Professional Documents
Culture Documents
$5 (beams)
From Section 9.5.2, item 2, M, of the beam at
A is 272 fips, corresponding to sidesway to
the left. From Table 9-5, the maximum axial
load on column A at the second floor level
for sidesway to the left is P, = 870 kips. Using
the P-M interaction charts given in ACI
SP-17A,°™ the moment capacity of the col-
lumn section corresponding to P, = oP, = 870
kips, f= 4 ksi, f= 60 ksi, 7 = 0.75 (y=
ratio of distance between centroids of outer
rows of bars to dimension of cross-section in the
direction of bending, and p = 0001 is obtained
as 6M, = M, = 284 fi-kips. With the same size
tS aoe
NJ [tem
wxa |
Ps
NS = 2080
Figure 9-53. Relatve lexural strengths of ban and columns at
fextoror joint — wansverse directiona
DESIGN EXAMPLES — REPRESENTATIVE ELEMENTS OF A 12 STORY FRAME-SHEAR.WALL SULOING 353
CU ee
i
pf a
NS wear
Figure 9-54 Relate foxura strengths of beams and columns
at exterior joint — longitudinal direction
@)
column above and below the beam, total mo-
‘ment capacity of columns = 2284) = $68 ft-
ips. Thus,
(6)(272)
3
= 26 fckips O.K,
DM, = 568 > 6M,
‘Moment strength of columns relative to that of
framing beams in longitudinal direction (see
Figure 9-54): Since the columns considered here
are located in the center portion of the exterior
longitudinal frames, the axial forces due to seis-
‘ic loads in the longitudinal direction are negl-
sible. (Analysis ofthe longitudinal frames under
Seismic loads indicated practically zero axial
forces in the exterior columns of the four trans-
verse frames represented by frame T-1 in Figure
9-46.) Under an axial load of (see Table 9-5)
O7S[1.4D + 1.7L +187] (E=0)
= (0.15)(930) = 698 kips,
the moment capacity of the column section with
eight No. 7 bars is obtained as gM, = M, = 319
{tckips. If we assume a ratio for the negative
‘moment reinforcement of about 0.0075 in the
‘beams of the exterior longitudinal frames (by =
20 in, d = 215 in), then
A, = pbyd = (0.0075)(20)(21.)
= 3.23in?
Assume four No. 8 bars, A,
‘moment capacity of beam:
3.16 in, Negative
Ay (3.16)(60)
@> Tasch, ~ asaya) ~ 279i
oMz= Mp= ¢4.h(4~$)
= 139
as
= (0,90)(3.16)(60)
= 286 f-kips
Aa>
‘Assume a postive moment capacity of the beams
‘on the opposite side of the: column equal to
‘one-half the negative moment capacity ealeae
lated above, or 143 ft-kips. Total moment eae
pacity of beams framing into joint in longitude
nal direction, for sidesway in either direction:
mM,
mM,
284 + 143 = 429 fi-kips
(319) = 638 fe-kips
> $IDM, = $(429) = 515 ftkips_O.K.
(b) Determine transverse reinforcement requirements:
(1) Confinement reinforcement (see Figure 9-37).
‘Transverse reinforcement for confinement is re-
quired over a distance /, from column ends,
where
depth of member = 22 in. (governs)
wx
6
10> ) 2(clear height) = =2in
18 in,
Maximum allowable spacing of rectangular
hoops:
‘(smallest dimension of column)
= 2 = 55in
in, (governs)
Required cross-sectional area of confinement re-
inforcement in the form of hoops:
7
0.12sh. =
“Fou
‘where the terms are as defined for Equation 9-6
For a hoop spacing of inf, = 60,000 Thin.”
and tentatively assuming N@. 4 bar hoops (for
the purpose of estimating 4, and A), the
required cross-sectional area is
(0.12)(4)(18.4)(4000)
60,000
= 0.59 in. (governs)
484) 4000
(0.3)(4)(18.4)| 555 — 1) Sroo0
= 0.52 in?a2
SEISMIC DESIGN OF REINFORCED-CONCRETE STRUCTURES
B=? Long. bars pe oe
Figure 9-55. etal of column transverse reinforcement
BaP nin?
No. 4 hoops with one crosstie, as shown in
Figure 9-55, provide yy = 0.20) = 0.60 in.
(2) Transverse reinforcement for shear: As in the
design of shear reinforcement for beams, the
design shear in columns is based not on the
factored shear forces obtained from a lateral-
load analysis, but rather on the nominal flexural
strength provided in the columns. ACI Ap-
pendix A requires that the shear be determined
from the largest nominal moment strength con-
sistent with the estimated axial for
column.
‘Assume that an axial force close to $P, = 484
kips (corresponding to the “balanced point” on
the interaction diagram for the column section,
considered—which would yield close to if not
the largest moment strength) can occur (see
‘Table 9-5). On this basis,
-M, (at column ends)
JM, = 355 fips
{rom which (See Figure 9-41)
2(355)
AP = nips
‘Assume, for convenience,
Vo= 2h
2/4000 (22)(19.5)
eS) = saps
1000
Required spacing of No. 4 hoops with A, =
0.40 in.? (neglecting crossties) and V,
295 kips:
Achyd _ (2)(0.20)(60){19.5)
% 25
= 15.930,
Thus, the transverse reinforcement spacing over
the distance [= 22 in. near the column ends is
governed by the requirement for confinement
rather than shear.
Maximum allowable spacing of shear
ment: d/2 = 9.7 in,
Use No. 4 hoops and crossties spaced at 4 in, within
4 disiance of 24 in. from the columns ends and No. 4
‘hoops spaced at 9 in. or less over the remainder of the
‘column.
(©) Minimum length of lap splices for column vertical
bars:
‘ACI Appendix A limits the location of lap splices
in column bars within the middle half of the mem-
ber length, the splices to be designed as tension
splices
Since generally all of the column bars will be
spliced at the same location, a Class C splice will be
required.
‘The required length of splice is 1.71,, where
0.044, f,
We
> 0.0004d,f, =
1
(0.04)(0.60)(60,000)
{0.08)(0:60){60 000),
> (0.0004)(0.875)(60,000)
= 23in, (governs) > 21 in.
‘Thus, required splice length = 1.723) = 39 in
Use 40-in. lap splices.
(@) Detail of column, See Figure 9-56.
4, Design of exterior beam-column connection. The
faim is to determine the coefficient and shear-rein-
forcement requirements for the exterior beam-column
connection between the beam considered in item 2
above and the column in item 3. Assume the joint to be
located at the sixth floor level,
(a) Transverse reinforcement for confinement: ACI Ap-
pendix A requires the same amount of confinement
Teinforeement within the joint as forthe ength fy at
column ends, unless the joint is confined by beams
framing into ‘all vertical faces of the column. In the
latter case, only one-half the transverse reinforce-
ment required for unconfined joints need be pro-
vided. AGRI
A622
In the case of the beam-column joint considered
here, beams frame into only three sides of the
column, so thatthe joint is considered unconfined
In item 4 above, confinement requirements at
column ends were satisfied by No. 4 hoops with
crossties, spaced at 4 in,
(©) Check shear strength of joint: The shear across
section x-x (see Figure 9.57) of the joint is ob-
tained as the difference between the jensile force
from the top flexural reinforcement of the framing
bbeam (stressed to 125/,) and the horizontal shearDESIGN EXAMPLES — REPRESENTATIVE ELEMENTS OF 12.STORY FRAME SHEAR-WALLBULDING 353
--1-]
L
cries ne
“a
20" be
fice
[ Lo soe must acta
oma ena
from the column above, The tensile force from the
beam (three No. 9 bars), 3.0 in.) is
(3)(1.25)(60) = 225 kips
An estimate of the horizontal shear from the col-
uma, V, can be obtained by assuming that the
‘beams in the adjoining floors are also deformed so
that plastic hinges form at their junctions with the
column, with M,(beam) = 372 {t-kips (see Table
sasha
Lo reas 225
\
H
}
jest
My tesa) = 272 kine
Yr3t kien
M, = 186 okie
Figure 8-57 Horizontal shear in exterior beam-column joint,
9-7, for sidesway to left). By further assuming that
the plastic moments in the beams are ‘equally
by the columns above and below the joint, one
obtains for the horizontal shear at the columa ends
M,(beam) _ 372
+ ory height ~ 12
Tins the net shear at sstion xx of joint is 225 —
31 ='194 kips. ACI Appendix A gives the nominal
Shear strength of a joint as «function only of the
s10ss area of the joint cross-section”, and the
degree of confinement by framing beams. For the
unconfined joint considered here,
31 kips
eV. = a5 A,
(0.85)(15)(V4000 (22)?
1000
= 300 kips > V,=194kips OK,
Aza
A631
‘Note that if the shear strength of the concrete in the
joint as calculated above were inadequate, any ad-
justment would have to take the form (since trans-
verse reinforcement above the minimum required
for confinement is considered not to have a signiti-
‘cant effect on shear strength) of either an increase in
the column cross-section (and hence A,) or an in-
crease in the beam depth (to reduce the amount of
flexural reinforcement required and hence the ten-
sile force T).
(©) Detail of joint. See Figure 9-58, (The design should
be checked for adequacy in the longitudinal direc-
tion)
Note: The use of crossties within the joint may
‘cause some placement difficulties. To relieve the
‘congestion, No. 6 hoops spaced at 4 in, but without
‘rossties may be considered as an alternative. Al-
though the cross-sectional area of confinement rein-
forcement provided by No. 6 hoops at 4 in. (Ay =
0.88 in.*) exceeds the required amount (0.59 in),
the requirement of A443 of ACI Appendix A
relating to a maximum spacing of 14 in, between
rossties or legs of overlapping hoops (see Figure
9-40) will not be satisfied. However, it is believed
that this will not be a serious shortcoming in this
‘case, since the joint is restrained by beams on three
sides,
3. Design of interior beam-column connection. The
objective is 10 determine the transverse reinforcement
and shear requirements for the interior beam-column
‘connection at the sixth floor of the interior transverse
frame considered in previous examples. The column is
26 in. square and is reinforced with eight No. 11 bars.304 SEISMIC DESIGN OF REINFORCED-CONGRETE STRUCTURES
het
40 bars
1p Boar
*;
ao
a
Fe tnt oop
(a) PLAN
(b) SECTION
Figure 9-58. Detal of exterior beam-column joint
‘The beams have dimensions b = 20 in. and d = 21.5 in.
and are reinforced as noted in Section item 2 abave (see
Figure 9-52).
(a) Transverse reinforcement requirements (for con-
finement): Maximum allowable spacing of rectangu-
lar hoops,
[atest dimension of column)
no aia
| 4in. (governs)
For the column cross-seotion considered and assum-
tapi. heaps > SSA
and A, = (26)? = 676 in, With a hoop spac-
ing of 4 in the required cross-sectional area of
‘confinement reinforcement in the form of hoops is
fe (0.12)(4)(21.9)(4000)
0.128h.= = So gg
“Fou
= 0.70 in?
(governs)
= osyayary( Fe ~1)
= 0.61 in?
Since the joint is framed by beams (having widths
of 20 in,, which is greater than + of the width of the
column)'on all four sides, it is considered confined,
and a 50% reduction in the amount of confinement
reinforcement indicated above is allowed. Thus,
Agsfrequired) > 0.35 in?
No. 4 hoops with crossties spaced at 4 in. o..
provide Ay, = 0.60 in.?, (See Note at end of item 4.)
(b) Check shear strength of joint: Following the same
procedure used in item 4, the forces affecting the
horizontal shear across a section near mid-depth of
the joint shown in Figure 9-59 are obtained:
Ny
82+ 208. 560 chips
$238 = 3601
420 Bur (4, = 40in2)
1A (1.25%,)= 300 Kis
2 \
it \
= Ag(.267)
J
2 ity, = 482 tekioe
= Tibi
927 Bars (4,9 = 182)
coan
in, = 360 kins
60 kins
Figure 959, Forces acting on interior beam-column joint,DESIGN EXAMPLES — REPRESENTATIVE ELEMENTS OF A 12.STORY FRAME-SHEAR-WALL SULOING 385
the joint shown in Figure 9-59 are obtained:
(Net shear across section x-x) = T, + G— Vy
= 300 + 135 - 60
375 kips = ¥,
Shear strength of joint, noting that joint is confined:
OF. = 920/774,
(0.85)(20) (4000 (26)*
1000
= 726 kips
>K=375kips OK,
6. Design of structural wall (shearwall). The aim i
to design the structural wall section atthe frst oor of
‘one of the identical frame-shear wall systems shown in
frame T-3 (see Figure 9-46). The preliminary design, as
shown in Figure 9.45, is based on a 14-in-thick wall
with 26-in-square vertical boundary elements, each of
the latter being reinforced with eight No. 11 bars.
Preliminary calculations indicated that the cross-sec-
sion of the structural wall at the lower floor levels
‘seeded to be increased. In the following, a 20-in-thick
‘wall section with 32 x'S0sin, boundary elements rein-
forced with 24 No. 11 bars is investigated, and other
seinforcement requirements determined.
The design forces on the structural wall at the fist
oor level are listed in Table 9.6. Note that becase the
‘axis of the shear wall coincides with the center line of
the transverse frame of which it isa part, lateral loads
do not induce any vertical (axial) force on the wall
‘The calculation of the maximum axial force on the
boundary element corresponding to. Equation 92b in
Table 9.6, P, = 4166 kips, shown in Table 96, involved
the following steps: At base of wall
‘+ Dead load, D = 2823 kips.
* Live load, L = 412 kips.
+ Moment at base of wall due to seismic load
(Grom lateral load analysis of transverse frames,
including a moment of 1806 ft-kips due to acci-
dental eccentricity), M, = 38,056 fi-kips
Referring to Figure 9-43, and noting the load factors
used in Equation 9-2b of Table 9.6,
W = 0.75(1.4D + 1.7L)
(0.75) [(1.4)(2823) + (1.7)(412)] = 3489 kips
Ha = 1.4M, = (1.4)(38,056) = 53,278 ft-kips
W Ha
Boa
3499 53,278
7 + Hy = 166 ips
(a) Check whether boundary elements are required: ACT
Appendix A requires boundary elements to be pro
vided if the maximum compressive extreme-fiber
stress under factored forces exceeds 0.2//, unless
the entire wall is reinforced to satisfy Sections
A4A\] through A.4.4.3 of the Appendix (relating to
confinement reinforcement.
It will be assumed that the wall will not be
provided with confinement reinforcement over its
entire height. For a homogeneous rectangular wall
26.17 ft long (horizontally) and 20 in, (1.67 ft) thick,
(1.67)(26.17)°
oer
Ay = (1.67)(26.17) = 43.7 02
= 2494 fet
Extreme-fiber compressive stress under M, = $3,280
{tckips and P, = 3449 kips (see Table 9-6);
Myhy/2 _ 3449 (53,280)(26.17)/2
is BI 98
= 358.4 ksf = 2.49 ksi > 0.2/" = (0.2)(4)
= 08 ksi
Therefore, boundary elements are required, subject
to the confinement and special loading requirements
sperifed in ACI Appendix A.
() Determine minimum longitudinal and transverse re
inforcement requirements for wall:
(1) Check whether two curtains of reinforcement
are required: ACI Appendix A requires that two
curtains of reinforcement be provided in a wall
ifthe in-plane factored shear force assigned to
the wall exceeds 24a’, where 4. is the
cross-sectional area bounded by the web thick:
ness and the length of section inte direction of
the shear force considered From Table 9-6, the
maximum factored shear force on the wall tthe
firs Noor level is V, = 1153 kips
- _ (2)(20)(26.17 x 12)/4000
2A {ff = DOC x eyo
1000
= 839 ips
< V, = 1153 kips
Therefore, mo curtains of reinforcement are re-
auired.
(@) Required longitudinal and transverse reinforce-
ment in wall: Minimum required reinforcement
ratio,
=p, > 0.0025
(max. spacing = 18 in.)336 SEISMIC DESIGN OF REINFORGED-CONCRETE STRUCTURES
With A, = 20(12) = 240 in? (per foot of
wall) the required area of reinforcement in each
direction per foot of wal is (0.0025)(240) = 0.60
in/ft, Required spacing of No. 5 bars [in two
curtains, 4, = 2(0.31) = 062 in?}
s(veqies) = 205) 1») -r24n