the evaporator is
isolated from the hot water loop
before changing over to the
heating mode.

CVGF-SVU02B-E4 75
Unit
Shutdown

Unit Shutdown 3. Open all disconnect switches  WARNING


except the control power
Unit Shutdown Procedures
disconnect switch. Refrigerant Discharge
Daily Unit Shutdown
4. Drain the condenser piping Hazard!
Note: Refer to Start-Run and cooling tower, if used.
Shutdown sequence (Figure 9). DO NOT ALLOW CHILLER TO
5. To drain the condenser, INCREASE IN TEMPERATURE OR
1. Press <STOP>. remove the drain and vent PRESSURE WHILE THE UNIT IS
2. After compressor and water plugs from the condenser OFF.
pumps shutdown turn Pump headers.
Continuous running of pumps
Contactors to OFF or open 6. Once the unit is secured for while the chiller is off can increase
pump disconnects. winter, the maintenance the temperature or pressure and
Seasonal Unit Shutdown procedures described under will result in premature release of
“Annual Maintenance” in the refrigerant causing bodily harm
CAUTION Periodic Maintenance section and possible death to anyone in
of this manual should be contact with refrigerant discharge
Refrigerant in Oil Pump performed by authorized
Trane service technicians.
Damage may occur
The control power disconnect
must remain closed to allow oil
sump heater operation. Failure to
do this will allow refrigerant to
condense in the oil pump.

76 CVGF-SVU02B-E4
Periodic
Maintenance

Periodic Maintenance Weekly Checks Annual Checks


Check the following after the The yearly maintenance should be
Overview machine has been in operation for performed by an authorized Trane
Use of a periodic maintenance at least 30 minutes: service technician. It should include
program is important to ensure 1. Chilled water and condenser weekly checks.
the best possible unit water entering and leaving 1. Check setting and operation of
performance and efficiency. temperatures. all controls and safety devices.
Daily Maintenance Checks 2. Current drawn by the 2. Leak test the entire machine for
compressor (Amps). refrigerant leaks.
Check the chiller’s evaporator
and condenser pressures, and 3. Oil level in the oil sump. The oil 3. Check starter contactors for wear
discharge oil pressure. level must be visible in the sight and replace if required.
glass. 4. Check motor winding insulation.
IMPORTANT: IT IS HIGHLY
RECOMMENDED THAT THE 4. Condenser pressure, evaporator 5. Check motor amps draw.
OPERATING LOG BE pressure.
6. Perform an oil analysis.
COMPLETED ON A DAILY BASIS. 5. Unusual noise, vibration, and so
forth 7. Perform vibration analysis.
Check the oil level in the chiller oil
sump using the two sight glasses It is strongly recommended that 8. Check and adjust the water flow
provided in the oil sump head. unit readings and observations are 9. Check and adjust interlocks.
When the unit is operating, the oil recorded on a weekly log sheet. 10. Clean condenser tubes.
level should be visible in the lower The acceptance of a warranty claim
sight glass. may depend on this.

CVGF-SVU02B-E4 77
Periodic
Maintenance

Condenser cleaning CAUTION Note: Trane assumes no


responsibility if deterioration of
Water available for cooling
Proper Water Treatment! the unit is due to inadequate
condensers frequently contains
water treatment.
minerals that collect on the The use of untreated or improperly
condenser tube walls as carbonate treated water in a CenTraVac may
scale. Scale accumulation rate will
Evaporator cleaning
result in scaling, erosion,
be increased by high condensing corrosion, algae and or slime The evaporator is part of a
temperatures and water with a conditions. It is recommended that closed water circuit and should
high mineral content. the services of a qualified water not accumulate an appreciable
treatment specialist be engaged to amount of scale or sludge.
Cooling towers, when used, may
determine what water treatment, However, if cleaning should be
collect dust and form material
if any, is required. Trane assumes required, use the same methods
that will deposit in the
no responsibility for equipment outlined for cleaning the
condenser tubes forming sludge.
failures which result from condenser.
Scale and sludge formation is untreated or improperly treated Note: Trane assumes no
indicated by high condensing water, or saline or brackish water. responsibility if deterioration of
temperatures and large
The mechanical method the unit is due to inadequate
differences between condensing
removes sludge and loose water treatment.
and leaving water temperatures.
material from the condenser
To maintain maximum efficiency, tubes. Working a round nylon or
the condenser must remain free bristle brush attached to a rod, in
of scale and sludge. Even a very and out of the tubes loosens the
thin coating on the tube surface sludge. After cleaning, flush the
may greatly decrease condenser tubes with clean water.
heat transfer capacity. Two
methods for cleaning condenser The chemical method removes
tubes are mechanical and scale deposits. The standard
chemical. condenser water circuit consists
of copper, steel and cast iron.
Any reliable water treatment
company will be able to
recommend a cleaning solution
for the job.

78 CVGF-SVU02B-E4
Periodic
Maintenance

Controls checkout and Leak Testing Procedure Taking an Oil Sample


adjustments To obtain an accurate oil sample,
To leak-test the CVGF, weigh a
the chiller must be operating for
Controls are checked and one-pound charge of trace gas
a minimum of 30 minutes. An
calibrated during run-in of the and bring the pressure up to a
approved oil sample cylinder for
unit prior to shipment. Any maximum of 75 psig (517 kPa)
R134a should be used. Make
adjustments should be made using dry nitrogen. This pressure
sure the upstream oil filter
exclusively by authorized Trane has been found to be adequate
isolation angle valve is
service technician. to find leaks in a CVGF when
completely backseated in order
using a sensitive electronic leak
It is strongly recommended to to close the 1/4 inch Schrader
detector. Set the scale to
have proper functioning and valve port. Attach a low loss
“medium” which corresponds to
setpoints of all controls checked hose or line with a Schrader
a 1/2-ounce (.015l) per year leak
once per year. valve depressor to the oil
rate and probe all joints
Control settings sampling 1/4 inch Schrader valve
thoroughly. Be sure and relieve
For control calibration and located on the upstream oil filter
the pressure in the unit before
check-out, contact an authorized isolation valve.
evacuation or leak repair. Local
Trane service technician. codes take precedence when Attach the other end of the hose
Trouble Analysis conducting evacuation. or the line to the oil-sampling
See the Diagnostic List for cylinder. Evacuate the cylinder
trouble shooting information. WARNING and hose or line to remove any
The diagnostic must be non-condensables or moisture.
analyzed, corrections made by  Hazard of Explosion! Open the valve on the sample
qualified personnel and the cylinder. Turn the upstream oil
Use only dry nitrogen with a isolation angle valve stem
latching diagnostic reset before pressure regulator for pressurizing
the chiller can be returned to approximately one turn
unit. Do not use acetylene, oxygen clockwise to allow oil under
operation. or compressed air or mixtures pressure to enter the sample
containing them for pressure cylinder.
Diagnostic Codes testing. Do not use mixtures of a
A Latching diagnostic will shut hydrogen containing refrigerant
down the machine or a part of and air above atmospheric
the machine if so indicated. A pressure for pressure testing as
latching diagnostic will require a they may become flammable and
manual reset to restore could result in an explosion.
operation. A Non-latching Refrigerant, when used as a trace
diagnostic will shut down the gas should only be mixed with dry
machine or a part of the machine nitrogen for pressurizing units.
if so indicated. A non-latching Failure to follow these
diagnostic will automatically recommendations could result in
reset when the condition causing death or serious injury or
the diagnostic goes away. If a equipment or property-only
diagnostic is informative only, damage.
no machine action is taken
except to load a diagnostic code
into the last diagnostic register.
Unless otherwise stated, all
active diagnostics will be lost on
loss of power.

CVGF-SVU02B-E4 79
Periodic
Maintenance

Weigh the cylinder as the oil is Figure 24. CVGF compressor oil system component locations
being transferred and shut off
the cylinder valve when the
desired weight of oil has been
transferred. Backseat the angle
valve to shut off oil flow and
remove the hose from the
Schrader valve. Be sure to
replace the Schrader and angle
valve cap and secure them when
sampling is complete. Recover Oil filter isolation valves
the oil and refrigerant from the 1/4” Schrader valve
oil sample hose or line with an
approved R134a recovery unit. Oil filter cover Oil level sightglasses
When oil analysis indicates the Oil heater - 500 w
need to change the oil (high
Oil sump drain valve
acidity, moisture, and so forth),
use the following procedure for Oil Heater - 500 w
removing the oil.

Removing Compressor Oil


Make sure the unit is not running
and the power has been
disconnected to the oil heaters.
To remove the compressor oil,
attach an oil recovery and
recharge hose or line to the oil
sump drain valve located on the
bottom of the oil sump (See
Figure 24. Attach the refrigerant
vapor return hose or line of the
recovery unit to the condenser
service valve. Open the oil sump
drain valve and condenser
service valve and activate the oil
recovery process according to
the operation specifications of
the recovery unit. After all the oil
has been recovered and residual
R134a refrigerant vapor returned
to the condenser, shut the oil
drain valve and condenser
service valve off and secure the
caps to both valves.

80 CVGF-SVU02B-E4
Periodic
Maintenance

Trane recommends subscribing Unit Charged With Refrigerant


CAUTION to an oil analysis program to 1. Decant the oil from the
determine the condition of the shipping container into the
OIL CONTAMINATION oil rather than changing the oil cylinder of an oil recovery and
Due to the hygroscopic properties on a periodic basis. This recharge unit per the unit
of POE oil, all oil must be stored in program will reduce the chiller’s operation instructions (15
metal containers. The oil will lifetime oil consumption and gallons (56.8 l) required).
absorb water if stored in a plastic minimize refrigerant emissions.
container. The oil analysis should be 2. A vacuum of at least 500
performed by a qualified microns must be attained and
Oil Charging laboratory, experienced in an oil temperature of at least
refrigerant and oil chemistry, 122°F (50°C) maintained to
CVGF units ship factory charged remove existing moisture. A
with 15 gallons (56.8 l) of oil and and the servicing of Trane
centrifugal chillers. standing vacuum rise test
a 5 psig (34 kPa) @ 70 °F (20°C) should be performed after the
dry nitrogen holding charge. distillation process is
Oil Charging Procedure
Note: The correct oil charge for complete to insure the oil has
all CVGF units is 15 gallons (56.8 Use appropriate oil as specified: completely outgassed any
l) of Trane OIL00037 (Trane USA Europe moisture or non-condensibles.
OIL00037 is R134a miscible oil in Oil 0037 Oil 021E
A vacuum rise of less than 100
Oil 0049 Oil 0020E
1-gallon (3.785 l) containers). A 5 microns (0.1 mm Hg) in a 2
gallon (18.9 l) container of Trane hour period indicates the oil is
approved R134a oil is available ready for transfer.
(Trane OIL00049). As with
mineral oil, if water is in the
system it will react with the oil to
form acids. Use the following
table to determine the
acceptability of the oil.

POE Oil Acceptable


Properties Levels
Moisture content less than
300 ppm
Acid Level less than
0.5 TAN (mg
KOH/g)

CVGF-SVU02B-E4 81
Periodic
Maintenance

3. Attach the oil transfer hose of 10. Close the oil sump drain 4. Make sure the oil heaters are
the recovery unit oil pump to valve and remove the oil energized and the oil is up to
the oil sump charging and charging line. temperature (greater than
drain valve and evacuate. 11. Reinstall the oil drain valve 122°F (50°C)).
4. Open the oil charging valve on cap and tighten securely. 5. Continue pulling a vacuum on
the bottom of the oil tank of Unit in a Vacuum. the unit to remove any
the CVGF and operate the oil residual moisture or non-
recovery and recharge unit oil 1. Connect one end of an oil condensables, which may
pump to charge the oil into charging line to an oil supply have been introduced during
the tank. (15 gallons (56.8 l) total the oil charging. A vacuum of
required) and the other end to at least 500 microns (0.5 mm
5. When the oil is at the center of the oil sump drain valve
the upper sight glass, stop the Hg) should be attained before
located at the bottom of the blanking off the vacuum
transfer of oil. oil sump (See Figure 23). If pump. A vacuum rise test
6. Energize the oil heaters. possible, evacuate the oil should be performed to insure
7. At the control panel, go to the charging line to remove any all non-condensables and
Service Tests menu and scroll non-condensables and moisture have been removed
down to the “oil pump” moisture. This will require a from the system before
screen. Turn the oil pump on shutoff valve on the oil supply charging the unit with
in manual mode and let it run side of the line and an access refrigerant 134a. The vacuum
for several minutes. This will valve located on the line itself. level should not rise by more
charge the oil lines and oil 2. Open the oil sump drain valve than 100 microns (0.1 mm Hg)
cooler with oil. and allow the vacuum to draw in a 2 hour period.
8. After shutting the oil pump the oil into the sump until the 6. After charging the unit with
off, check the oil level in the upper sight glass ball is refrigerant, operate the oil
sump sight glasses. The level located in the center of the pump in the manual mode as
should be between the center upper sight glass. outlined in step 7 in the
of the upper glass and center 3. Close the oil sump drain valve preceding procedure and
of the lower sight glass. Float and remove the oil charging follow that procedure if
balls are installed in each sight line. Reinstall the oil drain additional oil is required to
glass to allow easy level valve cap and tighten bring the level between the
determination. securely. center of the two sight
9. If the oil level is below the glasses.
center of the lower sight glass,
charge oil into the sump as
outlined in step 4.

82 CVGF-SVU02B-E4
Periodic
Maintenance

Replacing the Oil Filter Note: When removed, do not 10. Evacuate the oil filter cavity
allow any contaminants to get by attaching a deep vacuum
The oil filter should not be
on the oil filter cover. Re- pump to the 1/4 inch
changed unless absolutely
installing a contaminated oil Schrader valve and pulling at
required due to plugging, which
filter cover could decrease the least a 500 micron (0.5 mm
will shut the chiller off on low oil
life of the compressor. Hg) vacuum. Do a standing
pressure or if the oil is required
7. Remove the oil filter and o- vacuum rise test to
to be changed. To replace the oil
ring. determine if any leaks are
filter, use the following
present. If leak free, remove
procedure: 8. Install a new oil filter, o-ring, the vacuum pump from the
1. Be sure the chiller is in the and Roto-Lock nylon seal. valve.
Stop mode. 9. Replace the oil filter cover and 11. Replace the Schrader valve
2. Locate the two oil filter torque the bolts and Roto- cap and tighten.
isolation valves (See Figure Lock connector. The cover is
torqued to 19 lb-ft (2.62 N-m) 12. Open both isolation valves.
24).
and the Roto-Lock to 90 lb-ft 13. On the DynaView™ display,
3. Connect an approved
(12.44 N-m). select Settings, Mode
refrigerant recovery unit for
overrides and select Oil
R134a to the 1/4 inch Schrader
Pump. Start and run the oil
valve on the oil filter inlet
pump in manual mode to
isolation valve to allow
charge the oil filter with oil.
removal of oil and refrigerant
Allow the pump to run for
from the oil filter cavity.
several minutes and shut the
4. Close both isolation valves. oil pump off by going back
5. Recover the refrigerant and oil to the Auto mode at the
out of the oil filter cavity. control panel.
6. Remove the oil filter cover by 14. Check the oil level in the
removing the bolts and sump and if it is below the
loosening the Roto-Lock center of the lower sight
connector on the outlet oil glass, add oil by following
filter isolation valve. the oil charging procedure
outlined previously.

CVGF-SVU02B-E4 83
Periodic
Maintenance

Oil Sump Heaters Oil Pressure Protection 2. On the DynaView™ display,


The CVGF uses two 500 watt A differential oil pressure switch select Settings, Mode
heaters to maintain the oil sump provides protection for the CVGF overrides and select Oil Pump.
temperature at 136°F (57.7°C). should the oil pressure fall Place oil pump in manual
These heaters are located in the below safe operating levels for mode. Check the oil pressure
lower oil sump casting, one on any reason. This switch opens at gauge readings and calculate
each side of the oil sump cover, 9 psid (62kPa) and closes at 12 the differential oil pressure by
and can be serviced without psid (82 kPa). The oil pressure subtracting the oil sump
removing the refrigerant or oil, regulator is factory set to pressure reading from the
since the heaters are not located maintain oil pressure between discharge oil pressure
in the oil sump itself but in the 18 to 22 psid (124-151 kPa). The reading.
casting (See Figure 24). unit will not start if the oil If the differential pressure is
The CH530 will not allow the pressure is below 12 psid (82 between 18 to 22 psid (124-
chiller to start unless the oil kPa). 151 kPa), the oil pressure
sump temperature is at least Adjusting the Oil Pressure regulating valve should not be
30°F (16°C) above saturated Regulating Valve adjusted. If the oil pressure
evaporator temperature, or at The oil pressure regulator switch is not closed at
least 105°F (58°C), whichever is should be calibrated to maintain pressures above 12 psid
higher. The oil sump comes 18 to 22 psid during (82kPa), the switch is defective
factory insulated and must commissioning. In the event that and should be replaced. If the
remain insulated to allow the oil the oil pressure switch will not switch is closed the unit will
temperature to maintain 136°F close to allow unit not start due to a low oil
(57.7°C) while the unit is off. startup, the following diagnostic pressure diagnostic. If the
The oil heaters are only procedure should be followed: differential oil pressure cannot
energized during the unit “off” 1. With the unit and the oil pump be achieved, the oil pump
cycle to maintain oil off, connect a pressure gauge may be running backwards.
temperature for startup. During to the service valve after the
the run cycle, the oil sump oil filter and another gauge to
heaters are de-energized and the the Schrader valve located
oil temperature may vary next to the oil pressure switch
depending on load and capillary on the oil sump. (An
operating conditions. The unit optional method is to use a
will trip on a latching diagnostic differential pressure gauge
of high oil temperature if the oil instead of two separate
exceeds 165°F (74°C). gauges.)

84 CVGF-SVU02B-E4
Periodic
Maintenance

3. To reverse the oil pump motor 5. When the oil filter change is CVGF Oil Pump
rotation, two leads must be completed, check the The oil pump for the CVGF is a
swapped on the oil pump differential oil pressure and if positive displacement, direct
motor contactor. Be sure to it is below 18 psid (124 kPa), drive pump, three phase motor.
remove all power from the adjust the oil pressure The motor must be phased
unit before doing any regulator to obtain a reading correctly to provide positive
electrical wiring changes. of between 18 to 22 psid (124- differential oil pressure. This
Note: Be sure to perform the 151 kPa). pump and motor is located
Bump Start test to determine If the pressure drop across the within the oil sump and can not
proper compressor rotation filter is not excessive, but the be serviced without recovering
before operating the chiller. oil differential pressure is the refrigerant and removing the
below 18 psid, adjust the oil oil from the machine.
If the differential oil pressure
measured is below 12 psid (82 pressure regulating valve to
kPa), the oil filter may be obtain 18 to 22 psid (124-151
plugging or the regulator may kPa) oil pressure. To increase
need adjustment. pressure, remove the oil
pressure regulator cap and
4. Then check the pressure drop screw the regulator stem in a
across the oil filter, connect a clockwise direction. Be sure to
gauge to the service valve replace the cap and tighten
before the oil filter and when adjustment is complete.
another gauge to the service
valve after the oil filter. 6. Remove the pressure gauges
Subtract the pressure reading when all diagnostic work is
taken from after the oil filter complete. Be sure and replace
from the gauge before the oil and secure any valve caps
filter to obtain the pressure which were removed.
drop. If the pressure drop is
excessive (more than 8 psid
(54 kPa)), shut the oil pump off
and replace the oil filter per
the procedure outlined
previously.

CVGF-SVU02B-E4 85
Periodic
Maintenance

Refrigerant Charge 3. Remove all of the moisture Refrigerant Charging


from the system to insure a
If a low refrigerant charge is Once the system is leak and
leak free unit. Pull the system
suspected, first determine the moisture free, use the 5/8” flare
down below 500 microns (0.5
cause of lost refrigerant. Once connections at the bottom of the
mm Hg).
the problem is repaired follow evaporator and side of
the procedures below for 4. After the unit is evacuated, condenser to add refrigerant
evacuating and charging the perform a standing rise test charge. See Unit Nameplate for
unit. for at least an hour. This correct refrigerant charge
vacuum should not rise more amounts.
WARNING than 100 microns (0.1 mm Hg)
Add the refrigerant charge as a
per hour to a maximum of 500
vapor until the system pressure
Hazardous Voltage! microns (0.5 mm Hg) over 12
is above 29.4 psi (203 kPa) or
hours. If the vacuum rises
Disconnect all electric power, Temperature is above 34°F (1°C).
above this, either there is a
including remote disconnects Liquid refrigerant may be added
leak or the unit has moisture
before servicing. Follow proper once these conditions are
present.
lockout/tagout procedures to achieved.
ensure the power can not be Note: If oil is in the system, this
inadvertently energized. Failure to test is more difficult. The oil is CAUTION
disconnect power before servicing aromatic and will give off vapors
could result in death or serious that will raise the pressure of the Possible Freeze-up
injury. system. Check for oil
temperature >122°F (50°C). Water can freeze during charging.
Evacuation and Dehydration Circulate water during charging to
1. Disconnect ALL power while prevent freezing.
evacuating the system.
Caution
2. Connect the vacuum pump to
the 5/8” flare connection on
the bottom of the evaporator.
Charge vapor in the unit
until:
• System pressure is above 29.4
psig (203 kPa )
• The saturation temperature of
R134a is above 34°F (1°C)

86 CVGF-SVU02B-E4
Literature Order Number CVGF-SVU02B-E4
File Number SL-RF-CTV-CVGF-SVU02B-E4-0205
Supersedes CVGF-SVU02A-E4-1202
Stocking Location China
Trane has a policy of continuous product and product data improvement and reserves the right to
Trane change design and specifications without notice. Only qualified technicians should perform the
A business of American Standard Companies installation and servicing of equipment referred to in this publication.
www.trane.com Société Trane – Société Anonyme au capital de 41500 000 F – Siege Social: 1 rue des Amériques –
For more information contact your local Trane office 88190 Golbey – France – Siret 306 050 188-00011 – RSC Epinal B 306 050 188
or e-mail us at comfort@trane.com Numéro d’identification taxe intracommunanutaire: FR 83 3060501888

You might also like