Transformer Protection

Copyright © Siemens AG 2007. All rights reserved.


Page 188 2007-08 Author: G. Ziegler PTD SE PTI
Transformer: Function principle and equivalent circuits

w1 w2
I1 I2
R1 Xσ1 Xσ 2' R2 '
Φ
U1 U2
Φ σ1 Φ σ2 U1 I1 Iµ Xµ I2' U 2'

Equivalent electromagnetic circuit Equivalent electric circuit

I ⋅ w + I ⋅ w = I µ ⋅ w1
1 1 2 2
RTK X TK
I1⋅ w1 = I 2 ⋅ w2
At load and short-circuit: I µ << I1, 2 ' X TK = X σ 1 + X σ 2 '
U1 I1 = I 2 ' U 2'
RTK = R1 + R2 '

Copyright © Siemens AG 2007. All rights reserved.


Page 189 2007-08 Author: G. Ziegler PTD SE PTI
Typical Transformer data

Rated power Ratio Short-circuit No-load magnetizing


voltage current
MVA kV/kV % UN % In
850 850/21 17 0.2
600 400/230 18.5 0.25
300 400/120 19 0.1
300 230/120 24 0.1
40 110/11 17 0.1
16 30/10.5 8.0 0.2
6.3 30/10.5 7.5 0.2
0.63 10/0.4 4.0 0.15

Copyright © Siemens AG 2007. All rights reserved.


Page 190 2007-08 Author: G. Ziegler PTD SE PTI
Transformer Inrush current

IRush
Flux
φ φ

φRem Inrush-current of a single


U phase transformer

Im t

Source: Sonnemann, et al.: Magnetizing Inrush phenomena in transformer banks, AIEE Trans., 77, P. III, 1958, pp. 884-892

Copyright © Siemens AG 2007. All rights reserved.


Page 191 2007-08 Author: G. Ziegler PTD SE PTI
Inrush currents of a Y-∆-transformer
Neutral of Y-winding earthed

ΦT
IR
ΦS
ΦR IS ID
I mT
IC
I mR
Oscillogram:
IR 5 1
I R = ⋅ I mR − ⋅ I mC IR
6 6
1 1
IS IS = − ⋅ ImR − ⋅ ImT
6 6 IS
5 1
IT IT = ⋅ ImT − ⋅ ImR IT
6 6
Source: Sonnemann et al. : Magnetizing Inrush phenomena in transformer banks, AIEE Trans., 77, P. III, 1958, pp. 884-892

Copyright © Siemens AG 2007. All rights reserved.


Page 192 2007-08 Author: G. Ziegler PTD SE PTI
Inrush current : Content of 2nd und 3rd harmonic

I m(ν )
%
I m(1)
100

80 B B
360O
60
I m ( 2)
40 I m(1)
I m(3)
20 I m(1) 17,5%

90O 180O 270O 360O Width of base B


240O

Copyright © Siemens AG 2007. All rights reserved.


Page 193 2007-08 Author: G. Ziegler PTD SE PTI
Inrush currents of a three-phase transformer
recorded with relay 7UT51

Copyright © Siemens AG 2007. All rights reserved.


Page 194 2007-08 Author: G. Ziegler PTD SE PTI
Transformer Inrush current:
Amplitude and time constant

Î Rush 12

Î N 10 Rated power time constant


in MVA in seconds
8
0,5....1,0 0,16....0,2
6 1,0 10 0,2 .....1,2
>10 1,2 ....720
4

5 10 50 100 500

Rated transformer power in MVA

Copyright © Siemens AG 2007. All rights reserved.


Page 195 2007-08 Author: G. Ziegler PTD SE PTI
Sympathetic Inrush

Wave form: Transient currents:

I1
I
I1 Current circulating
I2 between transformers

I2
IT
IT t
I1 RS XS
Transformer
IT being closed
G T1 IT
G I1
resistance I2 I2
Transformer
already closed
T1 T2
T2

Copyright © Siemens AG 2007. All rights reserved.


Page 196 2007-08 Author: G. Ziegler PTD SE PTI
Transformer overfluxing

Deduction of wave form Harmonic content


%
Im 100 I150/I50 I50/InTr
B 80
×104 Gauß U
1,5 60 I250/I50
40 I350/I50
1,0
20
0,5 0
100 120 140 % 160
U/Un
5 10 15 A 0 10 20 ms
Im t

Copyright © Siemens AG 2007. All rights reserved.


Page 197 2007-08 Author: G. Ziegler PTD SE PTI
Vector group adaptation with matching CTs
Current distribution with external ph-ph fault

IR Ir
I1 r
R
3 1
IS I2 Is s
S G
IT It
I3 t
T

3 /1
87T 87T 87T

Copyright © Siemens AG 2007. All rights reserved.


Page 198 2007-08 Author: G. Ziegler PTD SE PTI
Vector group adaptation with matching CTs
Current distribution with external ph-E fault

IR Yd1 I1 Ir r
R
IS Is s
I2
S G
IT It
I3 t
T

tm
It
= 3
IT=3 tg
3 /1
87T 87T 87T Ir rm
= 3 rg
Tm Tg R0 S0 T0 30O 30O
tm tg
sm
sg
Sm Rm Rg Sg rm rg
Copyright © Siemens AG 2007. All rights reserved.
Page 199 2007-08 Author: G. Ziegler PTD SE PTI
Traditional I0-elimination with matching CTs
Current distribution in case of an internal earth fault

L1
L1

L2
L2 G
L3
L3

! ∆Ι ∆Ι ∆Ι • Sensitivity only 2/3 IF!


•Non-selective fault
indication!

Copyright © Siemens AG 2007. All rights reserved.


Page 200 2007-08 Author: G. Ziegler PTD SE PTI
Traditional I0-correction with matching CTs
Current distribution with external ph-E fault

a
A

b
B G
c
C

3/1

87T 87T 87T

Copyright © Siemens AG 2007. All rights reserved.


Page 201 2007-08 Author: G. Ziegler PTD SE PTI
Traditional I0-correction with matching CTs
Current distribution with internal ph-E fault

a
A

b
B G
c
C

3/1

87T 87T 87T

Copyright © Siemens AG 2007. All rights reserved.


Page 202 2007-08 Author: G. Ziegler PTD SE PTI
Transformer differential protection, connection

L1 IA1 IB1

UA UB
L2 IA2 IB2

(110 kV) L3 IA3 IB3 (20 kV)

Digital protection
contains:
Adaptation to
7UT6 ∆I ∆I ∆I
• Ratio UA / UB
• Vector group

Software replica of matching transformers

Copyright © Siemens AG 2007. All rights reserved.


Page 203 2007-08 Author: G. Ziegler PTD SE PTI
Digital transformer protection
Adaptation of currents for comparison (1)

CT 1 W1 W2 CT 2
JR-prim Jr-prim

JS-prim Js-prim

JT-prim Jt-prim

N Ir N Jr-sec
JR-sec IR IR* Com- Ir** Vector Ir*
o I0- Is* I0- o
JS-sec IS parison Is** group Is Js-sec
r elim. IS* elim. r
JT-sec IT IT* ∆I It** adapt. It* It Jt-sec
m m

SN SN
I N −Transf − W1 = I N −Transf − W2 =
3 ⋅ U N-1 3 ⋅ U N -2

IR J R −sec J R −sec Ir J r − sec J r − sec


I I
IS = N − Prim − CT 1 ⋅ J S −sec = kCT −1 ⋅ J S −sec I s = N − Prim −CT 2 ⋅ J s −sec = k CT − 2 ⋅ J s − sec
I N − Transf - W1 I N −Transf -W2
IT JT −sec JT −sec It J t −sec J t −sec

Copyright © Siemens AG 2007. All rights reserved.


Page 204 2007-08 Author: G. Ziegler PTD SE PTI
Digital transformer protection
Adaptation of currents for comparison (2)

CT 1 W1 W2 CT 2
JR-prim Jr-prim

JS-prim Js-prim

JT-prim Jt-prim

N Ir N Jr-sec
JR-sec IR IR* Com_ Ir** Vector Ir*
o I0- I0- o
JS-sec IS parison Is** group Is* Is Js-sec
r elim. IS* elim. r
JT-sec IT IT* ∆I It** adapt. It* It Jt-sec
m m

1 1
I0 = ⋅ (I R + IS + IT ) Example Yd5: I0 = ⋅ (I r + Is + I t )
3 3
I R * = I R − I0 I∆−R IR * Ir ** I r ** −1 0 1 Ir * I r * = I r − I0
1
IS* = IS − I0 I∆−S = I S * + I s ** I s ** = 1 −1 0 ⋅ I s * Is * = Is − I0
3
IT * = IT − I0 I ∆ −T IT * I t * * It ** 0 1 − 1 It * I t * = I t − I0

Copyright © Siemens AG 2007. All rights reserved.


Page 205 2007-08 Author: G. Ziegler PTD SE PTI
Adaptation of currents for comparison
Relay input data

Input data:
•n times 30O vector group number
Winding 1 (reference) is normally:
(only for 2nd and 3rd winding,
1st winding is reference) •High voltage side
•UN (kV) Rated winding voltage
At windings with
•SN (MVA) rated winding power
tap changer:
•INW (A) Primary rated CT current U max ⋅ U min
UN = 2⋅
•Line or BB direction of CT neutral U max + U min
•Elimination / I0-treatment
Correction /
without
•Side XX Assignment input for REF
•INW S (A) Primary rated current of neutral CT
•Neutral CT Earth side connection to relay: Q7 or Q8?

Copyright © Siemens AG 2007. All rights reserved.


Page 206 2007-08 Author: G. Ziegler PTD SE PTI
Digital transformer protection
Current adaptation, Example (1)

SN = 100 MVA
UN1= 20 kV Yd5 UN2= 110 kV

3000/5 A W2 W1 600/1 A

7621 A 2.400 A

1A
5A
∆I

Copyright © Siemens AG 2007. All rights reserved.


Page 207 2007-08 Author: G. Ziegler PTD SE PTI
Digital transformer protection
Current adaptation, Example (2)

20-kV-side 110-kV-side
100MVA 100MVA
I N − Trafo − W2 = = 2887A I N − Trafo − W1 = = 525A
3 ⋅ 20kV 3 ⋅110kV

1 1
J r,s, t -sek = ⋅13200 3 = 4,4 3 A J R,S,T -sek = ⋅ 2400 = 4,0 A
3000 600
3000 600
I Norm = ⋅ 4,4 3 = 4,57 3 A I Norm = ⋅ 4 = 4,57A
2887 525

I0-elimination: Vector group adaptation: Yd5


I r ** − 1 0 1 4,57 3 − 4,57 / 3 Ir * 2 −1 −1 0 4,57 3
1 1
I s ** = 1 − 1 0 ⋅ − 4,57 3 = 2 ⋅ 4,57 / 3 Is * = ⋅ − 1 2 − 1 ⋅ − 4,57 = − 2 ⋅ 4,57 3
3 3
It * * 0 1 −1 0 − 4,57 / 3 It * −1 −1 2 0 4,57 3

I A − R = I R * +I r * * = 4,57 3 − 4,57 3 =0
I A − S = I S * + I s * * = − 2 ⋅ 4,57 3 + 2 ⋅ 4,57 3 = 0
I A −T = IT * +I t * * = 4,57 3 − 4,57 3 =0

Copyright © Siemens AG 2007. All rights reserved.


Page 208 2007-08 Author: G. Ziegler PTD SE PTI
7UT6
Operating characteristic
I1 I2
9
IDiff/ In

B
8 I DIFF >>

A
ST
I
F =
7UT6

IF
7

ID
IDIFF = |I1+ I2|
6
IStab = |I1| + |I2| Tripping area
5

4 2
pe Stable operation
o
3 Sl

1 Additional stabilisation
Slope
1
I DIFF > for high Is.c.
0
0 1 2 3 4 5 6 7 8 9 10 11 Istab / In

Copyright © Siemens AG 2007. All rights reserved.


Page 209 2007-08 Author: G. Ziegler PTD SE PTI
I0-elimination / correction: Summary

Î I0- elimination necessary at all windings with earthed


neutral or with grounding transformer in the protection range
Earth fault sensitivity reduced to 2/3 !
Incorrect fault type indication!
Î I0- correction provides full earth current sensitivity and
correct phase selective fault type indication, however requires
CT in the neutral-to-earth connection of the transformer.
Î As an alternative, earth differential protection can be used
to enhance earth fault sensitivity.

Copyright © Siemens AG 2007. All rights reserved.


Page 210 2007-08 Author: G. Ziegler PTD SE PTI
Transformer winding to earth fault
Solid earthed neutral

IF
per unit
10

UR 8
IF
h⋅UR 6
Infeed side
4

IF IK
2
IK
0 20 40 60 80 100
Short-circuited winding part h in %

Source: P.M. Anderson: Power System Protection, McGraw-Hill and IEEE Press (Book)

Copyright © Siemens AG 2007. All rights reserved.


Page 211 2007-08 Author: G. Ziegler PTD SE PTI
Transformer winding to earth fault
Resistance or reactance earthed neutral

UR
%
100
h⋅UR
I
Infeed side I Max IF
50 IK
IF
IK RE

0
20 40 60 80 100
h ⋅U R Short-circuited winding part h in %
IF =
RE
h ⋅ w2 2 1 U 2n U R
IK = ⋅ IF = h ⋅
U 2n
⋅ IF IK = h ⋅ ⋅ ⋅
w1 U1n ⋅ 3 3 U1n RE

Source: P.M. Anderson: Power System Protection, McGraw-Hill and IEEE Press (Book)

Copyright © Siemens AG 2007. All rights reserved.


Page 212 2007-08 Author: G. Ziegler PTD SE PTI
Transformer winding to earth fault
Earth fault in the delta winding

IK R
IK
0%
5 20%
Grid x In
4

3 33,3%

50%
2

1 100%

20 40 60 80 100
Location of the earth fault h in %

Copyright © Siemens AG 2007. All rights reserved.


Page 213 2007-08 Author: G. Ziegler PTD SE PTI
Transformer winding short-circuit

100 10
IF , IK
IK IP
x In 80 8 x In

60 6
IF
40 4

IK
20 2
IF
0
5 10 15 20 25
Short-circuited winding part h in %
Source: Protective Relays, Application Guide, GEC Alstom T&D, 1995

Copyright © Siemens AG 2007. All rights reserved.


Page 214 2007-08 Author: G. Ziegler PTD SE PTI
Restricted earth fault protection of relay 7UT6

I0* = IN
I0** = I R + I S + IT = 3I0 IR
IS
I restr = I − I − I + I
*
0
**
0
*
0
**
0 IT
Basic operating area:
IOp = I0* IN I>

( )
for − 900 ≤ ϕ I 0* / I 0** ≤ +900
if IOp ≥ Iset ∆ IE
I0* I0**
Extended operating area:
IOp = I 0* − k0 ·I restr
( )
for + 900 ≤ ϕ I 0* / I 0** ≤ +2700
if IOP ≥ Irestr
Copyright © Siemens AG 2007. All rights reserved.
Page 215 2007-08 Author: G. Ziegler PTD SE PTI
Restricted earth fault protection of 7UT6
Operating characteristic (2)

k0 =2
K0 ϕ Limit I*0
ϕ Limit=110O
1.0 130 I 0-set
1.4 120
4
2.0 110 I*0* ΣI Ph
3 = =1
4.0 100
I*0 IN
∞ 90 2

1
External fault Internal fault

180O 130O 120O 110O 100O 90O 80O 70O 60O 50O 0O

(
ϕ I*0*/I*0 )

Copyright © Siemens AG 2007. All rights reserved.


Page 216 2007-08 Author: G. Ziegler PTD SE PTI
Restricted earth fault protection of 7UT6
Polar characteristic

K0= 4
K0= 2 100 80
2
120 60
1.6 I0 * ϕ (I 0 */I 0 **)
140 40
⋅e
K0= 1.4 I0 * *
1.2

160 0.8 20
K0= 1
Blocking 0.4
ϕ Tripping
180 0 +1 0

200 340

220 320

240 300
260 280

Copyright © Siemens AG 2007. All rights reserved.


Page 217 2007-08 Author: G. Ziegler PTD SE PTI
Restricted earth fault protection 87N (7UT6)
Application aspects

„ Increased sensitivity with earth faults near winding neutral


Preferably used in case of resistance or reactance neutral earthing
„ Sensitive to turns short-circuit
„ I0 / IN amplitude and angle comparison
„ 2nd harmonic stabilised
„ Can protect a separate shunt reactor or neutral earthing transformer
in addition to the two winding transformer differential protection
„ Not applicable with autotransformers! (as only one stabilising input at
transformer terminal side, -- high impedance principle to be used in this case.

Copyright © Siemens AG 2007. All rights reserved.


Page 218 2007-08 Author: G. Ziegler PTD SE PTI
Transformer HI-earth fault protection

IR
Ir
IS Is
IT It

ZE

∆IE>
IN ∆IE>

Copyright © Siemens AG 2007. All rights reserved.


Page 219 2007-08 Author: G. Ziegler PTD SE PTI
HI differential protection of an autotransformer

Ir
IR
Is
IS
It
IT

87 87 87

Copyright © Siemens AG 2007. All rights reserved.


Page 220 2007-08 Author: G. Ziegler PTD SE PTI
HI earth fault protection of an autotransformer

Ir
IR
Is
IS
It
IT

IN
∆I>

Copyright © Siemens AG 2007. All rights reserved.


Page 221 2007-08 Author: G. Ziegler PTD SE PTI
Transformer tank protection 64T: Principle

IE>

Insulated

Copyright © Siemens AG 2007. All rights reserved.


Page 222 2007-08 Author: G. Ziegler PTD SE PTI
Transformer protection, Relay design

Transformer Protection
with
Siemens SIPROTEC
7UT6

7UT612

Copyright © Siemens AG 2007. All rights reserved.


Page 223 2007-08 Author: G. Ziegler PTD SE PTI
Digital transformer protection relay 7UT613:
Current inputs and integrated protective functions

YN yn0 d5
R
S
T

ϑ> ϑ> I>>,


∆IT
∆ITE
(2) (1) I>t

Copyright © Siemens AG 2007. All rights reserved.


Page 224 2007-08 Author: G. Ziegler PTD SE PTI
Relay 7UT6: Application examples

∆I

∆I ∆I ∆I

Shunt Reactor Two winding Three winding Transformer bank


transformer transformer (1-1/2-LS)

G ∆I ∆I ∆I

Generator / Motor Busbars

Copyright © Siemens AG 2007. All rights reserved.


Page 225 2007-08 Author: G. Ziegler PTD SE PTI
7UT6
Operating characteristic

I1 I2
9
IDiff/ In
8

B
I DIFF >> (1604)

A
ST
I
F =
7UT61

IF
7

ID
6 IDIFF = |I1+ I2|
IStab = |I1| + |I2|
5 )
8
Tripping area 1 60
4 =
pe Restraining area
sl o
3 0 7,
2 1 6
ope t=
2 sl o in of 1606
p slope = 1/2 line) = (1618 )
1 ot pick-up limit
(left b ord er
1 slope (f o
)
I DIFF > (1606 Add-on restraint for high ISC
(1603) 0
0 1 2 3 4 5 6 7 8 9 10 11 Istab / In
Copyright © Siemens AG 2007. All rights reserved.
Page 226 2007-08 Author: G. Ziegler PTD SE PTI
Advantages of digital transformer differential protection

‹ High stability against c.t. saturation provided by integrated saturation detector


and add-on stabilisation
‹ High stabile against inrush currents due to advanced filter technology
(Fourier analysis) and optional cross-blocking function
‹ High stability against over-excitation ( 5th harmonic blocking)
‹ Short tripping time - typically 1.5 cycles
‹ High set ∆I fast tripping < 1 cycle
‹ Sensitive earth differential protection against interturn faults and earth faults
near winding neutral
‹ Integral ratio and vector group adaptation (no external auxiliary CTs required)
‹ Integral thermal overload protection
‹ External start of fault recording (e.g. by gas pressure relays)

Copyright © Siemens AG 2007. All rights reserved.


Page 227 2007-08 Author: G. Ziegler PTD SE PTI
7UT6
Integrated protection functions

87T Transformer differential protection


‰ ∆I>
‰ Rush-stabilised (2nd harmonic)

49-1 ‰ Stabilised against overfluxing (5th harmonic)


49-2 ‰ ∆I>> high set element, non-stabilised

Thermal overload protection


50/51
50HS Time overcurrent protection (IT or DT)
Earth current differential protection (7UT613)
87N
Tank protection (7UT613)

64T

Copyright © Siemens AG 2007. All rights reserved.


Page 228 2007-08 Author: G. Ziegler PTD SE PTI
Application examples

Copyright © Siemens AG 2007. All rights reserved.


Page 229 2007-08 Author: G. Ziegler PTD SE PTI
Protection of a two winding transformer

7SJ600
7UT512
50 51

W1 49
52

Bu 87T
W1 (OS)

W2 (US)
W2 51

52 52 52

Copyright © Siemens AG 2007. All rights reserved.


Page 230 2007-08 Author: G. Ziegler PTD SE PTI
Protection of a three winding transformer

7SJ600

50 51 7UT513

52 W1 49-1
Bu
W1 87T

W2 W3 W2 49-2

W3 51
52

Load

Copyright © Siemens AG 2007. All rights reserved.


Page 231 2007-08 Author: G. Ziegler PTD SE PTI
Restricted earth fault protection
for a two winding transformer

7SJ600
7UT513
50 51

52 W1 49-1

W1 (OS) Bu
87T
W2 (US)
ZE

51
W2
87TE

52 52 52

Copyright © Siemens AG 2007. All rights reserved.


Page 232 2007-08 Author: G. Ziegler PTD SE PTI
Protection of an autotransformer

7SJ600 52

50
51N 51BF
51

7UT513 87
TH 7VH600
87
TL 49

Load 52 3Y
52
Bu 50
51 51
59 50 50
BF BF 7SJ600
7RW600
7SJ600
51
N

Copyright © Siemens AG 2007. All rights reserved.


Page 233 2007-08 Author: G. Ziegler PTD SE PTI
Protection of a large transformer bank

52 52

7SA6

50
21 49
BF

87 7VH6 (3)
7UT513
TH
87
TL 49
3
Load 52
52
51
7SA6
59N 50
51
BF 51N 21 49
7RW6 BF
7SJ6 7SJ6

Copyright © Siemens AG 2007. All rights reserved.


Page 234 2007-08 Author: G. Ziegler PTD SE PTI
Differential protection of generation units

52 52 52 52

∆IT ∆IT ∆IT


∆IT

G 52
G ∆IG

G ∆IG

G ∆IG

Copyright © Siemens AG 2007. All rights reserved.


Page 235 2007-08 Author: G. Ziegler PTD SE PTI
Differential protection of generation units (2)

52

∆IT

52
*)

∆IT
G ∆IG
*) same ratio as generator CTs

52 Auxiliaries

Copyright © Siemens AG 2007. All rights reserved.


Page 236 2007-08 Author: G. Ziegler PTD SE PTI
Thermal protection of transformers

Legend:
ΘCu Rth1 ΘOil Rth2 PCu: Winding losses (I2·R)
PFe: Core and tank losses
Rth1: Thermal resistance Copper-Oil
C1 C2
Rth2: Thermal resistance Oil-Air (cooling medium)
PCu PFe C1: Winding thermal capacity
C2: Thermal capacity of Oil, Core and tank
ΘAmb
ΘCu: Winding copper temperature
ΘOil: Oil temperature
Lifetime of insulation depends on the
ΘAmb.: Ambient temperature
winding Hot-spot temperature.
6 OC higher temperature increases the
aging of the insulation by the factor 2!

Copyright © Siemens AG 2007. All rights reserved.


Page 237 2007-08 Author: G. Ziegler PTD SE PTI
7SA6: Temperature monitoring

RS485 Interface

Oil -
Temp.

Two thermo-devices can be connected to the serial service interface


Monitoring of up to 12 measuring points (6 per thermo-device)
One input is reserved for hot spot monitoring (measurement of oil temperature)
Thermistors: Pt100, Ni100 or Ni120

The the upper oil temperature is directly measured by the use of thermoelement.
The hot spot temperature is calculated by the relay using the thermal model Cu-Oil:
2 I = actual transformer current
dΘ Cu 1 ⎛I⎞ 1
= ⋅⎜ ⎟ − ⋅ (Θ Cu − Θ Oil ) Ir = rated transformer current
dt τ Th ⎝ Ir ⎠ τ Th τth =time constant of the winding

Copyright © Siemens AG 2007. All rights reserved.


Page 238 2007-08 Author: G. Ziegler PTD SE PTI
7UT6: Temperature monitoring with hot spot calculation (1)
Example: Natural cooling

Θh= hot spot temperature


Θ h = Θ O + H gr ⋅ k Y
Θh= oil temperature
Hgr=hot-spot-to-oil temperature gradient
k= load factor I/In
Y= winding exponent
Oil -
Temp.
Aging rate:
98O is reference for
Aging at Θ h
HV
V= = 2(Θ h −98)/6 the aging of
LV
Aging at 98°C Cellulose insulation

Mean value of aging during a fixed time interval:


T
1 2

L= ⋅ ∫ V ⋅ dt
T2 − T1 T1

Copyright © Siemens AG 2007. All rights reserved.


Page 239 2007-08 Author: G. Ziegler PTD SE PTI
7UT6: Temperature monitoring with hot spot calculation (2)
Example: Natural cooling

Θ h = Θ o + H gr ⋅ k Y ≈ 73 + 23 ⋅1.151.6 = 102°C
(L)
V = 2(Θ h −98)/6 = 2(102−98)/6 ≈ 1.6
108°C [°C]
k, 98°C
V,
102°C Θh
L
Θo
73°C
Θh Hot spot
temp.
1.6

Θo oil temp.
V (relative 1.15
(from thermo- aging)
device) L (mean
k (I/In)
value of V)

Copyright © Siemens AG 2007. All rights reserved.


Page 240 2007-08 Author: G. Ziegler PTD SE PTI