UNIT-1 HP BYPASS ATTEMPERATION PARAMETERS

Date: 05/01/2018

Parameter Before isolation After isolation After TMD side work done After one hours

Hp Bypass Attemp I/L Temp DEG C 240 240 237


Hp Bypass Attemp O/L Temp DEG C 247 379 237
M S Flow TPH 355 344 340
Feed Water Flow TPH 339 345 350
RH Pr. BAR 29 29 28
RH Temp DEG C 525 539 527
M S Pr. BAR 124 126 124
M S Temp DEG C 537 538 528
Drum Level MMWC 5 8 1
Load MW 108 108 107
VACUUM MBARA 134 138 137
HP BYPASS ATTEMPERATION PARAMETERS
Date: 06/10/2016

Parameter Before isolation After isolation

Hp Bypass Attemp I/L Temp DEG C 445 439


Hp Bypass Attemp O/L Temp DEG C 236 413
M S Flow TPH 315 328
Feed Water Flow TPH 337 330
RH Pr. BAR 25.9 26.2
RH Temp DEG C 522 538
M S Pr. BAR 118 122
M S Temp DEG C 536 537
Drum Level MMWC -1 0
Load MW 90 92
VACUUM MBARA 320 320
/10/2016

Present Condition

453
236
326
335
25.7
527
116
537
0
90
302