You are on page 1of 28

8/6/2008

Motor Calcs

2005 NEC Motor Circuit


Requirements and
Calculations

Copyright 1999-2007 Dan Dudley

Motor Calcs

NEC Motor Calculations


Basic Information

• 430.6(a)(1) Basic Calc information


– Name Plate Values (430.6(a)(2) are only used
to size overloads)
– Otherwise use T.430.247, 248, 249, & 250
• 430.22(a) Single motor 125% cont. duty
(3 hrs or more)
• T.430.22(e) Note Cont. Duty unless nature
of apparatus is otherwise.
Copyright 1999-2007 Dan Dudley

Copyright 2000-2007 Dan Dudley


8/6/2008

Motor Calcs

NEC Motor Calculations


Basic Information

• 430.52(c)(1) exception
– Next higher standard size overcurrent protective
device.
• 430.62 Feeder O.C. Protection
– Largest S.C. – G.F. Protective device plus the sum of
the F.L.C. of all other motors supplied by the same
feeder
• No provision for going UP to next standard size
must go down to next standard size
Copyright 1999-2007 Dan Dudley

Motor Calcs

Copyright 1999-2007 Dan Dudley

Copyright 2000-2007 Dan Dudley


8/6/2008

Motor Calcs

Hp Phases FLC Voltage

Hz

Locked
Temp Service Insulation Rotor
Rise Factor Class Letter
Copyright 1999-2007 Dan Dudley

Motor Calcs

Line side

Nameplate Data

Actuating Coil

Overload Relays

Load Side

Overload Reset

Copyright 1999-2007 Dan Dudley

Copyright 2000-2007 Dan Dudley


8/6/2008

Motor Calcs

For all other


calculations use
Table values

Copyright 1999-2007 Dan Dudley

Motor Calcs

Copyright 1999-2007 Dan Dudley

Copyright 2000-2007 Dan Dudley


8/6/2008

Motor Calcs

¾ @120 5 @208 Copyright 1999-2007 Dan Dudley

Motor Calcs

25 HP
208 Volts
50 HP
Synchronous
200 HP 440 Volts
480 Volts

25-208 50 sync – 440 200 - 480 Copyright 1999-2007 Dan Dudley

Copyright 2000-2007 Dan Dudley


8/6/2008

Motor Calcs

C.B.
3-phase Std. Fuse

Copyright 1999-2007 Dan Dudley

Motor Calcs

10HP 240V 1Φ
FLI 44

What minimum size THHN conductors are required


for this motor ?

Name Plate Not used


430.248:
430.248: 10hp @ 240v = 50 amps
430.22(a):
430.22(a): 50 X 125% = 62.5 amps
310.16:
310.16: 62.5 amps = #4 THHN

T.310.16 T.430.248 110.14 Copyright 1999-2007 Dan Dudley

Copyright 2000-2007 Dan Dudley


8/6/2008

Motor Calcs

25HP 480V 3Φ
FLI 32.5

What is the minimum ampacity of the branch circuit conductors


for a 25 HP , 480-volt, 3 phase, squirrel cage motor with
nameplate FLI of 32.5 amps ?

Name Plate value not used


430.250:
430.250: 25hp @480v = 34 amps
430.22(a):
430.22(a): 34 X 125% = 42.5 amps
310.16 : # 6 THHN @60º
@60ºC and 55 amps

T.310.16 T.430.250 110.14 Copyright 1999-2007 Dan Dudley

Circuits with more than one Motor


• Decide which motor
• Step 1. has largest FLI rating
(This may not be the largest HP)

• Step 2. • Largest FLI of one


motor X 125%
(only increase one)

• Add FLI rating of all


other motors
• Step 3.
(straight from tables)

Copyright 1999-2007 Dan Dudley

Copyright 2000-2007 Dan Dudley


8/6/2008

Motor Calcs

5HP 3Φ 5HP 3Φ
208V 208V

What is the minimum ampacity of the branch circuit


conductors for the two motors as shown ? 3∅, 208V

430.250:
430.250: 5 hp @ 208v = 16.7 amps
430.24: Ampacity = FLI 1st motor X 125% + FLI 2nd motor
430.24:
Ampacity = 16.7 X 125% + 16.7 = 37.575 amps

T.310.16 T.430.250 110.14 Copyright 1999-2007 Dan Dudley

Motor Calcs

5HP 1Φ 2HP 1Φ
230V 230V

What is the minimum ampacity of the branch circuit


conductors supplying the two motors as shown ? 1∅, 230V

430.248: 2hp @ 230v = 12 amps


430.248: 5hp @ 230v = 28 amps
Ampacity = Largest FLI X 125% + Second FLI
28 X 125% + 12 = 47 amps

T.310.16 T.430.248 110.14 Copyright 1999-2007 Dan Dudley

Copyright 2000-2007 Dan Dudley


8/6/2008

Motor Calcs

10HP 3Φ 25HP 3Φ 30HP 3Φ


480V 480V 480V
Squirrel Cage Squirrel Cage Synchronous

What is the minimum ampacity of the branch circuit


conductor serving the three motors as shown
above?

T.310.16 T.430.250 110.14 Copyright 1999-2007 Dan Dudley

Motor Calcs

10HP 3Φ 25HP 3Φ 30HP 3Φ


480V 480V 480V
Squirrel Cage Squirrel Cage Synchronous

430.250: FLI’s, 3-phase, 480v


10hp Squirrel cage = 14 FLI
25hp Squirrel cage = 34 FLI
30hp Synchronous = 32 FLI
34 X 125% + 14 + 32 = 88.5 amps
T.310.16 T.430.250 110.14 Copyright 1999-2007 Dan Dudley

Copyright 2000-2007 Dan Dudley


8/6/2008

Motor Calcs
10HP 3Φ 25HP 3Φ 30HP 3Φ
88.5A 480V 480V 480V
Squirrel Cage Squirrel Cage Synchronous

What Size THWN conductors are required for:


1: Ungrounded Conductors
Design
2: Grounded Conductor A
3: Grounding Conductor
T.310.16 & 110.14(c) = #2 THWN Ungrounded (60°C)
No Grounded Conductor Required
T.250.122 Grounding Conductor (EGC) = #8 Cu or #6 Al
T.310.16 T.250.122 110.14 T.430.250 Copyright 1999-2007 Dan Dudley

Motor Calcs

6000 watts 1HP 1Φ 120V


Incandescent Lighting FLI 12.4

What is the minimum size branch circuit conductors


supplying the motor and incandescent lighting above ?

430.248: 1hp @ 120v = 16 amps


Lighting: I=W / E = 6000 / 120 = 50 amps
430.24(a): Ampacity = motor FLI X 125% + Lighting I
16 X 125% + 50 = 70 amps
#4 THHN Cu (60°C)
T.310.16 T.430.248 110.14 Copyright 1999-2007 Dan Dudley

Copyright 2000-2007 Dan Dudley


8/6/2008

Copyright 1999-2007 Dan Dudley

Motor Calcs

T.310.16 T.430.250 110.14 Copyright 1999-2007 Dan Dudley

Copyright 2000-2007 Dan Dudley


8/6/2008

Motor Calcs

81.25

26.25

123.25

T.310.16 T.430.250 110.14 Copyright 1999-2007 Dan Dudley

Motor Calcs

T.310.16 T.430.250 110.14 Copyright 1999-2007 Dan Dudley

Copyright 2000-2007 Dan Dudley


8/6/2008

Motor Calcs

T.310.16 T.430.250 110.14 430.52 Copyright 1999-2007 Dan Dudley

Motor Calcs

T.310.16 T.430.250 110.14 430.52 240.6 Copyright 1999-2007 Dan Dudley

Copyright 2000-2007 Dan Dudley


8/6/2008

Motor Calcs

Time Delay 20HP 3Φ


Fuses 480V FLI 29

T.310.16 T.430.250 110.14 430.52 240.6 Copyright 1999-2007 Dan Dudley

Motor Calcs

Time Delay
Fuses 20HP 3Φ
480V FLI 29

T.430.250: 20hp = 27 amps


T.430.52: Time Delay Fuse = 175%
Max. O.C. device = 27 X 175% = 47.25 amps
430.52(c)(1) exception #1: Next Larger size permitted
240.6(a) Next Larger Std size = 50 amps

Answer: 50 amp Time Delay Fuse

T.310.16 T.430.250 110.14 430.52 240.6 Copyright 1999-2007 Dan Dudley

Copyright 2000-2007 Dan Dudley


8/6/2008

Motor Calcs

Non-Time 20HP 3Φ
Delay Fuses 480V FLI 29

T.430.250: 20hp = 27 amps


T.430.52: Non-Time Delay Fuse = 300%
Max. O.C. device = 27 X 300% = 81 amps
430.52(c)(1) exception #1: Next Larger size permitted
240.6(a) Next Larger Std size = 90 amps

Answer: 90 amp Non-Time Delay Fuse


T.310.16 T.430.250 110.14 430.52 240.6 Copyright 1999-2007 Dan Dudley

Motor Calcs

Inverse Time
Breaker
20HP 3Φ
480V FLI 29

T.430.250: 20hp = 27 amps


T.430.52: Inverse Time Breaker = 250%
Max. O.C. device = 27 X 250% = 67.5 amps
430.52(c)(1) exception 1: Next Larger size permitted
240.6(a) Next Larger Std size = 70 amps

Answer: 70 amp Inverse Time Circuit Breaker

T.310.16 T.430.250 110.14 430.52 240.6 Copyright 1999-2007 Dan Dudley

Copyright 2000-2007 Dan Dudley


8/6/2008

Selecting Minimum Size Overloads 430.32(A)(1)

„ Service Factor „ Temperature Rise

„ Less than 1.15 „ 40°C or less use


use 115% 125%

„ 1.15 or greater
use 125% „ Over 40°C use
115%
„ No Service Factor
Listed use 115% „ No Temp Listed
use 115%

Copyright 1999-2007 Dan Dudley

Selecting Maximum Size Overloads 430.32(C)

„ Service Factor „ Temperature Rise

„ Less than 1.15 „ 40°C or less use


use 130% 140%

„ 1.15 or greater
use 140% „ Over 40°C use
130%
„ No Service Factor
Listed use 130% „ No Temp Listed
use 130%

Copyright 1999-2007 Dan Dudley

Copyright 2000-2007 Dan Dudley


8/6/2008

Motors with a Duty Cycle - Welders

Solution:

Welder No.1
630.11(a) Nonmotor Generator
Duty cycle 30 Multiplier = 0.55
I=RPCXM
I = 28 amps x 0.55 = 15.4 amps

Welder No.2
630.11(a) Nonmotor Generator
Duty cycle 80 Multiplier = 0.89 RPC 28A
I=RPC xM Duty Cycle
30% RPC 18A
I = 18 amps x 0.89 = 16.02 amps
Duty Cycle
630.11(b)
80%
Total = No.1+ No.2

Total = 15.4 + 16.02 = 31.42 amps


Ans. 31.42 amps

T.310.16 T.630.11 110.14 430.52 240.6 Copyright 1999-2007 Dan Dudley

Motor Calcs

5HP 230V 1Φ
FLI 24.5
Periodic Duty
15 Min

Solution:

Nameplate current rating is used.


Table 430.22(e)
FLI 15 min. periodic duty = 90%

Ampacity -Nameplate FLI x 90%


= 24.5 x 90% = 22.05 amps.
Answer: 22.05 amperes
T.310.16 T.430.22(e) 110.14 430.52 240.6 Copyright 1999-2007 Dan Dudley

Copyright 2000-2007 Dan Dudley


8/6/2008

Motor Calcs

15HP 230V 3Φ
FLI 16.5
Varying Duty

Solution:

Nameplate FLI is used.


Table 430.22(e)
Continuous use, varying duty= 200%
Ampacity = nameplate FLI x 200 %
Ampacity= 16.5 x 200 = 33 amps

Answer: 33 amperes

T.310.16 T.430.22(e) 110.14 430.52 240.6 Copyright 1999-2007 Dan Dudley

Motor Calcs
Motor Efficiency

No motor is 100% efficient • Efficiency = Output / Input

Efficiency = Output / Input • 5HP, 240V, 1∅ = 28A F.L.C.


T.430.248
• W = E X I = 240V X 28A =
6720 VA
• 6720 VA input and 5712 VA
output
• 5712/6720 = .85
• 6720 VA X .85 = 5712 VA
output
• 85% efficiency

Copyright 1999-2007 Dan Dudley

Copyright 2000-2007 Dan Dudley


8/6/2008

Motor Calcs

Motor Duty Rating


„ Intermittent Duty = T.430.22(e)
„ Nameplate F.L.C. used
„ 50HP,480V,3∅, 15 minute rated elevator
motor, Name Plate FLC =61.2A
„ T.430.22(e) = 85%
„ Name Plate FLC = 61.2 X 85% = 52.02A
Branch Circuit Ampacity
„ Conductor Required = #6 (60°C column)

Copyright 1999-2007 Dan Dudley

Motor Calcs

Motor Calculations
Practice Questions

10 Questions
30 Minutes
Copyright 1999-2007 Dan Dudley

Copyright 2000-2007 Dan Dudley


8/6/2008

Motor Calcs

Copyright 1999-2007 Dan Dudley

Motor Calcs
Motor Calculations Answers

1. (a) 33A 13.2 X 250% = 33A KW

2. (a) 38.5A 30.8 X 125% = 38.5A KW

3. (b) #3/0 THHN 2 – 7.5 hp 1Ø = 44 A each


2 – 5 hp 1Ø = 30.8 A
1 – 2 hp 1Ø = 13.2 A
1 - 1 HP 1Ø = 8.8 A
56 X 125% + 44 + 30.8 + 24 + 13.2 + 11
70 + 44 + 30.8 + 13.2 + 13.2 + 8.8
Answer: 193 amps

*Note #2 T. 430.248: 5hp, 208v, 1∅ = 30.8 amps


30.8 X 125% = 38.5 amps

T.310.16 T.430.248 T.430.250 T.430.250 110.14Copyright 1999-2007 Dan


430.52 Dudley
240.6

Copyright 2000-2007 Dan Dudley


8/6/2008

Motor Calcs
Motor Calculations Answers

4. (c) #3 TW 65 X 125% = 81.25 amps


required. T. 310.16
5. (b) 9152 va Power(va) = E X I
W= 208v X 44 = 9152 va
6. (d) 15.18 A 13.2 X 115% = 15.8 amps

7. (b) 80 amp 44 A FLC X 175% = 77 A

8. (a) 250 amp 175 A + 44 A + 30.8 A


+24 A + 13.2A + 11 A = 298 amps
240.6 = 250 amp
Can’t go up on FEEDER

T.310.16 T.430.248 T.430.250 T.430.250 110.14Copyright 1999-2007 Dan


430.52 Dudley
240.6

Motor Calcs
Motor Calculations Answers

9. (d) 200 amps


1. 175 + 21 + 21 = 217
2. Can’t go up on feeder - drop down to 200 amp
(240.6)

10. (d) #4 41 amps X 1.25 = 51.25a


Be careful of TYPE of MOTOR, in this case
SYNCHRONOUS Also be careful of type of
CONDUCTOR
Look in Right side – aluminum conductors in the
middle column since design “D” is stated
** For motors marked with design letters B, C, or D conductors having an
insulation rating of 75°C (167°F) or higher shall be permitted to be used
provided the ampacity of such conductors does not exceed the 75°C
(167°F) ampacity.

T.310.16 T.430.248 T.430.250 T.430.250 110.14Copyright 1999-2007 Dan


430.52 Dudley
240.6

Copyright 2000-2007 Dan Dudley


8/6/2008

Motor Calcs

Copyright 1999-2007 Dan Dudley

Motor Calcs

25-208 50 sync – 440 200 - 480

Copyright 1999-2007 Dan Dudley

Copyright 2000-2007 Dan Dudley


8/6/2008

Motor Calcs

Copyright 1999-2007 Dan Dudley

Motor Calcs

Copyright 1999-2007 Dan Dudley

Copyright 2000-2007 Dan Dudley


8/6/2008

Motor Calcs

Copyright 1999-2007 Dan Dudley

Motor Calcs

Copyright 1999-2007 Dan Dudley

Copyright 2000-2007 Dan Dudley


8/6/2008

Motor Calcs

Copyright 1999-2007 Dan Dudley

Motor Calcs

Copyright 1999-2007 Dan Dudley

Copyright 2000-2007 Dan Dudley


8/6/2008

Motor Calcs

Copyright 1999-2007 Dan Dudley

Motor Calcs

Copyright 1999-2007 Dan Dudley

Copyright 2000-2007 Dan Dudley


8/6/2008

Motor Calcs

Copyright 1999-2007 Dan Dudley

Motor Calcs

Question 1 Keywords
What size short circuit/ground fault protection is
required for the branch circuit serving motor #1 in
motor diagram #1?

What size short circuit/ground fault protection is


required for the branch circuit serving motor #1 in
motor diagram #1?
We are looking for the smallest fuse or circuit breaker
required to protect motor #1 on Motor Diagram #1.

Copyright 1999-2007 Dan Dudley

Copyright 2000-2007 Dan Dudley


8/6/2008

Motor Calcs

Question 2 Keywords
What is the minimum size overloads required for
motor #2 on motor diagram #1 ?

What is the minimum size overloads required for


motor #2 on motor diagram #1 ?

We are looking for the smallest heater/overload size


allowed for motor #2 on motor diagram #1.
Overloads = name plate full load current times either
115% or 125% depending on S.F. and/or Temp Rise.

Copyright 1999-2007 Dan Dudley

Motor Calcs

Question 3 Keywords
What is the minimum size THHN feeder required for
the six motors as shown on Motor Diagram #1 ?

What is the minimum size THHN feeder required for


the six motors as shown on Motor Diagram #1 ?
We are looking for the smallest legally allowed THHN
copper conductor to feed these 6 motors. Feeder
conductor = three steps:
1 find largest FLA motor and multiply by 1.25 (125%)
2. Add FLA of all other motors on same feeder
3. Can’t go up in size = drop down to standard at 240.6

Copyright 1999-2007 Dan Dudley

Copyright 2000-2007 Dan Dudley

You might also like