Professional Documents
Culture Documents
Stephen Marx
Bonneville Power Administration
Brian K. Johnson
University of Idaho
Presented at the
16th Annual Georgia Tech Fault and Disturbance Analysis Conference
Atlanta, Georgia
May 6–7, 2013
1
Abstract—Faults in power transmission lines cause transients Later on, utilities like BPA used dedicated TW-based fault
that travel at a speed close to the speed of light and propagate locating devices that sample the currents or voltages at
along the line as traveling waves (TWs). This paper shows how sampling rates greater than 1 MHz [6]. Some of these devices
these transients can be measured in a protective relay and used
to enhance its fault locating function. The TW-based fault
also include fault disturbance recording and are capable of
locating function in a protective relay takes advantage of the reporting accurate fault location results [7].
internal protection elements, the communications channel to the Numerical protective relays include fault location
remote terminal, and Global Positioning System-based time estimation algorithms based on the line impedance and voltage
synchronization. This approach provides accurate fault location and current measurements. In most applications, these relays
estimation for transmission lines automatically within a couple of only use measurements from the local terminal. Some relays
seconds after the fault. The TW fault locator within the relay
uses conventional current transformer measurements and does
also use information from the remote terminal to estimate the
not require any additional wiring or special installation fault location. Using information from the local and remote
considerations. These relays detect internal line faults and use terminals minimizes errors due to mutual coupling with
TW- and impedance-based algorithms to optimize the estimation adjacent lines, system nonhomogeneity, and fault resistance
and reporting of the fault location. The TW- and impedance- [8] [9]. In some applications, such as series-compensated
based algorithms complement each other to provide accurate lines, the impedance-based fault locating methods are
fault location estimation for all internal faults, independent of the
fault incidence angle. This paper provides a tutorial on TW fault
challenged and utilities require more accurate estimation than
location and describes a TW fault locating algorithm that uses traditional relays provide.
time-synchronized measurements of the TW currents at the line This paper discusses the basic principles of TWs, a
terminals to determine the fault location. The proposed protective relay that estimates fault location using TW
implementation is suitable for line terminals with one or two information, and the benefits of having TW fault location
breakers. The paper also discusses methods for testing the TW estimation within a protective relay. The paper also describes
fault locating algorithm using a playback system and a hardware
model that mimics a transmission line. The paper presents the
how to test the TW fault locating system using low-energy
details and experiences of a field application of these relays on a analog signals and an analog transmission line model. We also
high-voltage transmission line. share the field experiences from an installation on a BPA
161 kV transmission line.
I. INTRODUCTION
The Bonneville Power Administration (BPA) has been II. OVERVIEW OF TRAVELING WAVES IN TRANSMISSION LINES
using traveling wave (TW) technology to locate faults in their A fault on a transmission line generates TWs that
extra-high voltage (EHV) transmission networks since the propagate from the fault location to the line terminals with a
1950s [1]. In the 1960s and 1970s, BPA installed an propagation velocity that depends on the inductance and
automated fault locating system that used microwave capacitance of the line. Fig. 1 shows the equivalent circuit of a
communications to send the TW arrival information to the segment with length ∆x of a two-conductor transmission line.
remote terminal for fault location estimation [2]. The circuit includes the resistance R, inductance L,
References [3] and [4] describe the development and field conductance G, and capacitance C of the line in per unit of the
evaluation of the performance of a digital fault locator for total line length [10].
high-voltage direct current (HVDC) lines that uses voltage and
R• x L• x
current measurements from one line terminal to estimate the i(x,t) i(x + x,t)
2 v x, t i x, t 2 i x, t
–1,000
0.2
0.2 0.4
0.4 0.6
0.6 0.8
0.8 11 1.2
1.2 1.4
1.4 1.6
1.6
–R –L (5) 150 km
x 2
x xt 1,000
150 km
2 i x, t v x, t 2 v x, t 0
–G –C (6)
xt t t 2 –1,000
0.2 0.4 0.6 0.8 1 1.2 1.4 1.6
0.2 0.4 0.6 0.8 1 1.2 1.4 1.6
i x, t i x, t
2
1,000
300 km
300 km
We substitute from (4) and from (6)
x xt
0
into (5) to obtain the voltage wave equation shown in (7).
–1,000
2 v x, t 2 v x, t
0.2
0.2 0.4
0.4 0.6
0.6 0.8
0.8 11 1.2
1.2 1.4
1.4 1.6
1.6
LC 450 km
450 km
x 2 t 2 (7)
1,000
v x, t 0
RC GL GR • v x, t
t –1,000
0.2 0.4 0.6 0.8 1 1.2 1.4 1.6
Similarly, we differentiate (3) with respect to t and (4) with
Time (milliseconds)
respect to x to obtain (8) and (9), respectively.
Fig. 2. Current waves at 50, 150, 300, and 450 kilometers traveling on a
2 v x, t i x, t 2 i x, t 400 kV line for a nominal voltage step change at the sending end, where
–R –L (8) A-phase is green, B-phase is blue, and C-phase is red.
xt t t 2
2 i x, t v x, t 2 v x, t
–G –C (9)
x 2 x xt
3
III. TRAVELING WAVE FAULT LOCATION Voltage and/or current measurements capture the TWs. The
FOR TWO-TERMINAL LINES adequate frequency bandwidth of current transformers (CTs)
TW-based fault location provides better accuracy relative makes current TWs better suited for this application than
to impedance-based fault locating methods. Single end voltage TWs measured at the secondary terminals of the step-
(Type A) and double end (Type D) are the two most common down transformer of the capacitance coupled voltage
methods for computing fault location using TWs [1]. Type A transformer (CCVT) [14]. Typical installations have
uses the time difference between the first arrived wave and the communications between the substation and the control center,
successive reflections from the fault location to compute the where computer-based analysis tools retrieve the TW
fault location. This method is appealing because it only information captured at the line terminals and compute the
depends on local information; therefore, it does not require a fault location. In this paper, we discuss installations where
communications channel. However, identifying the reflections protective relays exchange TW information obtained from the
is a major challenge. The reflections can arrive from the fault phase currents and automatically calculate the fault location at
location, from the remote terminal, or from behind the local the line terminals within a couple of seconds after the fault.
terminal. Accurately identifying the reflection from the fault
location poses a challenge for single-end TW-based fault IV. TW FAULT LOCATION IN PROTECTIVE RELAYS
location, especially on ac transmission lines. The double-end A. Benefits of TW Fault Location in a Protective Relay
method overcomes the challenge of identifying the reflections Numerical protective relays have included fault location
from the fault but requires the TW information from the estimation based on voltage and current measurements and
remote terminal. This Type D method uses the time difference line impedance since 1982 [15] [16]. These relays use voltage
between the first arrived TWs captured at both terminals along and current measurements acquired at the local terminal and
with the line length and the wave propagation velocity to report the fault location estimation results at the substation and
compute the fault location. Fig. 3 shows the waves the control center through automessaging right after the
propagating to Terminals A and B following a fault condition occurrence of a fault. While this approach provides
on a transmission line. estimations within 2 percent of the line length, there are cases
where mutual coupling, fault resistance, and system
nonhomogeneity can cause large errors. In these cases, the
impedance-based fault locating methods in protective relays
can be improved using local and remote (double-end)
measurements [8] [9] [17].
Fig. 3. TWs propagating to Terminals A and B.
Impedance-based fault location estimation requires the
presence of the fault for a couple of cycles to provide accurate
Measurement devices at the line terminals detect the TWs results. While this requirement is not an issue in
and accurately time-stamp the arrival of the wave using a subtransmission network applications, it can be an issue in
common time reference (e.g., IRIG-B or IEEE 1588). The EHV and ultra-high voltage (UHV) applications where faults
typical time-stamping accuracy is better than 1 microsecond. are sometimes cleared in less than two cycles. Furthermore,
The TW-based fault location is computed using (11). these impedance-based estimation methods might not be
LL TwaveA TwaveB • c • LPVEL applicable to lines with series compensation or lines close to
TWFL (11) series compensation due to subsynchronous oscillations,
2
voltage inversion, and so on. Because of the importance of
where: locating faults to avoid fault reoccurrences and the high cost
TWFL is the TW-based fault location. associated with finding line faults, utilities require accurate
LL is the line length. fault locating devices for all applications. For this reason,
TwaveA is the TW arrival time recorded at Terminal A. some utilities have installed dedicated devices that detect the
TwaveB is the TW arrival time recorded at Terminal B. time of arrival of TWs at the line terminals and estimate the
c is the speed of light. fault location using this information [6] [18]. While these
LPVEL is the propagation velocity of the TW in per unit devices provide more accurate fault location estimation than
of the speed of light. relays that use impedance-based methods to estimate the fault
location, there are cases where they cannot estimate the fault
The TW propagation velocity is a key parameter in the
location when faults occur at the voltage zero crossing.
fault location calculation and is typically obtained from line
Protective relays that include both impedance-based and
parameter estimation programs. We can also estimate
TW-based fault location have the advantage of providing fault
propagation velocity using TW measurements with the
location even in cases where the TW amplitude is too low for
following:
reliable detection (e.g., faults that occur at voltage zero). In
Local TW information recorded during line or reactor
these cases, the relays estimate the fault location using line
energization tests.
impedance and local and remote voltage and current
Local and remote TW information recorded during
measurements. If the remote measurements are not available,
external faults.
the relay estimates the fault location using local measurements
4
only, thus providing robust response with the best possible signal levels at the transmission line ends to indicate the
accuracy under all fault conditions. presence of a fault on the line.
B. Relay-to-Relay Communications
The relay discussed in this paper uses a 64 kbps channel
that exchanges currents for differential protection purposes.
The relay takes advantage of this bandwidth and includes TW
information within the data packet without affecting the
40.35 feet
performance of the differential element. The relays exchange (12.3 meters)
the times of arrival of the TWs (see Fig. 4) and use this
information to estimate the fault location, make the results
available at the relay location, and send the results to the
control center within a couple of seconds after the occurrence
of the fault. 82 feet
(25 meters)
Magnitude Response
Phase Response
Fig. 7. Frequency response of the relay analog circuitry (excluding anti-aliasing filter).
6
Fig. 8. LTspice simulation showing ringing of the current signal at the relay end caused by the secondary wiring of the CT.
Fig. 9. LTspice simulation showing the peaks in the frequency response caused by the secondary wiring of the CT.
Fig. 8 shows the results of an LTspice simulation that The TW voltage transients are also suitable for fault
demonstrates the secondary cable ringing effects, while Fig. 9 location estimation. Unfortunately, the quality of the
shows the frequency response peaks caused by the same measurements provided by conventional VTs is significantly
effect. inferior to that of their CT counterparts. CCVTs normally
Ringing effects are present in real life, as demonstrated by used at transmission levels are tuned to the nominal power
the TW transient waveform shown in Fig. 10. This waveform system frequency. Although the high-frequency capacitor
was recorded in the field during an actual power system fault. stacks used in these transformers are often usable up to
The TW spectral content is inherently limited by the high- 1 MHz, the tuning reactor eliminates the high-frequency
frequency attenuation provided by the power system signals, leaving only the unintended transients caused by
transmission line. However, as the TW transient reaches the parasitic capacitance, which tends to be different for every
substation (the relay location), it is capable of exciting a large CCVT design [23]. Because the voltage measurements
number of local high-frequency resonances, which have no captured at the secondary terminals of the CCVT step-down
value for fault location estimation. Therefore, sampling transformer do not properly measure TW transients, some
frequencies found on most TW systems are normally systems use additional high-frequency transducers mounted in
somewhere in the 0.5 to 5 MHz range. series with the CCVT stack or nonconventional resistive-
capacitive dividers to capture the voltage TWs.
7
The TW-based fault locator described in this paper does V. TRAVELING WAVE TESTING
not require additional CTs or CT wiring because the relay is
A. Testing Using Low-Energy Analog Signals
able to use the same current measurements for line protection
and fault location estimation. To verify the accuracy of the TW-based fault location
The TW-based fault locating subsystem is implemented in estimation, we created a power system model using an EMTP.
parallel with the conventional data acquisition chain, ensuring The power system model includes frequency-dependent
no interference with the mission-critical protection functions. transmission line models and effective terminal capacitance at
The TW-based fault locating subsystem uses high-speed the buses. Table I shows typical terminal capacitances for
analog-to-digital (A/D) converters that sample the phase generators, transformers, and bus systems [24].
currents at 1.56 MHz and creates dedicated COMTRADE TABLE I
event reports that contain TW information. TYPICAL TERMINAL CAPACITANCES IN MICROFARADS (µF)
(Distribution)
100
Transformers
0.001 0.0002 0.0005
(Power)
50
Bus Systems 0.015 0.0020 0.0050
0
We simulated phase-to-ground and phase-to-phase faults at
known locations on a 189-mile line. We saved the current
signals from both terminals (sending end and receiving end)
320 340 360 380 400 420 440 460 480 500 520 that were sampled at a rate of 3 MHz as comma-separated
Time (microseconds) value (CSV) files. We used a signal generator that is capable
Fig. 10. Field-recorded TW waveform showing ringing effects in an actual of playing back megahertz sampling rate data with 16-bit
substation application. resolution (see Fig. 12). The signal generator plays back the
CSV files via the low-energy analog (LEA) interface of the
D. Current Monitoring in Double-Breaker Applications
relay. Two playback units supplied the three-phase currents
The protective relay has two sets of current inputs to from each line terminal to the corresponding relays. The
measure the currents through the two breakers in breaker-and- playback units were configured to inject the signals
a-half and double-breaker schemes, as Fig. 11 illustrates. This synchronously to both relays.
capability allows the relay to monitor the line currents based
on user-programmable logic variables that select which
currents to use according to the operation requirements of the
power system. The fault locating algorithm uses the selected
TWIA, TWIB, and TWIC currents for fault location
estimation.
Fig. 12. Test setup using LEA signals to test the TW fault locating system.
Fig. 13 and Fig. 14 show the phase currents at the sending The relays filter the phase currents to capture the high-
and receiving terminals, respectively, for an AB fault at frequency content of the signals. The relays exchange the time
160.45 miles (from the sending terminal). stamp of the retrieved high-frequency wave. Fig. 15 and
Fig. 16 show the high-frequency content of the phase currents
that were retrieved from the relays.
Primary Current (A)
Fig. 13. Phase currents applied to the sending-end terminal for an AB fault.
x 104
2
1.5
Fault Initiated
1
Fig. 16. TWs captured at the receiving end for an AB fault.
B. Testing Using a Physical Line Model another 161 kV line for the next 17 miles. The line was
Additional verification was performed using the physical originally built for 115 kV and was later upgraded to 161 kV
single-phase transmission line model shown in Fig. 17. without changing conductors or insulators.
Although less precise and significantly less versatile than
EMTP simulations, the physical low-energy transmission line
Drummond
model offered the ability to test the entire system (including
the relay input CTs).
Idaho Wyoming
Targhee
Targhee Tap
H33 J7 0.25
GW
7' J7 0.94
H33 2.22
J7 4.08
.5 5'
16 J30 0.79
J30 0.42
J30 0.08
15'
J7 8.86
18.67' 24.67'
24.67' 18.67'
Fig. 22. Phase voltages and currents captured during line energization from
Goshen.
Fig. 25. Phase currents at Drummond for the C-phase-to-ground fault at Fig. 27. Phase currents at Goshen for the B-phase-to-ground fault at
67.91 miles from Goshen terminal. 38.16 miles from the Goshen terminal.
Fig. 29. Damaged insulator at 38.16 miles from the Goshen terminal.
13
VII. CONCLUSION
Adding TW-based fault location to line protective relays
improves their fault locating capability compared with relays
that use only impedance-based fault locating methods.
Relays that use TWs and impedance-based methods to
estimate fault location provide results independent of the fault
incidence angle. These relays provide fault location at the line
Fig. 30. Phase currents at Goshen for the B-phase-to-ground fault at
66.86 miles from the Goshen terminal. terminals within a couple of seconds without the need for an
additional computer and software.
Field cases demonstrate that relays with TW fault locating
capability can locate faults to within a tower span in
applications including lines with mutual coupling.
Furthermore, there is no need for additional secondary wiring
and communications equipment when TW-based fault location
is part of the line differential relay.
VIII. REFERENCES
[1] T. W. Stringfield, D. J. Marihart, and R. F. Stevens, “Fault Location
Methods for Overhead Lines,” Transactions of the American Institute of
Electrical Engineers – Part III: Power Apparatus and Systems, Vol. 76,
Issue 3, April 1957, pp. 518–530.
Fig. 31. Phase currents at Drummond for the B-phase-to-ground fault at [2] D. J. Marihart and N. W. Haagenson, “Automatic Fault Locator for
66.86 miles from the Goshen terminal. Bonneville Power Administration,” proceedings of the 1972 IEEE
Power and Energy Society Summer Meeting, San Francisco, CA,
Based on the prestrikes recorded at the Goshen terminal, it July 1972.
is suspected that the fault was due to lightning. The time [3] M. Ando, E. O. Schweitzer, III, and R. A. Baker, “Development and
stamps corresponding to the TW arrival obtained from the Field-Data Evaluation of Single-End Fault Locator for Two-Terminal
HVDC Transmission Lines, Part I: Data Collection System and Field
event records include the following: Data,” IEEE Transactions on Power Apparatus and Systems,
Goshen: TwaveGosh = 32.815358756 seconds Vol. PAS–104, Issue 12, December 1985, pp. 3524–3530.
Drummond: TwaveDrum = 32.815023378 seconds [4] M. Ando, E. O. Schweitzer, III, and R. A. Baker, “Development and
We estimated a fault location of 67.25 miles from the Field-Data Evaluation of Single-End Fault Locator for Two-Terminal
HVDC Transmission Lines, Part II: Algorithm and Evaluation,” IEEE
Goshen terminal. The line crew found the fault at 66.86 miles Transactions on Power Apparatus and Systems, Vol. PAS–104,
from Goshen. Issue 12, December 1985, pp. 3531–3537.
[5] M. A. Street, “Delivery and Application of Precise Timing for a
4) Summary of Results
Traveling Wave Powerline Fault Locator System,” proceedings of the
Table III provides the fault location reported by the relay 22nd Annual Precise Time and Time Interval (PTTI) Applications and
based on TW measurements and the actual fault location Planning Meeting, Vienna, VA, December 1990, pp. 355–360.
reported by BPA. The errors between the TW-based estimated [6] P. F. Gale, “Overhead Line Fault Location Based on Travelling Waves
distances and the BPA reported distances are attributed to the and GPS,” proceedings of the Precise Measurements in Power Systems
Conference, Arlington, VA, October 1993.
nonuniformity of the line sag due to terrain elevation changes
[7] M. Aurangzeb, P. A. Crossley, and P. Gale, “Fault Location on a
and differences in tower structures. BPA is working on
Transmission Line Using High Frequency Travelling Waves Measured
providing accurate line length estimates to include line sag. at a Single Line End,” proceedings of the 2000 IEEE Power Engineering
Society Winter Meeting, Vol. 4, Singapore, January 2000,
pp. 2437–2442.
14