Significant Changes

to the
Philippine Electrical Code
2009 Edition

Jaime V. Mendoza, MTM


Board Member

BOARD OF ELECTRICAL ENGINEERING


PROFESSIONAL REGULATION COMMISSION
2

PEC – 2009 (8th Edition)


‰ BEE Resolution No. 12 Series of 2009 –
Adoption of the Revised (8th Edition)
Philippine Electrical Code Part I as Part of
the Rules and Regulations Concerning the
Practice of Electrical Engineering and as
Referral Code in Accordance with the
National Building Code – Sept. 14, 2009.
‰ Published in the Philippine Star last
February 18, 2010 (Thursday) page B-10

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
3

R. A. 7920
‰ An Act For, A More Responsive and
Comprehensive Regulation For the Practice,
Licensing, and Registration of Electrical
Engineers and Electricians.
‰ Sec. 4 Powers and Duties of the Board
¾ The Board shall exercise executive
/administrative or quasi-legislative (rule-
making) or quasi-judicial (investigative)
powers in carrying out the provisions of
this Act.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
4

Powers of the Board


‰ Sec. 29. Revocation of Certificates of
Registration and Suspension from the
Practice of the Profession.
ƒ The Board shall have the power, upon proper
notice and hearing, to revoke any certificate of
registration of any registrant, to suspend him
from the practice of the profession or to
reprimand him for any specified in the preceding
section, or for the use of perpetration of any
fraud or deceit in obtaining a certificate of
registration, or for gross negligence or
incompetence or for unprofessional or
dishonorable conduct, for violation of this Act, the
rules and regulations and other policies of the
Board and the Code of Professional Ethics.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
5

Licensing
‰ Definition – a permission granted by competent
authority to engage in a practice of profession or
business or in an activity.
‰ A PEE who designed, signed, and sealed an electrical
plans – means he/she guaranteed the safety of the
electrical plans for 15 years in accordance to Civil
Code.
‰ PEE, REE or RME who signed as in-charge of
installations also guaranteed the safety of the
electrical installations for 15 years.
‰ You can only guaranteed the safety of your electrical
designs/installations if you are well-versed in the
Philippine Electrical Code.
“Licensing guarantees the safety
of your works!!!!”

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
6

THE PHILIPPINE ELECTRICAL CODE


KEY TO SAFETY AND FIRE PREVENTION

PURPOSE OF PEC
The primary objective of the code is to
establish basic materials quality and electrical
works standards for the safe use of electricity
for light, heat, power, communications,
signaling and for other purposes.
“Practical safeguarding of persons and
property from hazards arising from the use of
electricity”
COMPLIANCE TO THE PEC WILL ENSURE SAFETY AND
PREVENT ELECTRICAL FIRES

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
7

The Philippine
The Philippine
Grid/Distribution
Electrical Code
Codes
Performance Safety
Standards Standards
• Power Quality • Design and Specifications
• Reliability • Installation
• System Loss • Operation & Maintenance

GRID/DISTRIBUTION
DEVELOPMENT
PLANNING CRITERIA

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
8

THE PHILIPPINE ELECTRICAL CODE


The PEC is a safety standard,
not a design guide. Electrical
designs must comply with
the requirements of PEC to
ensure safety.

Energy management,
maintenance, and power
quality issues aren’t within
the scope of the PEC.

Consideration should be
given for future expansion
of electrical systems but this
is not a Code requirement.
BOARD OF ELECTRICAL ENGINEERING Significant Changes to the
PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
9

Philippine Electrical Code


‰ Enforcement
1. This Code is intended for mandatory application
by government bodies exercising legal
jurisdiction over electrical installation.
2. These government bodies will have the
responsibility of implementing the provision of
this Code in deciding on the approval of
equipment and materials and for granting the
special permission contemplated in this Code,
where it assured that equivalent objectives can
be achieved by establishing and maintaining
effective safety.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
10

Philippine Electrical Code


‰ Interpretation
Upon recommendation of the Code
Committee, the Board of Electrical
Engineering shall render the final
decision in the interpretation of any
portion of the Philippine Electrical
Code, in case of controversy.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
11

The National Electrical Code


‰ The first documented case of a Code as a
requirement of rules was published on 16th Nov.
1881 entitled “The Dangers of Electric Lighting”.
‰ The first NEC was developed in 1897, eighteen after
the invention of incandescent light bulb by Thomas
A. Edison.
‰ Since 1911, the NFPA of Quincy, Massachussets, has
been responsible for the maintenance and
publication of the NEC.
‰ Regularly revised (every three years) to reflect the
evolution of products, materials, and installation
techniques.
‰ 21 Separate Committee, each consisting of 15-20
persons. Members of each committee meet several
times, discuss proposed changes, accepting some
and rejecting others, and rewrite (as required) the
sections of the Code that were assigned to their
committee.
BOARD OF ELECTRICAL ENGINEERING Significant Changes to the
PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
12

THE PHILIPPINE ELECTRICAL CODE

Code Arrangement

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
13

THE PHILIPPINE ELECTRICAL CODE

CLASSIFICATION OF CODE
RULES
1. Wiring Design Rules
2. Installation Rules
3. Manufacturing Rules

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
14

THE PHILIPPINE ELECTRICAL CODE

CLASSIFICATION OF CODE RULES

Wiring design rules used to determine


sizes and rating of circuit conductors and
devices.
Example:
1. Branch circuit conductors supplying a single
motor shall have an ampacity not less than
125% of the full-load current. Section 4.30.2.2
2. The disconnecting means for motor circuits shall
have an ampere rating of at least 115% of the
full-load current rating of the motor. Section
4.30.10.10(a)
BOARD OF ELECTRICAL ENGINEERING Significant Changes to the
PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
15

THE PHILIPPINE ELECTRICAL CODE

CLASSIFICATION OF CODE RULES

Installation rules
Example:
1. A disconnecting means shall be located within
sight from the motor controller. Section
4.30.102
2. In class II Division I Locations, motors,
generators, and other rotating electric
machinery shall be dust ignition proof or totally
enclosed pipe ventilated and shall be approved
for class II locations. Sections 5.02.8

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
16

THE PHILIPPINE ELECTRICAL CODE

CLASSIFICATION OF CODE RULES

Manufacturing rules
Example:
Section 4.30.1.7
A motor shall be marked with the following
information:
1) Manufacturer’s Name
2) Rated Volts and Full-load Amperes
3) Rated Frequency and Number of Phases, if
an alternating current motor, etc.
4) Rated full-load speed

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
17

The Philippine Electrical Code

Various Categories of the Code Rules which apply in a Motor and the Circuits

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
18

ELECTRICAL FIRES
‰ If a fault develops, the current (and heat energy)
can increase to the extent that either the appliance
burns out, the connecting wiring overheats and
melts the plastic insulation or the plug and socket
may burn out.
‰ An electrical fire then occur where the overheated
wiring, motor, plug, etc. are in contact with or close
to flammable or combustible material.

‰ ELECTRICAL FIRE can be defined as a fire


where an electric current or electrical fault
is found to have been the source of ignition.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
19

Components that Create a Fire or


Explosion

combustion

Triangle of Fire

Very Significant on PEC Installation Rules!!!


BOARD OF ELECTRICAL ENGINEERING Significant Changes to the
PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
20

Significant Changes to the


Philippine Electrical Code 2009 Edition
‰ Regularly revised (every three years) to
reflect the evolution of products, materials,
and installation techniques.
‰ 21 Separate Committee, each consisting of
15-20 persons. Members of each committee
meet several times, discuss proposed
changes, accepting some and rejecting
others, and rewrite (as required) the
sections of the Code that were assigned to
their committee.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
21

Change Type in the PEC 2009


1. New
2. Revision
3. Relocated
4. Reorganization
5. Universal Change
6. Deletion (310.5)

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
22

New - Definitions
‰ AHJ – Authority Having Jurisdiction
‰ Bonding Jumper, System
‰ Coordination (Selective)
‰ Electrical Practitioner, Licensed
‰ Electrical Practitioner, Non-Licensed
‰ Guest Rooms
‰ Guest Suite
‰ Handhole Enclosure

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
23

Guest Room

An accommodation combining living, sleeping,


sanitary and storage facilities.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
24

Guest Suite

An accommodation with two or more contiguous rooms


comprising a compartment, with or without doors between
such rooms, that provides living, sleeping, sanitary, and
storage facilities.
BOARD OF ELECTRICAL ENGINEERING Significant Changes to the
PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
25

New Provision
‰ PEC 2.10.1.5 (c) Identification for Branch
Circuits, page 69
‰ (c) Ungrounded Conductors
Where the premises wiring system has branch
circuits supplied from more than one nominal
voltage system, each ungrounded conductor of a
branch circuit, where accessible shall be
identified by system. The means of identification
shall be permitted to be by separate color
coding, marking tape, tagging, or other
approved means and shall be permanently
posted at each branch-circuit panelboard or
similar branch-circuit distribution equipment.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
26

PEC 2.10.1.5 (c) – Identification for Branch


Circuit for Ungrounded Conductors

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
27

New Provision
‰ 2.10.1.8(b)(2) –GFCI
Protection Other than
Dwelling
ƒ Commercial and
institutional kitchens –
for the purposes of this
section, a kitchen is an
area with a sink and
permanent facilities for
food preparation and
cooking. (Culinary
Schools)

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
28

New Provision

‰ 2.10.1.8(b)(4) –GFCI
Protection Other than
Dwelling
ƒ Outdoor in Public
Spaces – for the
purpose of this section
a public space is
defined as any space
that is for use by, or is
accessible to the
public.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
29

New Provision
‰ 2.10.1.8(b)(5) –GFCI
Protection Other than
Dwelling
ƒ (5)Outdoor , where
installed to comply with
2.10.3.14 Heating, Air-
conditioning, and
Refrigeration Outlet

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
30

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
31

New Provision

2.10.1.8(c)Boat Hoists
ƒ GFCP for personnel
shall be provided for
outlets that supply
boat hoists installed in
dwelling unit locations

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
32

2.10.1.8 GFCI Protection for


Personnel
b) Other than Dwelling Units
1) Bathrooms*
2) Commercial and institutional kitchens
3) Rooftops*
4) Outdoors in public spaces
5) Outdoors, where installed to comply with
2.10.3.14

* Including in PEC 2000

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
33

GFCI Protection for Personnel


PEC-2.10.1.8 (a)
a) Dwelling Units
1. Bathrooms
2. Garages
3. Outdoors
4. Crawl spaces at or
below grade level
5. Unfinished
basements
6. Kitchens for
countertop
appliances
7. Wet bar sinks
8. Boathouses (New Provision)
BOARD OF ELECTRICAL ENGINEERING Significant Changes to the
PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
34

New Provision
‰ 2.10.1.12.Arc-Fault
Circuit Interrupter
Protection
(b) Dwelling Unit
Bedrooms – All single
phase, 15 and 20 A
branch circuits supplying
outlets installed in
dwelling unit bedrooms
shall be protected by a
listed AFCI. Combination
type installed to provide
protection of the branch
circuit.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
35

Arc-Fault Circuit Interrupter

An AFCI is a device intended to open the circuit when


it detects the current waveform characteristics that are
unique to an arcing fault.
BOARD OF ELECTRICAL ENGINEERING Significant Changes to the
PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
36

AFCI

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
37

Ground Fault Circuit Interrupter

A GFCI is designed to protect persons against electric shock.


It operates on the principles of monitoring the unbalanced current
Between the ungrounded and the grounded neutral conductor.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
38

New Provision

p88
BOARD OF ELECTRICAL ENGINEERING Significant Changes to the
PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
39

Revised - Definition
‰ Dwelling Unit – one or more rooms for
the use of one or more persons as a
housekeeping unit with space for eating,
living, sleeping, and permanent
provisions for cooking and sanitation. PEC
2000
‰ Dwelling Unit – a single unit, providing
complete and independent living facilities
for one or more persons, including
permanent provisions for living, sleeping,
cooking, and sanitation. (PEC 2009)
BOARD OF ELECTRICAL ENGINEERING Significant Changes to the
PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
40

Revised - Definition
‰ 2.10.1.8(a)(8) GCFI Protection
‰ Laundry, utility, and wet bar sinks –
where the receptacles are installed to
serve the countertop surfaces and are
located within 1.8 m (6 ft) of the outside
edge of the sink.
‰ Laundry, utility, and wet bar sinks –
where the receptacles are installed within
1.8 m (6 ft) of the outside edge of the
sink.
BOARD OF ELECTRICAL ENGINEERING Significant Changes to the
PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
41

GFCI Protection for Personnel


7. Dwelling Wet Bar Sinks

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
42

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
43

Revised - Definition
‰ Garage – a building or portion of a building in
which one or more self-propelled vehicles
carrying volatile flammable liquid, for fuel or
power are kept for use, sale, storage, rental,
repair, exhibition, or demonstrating purposes,
and all that portion of a building that is on or
below the floor or floors in which such vehicles
are kept and that is not separated there from by
suitable cutoffs.
‰ Garage – A building or portion of a building in
which one or more self-propelled vehicles can be
kept for use, sale, storage, rental, repair,
exhibition, or demonstration purposes.
BOARD OF ELECTRICAL ENGINEERING Significant Changes to the
PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
44

Relocated -Definition
‰ Solidly Grounded – PEC 2000
‰ Grounded, Solidly – PEC 2009

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
45

2.1.1.6(b) Means of Identying


Grounded Conductors PEC-2000
(b) Sizes Larger than 14 mm2. An
insulated rounded conductor larger than
14 mm2 shall be identified either by a
continuous white or natural gray outer
finish or by three continuous white stripes
on other than green insulation along its
entire length or at the time of installation
by a distinctive white marking at its
terminations. This marking shall encircle
the conductor or insulation.
BOARD OF ELECTRICAL ENGINEERING Significant Changes to the
PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
46

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
47

2.1.1.6(b) Means of Identying


Grounded Conductors PEC-2009
‰ Sizes Larger Than 14 mm2. An insulated
conductor larger than 14 mm2 shall be
identified by one of the following means:
1) By a continuous white or gray cover finish.
2) By three continuous white stripes along its
entire length on its entire length on other
than green insulation
3) At the time of installation, by a distinctive
white or gray marking at its terminations.
This marking shall encircle the conductor or
insulation.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
48

Section 2.0.1.6 (a)

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
49

2.1.1.6(d) Means of Identifying


Grounded Conductors PEC-2000
(d) Grounded Conductors of Different
Systems. Where conductors of different
systems are installed in the same raceway,
cable, box, auxiliary gutter, or other type of
enclosure, one system grounded conductor, if
required, shall have an outer covering
conforming to Section 2.1.1.6(a) or (b). Each
other system grounded conductor shall have an
outer covering of white with a readily
distinguishable different colored stripe (not
green) running along the insulation, or other and
different means of identification as allowed by
Section 2.1.1.6(a) or (b) that will distinguish
each system grounded conductor.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
50

2.1.1.6(d) Means of Identifying


Grounded Conductors PEC-2009
(d) Grounded Conductors of Different Systems. Where grounded
conductors of different systems are installed in the same raceway,
cable, box, auxiliary gutter, or other type of enclosure, each grounded
conductor shall be identified by system. Identification that distinguishes
each system grounded conductor shall be permitted by one of the
following means:
(1) One system grounded conductor shall have an outer
covering
conforming to 2.0.1.6(a) or 2.0.1.6(b).
(2) The grounded conductor(s) of other systems shall have a
different outer covering conforming to 2.0.1.6(a) or 2.0.1.6(b) or by an
outer covering of white or gray with a readily distinguishable colored
stripe other than green running along the insulation.
(3) Other and different means of identification as allowed by
2.0.1.6(a) or 2.0.1.6(b) that will distinguish each system grounded
conductor.
This means of identification shall be permanently posted at each
branch-circuit panelboard.
BOARD OF ELECTRICAL ENGINEERING Significant Changes to the
PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
51

An Example of Conductor
Color Coding

120/240 – 208Y/120 – 480Y/277-


V, Single V, Three- V, Three-
Phase Phase Phase
Phase A Black Black Brown
Phase B Red Red Orange

Phase C Blue Yellow


Neutral White White with Gray
red Stripe

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
52

Section 2.0.1.6 (d) (1)

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
53

Mixing Grounded Neutral Conductors


Different System Sec. 2.0.1.6(d)(2)

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
54

Section 2.0.1.7(c)

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
55

Branch Circuits
A. Tamper-Resistant Receptacles in
Dwellings Unit (406.11) (NEC-2008)
Why do you think it is a tamper-
resistant receptacle?

…..To increase safety for children.

…..maybe that your son, daughter, or


grandchildren that you will save…

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
56

Branch Circuits
A. Tamper-Resistant Receptacles in
Dwellings Unit (406.11) (NEC-2008)

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
57

Reorganization – Article 2.20


Branch-Circuit, Feeder, and Service Calculations
2000 Article 2.20 2009 Article 2.20
Part Sections Part Sections
I. General 2.20.1.1- 4 I. General 2.20.1.1 -5
II. Feeders and 2.20.2.1 - 14 II. Branch Circuit 2.20.2.1 - 7
Services Load Calculations

III. Optional 2.20.3.1 - 7 III. Feeder and 2.20.3.1 - 23


Calculations for Service Load
Computing Feeder Calculations
and Service Loads
IV. Method for 2.20.4.1 - 2 IV. Optional Feeder2.20.4.1 - 9
Computing Farm Loads And Service Load
Calculations
V. Farm Calculation 2.20.5.1- 4

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
58

Universal Change
‰ A universal change throughout the 2009
PEC is the replacement of “computed
load” and “demand load” with “calculated
load.” For example, the term demand
load is being replaced with calculated load
to improve clarity and to reduce
confusion, especially when related to
“calculated load” and “demand factor.”
The term calculated load includes demand
factor, the concepts of diversity, and
historical data.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
59

2.30.6 Service Equipment –


Disconnecting Means
a) Location
a) Readily Accessible Location. The service
disconnecting means shall be installed at a
readily accessible location of a building or a
structure. For a building, the service
disconnecting means shall be installed either
at the outside wall or inside nearest point of
entrance of the service conductors to the
building.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
60

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
61

2.30.6 Service Equipment –


Disconnecting Means
a) Location
2) Bathrooms. Service disconnecting means
shall NOT be installed in bathrooms.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
62

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
63

Article 2.50 Grounding


and Bonding
‰ The title of Article 2.50 has been changed from
“Grounding” to “Grounding and Bonding.”
‰ Change Significance: The scope of the article
clearly covers both grounding and bonding.
Adding the term bonding to the title of the
article is appropriate, and is consistent with the
fact that there are generally as many bonding
requirements and provisions included within
Article 2.50 as there are grounding
requirements, if not more.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
64

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
65

2.50.1.2 Definitions (Revision)


‰ Effective Ground-Fault Current Path – An
intentionally constructed, permanent, low
impedance electrically conductive path
designed and intended to carry current
under ground-fault conditions from the
point of a ground fault on a wiring system
to the electrical supply source and that
facilitates the operation of the
overcurrent protective device or ground-
fault detectors on high-impedance
grounded systems.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
66

Effective Ground-Fault Current Path

Metal parts of premises wiring are bonded to an effective


ground-fault current path that has sufficiently low impedance
to quickly clear line-to-case faults by opening the circuit
protection device.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
67

Effective Ground-Fault Current Path

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
68

Effective Ground-Fault Current Path

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
69

Earth is Not an Effective Ground-


Fault Current Path

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
70

2.50.1.2 Definitions
‰ Ground Fault- An unintentionally, electrically
conducting connection between an ungrounded
conductor of an electrical circuit and the
normally non-current-carrying conductors,
metallic enclosures, metallic raceways, metallic,
or earth.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
71

2.50.1.2 Definitions
‰ Ground-Fault Current
Path- An electrically
conductive path from
the point of ground
fault on a wiring
system through
normally non-
current-carrying
conductors,
equipment, or the
earth to the electrical
supply source.
BOARD OF ELECTRICAL ENGINEERING Significant Changes to the
PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
72

Article 2.50
‰ 2.50.2.5(b) Main Bonding Jumper
‰ 2.50.2.11 Grounding Separately Derived
Alternating-Current Systems
‰ 2.50.2.13 Buildings or Structures Supplied by
Feeder(s) or Branch Circuit(s)
‰ 2.50.3 Grounding Electrode System and
Grounding Electrode Conductor
‰ 2.50.10 Grounding of Systems and Circuits of 1
kV and Over (High Voltage)

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
73

3.10.1.4 Conductors in Parallel


‰ The paralleled conductors in each phase,
polarity, neutral, or grounded circuit
conductor shall comply with all the
following:
1. Be the same length
2. Have the same conductor material
3. Be the same size in circular mil area
4. Have the same insulation type
5. Be terminated in the same manner.
Why?????? …….. See FPN:

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
74

3.10.1.5 Minimum Size of Conductors

‰ The minimum size of conductors shall be


as shown in Table 3.10.1.5, except as
permitted elsewhere in this Code.
‰ Removal of 10 previous exceptions were
not needed

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
75

3.10.1.6 Shielding
‰ In this section’s exception, the voltage
has been reduced from 8 kV to 2.4 kV for
use of unshielded conductors. Cables
operated at a voltage higher than 2.4 kV
will now be required to be shielded.
‰ Many cable manufacturers specifically
recommend against the use of non-
shielded cable above 2 kV because of
arcing problems and cables without
shielding have a very high failure rate.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
76

3.10.1.8 Locations
d) Locations Exposed to Direct Sunlight. Insulated
conductors and cables used where exposed to
direct rays of the sun shall comply with one of
the following: (be of a type listed for sunlight
resistance or listed and marked “sunlight
resistant”)
1) Cables listed, or listed and marked , as being sunlight
resistant
2) Conductors listed, or listed and marked , as being
sunlight resistant
3) Covered with insulating material, such as tape or
sleeving, that is listed and marked ,as being sunlight
resistant.”

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
77

3.10.1.10 Temperature Limitation


of Conductors
‰ The PEC 2009 has added a new Fine Print
Note with information on derating for
conduits on rooftops that have direct
sunlight exposures; 17ºC is the indicated
value to be added to the outdoor ambient
temperature to compensate for the direct
solar gain.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
78

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
79

3.10.1.15(b)(2) Adjustment Factors

‰ A new last sentence has been added to


3.10.15(b)(2)(a) to require that individual
conductors of paralleled sets be counted as
current-carrying conductor. This is intended to
clarify varying interpretations of whether each
conductor of a paralleled set of conductors is
required to be counted individually or if all of the
conductors count as one for the purpose of
derating. Clearly, each conductor of the parallel
set is required to be counted individually for the
purposes of rating.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
80

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
81

Configuration Conductor if Derating Conductors Derating


Neutral is Percentage if Neutral is Percentage
Counted Not Counted

All conductors
in single
12 9
conduit

4 conductors in
3 conduits or
4 3
cables
All conductors
in metal
wireway or 12 9
auxiliary gutter
All conductors
in nonmetallic
wireway or 12 9
auxiliary gutter
BOARD OF ELECTRICAL ENGINEERING Significant Changes to the
PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
82

Table 3.10.1.15(b)(2)(a) Adjustment Factors for More than Three Current-


Carrying Conductors in a Raceway or Cable

Percent of Values in Tables 3.10.1.16


Number of Current- Through 3.10.1.19 as Adjusted for
Carrying Conductors Ambient
Temperature if Necessary
4–6 80
7–9 70
10 – 20 50
21 – 30 45
31 – 40 40
41 and above 35

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
83

Configuration Conductor if Derating Conductors Derating


Neutral is Percentage if Neutral is Percentage
Counted Not Counted

All conductors
in single
12 50 9 70
conduit

4 conductors in Not
3 conduits or
4 80 3 required
cables
All conductors Not Not
in metal
12 required 9 required
wireway or
auxiliary gutter
All conductors
in nonmetallic
wireway or 12 50 9 70
auxiliary gutter
BOARD OF ELECTRICAL ENGINEERING Significant Changes to the
PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
84

Section 3.10.1.15(b)(4)

(4) Neutral Conductor.


a) A neutral conductor that carries only the unbalanced current
from other conductors of the same circuit shall not be required
to be counted when applying the provisions of
Section3.10.1.15(b)(2)(a).
b) In a 3-wire circuit consisting of two phase wires and the
neutral of a 4-wire, 3-phase wye-connected system, a common
conductor carries approximately the same current as the line-
to-neutral load currents of the other conductors and shall be
counted when applying the provisions of Section
3.10.1.15(b)(2)(a).
c) On a 4-wire, 3-phase wye circuit where the major portion of the
load consists of nonlinear loads, harmonic currents are
present in the neutral conductor; the neutral shall therefore be
considered a current-carrying conductor.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
85

Notes
‰ For metal auxiliary gutters, 3.66.2.14(a)
indicates that derating is not required so long as
the number of current-carrying conductors at
any cross section does not exceed 30. A similar
statement is included for sheet metal wireways
in 3.76.2.13.
‰ Derating for the number of current-carrying
conductors in non-metallic auxiliary gutters and
wireways is required, beginning at four-current
carrying conductors, because conductors in non-
metallic enclosures do not dissipate heat as well
as those in sheet-metal enclosures.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
86

Introduction
‰ Art. 6.95 contains many requirements to
keep that supply of water uninterrupted.
For example:
1. Locating the pump so as to minimize its
exposure to fire.
2. Ensuring that the fire pump and its jockey
pump have a reliable source of power.
3. It makes sense to keep fire pump wiring
independent.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
87

Introduction
‰ Other requirements seem wrong at first
glance, until you remember why the fire
pump is there in the first place.
For example:
1. The disconnect must be lockable in the
closed position.
2. Fire pumps power circuits cannot have
automatic protection against overload.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
88

Introduction

¾ “ It’s better to run the fire pump until


its winding melt, than to save the fire
pump and lose the facility”

¾ And the intent of Article 6.95 is to


save the facility.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
89

6.95.1.1 Scope
a) Covered
1) Electric power sources and interconnecting
circuits
2) Switching and control equipment dedicated
to fir pump drivers
b) Not Covered
1) The performance, maintenance, and
acceptance testing of the fire pump system,
and the internal wiring of the components
of the system
2) Pressure maintenance (jockey or makeup)
pumps

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
90

6.95.1.3 Power Sources for


Electric-Motor Driven Fire Pumps
a) Individual Source
1) Electric Utility Service. A separate
service from a connection located ahead
of but not within the service
disconnecting means.
2) On-Site Power. An on-site power supply,
such as generator, located and
protected to minimize damage by fire is
permitted to supply a fire pump.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
91

6.95.1.3 Power Sources for


Electric-Motor Driven Fire Pumps

a) Electric-Utility Service Connection

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
92

6.95.1.3 Power Sources for


Electric-Motor Driven Fire Pumps

a) Electric-Utility Service Connection

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
93

6.95.1.3 Power Sources for


Electric-Motor Driven Fire Pumps

2) On-Site Power Production Facility


BOARD OF ELECTRICAL ENGINEERING Significant Changes to the
PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
94

6.95.1.3 Power Sources for


Electric-Motor Driven Fire Pumps
b) Multiple Sources
1) Generator Capacity. Shall have
sufficient capacity to allow normal
starting and running 0f the motor(s)
driving the fire pump(s) while supplying
other simultaneously operated load.
2) Feeder Sources.
3) Arrangement. The power sources shall
be arranged so that a fire at one will not
cause an interruption at the other
source.
BOARD OF ELECTRICAL ENGINEERING Significant Changes to the
PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
95

6.95.1.3 Power Sources for


Electric-Motor Driven Fire Pumps

2) Feeder Sources
BOARD OF ELECTRICAL ENGINEERING Significant Changes to the
PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
96

6.95.1.5 Transformers
‰ Dedicated transformer and overcurrent
protection sizing can be broken down into
three requirements.
1. The transformer must be size to at least 125%
of the sum of the loads.
2. The transformer primary overcurrent device
must be at least a specified minimum size.
3. The transformer secondary must not contain any
overcurrent device whatsoever.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
97

6.95.1.5 Transformers

The overcurrent device in the primary of a transformer supplying


a fire pump installation. The device is required to be sized to carry
the locked-rotor current motor(s) and associated fire pump
accessory equipment indefinitely.
BOARD OF ELECTRICAL ENGINEERING Significant Changes to the
PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
98

6.95.1.6 Power Wiring


a) Service and Feeder Conductors.
Supply conductors must be
physically routed outside buildings
and must be installed in accordance
with Article 2.30. Where supply
conductors cannot be routed outside
buildings, they must be encased in 2
inches or 50 mm of concrete or brick.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
99

6.95.1.6 Power Wiring


b) Circuit Conductors.
Fire pump supply conductors on the load
side of the final disconnecting means and
overcurrent device(s) must be kept entirely
independent of all other wiring. They can
be routed through a building using one of
the following methods:
1) Be encased in a minimum 2 inches or 50 mm of
concrete
2) Be within an enclosed construction dedicated to
the fire pump circuit(s) and having a minimum
of a 1-hour fire-resistant rating
3) Be listed electrical circuit protective system with
a minimum 1-hour fire rating.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
100

6.95.1.6(c)(2) BC Conductor Size


Fire Pump Motor
Branch Circuit Conductor Size
From Table
4.30.14.5(b)

Branch circuit conductors to a single fire pump


motor must have a rating not less than 125% of the
motor
FLC as listed in Table 4.30.14.2 or 4.30.14.4
BOARD OF ELECTRICAL ENGINEERING Significant Changes to the
PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
101

6.95.1.7 Voltage Drop

The voltage drop at the line terminals of the controller


when the motor starts (locked-rotor current), must not
drop more than 15% below the controller’s rated voltage.
BOARD OF ELECTRICAL ENGINEERING Significant Changes to the
PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
102

6.95.1.7 Voltage Drop

Fire Pump Conductor Size – Voltage Drop

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
103

6.80 Swimming Pools, Fountains,


and Similar Installations
Article 6.80 - applies to decorative pools
and fountains; swimming, wading, and
wave pools; therapeutic tubs and tanks;
hot tubs; spas; hydromassage bathtubs;
and similar installation including pools
used in religious services where
participants are immersed in water. The
installations covered by this article can be
indoors or outdoors, permanent or
storable, and may or may not be directly
supplied by electrical circuits of any
nature.
BOARD OF ELECTRICAL ENGINEERING Significant Changes to the
PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
104

6.80.1.2 Definitions

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
105

6.80.1.2 Definitions

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
106

6.80.1.3 Other Articles

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
107

6.80.1.8 Overhead Conductor Clearance

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
108

6.80.1.8 Overhead Conductor Clearance

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
109

6.80.1.12 Maintenance Disconnecting Means

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
110

6.80.2 Permanently Installed Pools

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
111

6.80.2 Permanently Installed Pools

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
112

6.80.2.3(a)(4) Restricted Space

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
113

6.80.2.3(a)(5) GFCI Protection

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
114

6.80.2.3(a)(5) GFCI Protection

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
115

6.80.2.3(a)(5) GFCI Protection

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
116

4.11.1.4(b) Lighting Systems


Operating at 30 V or less

10 ft = 3 m

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
117

6.80.2.3(b) Luminaires

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
118

6.80.2.4(a)(4) Underwater Luminaires

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
119

6.80.2.4(f) Branch-Circuit Wiring

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
120

6.80.2.7 Equipotential Bonding

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
121

6.80.2.7 Equipotential Bonding

Bonding of conductive metal parts in a swimming pool.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
122

6.80.4.2 Emergency Switch for


Spas and Hot tubs

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
123

6.80.4.4 Indoor Installations of


Spas and Hot Tubs

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
124

6.80.4.5 GFCI Protection

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
125

6.80.5 Fountains

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
126

6.80.7 Hydromassage bathtubs

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
127

6.82 Natural and Artificially Made


Bodies of Water –(New Article)

An artificially made of body of water. The electrical equipment


associated with pumps used to circulate water in this artificial
pond is subject to the requirements of Article 6.82.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
128

Definitions
‰ Artificially Made of Bodies of Water – Bodies of
water that have been constructed or modified to
fit some decorative or commercial purpose such
as, but not limited to, aeration ponds, fish farm
ponds, storm retention basins, treatment ponds,
irrigation (channel) facilities. Water depths may
vary seasonally or be controlled.
‰ Natural Bodies of Water – Bodies of water such
as lakes, streams, ponds, river, and other
naturally occuring bodies of water, which may
vary in depth throughout the year.

BOARD OF ELECTRICAL ENGINEERING Significant Changes to the


PROFESSIONAL REGULATION COMMISSION Philippine Electrical Code 2009
129