Owners´s Engineer
Consortium
Originator
SIEMENS AG
Contract No.:
Projekt/Project PKZ/PC
Abtlg. Zähl-Nr
Dept. Reg. No. 116022
Dienstst./Dept. UNID Index/Rev. Version
Siemens AG
Energy Sector EN ETEC EE 443653306 00
Ang.-Var./Offer-Var. Var./Opt Blatt-Nr./Page-No.
AE1172-&EFQ010-71CHA-116022 1 / 68
Georg om
Date: 2014.08.14 10:57:04 +02'00' Edmund email=edmund.eisenburger@siemen
s.com
Date: 2014.08.14 11:18:05 +02'00'
Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents
Siemens and communication thereof to others without express authorization are prohibited. Offenders will be held
liable for payment of damages. All rights created by patent grant or registration of a utility model or design
patent are reserved.
Parameter Settings
AE1172 Shuweihat S3 IPP
+71CHA01/02
Table of Contents
1 INTRODUCTION 5
2 TECHNICAL DATA 6
2.1 Generator (71MKA) 6
2.1.1 Generator Data 6
2.1.2 Current Transformer 6
2.1.3 External Voltage Transformer 6
4.2 Parameter Settings Unit Auxiliary Transformer 71BBT01 Protection 7UT 633 -F13 30
4.2.1 Device Configuration Parameters - address block 01 30
4.2.2 Protected Object Parameters - address block 02 to 08 30
4.2.3 Fault recording- address block 09 31
4.2.4 Power System System Data 2 – address block 1100 32
4.2.5 Differential Protection Parameters (ANSI 81) – address block 12 32
4.2.6 Restricted Earth fault Protection (ANSI 81N) - address block 13 33
4.2.7 Settings for Measured Value Supervision (address block 81) 33
4.2.8 Broken-wire monitoring (address block 84) 33
7.1.6 Settings for Over-current Phase Protection (ANSI 50/51) 71BAT01 – address block 20 55
7.1.7 Settings for Over-current Earth Protection (ANSI 50/51N) for 71BAT01 - address block 24 56
7.1.8 Settings for Over-current Phase 3 Protection (ANSI 50/51) 71BBT01 – address block 32 57
7.1.9 Settings for Over-current Earth 2 Protection (ANSI 50/51N) for 71BBT01 address block 38 57
7.1.10 Settings for the Over-excitation Protection (ANSI 24) – address block 43 58
7.1.11 Measurement Supervision (address block 81) 58
7.1.12 Settings for Broken-wire monitoring (address block 84) 59
7.1.13 Settings for flexible functions (Flexible Function 01) (address block 255) 59
10 ANEXES 66
10.1 Annex 1 – BAT overexcitation curve 66
1 Introduction
This report gives the functional settings of the protection relays necessary for the operation of the
protection system and for selective clearance of faults.
This report includes the protective functions for the following components:
Generator
Generator leads
Generator neutral point
Unit auxiliary transformers
Excitation transformer
Generator transformer
HV Cable (Differential protection)
For complete settings of the digital protection devices refer to the DIGSI printout of each relay.
2 Technical Data
2.1 Generator (71MKA)
2.1.1 Generator Data
Type SGen5-1000A
Rated voltage UN 20 kV +/- 5 %
Rated apparent power SN 295 MVA
Power factor p.f. 0,85
Rated active power PN 251 MW
Rated current IN 8515,92 A
Max. permissible current ImaxGen 10.666 A
Rated frequency fN 50 Hz
Permissive overexcitation capability time t (U/f)max see curve about
permissive over-
excitation
Synchronous reactance (sat.) Xd 171,60 %
(for cylindrical rotor machine: xd = xq)
Transient synchronous reactance (sat.) xd’ 20,94 %
Minimum excitation voltage Uexc-min 91,8 V
Maximum continuously permissible
negative sequence current I2 I2max / IN 8%
Thermal capability time (I2) C=(I2/IN)² t 10 s
3.1.2.1 Settings for Over-current Phase Protection (ANSI 51) – address block 12
This function is used as backup stage for the 420kV Network Protection.
The current input is connected to the generator bus duct. The same values are
In advance the stage is carried out as definite time stage wit the following setting values:
Basis for the calculation are the Transco guidelines, where a primary setting current of 900A (HV-
Side of the BAT Transformer) transformed to the LV-Side, at a definite trip time of 1,2 s are agreed.
Please refer to section 3.4 of
“Protection Coordination Report HV-Connection to Power Plant” / pc 200 038/ab
AE1172-&EFQ30-ACA-116022, UNID 443654297 (TRANSCO Drw no. NS3PS RS 0010 G 0010)
Whereby:
Imax Gen Permissible maximum generator current 10666 A
UNTrafo sec Rated voltage of generator transformer (secondary) 20 kV
UNTrafor pri Rated voltage of generator transformer (primary) 420 kV
TRI transformer ratio of current transformers 12000
The maximum continuously permissible negative sequence current is decisive for the thermal
replica. For larger machines and in cases of doubt, the data supplied by the manufacturer should
prevail. Settings to be based on the unbalanced load time curve of the manufacturer.
The factor K is 10s at the point I2/IN = 1 and valid for the primary side. Conversion to the secondary
side by means of the following formula:
2
INmach 8516
2
The parameter 1705 Time for cooling down is defined as the time required by the thermal image to
cool down linear from 100% to 0% or to say with other words: the start gradient of the cooling down
curve. The formula below shows the relation between the K asymmetry factor and the cool down
time:
K prim 8s
t Cool down = 1250s
(I2perm /IN ) 2
0,082
where: I2perm=I2max mach = 8% of IN. This value tcool down = 1250 s is set in address 1705
The definite time negative sequence current characteristic I2>> is set to:
I 8516
I 2 60% NMach 60% 42,58% 43%
I 12000
NCTprim
3.1.4 Settings for the Generator Differential Protection (ANSI 87G) – address block 20
The stabilised differential current I> should be set about 20 per cent of the nominal machine current.
The un-stabilised high-current stage in address 2031 should be set higher than (1/ x`d= 4,7) of the
generator. Here it is set to 5.
For stator circuit criterion the reciprocal of the impedance (equal the admittance) is calculated from
the positive sequence systems of currents and voltages. In the admittance plane the stability limit of
machine is independent of the voltage. The shape of the under excitation trip characteristic is like
the under excitation limiting curve of the generator capability curve.
The excitation voltage supervision is set to approximately 50% of the no-load excitation voltage:
Uexc0 V
EXCIT. VOLT. V 0,30
91,8
0,3 1,37 V
kU 20
Calculation:
Uexc< 1,37 V
The rated machine data must refer to secondary values to enable setting. Furthermore it must be
noted, that rated current and rated voltage of the machine in general are not equal to the rated data
of the instrument transformers. Matching is performed according to the following formula:
1 1 U NP I Nmach
xd sec xdmach I NP U Nmach
whereby
xdsec secondary per unit synchronous reactance
xdmach per unit synchronous reactance of machine
UNP primary rated voltage (CT and unit)
INP primary rated current (CT and unit)
INMach rated machine current
UNmach rated machine voltage
1 Q M var U NP
1/ xd sec C
U n kV 3 I NP
2
whereby:
Q reactive power
UN rated current of generator
UNP primary rated voltage (CT and unit)
INP primary rated current (CT and unit)
C security factor (1.03 to1.1)
Note: The protection is to be set such that the Under-excitation limiter can act before the protection
picks up. To enable this, the limiter characteristic must be known.
In this case the protection is set 5% above the static under-excitation limit curve as shown in the
reactive capability diagram of the generator supplied by the manufacture.
Measured values from the generator capability diagram excluding the safety factor C
Q1 ˜ 155 Mvar α1 = 78 ° UN = 20 kV
Q2 ˜ 135 Mvar α2 = 88 ° UNP = 20000
Q3 ˜ 415 Mvar (estimated) α3 = 110 ° INP = 12000
C = 1,05
Calculation:
1 Q1 M var U NP
λ1 = 1 / xd sec1 C = 0,39(address 3002)
U n kV 3 I NP
2
1 Q2 M var U NP
λ2 = 1 / xd sec 2 C = 0,34(address 3005)
U n kV 3 I NP
2
λ3 = 1/xdsec 3 > 2 · 1/xdsec 2 = 0,68 -> selected setting value: 1,05 (address 3008)
The determination of the setting values is done according method b (reactive capability curve)
Characteristic 3 serves to adapt the protection to the dynamic machine stability limits. If there are no
precise indications, the user must select a value 1/xdsec3 situated approximately between the
synchronous reactance and the transient reactance.
However, it should be greater than 90° to 110° is usually chosen for α3 in order to ensure that only a
dynamic instability leads to pickup with characteristic 3.
5 sec. after over passing characteristic 1+2 an alarm will be given to the operator.
Psec P U I Pmach
PPick up mach Nmach Nmach
S N sec S Nmach U Npri I Npri 3 U Npri I Npri
The maximum load current during operation is the most important criterion to be considered when
determining the over current pickup. A pickup by an overload must be excluded in any cases! For
this reason the address 3302 I> Pickup must be set above the maximum (over)load current to be
expected. Recommended setting: 1,2 to 1,5 times the nominal machine current ( secondary)
Setting primary: 130 % x In 11071 A
Setting secondary: Setting primary / ratio of CT 0,92 A
The settings have to be made in accordance with the time grading plan of the network.
kR uK U 2 N 70 20 20 2
Z1prim = 189 mΩ
100 100 SN 100 100 296
The values determined such must be converted for the secondary side of current and voltage
transformers.
12000
Z1sec = TRI Zprim 0,151 11,34
TRU 200
(Similarly-here not used-, zone reach of the overreach stage Z1b and the second stage Z2 can be
determined from e.g. 110% transformer reactance.)
The resistance setting R allows a margin for fault resistance, which appears as in-phase resistance,
in addition to the fault impedance, at the point of fault. It compromises, for example, arc resistances
in case of arcing faults.
Normally a resistance setting equal to the reactance setting is adequate (R/X=1) to form sufficient
arc resistance allowance.
The power swing block is mostly used for impedance stage1 because the delay time T1 for this
stage is set low. (address 3316A)
A compromise has to be found for the distance between power swing polygon and the trip polygon
( P/SPOL-TPOL address 3314 ) and for the rate of changing of the impedance vector ( dZ/dt
address 3315 )
Zlmin - Z1
dZ/dt = 300 Ω/s A safety factor of approx. 4 has to be
t taken into account.
The default setting for dZ/dt is 300 Ω/s, which is adequate for most applications. This is also the
basis for the minimum distance P/PSOL-TPOL assuming, that the detection for a power swing there
must be one impedance value between P/PSOL-TPOL.
Setting condition: P/PSOL-TPOL > dZ/dt x ∆t = 300 Ω/s 0,02 s = 6Ω (selected setting value: 8Ω)
The measured impedances during power swing condition are decisive for the settings.
Xd’ can be calculated from the per unit reactance xd’ as follows:
UN gen Nct 20000 20,94 12000
Xd' xd' 17 Ω
3 IN gen Nvt 3 8516 100 200
Where:
Zb Xd’ = 17 Ω
The secondary reactance of the unit transformer is derived from the primary reactance by
considering the instrument transformer ratios:
uK UN 2 Nct 20 202 12000
XKsec 16,02Ω
100 SN Nvt 100 296 200
uk Percent impedance voltage of the generator transformer 20 %
Sn Rated power of the generator transformer 296 MVA
UN gen Rated voltage of the generator transformer 20 kV
Nct Current transformer transformation ratio 12000
Nvt Voltage transformer transformation ratio 200
Xksec Secondary reactance of the generator transformer 16,02 Ω
The reactance of the grid is similar to the grid impedance and can be calculated from the apparent
three phase short circuit power of the grid. The following formula for the secondary grid reactance
relates the grid impedance to the nominal generator voltage:
1 Nct 1 12000
XNsec 2
XN 2
6,35 0,95
TR T rafo Nvt 20 200
Where:
XNsec Grid reactance related to the nominal generator voltage 0,95 Ω
XN Grid reactance (400kV /63kA) 6,35 Ω
TRTrafo Transformer Ratio (Un_Grid / UN gen = 400/20) 20
Nct Current transformer transformation ratio 12000
Nvt Voltage transformer transformation ratio 200
Assuming that characteristic 1 should cover 90 % of the transformer reactance, the setting of
address 3506 Zc results in:
Zc ≈ 90%. Xksec = 14,42 Ω
The width Za of the polygon is determined by the total impedance Ztot.. Assuming the power swing
angle δ =120 °between generator and transformer, Ztot is the sum of Zb and Zd.
The holding time (Addr. 3511) determines how long time a detected out-of-step condition (passing
through) is maintained so that the counter is incremented with the next passing through. This time
should be set higher than the longest expected slip period (i.e. the smallest slip frequency).
Conventional values lie between 20s and 30s.
The time settings are preliminary and should be adapted due to the voltage regulator characteristic
during commissioning.
Four high-accuracy frequency stages are available. Each stage can be set as over-frequency stage
or under-frequency stage. This is determined by the rated frequency as configured under address
270 and the set limit value. When the limit value is set smaller than the rated frequency, the stage
operates as under-frequency stage. When the limit value is set equal to the rated frequency, the
concerned stage is ineffective.
The frequency protection function is acting as back up protection to the turbine speed
monitoring protection. As a matter of principle, the setting values for frequency and delay
times depend on the values supplied by the turbine manufacturer.
3.1.12 Settings for the Over-excitation Protection (ANSI 24) – address block 43
The overexcitation protection serves to measure the voltage/frequency ratio which is proportional to
the induction B and puts it in relation to the BN nominal induction
The factor U/ f is given as quotient from voltage and frequency. Both values are related to nominal
values.
The over excitation function of the 7UM622 devices –F11 and –F21 will be used to protect the
generator itself against over excitation. Therefore the settings are based on the generator over
excitation curve provided by the manufacturer. For the protection of BAT and BBT transformer the
over excitation function in the device –F26 7UT633 will be used.
Time for cooling down (stator) from 100% to 0% for thermal image tcool down = 3600 s (address 4314).
Means after a cooling down time of 60 minutes the trip is reset.
The function requires the following settings to be made in Power System Data 1:
Address 223: UE connection should be set to “loading Resistor” for this application to pick up
the 20 Hz voltage at the UE input.
Address 275: Factor R SEF; calculation see below
Transformation factor for primary earth resistance:
The transformation factor REprim/REsek is the overall transformation ratio and is to be calculated as
2
T R 2 E Tr TRVD 18000 1650 5
FACTOR R S/E/F = 87,89
1 TRICT 480 660 200
where:
TRETr Ratio of earthing transformer 18000 / 480
TRVD Ratio of Voltage Divider 1650 / 660
TRICT Ratio of small Intermediate Current Transformer 200 / 5
0,10 480V 1 48 5
S/E/F I = 1,33 A
R TRICT 0,9 200
where:
S/E/F I>> Pick up value of the earth current stage Addr. 5306
R loading resistor at the earthing transformer 0,90
TRICT transformation ratio of the intermediate current transformer 200 / 5
3.1.14 Settings for Breaker Failure Protection (ANSI 50BF) – address block 70
For the use as a circuit-breaker failure protection, the protection must detect smaller fault currents
which have not been cleared by the circuit breaker.
The trip time delay is determined from the maximum tripping time of the circuit breaker, the reset
time of the current detectors plus a safety margin.
The inadvertent energizing protection serves to limit damage by accidental connection of the
stationary or already started, but not yet synchronized generator, by fast actuation of the mains
breaker. A connection to a stationary machine is equivalent to connection to a low-ohmic resistor.
Due to the nominal voltage impressed by the power system, the generator starts up with a high slip
as an asynchronous machine. In this context, impermissibly high currents are induced inside the
rotor which may finally destroy it.
3.1.16 Settings for DC Voltage / Current Protection (ANSI 59N, DC/ 51N, DC) – address
block 72
The protection is used to detect earth faults inside the static frequency converters during start-up
phase of gas turbines.
The monitoring function is able to detect 1- phase, 2- phase, or 3- phase failures in the VT
measuring voltage caused for example by blown fuses in case these are used instead of MCB’s. For
further Information please refer to product manual 7UM 62, chapter 2.38.
The function enables a continuously checking of the measuring input values For further Information
please refer to product manual 7UM 62 chapter 2.38.2
The function is used for supervision of the tripping circuit of the generator circuit breaker channel
Address 0182 has to be set with 2 Binary Inputs. The supervision time for this function is set on
2 sec.
For further Information please refer to product manual 7UM 62 chapter 2.43.
Only the parameters, which are relevant for the provided application as 3-leg unit transformer
differential protection have been listed.
The general protection data (P. System Data 2) include settings associated with all functions rather
than a specific protection, monitoring or control function. Please ensure that the definition of signs
conforms to the direction of the reverse power protection and the forward power monitoring when
using this functions.
During first energization of the transformer from the HV side too low 2nd harmonic content
may appear due to low remanence of the transformer.
Therefore before first backenergization the following temporary settings should be applied
in order to minimize the possibility for a spurious trip:
After successful first backenergization the original settings for addresses 1271 and 1272A should be
applied.
4.1.6 Settings for restricted Earth Fault Protection (ANSI 87N) – address block 13
The restricted earth fault protection detects earth faults in power transformers the star point of which
is led to earth.
4.1.7 Settings for Over-current Phase Protection (ANSI 50/51) – address block 20
This function is used as backup stage for the Impedance Protection function activated at the Devices
–F11 and –F21 (7UM622). For the measuring has been attached to the Unit Transformer High
Voltage side it is ensured that electric faults inside the generator area can not cause a transformer
trip if the generator circuit breaker has already been opened. The stage is usually carried out as
Definite Time stage.
Connected to the Current Transformer at the HV-Side of the BAT-Transformer.
Whereby:
Imax Gen Rated maximum generator current 10666 A
UNTrafo sec Rated voltage of generator transformer (secondary) 20 kV
UNTrafor pri Rated voltage of generator transformer (primary) 420 kV
TRI transformer ratio of current transformers 600
Basis for the calculation are the Transco guidelines, where a primary setting current of 900A (HV-
Side of the BAT Transformer) at a definite trip time of 1,2 s are agreed. Please refer to section 3.4
of “Protection Coordination Report HV-Connection to Power Plant” / pc 200 038/ab
AE1172-&EFQ30-ACA-116022, UNID 443654297 (TRANSCO Drw no. NS3PS RS 0010 G 0010)
The function enables a continuously checking of the measuring input values For further Information
please refer to product manual 7UT63 chapter 2.19.1
4.2 Parameter Settings Unit Auxiliary Transformer 71BBT01 Protection 7UT 633 -F13
4.2.1 Device Configuration Parameters - address block 01
Only the parameters, which are relevant for the provided application as 3-leg unit auxiliary
transformer differential protection have been listed.
The general protection data (P. System Data 2) include settings associated with all functions rather
than a specific protection, monitoring or control function. Please ensure that the definition of signs
conforms to the direction of the reverse power protection and the forward power monitoring when
using this functions.
During first energization of the transformer from the HV side too low 2nd harmonic content
may appear due to low remanence of the transformer.
Therefore before first backenergization the following temporary settings should be applied
in order to minimize the possibility for a spurious trip:
After successful first backenergization the original settings for addresses 1271 and 1272A should be
applied.
The restricted earth fault protection detects earth faults in power transformers the star point of which
is led to earth.
The function enables a continuously checking of the measuring input values For further Information
please refer to product manual 7UT63 chapter 2.19.1
The Relay –F18 is foreseen to serve as differential protection for the HV line. For the complete
settings refer to the software print-out attached to this document.
6.1.4 Settings for Over-current Phase Protection (ANSI 51) – address block 12
This function is used as backup stage for the 420kV Network Protection.
The current input is connected to the generator bus duct. The same values are
In advance the stage is carried out as definite time stage wit the following setting values:
Whereby:
Imax Gen Permissible maximum generator current 10666 A
UNTrafo sec Rated voltage of generator transformer (secondary) 20 kV
UNTrafor pri Rated voltage of generator transformer (primary) 420 kV
TRI transformer ratio of current transformers 600
The maximum continuously permissible negative sequence current is decisive for the thermal
replica. For larger machines and in cases of doubt, the data supplied by the manufacturer should
prevail. Settings to be based on the unbalanced load time curve of the manufacturer.
The factor K is 10s at the point I2/IN = 1 and valid for the primary side. Conversion to the secondary
side by means of the following formula:
2
I 8516
2
The parameter 1705 Time for cooling down is defined as the time required by the thermal image to
cool down linear from 100% to 0% or to say with other words: the start gradient of the cooling down
curve. The formula below shows the relation between the K asymmetry factor and the cool down
time:
K prim 8s
t Cool down = 1250s
(I2perm /IN ) 2
0,082
where: I2perm=I2max mach = 8% of IN. This value tcool down = 1250 s is set in address 1705
The definite time negative sequence current characteristic I2>> is set to:
I 8516
I 2 60% NMach 60% 42,58% 43%
I 12000
NCTprim
6.1.6 Settings for the Generator Differential Protection (ANSI 87G) – address block 20
The stabilised differential current I> should be set about 20 per cent of the nominal machine current.
The un-stabilised high-current stage in address 2031 should be set higher than (1/ x`d=4,7) of the
generator. Here it is set to 5
For stator circuit criterion the reciprocal of the impedance (equal the admittance) is calculated from
the positive sequence systems of currents and voltages. In the admittance plane the stability limit of
machine is independent of the voltage. The shape of the under excitation trip characteristic is like
the under excitation limiting curve of the generator capability curve.
The excitation voltage supervision is set to approximately 50% of the no-load excitation voltage.
Uexc0 V
EXCIT. VOLT. V 0,30
91,8
0,3 1,37 V
kU 20
The rated machine data must refer to secondary values to enable setting. Furthermore it must be
noted, that rated current and rated voltage of the machine in general are not equal to the rated data
of the instrument transformers. Matching is performed according to the following formula:
1 1 U NP I Nmach
xd sec xdmach I NP U Nmach
whereby
xdsec secondary per unit synchronous reactance
xdmach per unit synchronous reactance of machine
UNP primary rated voltage (CT and unit)
INP primary rated current (CT and unit)
INMach rated machine current
UNmach rated machine voltage
1 Q M var U NP
1 / xd sec C
U n kV 3 I NP
2
whereby:
Q reactive power
UN rated current of generator
UNP primary rated voltage (CT and unit)
INP primary rated current (CT and unit)
C security factor (1.03 to1.1)
Note: The protection is to be set such that the Under-excitation limiter can act before the protection
picks up. To enable this, the limiter characteristic must be known.
In this case the protection is set 5% above the static under-excitation limit curve as shown in the
reactive capability diagram of the generator supplied by the manufacturer.
Measured values from the generator capability diagram including the safety factor C
Q1 ˜ 155 Mvar α1 = 78 ° UN = 20 kV
Q2 ˜ 135 Mvar α2 = 88 ° UNP = 20000
Q3 ˜ 415 Mvar (estimated) α3 = 110 ° INP = 12000
C = 1,05
Calculation:
1 Q1 M var U NP
λ1 = 1 / xd sec1 C = 0,39 (address 3002)
U n kV 3 I NP
2
1 Q2 M var U NP
λ2 = 1 / xd sec 2 C = 0,34 (address 3005)
U n kV 3 I NP
2
λ3 = 1/xdsec 3 > 2 · 1/xdsec 2 = 0,68 -> selected setting value: 1,05 (address 3008)
The determination of the setting values is done according method b (reactive capability curve)
Characteristic 3 serves to adapt the protection to the dynamic machine stability limits. If there are no
precise indications, the user must select a value 1/xdsec3 situated approximately between the
synchronous reactance and the transient reactance.
However, it should be greater than 90° to 110° is usually chosen for α3 in order to ensure that only a
dynamic instability leads to pickup with characteristic 3.
5 sec. after over passing characteristic 1+2 an alarm will be given to the operator.
Psec P U I Pmach
mach Nmach Nmach
S N sec S Nmach U Npri I Npri 3 U Npri I Npri
The maximum load current during operation is the most important criterion to be considered when
determining the overcurrent pickup. A pickup by an overload must be excluded in any cases! For this
reason the address 3302 I> Pickup must be set above the maximum (over)load current to be
expected. Recommended setting: 1,2 to 1,5 times the nominal machine current ( secondary)
Setting primary: 130 % x In 11071 A
Setting secondary: Setting primary / ratio of CT 0,92 A
U< = 75 % UNsec)
3305 T-Seal-in (Duration of seal-in; must be longer than backup 10,00 s
time plus circuit breaker opening time)
3312 T-END: Final Time Delay oo s
The settings have to be made in accordance with the time grading plan of the network.
kR uK U 2 N 70 20 20 2
Z1prim = 189 mΩ
100 100 SN 100 100 296
where
The values determined such must be converted for the secondary side of current and voltage
transformers.
12000
Z1sec = TRI Zprim 0,151 11,34
TRU 200
(Similarly-here not used-, zone reach of the overreach stage Z1b and the second stage Z2 can be
determined from e.g. 110% transformer reactance.
The resistance setting R allows a margin for fault resistance, which appears as in-phase resistance,
in addition to the fault impedance, at the point of fault. It compromises, for example, arc resistances
in case of arcing faults.
Normally a resistance setting equal to the reactance setting is adequate (R/X=1) to form sufficient
arc resistance allowance.
For zone 1: R1sec = 11,34
For zone 2: R2sec = 17,82
The power swing block is mostly used for impedance stage1 because the delay time T1 for this
stage is set low. (address 3316A)
A compromise has to be found for the distance between power swing polygon and the trip polygon
(P/SPOL-TPOL address 3314) and for the rate of changing of the impedance vector (dZ/dt address
3315)
The default setting for dZ/dt is 300 Ω/s, which is adequate for most applications. This is also the
basis for the minimum distance P/PSOL-TPOL assuming, that the detection for a power swing there
must be one impedance value between P/PSOL-TPOL.
Setting condition: P/PSOL-TPOL > dZ/dt x ∆t = 300 Ω/s 0,02 s = 6Ω (selected setting value: 8Ω)
The measured impedances during power swing condition are decisive for the settings.
Xd’ can be calculated from the per unit reactance xd’ as follows:
Where:
Zb Xd’= 17 Ω
The secondary reactance of the unit transformer is derived from the primary reactance by
considering the instrument transformer ratios:
uK UN 2 Nct 20 20 2 12000
XKsec 16,02Ω
100 SN Nvt 100 296 200
The reactance of the grid is similar to the grid impedance and can be calculated from the apparent
three phase short circuit power of the grid. The following formula for the secondary grid reactance
relates the grid impedance to the nominal generator voltage:
1 Nct 1 12000
XNsec 2
XN 2
6,35 0,95
TR T rafo Nvt 20 200
Where:
XNsec Grid reactance related to the nominal generator voltage 0,95 Ω
XN Grid reactance (400kV /63kA) 6,35 Ω
TRTrafo Transformer Ratio (Un_Grid / UN gen = 400/20) 20
Nct Current transformer transformation ratio 12000
Nvt Voltage transformer transformation ratio 200
Assuming that characteristic 1 should cover 90 % of the transformer reactance, the setting of
address 3506 Zc results in:
Zc ≈ 90%. Xksec = 14,42
The width Za of the polygon is determined by the total impedance Ztot.. Assuming the power swing
angle δ =120 °between generator and transformer, Ztot is the sum of Zb and Zd.
The holding time (Addr. 3511) determines how long time a detected out-of-step condition (passing
through) is maintained so that the counter is incremented with the next passing through. This time
should be set higher than the longest expected slip period (i.e. the smallest slip frequency).
Conventional values lie between 20s and 30s.
The time settings are preliminary and should be adapted due to the voltage regulator characteristic
during commissioning.
Four high-accuracy frequency stages are available. Each stage can be set as over-frequency stage
or under-frequency stage. This is determined by the rated frequency as configured under address
270 and the set limit value. When the limit value is set smaller than the rated frequency, the stage
operates as under-frequency stage. When the limit value is set equal to the rated frequency, the
concerned stage is ineffective.
The frequency protection function is acting as back up protection to the turbine speed
monitoring protection. As a matter of principle, the setting values for frequency and delay
times depend on the values supplied by the turbine manufacturer.
The overexcitation protection serves to measure the voltage/frequency ratio which is proportional to
the induction B and puts it in relation to the BN nominal induction
The factor U/ f is given as quotient from voltage and frequency .Both values are related to nominal
values.
The over excitation function of the 7UM622 devices –F11 and –F21 will be used to protect the
generator itself against over excitation. Therefore the settings are based on the generator over
excitation curve provided by the manufacturer. For the protection of BAT and BBT transformer the
over excitation function in the device –F26 7UT633 will be used.
Time for cooling down (stator) from 100% to 0% for thermal image tcool down = 3600s (address 4134).
Means after a cooling down time of 60 minutes the trip is reset.
6.1.15 Settings for 90% Stator Earth Fault Protection U0> (ANSI 59N, 64G, 67G)
– address block 50
The function requires the following settings to be made in Power System Data 1:
Address 0223: UE connection should be set to “broken delta winding” for this application
to pickup the displacement voltage.
Address 0224: VT Ratio Prim/Sec. UE, calculation see below
For the conversion of the displacement voltage UE in primary quantities, the device requires the
primary/secondary transformation ratio of the transformer delivering the UE voltage. The following
formula applies:
U VT , prim 20 3
FACTOR UE 115,5
U E , sec 0,1
where
UVT, prim primary voltage 20 kV / √3
UE, sec secondary displacement voltage applied to the device 100 V
Factor UE should be entered under address 224 in the Power System Data 1.
The matching ratio between phase-to-phase measurement and broken delta measurement is √3.
This value should be entered under address 225 in the Power System Data 1.
The pickup value, address 5002, should be at least twice the value of the operational asymmetry. A
value of 5% to 10% the full displacement value is normal. Final determination of the setting value
occurs during commissioning with primary values.
6.1.16 Settings for R/E/F Protection with 1 to 3Hz Square Wave Voltage Injection (ANSI
64R 1to 3 Hz) address block 61
6.1.17 Settings for Breaker Failure Protection (ANSI 50BF) – address block 70
For the use as a circuit-breaker failure protection, the protection must detect smaller fault currents
which have not been cleared by the circuit breaker.
The trip time delay is determined from the maximum tripping time of the circuit breaker, the reset
time of the current detectors plus a safety margin.
The inadvertent energizing protection serves to limit damage by accidental connection of the
stationary or already started, but not yet synchronized generator, by fast actuation of the mains
breaker. A connection to a stationary machine is equivalent to connection to a low-ohmic resistor.
Due to the nominal voltage impressed by the power system, the generator starts up with a high slip
as an asynchronous machine. In this context, impermissibly high currents are induced inside the
rotor which may finally destroy it.
The monitoring function is able to detect 1- phase, 2- phase, or 3- phase failures in the VT
measuring voltage caused for example by blown fuses in case these are used instead of MCBs. For
further Information please refer to product manual 7UM 62, chapter 2.42.
The function enables a continuously checking of the measuring input values For further Information
please refer to product manual 7UM 62 chapter 2.42.2
The function is used for supervision of the tripping circuit of the generator circuit breaker channel
Address 0182 has to be set with 2 Binary Inputs. The supervision time for this function is set on
2 sec.
For further Information please refer to product manual 7UM 62 chapter 2.43.
Measurement location
0251 Auxiliary CT IX1 is used as 1 earth
0252 Auxiliary CT IX2 is used as Not connected
Measurement location
0253 Auxiliary CT IX3 is used as 3 earth
0255 Type of auxiliary CT IX3 1A/5A current input
VT-Assign
0261 VT set UL1, UL2, UL3 is assigned Measuring location 3
0262 VT U4 is assigned Measuring location 3
0263 VT U4 is used as Udelta transformer
Power System
0270 Rated frequency 50 Hz
0271 Phase seq. L1-L2-L3
0276 Temp.Unit Degree celsius
Transf.
0311 Rated Primary Voltage Side 1 420 KV
0312 Rated Apparent Power of Transf. Side 1 296 MVA
0313 Starpoint of Side 1 is Earthed
0314 Transf. Winding Connection Side 1 Y(Wye)
0321 Rated Primary Voltage Side 2 20 kV
0322 Rated Apparent Power of Transf. Side 2 296 MVA
0323 Starpoint of Side 2 Isolated
0324 Transf. Winding Connection Side 2 D (Delta)
0325 Vector Group Numeral of Side 2 11
0331 Rated Primary Voltage Side 3 (irrelevant) 20 kV
0332 Rated Apparent Power of Transf. Side 3 (irrelevant) 40 MVA
0333 Starpoint of Side 3 is (irrelevant) Isolated
0334 Transf. Winding Connection Side 3 (irrelevant) D (Delta)
0335 Vector Group Numeral of Side 3 (irrelevant) 11
Funct.
0420 DMT / IDMT Phase assigned to Measuring location 1
0432 DMT / IDMT Phase 3 assigned to Measuring location 3
0424 DMT / IDMT Earth assigned to Auxiliary CT IX1
0438 DMT / IDMT Earth 2 assigned to Auxiliary CT IX3
CT’s
0511 CT-Strpnt. Meas. Loc.1 in Dir. of Object Yes
0512 CT Rated Primary Current Meas. Loc. 1 600 A
0513 CT Rated Secondary Current Meas. Loc. 1 1 A
0521 CT-Strpnt. Meas. Loc.2 in Dir. of Object Yes
0522 CT Rated Primary Current Meas. Loc. 2 12000 A
0523 CT Rated Secondary Current Meas. Loc. 2 1 A
0531 CT-Strpnt. Meas. Loc.3 in Dir. of Object No
0532 CT Rated Primary Current Meas. Loc. 3 1500 A
0533 CT Rated Secondary Current Meas. Loc. 3 1 A
0711 Earthing electrod IX1 connected to Terminal Q7
0712 CT rated primary current IX1 600 A
0713 CT rated secondary current IX1 1 A
The general protection data (P. System Data 2) include settings associated with all functions rather
than a specific protection, monitoring or control function Please ensure that the definition of signs
conforms to the direction of the reverse power protection and the forward power monitoring when
using these power functions.
During first energization of the transformer from the HV side too low 2nd harmonic content
may appear due to low remanence of the transformer.
Therefore before first backenergization the following temporary settings should be applied
in order to minimize the possibility for a spurious trip:
After successful first backenergization the original settings for addresses 1271 and 1272A should be
applied.
The over-current time protection is used as back-up function. The settings must be made in
accordance with the grading plan of the network. From the HV protection setting study the maximum
time delay for the HV back up protection must be given to allow proper setting. The time delay for
the back up O/C protection has to be set longer than this time but shorter than the short circuit ability
of the generator transformer.
The setting value for the back up over-current time protection has been chosen in that way that it will
work in case of an three or two-phase short circuit on the transformer LV winding.
The calculated values are:
S N(Tr) 296
I K 3phase 2,034 kA
3 UN uk 3 420 0,2
Whereby:
Ik-3phase 3-phase short circuit on HV side 2,034 kA
uk Impedance voltage 20%
SN(Tr) Rated power of transformer 296 MVA
UN Rated voltage of transformer HV side 420 kV
3 3
I K 2phase I K 3phase 2,034 1,76 kA
2 2
Whereby:
Ik-2phase 2-phase short circuit on HV side
With the I>> stage the unit transformer is protected against three-pole short circuits at the HV side.
The setting for sensing short circuits on the HV side of the transformer should be higher than the 3-
phase short circuit (>1,2 ∙ Ik-3phase).
With the I> stage the unit transformer is protected against currents higher than 0,8 ∙ IK-2phase.
The maximum inrush current for the transformer is not known. Therefore the inrush current is
assumed to:
1 1
I inR 5 (Address 2042)
u k 0,1
The settings are according the grading plan of the HV network. Please refer to section 3.4 of
“Protection Coordination Report HV-Connection to Power Plant” / pc 200 038/ab
AE1172-&EFQ30-ACA-116022, UNID 443654297 (TRANSCO Drw no. NS3PS RS 0010 G 0010)
7.1.7 Settings for Over-current Earth Protection (ANSI 50/51N) for 71BAT01 -
address block 24
This Function is used as definitive-time earth-current stage for the main transformer protection
(BAT01). The earth fault over-current time protection is used as back-up function.
The settings for the delay time (address 2414) and IE> (address 2413) have to be made in
accordance with the time grading plan of the HV network.
Basis for the calculation are the Transco guidelines, where a primary setting current of 900A (HV-
Side of the BAT Transformer), at a definite trip time of 1,2 s are agreed.
Please refer to section 3.4 of
“Protection Coordination Report HV-Connection to Power Plant” / pc 200 038/ab
AE1172-&EFQ30-ACA-116022, UNID 443654297 (TRANSCO Drw no. NS3PS RS 0010 G 0010)
This function is used as definite-time over-current stage for the unit auxiliary transformer protection.
Its settings are made in accordance with the grading plan of the MV network AE1172-&EFQ010-BY-
126001. The protection is designed to be the back-up protection of the over-current protection at the
feeder circuit breaker BBT01. The pickup value (address 3214) is set approximately 70% of the
phase-to-phase fault of the LV-side of the unit auxiliary transformer that it will work in case of an
three-or two phase short circuit on the transformer LV-winding. The time delay is set above the time
delay of the over-current protection on the LV-side.
Also this function is used as short-circuit stage for the unit auxiliary transformer protection and is the
back-up protection to the differential protection. Its settings are made in accordance with the grading
plan of the MV network. The high-current pickup value (address 3211) is set to approximately 80%
of the phase-to-phase value of the HV-side of the unit auxiliary transformer. A short time delay is set
to have no interference with the inrush current.
7.1.9 Settings for Over-current Earth 2 Protection (ANSI 50/51N) for 71BBT01
address block 38
This Function is used as earth-fault over-current stage for the unit auxiliary transformer protection
(71BBT01 / MV SWGR71BBE)
The settings are made in accordance with the grading plan of the MV network AE1172-&EFQ010-
BY-126001.
7.1.10 Settings for the Over-excitation Protection (ANSI 24) – address block 43
The over excitation protection serves to measure the voltage/frequency ratio which is proportional to
the induction B and puts it in relation to the BN nominal induction.
The factor U/f is given as quotient from voltage and frequency. Both values are related to nominal
values.
The over excitation function of the 7UT633 device –F26 will be used to protect the transformer itself
against over excitation. Therefore the settings are based on the transformer over excitation curve
provided by the manufacturer.
Time for cooling down from 100% to 0% for thermal image (address 4314 t cool down 3600 s) means
after a cooling down time of 60 minutes the trip is reset.
7.1.13 Settings for flexible functions (Flexible Function 01) (address block 255)
Twelve flexible functions can be activated and used for several protection functions. In this case the
first flexible function is used as Start-up Earth Fault Protection.
Only the parameters, which are relevant for differential protection and for the Earth Fault
Overcurrent Protection of the Unit transformer have been listed.
*Remark: At address 0221 is factor 1 while the input current must be treated without changes! At
the same time it must be known that the current displayed on the Relay Screen as
Primary Value must be understood and interpretated with a factor 0,5
E.g.: Input value at the relay terminal = 1 A
Corresponding real primary current = 600 A (Correct value)
Current Shown on Relay Display = 1200 A (Value must be multiplied with 0,5)
8.1.5 Settings for Differential Protection (ANSI 81C) for HV Cable – address block 12
8.1.8 Settings for Over-current Earth Protection (ANSI 50/51N) for 71BAT01 – address
block 31
This Function is used as definitive-time earth-current stage for the main transformer protection
(BAT01). The earth fault over-current time protection is used as back-up function.
The settings must be made in accordance with the grading plan of the network.
Basis for the calculation are the Transco guidelines, where a primary setting current of 900A (HV-
Side of the BAT Transformer) transformed to the LV-Side, at a definite trip time of 1,2 s are agreed.
Please refer to section 3.4 of
“Protection Coordination Report HV-Connection to Power Plant” / pc 200 038/ab
AE1172-&EFQ30-ACA-116022, UNID 443654297 (TRANSCO Drw no. NS3PS RS 0010 G 0010)
Direction
3160 Polarization with U0 + IY or U2
3162A ALPHA, lower angle for forward direction 338 °
3163A BETA, upper angle for forward direction 122 °
3164 Min. zero seq.voltage 3U0 for polarizing 0,50 V
3166 Min. neg. seq. polarizing voltage 3U2 0,50 V
3167 Min. neg. seq. polarizing current 3I2 0,05 A
3168 Compensation angle PHI comp. for Sr 255 °
3169 Forward direction power threshold 0,30 VA
10 Anexes
10.1 Annex 1 – BAT overexcitation curve
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:04:55
MLFB: 7UM6221**B020CB0
Parametersatzversion: V04.63.02
Gerätepfad: C:\Siemens\DIGSI4\D4Proj\Shuweihat_S3\P7DI\GV\SD\0000000e
Autor: RUA
Erstellt am: 10.12.12 15:12:24
Zuletzt geändert am: 13.08.14 12:04:47
Betriebsart: Offline
Kommentar: Issued with DIGSI V4.83.34
Einstellwerte in: Sekundärwertdarstellung
DRUCK - INHALT
Page 1 of 32
+71_-F11_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:04:55
Page 2 of 32
+71_-F11_7UM622 V4_63_prn
Device Configuration
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:04:55
1 Device Configuration
Page 3 of 32
+71_-F11_7UM622 V4_63_prn
Rangierung - kurz (spaltensortiert)
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:04:55
2.1 Binäreingänge
Binäreingänge
Binäreingänge Nr. Gruppe Information Typ Rangierung
2.2 Binärausgänge
Binärausgänge
BA Nr. Gruppe Information Typ Rangierung
Page 4 of 32
+71_-F11_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:04:55
Binärausgänge(2)
BA Nr. Gruppe Information Typ Rangierung
Page 5 of 32
+71_-F11_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:04:55
Binärausgänge(3)
BA Nr. Gruppe Information Typ Rangierung
Page 6 of 32
+71_-F11_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:04:55
Binärausgänge(4)
BA Nr. Gruppe Information Typ Rangierung
Page 7 of 32
+71_-F11_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:04:55
Binärausgänge(5)
BA Nr. Gruppe Information Typ Rangierung
2.3 LED
LED
LED Nr. Gruppe Information Typ Rangierung
Page 8 of 32
+71_-F11_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:04:55
LED(2)
LED Nr. Gruppe Information Typ Rangierung
Page 9 of 32
+71_-F11_7UM622 V4_63_prn
CFC
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:04:55
2.4 CFC
CFC
Nr. Gruppe Information Quelle Ziel
Page 10 of 32
+71_-F11_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:04:55
CFC(2)
Nr. Gruppe Information Quelle Ziel
2.5 Funktionstasten
nichts rangiert
2.6 Puffer
2.6.1 Betriebsmeldepuffer
Betriebsmeldepuffer
Nr. Gruppe Information Puffer
Page 11 of 32
+71_-F11_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:04:55
Betriebsmeldepuffer(2)
Nr. Gruppe Information Puffer
01965 O/C Prot. I> O/C prot. stage I> is switched OFF KG
01966 O/C Prot. I> O/C prot. stage I> is BLOCKED KG
01967 O/C Prot. I> O/C prot. stage I> is ACTIVE KG
01815 O/C Prot. I> O/C I> TRIP KG
05146 Unbalance Load >Reset memory for thermal replica I2 KG
05151 Unbalance Load I2 is switched OFF KG
05152 Unbalance Load I2 is BLOCKED KG
05153 Unbalance Load I2 is ACTIVE KG
05158 Unbalance Load Reset memory of thermal replica I2 KG
05156 Unbalance Load Unbalanced load: Current warning stage KG
05160 Unbalance Load Unbalanced load: TRIP of current stage KG
05161 Unbalance Load Unbalanced load: TRIP of thermal stage KG
05615 Diff. Prot Differential protection is switched OFF KG
05616 Diff. Prot Differential protection is BLOCKED KG
05617 Diff. Prot Differential protection is ACTIVE KG
05666 Diff. Prot Diff: Increase of char. phase L1 KG
05667 Diff. Prot Diff: Increase of char. phase L2 KG
05668 Diff. Prot Diff: Increase of char. phase L3 KG
05671 Diff. Prot Differential protection TRIP KG
05620 Diff. Prot Diff: adverse Adaption factor CT K
05329 Underexcitation >BLOCK underexc. prot. char. 1 KG
05330 Underexcitation >BLOCK underexc. prot. char. 2 KG
05327 Underexcitation >BLOCK underexc. prot. char. 3 KG
05328 Underexcitation >Exc. voltage failure recognized KG
05331 Underexcitation Underexc. prot. is switched OFF KG
05332 Underexcitation Underexc. prot. is BLOCKED KG
05333 Underexcitation Underexc. prot. is ACTIVE KG
05334 Underexcitation Underexc. prot. blocked by U< KG
05344 Underexcitation Underexc. prot. char. 1 TRIP KG
05345 Underexcitation Underexc. prot. char. 2 TRIP KG
05343 Underexcitation Underexc. prot. char. 3 TRIP KG
05346 Underexcitation Underexc. prot. char.+Uexc< TRIP KG
Underexcitation Underexc. Warning 5s after pick-up KG
Underexcitation EXT Exc to BO14 KG
05086 Reverse Power >Stop valve tripped KG
05091 Reverse Power Reverse power prot. is switched OFF KG
05092 Reverse Power Reverse power protection is BLOCKED KG
05093 Reverse Power Reverse power protection is ACTIVE KG
05097 Reverse Power Reverse power: TRIP KG
03956 Impedance >Zone 1B extension for impedance prot. KG
03958 Impedance >Imp. prot. : BLOCK undervoltage seal-in KG
03961 Impedance Impedance protection is switched OFF KG
03962 Impedance Impedance protection is BLOCKED KG
03963 Impedance Impedance protection is ACTIVE KG
03977 Impedance Imp.: Z1< TRIP KG
05061 Out-of-Step Out-of-step protection is switched OFF KG
Page 12 of 32
+71_-F11_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:04:55
Betriebsmeldepuffer(3)
Nr. Gruppe Information Puffer
Page 13 of 32
+71_-F11_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:04:55
Betriebsmeldepuffer(4)
Nr. Gruppe Information Puffer
Page 14 of 32
+71_-F11_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:04:55
Betriebsmeldepuffer(5)
Nr. Gruppe Information Puffer
2.6.2 Erdschlussmeldepuffer
nichts rangiert
Page 15 of 32
+71_-F11_7UM622 V4_63_prn
Netzstörfallmeldepuffer
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:04:55
2.6.3 Netzstörfallmeldepuffer
Netzstörfallmeldepuffer
Nr. Gruppe Information Puffer
Page 16 of 32
+71_-F11_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:04:55
Netzstörfallmeldepuffer(2)
Nr. Gruppe Information Puffer
Page 17 of 32
+71_-F11_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:04:55
Netzstörfallmeldepuffer(3)
Nr. Gruppe Information Puffer
Page 18 of 32
+71_-F11_7UM622 V4_63_prn
Störfallwertepuffer
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:04:55
2.6.4 Störfallwertepuffer
nichts rangiert
2.7 Bild
nichts rangiert
Page 19 of 32
+71_-F11_7UM622 V4_63_prn
Interfaces
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:04:55
3 Interfaces
3.2 VD-Adressen:
DIGSI-VD-Adresse: 3
SIPROTEC-VD-Adresse: 10026
Proxy-VD-Adresse: 4
SIPROTEC-T103-VD-Adresse: 0
3.3 Bedienschnittstelle
Adresse: 26
Frame: 8 E(ven) 1
Baudrate: 115200
Max. Telegramm-Lücke (0...50): 0
IP-Adresse: 192.168.1.1
Subnetzmaske: 255.255.255.0
Linkschicht: PPP (Punkt zu Punkt, seriell)
Zugriffsberechtigung an der Schnittstelle für Parametrierung: Aktiviert
Zugriffsberechtigung an der Schnittstelle für Test und Diagnose: Aktiviert
Web Monitor-Bedienung: Vollzugriff
3.4 Serviceschnittstelle
Adresse: 26
Frame: 8 E(ven) 1
Baudrate: 38400
Max. Telegramm-Lücke (0...50): 0
IP-Adresse: 192.168.2.1
Subnetzmaske: 255.255.255.0
Linkschicht: PPP (Punkt zu Punkt, seriell)
Zugriffsberechtigung an der Schnittstelle für Parametrierung: Aktiviert
Zugriffsberechtigung an der Schnittstelle für Test und Diagnose: Aktiviert
Web Monitor-Bedienung: Lesen
Page 20 of 32
+71_-F11_7UM622 V4_63_prn
General Device Settings
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:04:55
0610 Fault Display on LED / LCD Display Targets on every Pickup alle
0615 Minimum hold time of latched LEDs 5 min alle
0640 Start image Default Display image 1 alle
Page 21 of 32
+71_-F11_7UM622 V4_63_prn
Power System Data 1
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:04:55
Page 22 of 32
+71_-F11_7UM622 V4_63_prn
Gruppe Power System Data 1; Gruppe VT's
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:04:55
Page 23 of 32
+71_-F11_7UM622 V4_63_prn
Parametergruppen
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:04:55
6 Parametergruppen
6.2 Gruppe O/C I> (with undervoltage seal-in); Gruppe O/C I>
Page 24 of 32
+71_-F11_7UM622 V4_63_prn
Gruppe Differential Protection; Gruppe General
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:04:55
Page 25 of 32
+71_-F11_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:04:55
Page 26 of 32
+71_-F11_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:04:55
Page 27 of 32
+71_-F11_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:04:55
Page 28 of 32
+71_-F11_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:04:55
Page 29 of 32
+71_-F11_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:04:55
Page 30 of 32
+71_-F11_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:04:55
Page 31 of 32
+71_-F11_7UM622 V4_63_prn
Gruppe Threshold supervision; Gruppe Threshold
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:04:55
Page 32 of 32
+71_-F12_7UT633 V4_62_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:06:03
MLFB: 7UT6331*EB021BA0
Parametersatzversion: V04.62.05
Gerätepfad: C:\Siemens\DIGSI4\D4Proj\Shuweihat_S3\P7DI\GV\SD\0000000d
Autor: RUA
Erstellt am: 10.12.12 15:12:24
Zuletzt geändert am: 13.08.14 12:05:57
Betriebsart: Offline
Kommentar: Issued with DIGSI V4.83.34
Einstellwerte in: Sekundärwertdarstellung
DRUCK - INHALT
Page 1 of 22
+71_-F12_7UT633 V4_62_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:06:03
Page 2 of 22
+71_-F12_7UT633 V4_62_prn
Device Configuration
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:06:03
1 Device Configuration
Page 3 of 22
+71_-F12_7UT633 V4_62_prn
Rangierung - kurz (spaltensortiert)
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:06:03
2.1 Binäreingänge
Binäreingänge
Binäreingänge Nr. Gruppe Information Typ Rangierung
2.2 Binärausgänge
Binärausgänge
BA Nr. Gruppe Information Typ Rangierung
Page 4 of 22
+71_-F12_7UT633 V4_62_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:06:03
Binärausgänge(2)
BA Nr. Gruppe Information Typ Rangierung
2.3 LED
LED
LED Nr. Gruppe Information Typ Rangierung
Page 5 of 22
+71_-F12_7UT633 V4_62_prn
CFC
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:06:03
2.4 CFC
CFC
Nr. Gruppe Information Quelle Ziel
2.5 Funktionstasten
nichts rangiert
2.6 Puffer
2.6.1 Betriebsmeldepuffer
Betriebsmeldepuffer
Nr. Gruppe Information Puffer
Page 6 of 22
+71_-F12_7UT633 V4_62_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:06:03
Betriebsmeldepuffer(2)
Nr. Gruppe Information Puffer
Page 7 of 22
+71_-F12_7UT633 V4_62_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:06:03
Betriebsmeldepuffer(3)
Nr. Gruppe Information Puffer
Page 8 of 22
+71_-F12_7UT633 V4_62_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:06:03
Betriebsmeldepuffer(4)
Nr. Gruppe Information Puffer
2.6.2 Erdschlussmeldepuffer
nichts rangiert
2.6.3 Netzstörfallmeldepuffer
Netzstörfallmeldepuffer
Nr. Gruppe Information Puffer
Page 9 of 22
+71_-F12_7UT633 V4_62_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:06:03
Netzstörfallmeldepuffer(2)
Nr. Gruppe Information Puffer
Page 10 of 22
+71_-F12_7UT633 V4_62_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:06:03
Netzstörfallmeldepuffer(3)
Nr. Gruppe Information Puffer
2.6.4 Störfallwertepuffer
nichts rangiert
2.7 Bild
Bild
Nr. Gruppe Information Abzweigsteuerbild Grundbild
Page 11 of 22
+71_-F12_7UT633 V4_62_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:06:03
Bild(2)
Nr. Gruppe Information Abzweigsteuerbild Grundbild
Page 12 of 22
+71_-F12_7UT633 V4_62_prn
Interfaces
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:06:03
3 Interfaces
3.2 VD-Adressen:
DIGSI-VD-Adresse: 3
SIPROTEC-VD-Adresse: 10027
Proxy-VD-Adresse: 4
SIPROTEC-T103-VD-Adresse: 0
3.3 Bedienschnittstelle
Adresse: 27
Frame: 8 E(ven) 1
Baudrate: 115200
Max. Telegramm-Lücke (0...50): 0
IP-Adresse: 192.168.1.1
Subnetzmaske: 255.255.255.0
Linkschicht: PPP (Punkt zu Punkt, seriell)
Zugriffsberechtigung an der Schnittstelle für Parametrierung: Aktiviert
Zugriffsberechtigung an der Schnittstelle für Test und Diagnose: Aktiviert
Web Monitor-Bedienung: Vollzugriff
3.4 Serviceschnittstelle
Adresse: 27
Frame: 8 E(ven) 1
Baudrate: 38400
Max. Telegramm-Lücke (0...50): 0
IP-Adresse: 192.168.2.1
Subnetzmaske: 255.255.255.0
Linkschicht: PPP (Punkt zu Punkt, seriell)
Zugriffsberechtigung an der Schnittstelle für Parametrierung: Aktiviert
Zugriffsberechtigung an der Schnittstelle für Test und Diagnose: Aktiviert
Web Monitor-Bedienung: Lesen
Page 13 of 22
+71_-F12_7UT633 V4_62_prn
General Device Settings
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:06:03
0201 Fault Display on LED / LCD Display Targets on every Pickup alle
0202 Spontaneous display of flt.annunciations NO alle
Page 14 of 22
+71_-F12_7UT633 V4_62_prn
Power System Data 1
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:06:03
Page 15 of 22
+71_-F12_7UT633 V4_62_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:06:03
Page 16 of 22
+71_-F12_7UT633 V4_62_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:06:03
Page 17 of 22
+71_-F12_7UT633 V4_62_prn
Parametergruppen
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:06:03
6 Parametergruppen
Page 18 of 22
+71_-F12_7UT633 V4_62_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:06:03
Page 19 of 22
+71_-F12_7UT633 V4_62_prn
Gruppe Restricted Earth Fault Protection; Gruppe Settings
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:06:03
Page 20 of 22
+71_-F12_7UT633 V4_62_prn
Gruppe Measurement Supervision; Gruppe General
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:06:03
Page 21 of 22
+71_-F12_7UT633 V4_62_prn
Gruppe Supervision; Gruppe General
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:06:03
Page 22 of 22
+71_-F13_7UT633 V4_62_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:07:39
MLFB: 7UT6331*EB021BA0
Parametersatzversion: V04.62.05
Gerätepfad: C:\Siemens\DIGSI4\D4Proj\Shuweihat_S3\P7DI\GV\SD\0000000c
Autor: RUA
Erstellt am: 10.12.12 15:12:24
Zuletzt geändert am: 13.08.14 12:06:53
Betriebsart: Offline
Kommentar: Issued with DIGSI V4.83.34
Einstellwerte in: Sekundärwertdarstellung
DRUCK - INHALT
Page 1 of 18
+71_-F13_7UT633 V4_62_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:07:39
Page 2 of 18
+71_-F13_7UT633 V4_62_prn
Device Configuration
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:07:39
1 Device Configuration
Page 3 of 18
+71_-F13_7UT633 V4_62_prn
Rangierung - kurz (spaltensortiert)
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:07:39
2.1 Binäreingänge
Binäreingänge
Binäreingänge Nr. Gruppe Information Typ Rangierung
2.2 Binärausgänge
Binärausgänge
BA Nr. Gruppe Information Typ Rangierung
Page 4 of 18
+71_-F13_7UT633 V4_62_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:07:39
Binärausgänge(2)
BA Nr. Gruppe Information Typ Rangierung
2.3 LED
LED
LED Nr. Gruppe Information Typ Rangierung
2.4 CFC
CFC
Nr. Gruppe Information Quelle Ziel
2.5 Funktionstasten
nichts rangiert
Page 5 of 18
+71_-F13_7UT633 V4_62_prn
Puffer
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:07:39
2.6 Puffer
2.6.1 Betriebsmeldepuffer
Betriebsmeldepuffer
Nr. Gruppe Information Puffer
Page 6 of 18
+71_-F13_7UT633 V4_62_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:07:39
Betriebsmeldepuffer(2)
Nr. Gruppe Information Puffer
Page 7 of 18
+71_-F13_7UT633 V4_62_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:07:39
Betriebsmeldepuffer(3)
Nr. Gruppe Information Puffer
2.6.2 Erdschlussmeldepuffer
nichts rangiert
2.6.3 Netzstörfallmeldepuffer
Netzstörfallmeldepuffer
Nr. Gruppe Information Puffer
Page 8 of 18
+71_-F13_7UT633 V4_62_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:07:39
Netzstörfallmeldepuffer(2)
Nr. Gruppe Information Puffer
Page 9 of 18
+71_-F13_7UT633 V4_62_prn
Störfallwertepuffer
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:07:39
2.6.4 Störfallwertepuffer
nichts rangiert
2.7 Bild
Bild
Nr. Gruppe Information Abzweigsteuerbild Grundbild
Page 10 of 18
+71_-F13_7UT633 V4_62_prn
Interfaces
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:07:39
3 Interfaces
3.2 VD-Adressen:
DIGSI-VD-Adresse: 3
SIPROTEC-VD-Adresse: 10028
Proxy-VD-Adresse: 4
SIPROTEC-T103-VD-Adresse: 0
3.3 Bedienschnittstelle
Adresse: 28
Frame: 8 E(ven) 1
Baudrate: 115200
Max. Telegramm-Lücke (0...50): 0
IP-Adresse: 192.168.1.1
Subnetzmaske: 255.255.255.0
Linkschicht: PPP (Punkt zu Punkt, seriell)
Zugriffsberechtigung an der Schnittstelle für Parametrierung: Aktiviert
Zugriffsberechtigung an der Schnittstelle für Test und Diagnose: Aktiviert
Web Monitor-Bedienung: Vollzugriff
3.4 Serviceschnittstelle
Adresse: 28
Frame: 8 E(ven) 1
Baudrate: 38400
Max. Telegramm-Lücke (0...50): 0
IP-Adresse: 192.168.2.1
Subnetzmaske: 255.255.255.0
Linkschicht: PPP (Punkt zu Punkt, seriell)
Zugriffsberechtigung an der Schnittstelle für Parametrierung: Aktiviert
Zugriffsberechtigung an der Schnittstelle für Test und Diagnose: Aktiviert
Web Monitor-Bedienung: Lesen
Page 11 of 18
+71_-F13_7UT633 V4_62_prn
General Device Settings
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:07:39
0201 Fault Display on LED / LCD Display Targets on every Pickup alle
0202 Spontaneous display of flt.annunciations NO alle
Page 12 of 18
+71_-F13_7UT633 V4_62_prn
Power System Data 1
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:07:39
Page 13 of 18
+71_-F13_7UT633 V4_62_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:07:39
Page 14 of 18
+71_-F13_7UT633 V4_62_prn
Parametergruppen
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:07:39
6 Parametergruppen
Page 15 of 18
+71_-F13_7UT633 V4_62_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:07:39
Page 16 of 18
+71_-F13_7UT633 V4_62_prn
Gruppe Restricted Earth Fault Protection; Gruppe Settings
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:07:39
Page 17 of 18
+71_-F13_7UT633 V4_62_prn
Gruppe Supervision; Gruppe General
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA01 / 13.08.14 12:07:39
Page 18 of 18
+71_-F21_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:10:42
MLFB: 7UM6221**B020CB0
Parametersatzversion: V04.63.02
Gerätepfad: C:\Siemens\DIGSI4\D4Proj\Shuweihat_S3\P7DI\GV\SD\00000011
Autor: RUA
Erstellt am: 10.12.12 15:12:24
Zuletzt geändert am: 13.08.14 12:10:35
Betriebsart: Offline
Kommentar: Issued with DIGSI V4.83.34
Einstellwerte in: Sekundärwertdarstellung
DRUCK - INHALT
Page 1 of 31
+71_-F21_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:10:42
Page 2 of 31
+71_-F21_7UM622 V4_63_prn
Device Configuration
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:10:42
1 Device Configuration
Page 3 of 31
+71_-F21_7UM622 V4_63_prn
Rangierung - kurz (spaltensortiert)
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:10:42
2.1 Binäreingänge
Binäreingänge
Binäreingänge Nr. Gruppe Information Typ Rangierung
2.2 Binärausgänge
Binärausgänge
BA Nr. Gruppe Information Typ Rangierung
Page 4 of 31
+71_-F21_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:10:42
Binärausgänge(2)
BA Nr. Gruppe Information Typ Rangierung
Page 5 of 31
+71_-F21_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:10:42
Binärausgänge(3)
BA Nr. Gruppe Information Typ Rangierung
Page 6 of 31
+71_-F21_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:10:42
Binärausgänge(4)
BA Nr. Gruppe Information Typ Rangierung
Page 7 of 31
+71_-F21_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:10:42
Binärausgänge(5)
BA Nr. Gruppe Information Typ Rangierung
2.3 LED
LED
LED Nr. Gruppe Information Typ Rangierung
Page 8 of 31
+71_-F21_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:10:42
LED(2)
LED Nr. Gruppe Information Typ Rangierung
2.4 CFC
CFC
Nr. Gruppe Information Quelle Ziel
Page 9 of 31
+71_-F21_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:10:42
CFC(2)
Nr. Gruppe Information Quelle Ziel
Page 10 of 31
+71_-F21_7UM622 V4_63_prn
Funktionstasten
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:10:42
2.5 Funktionstasten
nichts rangiert
2.6 Puffer
2.6.1 Betriebsmeldepuffer
Betriebsmeldepuffer
Nr. Gruppe Information Puffer
Page 11 of 31
+71_-F21_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:10:42
Betriebsmeldepuffer(2)
Nr. Gruppe Information Puffer
Page 12 of 31
+71_-F21_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:10:42
Betriebsmeldepuffer(3)
Nr. Gruppe Information Puffer
Page 13 of 31
+71_-F21_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:10:42
Betriebsmeldepuffer(4)
Nr. Gruppe Information Puffer
Page 14 of 31
+71_-F21_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:10:42
Betriebsmeldepuffer(5)
Nr. Gruppe Information Puffer
2.6.2 Erdschlussmeldepuffer
nichts rangiert
2.6.3 Netzstörfallmeldepuffer
Netzstörfallmeldepuffer
Nr. Gruppe Information Puffer
Page 15 of 31
+71_-F21_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:10:42
Netzstörfallmeldepuffer(2)
Nr. Gruppe Information Puffer
Page 16 of 31
+71_-F21_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:10:42
Netzstörfallmeldepuffer(3)
Nr. Gruppe Information Puffer
Page 17 of 31
+71_-F21_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:10:42
Netzstörfallmeldepuffer(4)
Nr. Gruppe Information Puffer
2.6.4 Störfallwertepuffer
nichts rangiert
2.7 Bild
nichts rangiert
Page 18 of 31
+71_-F21_7UM622 V4_63_prn
Interfaces
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:10:42
3 Interfaces
3.2 VD-Adressen:
DIGSI-VD-Adresse: 3
SIPROTEC-VD-Adresse: 10029
Proxy-VD-Adresse: 4
SIPROTEC-T103-VD-Adresse: 0
3.3 Bedienschnittstelle
Adresse: 29
Frame: 8 E(ven) 1
Baudrate: 115200
Max. Telegramm-Lücke (0...50): 0
IP-Adresse: 192.168.1.1
Subnetzmaske: 255.255.255.0
Linkschicht: PPP (Punkt zu Punkt, seriell)
Zugriffsberechtigung an der Schnittstelle für Parametrierung: Aktiviert
Zugriffsberechtigung an der Schnittstelle für Test und Diagnose: Aktiviert
Web Monitor-Bedienung: Vollzugriff
3.4 Serviceschnittstelle
Adresse: 29
Frame: 8 E(ven) 1
Baudrate: 38400
Max. Telegramm-Lücke (0...50): 0
IP-Adresse: 192.168.2.1
Subnetzmaske: 255.255.255.0
Linkschicht: PPP (Punkt zu Punkt, seriell)
Zugriffsberechtigung an der Schnittstelle für Parametrierung: Aktiviert
Zugriffsberechtigung an der Schnittstelle für Test und Diagnose: Aktiviert
Web Monitor-Bedienung: Lesen
Page 19 of 31
+71_-F21_7UM622 V4_63_prn
General Device Settings
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:10:42
0610 Fault Display on LED / LCD Display Targets on every Pickup alle
0615 Minimum hold time of latched LEDs 5 min alle
0640 Start image Default Display image 1 alle
Page 20 of 31
+71_-F21_7UM622 V4_63_prn
Power System Data 1
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:10:42
Page 21 of 31
+71_-F21_7UM622 V4_63_prn
Gruppe Power System Data 1; Gruppe VT's
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:10:42
Page 22 of 31
+71_-F21_7UM622 V4_63_prn
Parametergruppen
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:10:42
6 Parametergruppen
6.2 Gruppe O/C I> (with undervoltage seal-in); Gruppe O/C I>
Page 23 of 31
+71_-F21_7UM622 V4_63_prn
Gruppe Differential Protection; Gruppe General
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:10:42
Page 24 of 31
+71_-F21_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:10:42
Page 25 of 31
+71_-F21_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:10:42
Page 26 of 31
+71_-F21_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:10:42
Page 27 of 31
+71_-F21_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:10:42
Page 28 of 31
+71_-F21_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:10:42
6.20 Gruppe Rotor Earth Fault Protection (1-3Hz); Gruppe REF 1-3Hz
Page 29 of 31
+71_-F21_7UM622 V4_63_prn
Gruppe Measurement Supervision; Gruppe MeasSupervision
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:10:42
Page 30 of 31
+71_-F21_7UM622 V4_63_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:10:42
Page 31 of 31
+71_-F26_7UT633 V4_6_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:13
MLFB: 7UT6331*EB021AC3
Parametersatzversion: V04.62.05
Gerätepfad: C:\Siemens\DIGSI4\D4Proj\Shuweihat_S3\P7DI\GV\SD\00000010
Autor: RUA
Erstellt am: 10.12.12 15:12:24
Zuletzt geändert am: 13.08.14 12:11:03
Betriebsart: Offline
Kommentar: Issued with DIGSI V4.83.34
Einstellwerte in: Sekundärwertdarstellung
DRUCK - INHALT
Page 1 of 30
+71_-F26_7UT633 V4_6_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:13
Page 2 of 30
+71_-F26_7UT633 V4_6_prn
Device Configuration
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:13
1 Device Configuration
Page 3 of 30
+71_-F26_7UT633 V4_6_prn
Rangierung - kurz (spaltensortiert)
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:13
2.1 Binäreingänge
Binäreingänge
Binäreingänge Nr. Gruppe Information Typ Rangierung
2.2 Binärausgänge
Binärausgänge
BA Nr. Gruppe Information Typ Rangierung
Page 4 of 30
+71_-F26_7UT633 V4_6_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:13
Binärausgänge(2)
BA Nr. Gruppe Information Typ Rangierung
Page 5 of 30
+71_-F26_7UT633 V4_6_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:13
Binärausgänge(3)
BA Nr. Gruppe Information Typ Rangierung
Page 6 of 30
+71_-F26_7UT633 V4_6_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:13
Binärausgänge(4)
BA Nr. Gruppe Information Typ Rangierung
Page 7 of 30
+71_-F26_7UT633 V4_6_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:13
Binärausgänge(5)
BA Nr. Gruppe Information Typ Rangierung
2.3 LED
LED
LED Nr. Gruppe Information Typ Rangierung
2.4 CFC
CFC
Nr. Gruppe Information Quelle Ziel
Page 8 of 30
+71_-F26_7UT633 V4_6_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:13
CFC(2)
Nr. Gruppe Information Quelle Ziel
2.5 Funktionstasten
nichts rangiert
2.6 Puffer
2.6.1 Betriebsmeldepuffer
Betriebsmeldepuffer
Nr. Gruppe Information Puffer
Page 9 of 30
+71_-F26_7UT633 V4_6_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:13
Betriebsmeldepuffer(2)
Nr. Gruppe Information Puffer
Page 10 of 30
+71_-F26_7UT633 V4_6_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:13
Betriebsmeldepuffer(3)
Nr. Gruppe Information Puffer
Page 11 of 30
+71_-F26_7UT633 V4_6_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:13
Betriebsmeldepuffer(4)
Nr. Gruppe Information Puffer
Page 12 of 30
+71_-F26_7UT633 V4_6_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:13
Betriebsmeldepuffer(5)
Nr. Gruppe Information Puffer
Page 13 of 30
+71_-F26_7UT633 V4_6_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:13
Betriebsmeldepuffer(6)
Nr. Gruppe Information Puffer
2.6.2 Erdschlussmeldepuffer
nichts rangiert
2.6.3 Netzstörfallmeldepuffer
Netzstörfallmeldepuffer
Nr. Gruppe Information Puffer
Page 14 of 30
+71_-F26_7UT633 V4_6_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:13
Netzstörfallmeldepuffer(2)
Nr. Gruppe Information Puffer
Page 15 of 30
+71_-F26_7UT633 V4_6_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:13
Netzstörfallmeldepuffer(3)
Nr. Gruppe Information Puffer
Page 16 of 30
+71_-F26_7UT633 V4_6_prn
Störfallwertepuffer
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:13
2.6.4 Störfallwertepuffer
nichts rangiert
2.7 Bild
Bild
Nr. Gruppe Information Abzweigsteuerbild Grundbild
Page 17 of 30
+71_-F26_7UT633 V4_6_prn
Interfaces
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:13
3 Interfaces
3.2 VD-Adressen:
DIGSI-VD-Adresse: 3
SIPROTEC-VD-Adresse: 10030
Proxy-VD-Adresse: 4
SIPROTEC-T103-VD-Adresse: 0
3.3 Bedienschnittstelle
Adresse: 30
Frame: 8 E(ven) 1
Baudrate: 115200
Max. Telegramm-Lücke (0...50): 0
IP-Adresse: 192.168.1.1
Subnetzmaske: 255.255.255.0
Linkschicht: PPP (Punkt zu Punkt, seriell)
Zugriffsberechtigung an der Schnittstelle für Parametrierung: Aktiviert
Zugriffsberechtigung an der Schnittstelle für Test und Diagnose: Aktiviert
Web Monitor-Bedienung: Vollzugriff
3.4 Serviceschnittstelle
Adresse: 30
Frame: 8 E(ven) 1
Baudrate: 38400
Max. Telegramm-Lücke (0...50): 0
IP-Adresse: 192.168.2.1
Subnetzmaske: 255.255.255.0
Linkschicht: PPP (Punkt zu Punkt, seriell)
Zugriffsberechtigung an der Schnittstelle für Parametrierung: Aktiviert
Zugriffsberechtigung an der Schnittstelle für Test und Diagnose: Aktiviert
Web Monitor-Bedienung: Lesen
Page 18 of 30
+71_-F26_7UT633 V4_6_prn
General Device Settings
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:13
0201 Fault Display on LED / LCD Display Targets on every Pickup alle
0202 Spontaneous display of flt.annunciations NO alle
Page 19 of 30
+71_-F26_7UT633 V4_6_prn
Power System Data 1
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:13
Page 20 of 30
+71_-F26_7UT633 V4_6_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:13
Page 21 of 30
+71_-F26_7UT633 V4_6_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:13
0801 VT Rated Prim. Voltage Set UL1, UL2, UL3 20,0 kV alle
0802 VT Rated Sec. Voltage Set UL1, UL2, UL3 100 V alle
0803 Angle correction UL1, UL2, UL3 - VT 0,00 ° alle
0816 Matching ratio Phase-VT to Open-Delta-VT 1,73 alle
Page 22 of 30
+71_-F26_7UT633 V4_6_prn
Parametergruppen
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:13
6 Parametergruppen
Page 23 of 30
+71_-F26_7UT633 V4_6_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:13
Page 24 of 30
+71_-F26_7UT633 V4_6_prn
Gruppe Time overcurrent Phase; Gruppe General
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:13
Page 25 of 30
+71_-F26_7UT633 V4_6_prn
Gruppe Time overcurrent Phase 3; Gruppe DMT
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:13
Page 26 of 30
+71_-F26_7UT633 V4_6_prn
Gruppe Time overcurrent Earth; Gruppe Inrush
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:13
Page 27 of 30
+71_-F26_7UT633 V4_6_prn
Gruppe Overexcitation Protection (U/f); Gruppe General
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:13
Page 28 of 30
+71_-F26_7UT633 V4_6_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:13
Page 29 of 30
+71_-F26_7UT633 V4_6_prn
Gruppe Supervision; Gruppe General
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:13
Flexible Function ON A
Page 30 of 30
+71_-F28_7SD522 V4_7_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:41
MLFB: 7SD52215PB999HL4
Parametersatzversion: V04.71.05
Gerätepfad: C:\Siemens\DIGSI4\D4Proj\Shuweihat_S3\P7DI\GV\SD\0000000f
Autor: RUA
Erstellt am: 10.12.12 15:12:24
Zuletzt geändert am: 13.08.14 12:11:34
Betriebsart: Offline
Kommentar: Issued with DIGSI V4.83.34
Einstellwerte in: Sekundärwertdarstellung
DRUCK - INHALT
Page 1 of 27
+71_-F28_7SD522 V4_7_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:41
Page 2 of 27
+71_-F28_7SD522 V4_7_prn
Device Configuration
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:41
1 Device Configuration
Page 3 of 27
+71_-F28_7SD522 V4_7_prn
Rangierung - kurz (spaltensortiert)
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:41
2.1 Binäreingänge
Binäreingänge
Binäreingänge Nr. Gruppe Information Typ Rangierung
2.2 Binärausgänge
Binärausgänge
BA Nr. Gruppe Information Typ Rangierung
Page 4 of 27
+71_-F28_7SD522 V4_7_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:41
Binärausgänge(2)
BA Nr. Gruppe Information Typ Rangierung
2.3 LED
LED
LED Nr. Gruppe Information Typ Rangierung
Page 5 of 27
+71_-F28_7SD522 V4_7_prn
CFC
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:41
2.4 CFC
CFC
Nr. Gruppe Information Quelle Ziel
2.5 Funktionstasten
nichts rangiert
2.6 Puffer
2.6.1 Betriebsmeldepuffer
Betriebsmeldepuffer
Nr. Gruppe Information Puffer
Page 6 of 27
+71_-F28_7SD522 V4_7_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:41
Betriebsmeldepuffer(2)
Nr. Gruppe Information Puffer
Page 7 of 27
+71_-F28_7SD522 V4_7_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:41
Betriebsmeldepuffer(3)
Nr. Gruppe Information Puffer
Page 8 of 27
+71_-F28_7SD522 V4_7_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:41
Betriebsmeldepuffer(4)
Nr. Gruppe Information Puffer
Page 9 of 27
+71_-F28_7SD522 V4_7_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:41
Betriebsmeldepuffer(5)
Nr. Gruppe Information Puffer
Page 10 of 27
+71_-F28_7SD522 V4_7_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:41
Betriebsmeldepuffer(6)
Nr. Gruppe Information Puffer
2.6.2 Erdschlussmeldepuffer
nichts rangiert
2.6.3 Netzstörfallmeldepuffer
Netzstörfallmeldepuffer
Nr. Gruppe Information Puffer
Page 11 of 27
+71_-F28_7SD522 V4_7_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:41
Netzstörfallmeldepuffer(2)
Nr. Gruppe Information Puffer
2.6.4 Störfallwertepuffer
nichts rangiert
2.7 Bild
nichts rangiert
Page 12 of 27
+71_-F28_7SD522 V4_7_prn
Systemschnittstelle IEC 61850
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:41
Page 13 of 27
+71_-F28_7SD522 V4_7_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:41
Page 14 of 27
+71_-F28_7SD522 V4_7_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:41
Page 15 of 27
+71_-F28_7SD522 V4_7_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:41
Page 16 of 27
+71_-F28_7SD522 V4_7_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:41
Page 17 of 27
+71_-F28_7SD522 V4_7_prn
Interfaces
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:41
3 Interfaces
3.2 VD-Adressen:
DIGSI-VD-Adresse: 3
SIPROTEC-VD-Adresse: 10031
Proxy-VD-Adresse: 4
SIPROTEC-T103-VD-Adresse: 0
3.3 Bedienschnittstelle
Adresse: 31
Frame: 8 E(ven) 1
Baudrate: 115200
Max. Telegramm-Lücke (0...50): 0
IP-Adresse: 192.168.1.1
Subnetzmaske: 255.255.255.0
Linkschicht: PPP (Punkt zu Punkt, seriell)
Zugriffsberechtigung an der Schnittstelle für Parametrierung: Aktiviert
Zugriffsberechtigung an der Schnittstelle für Test und Diagnose: Aktiviert
Web Monitor-Bedienung: Vollzugriff
3.4 Serviceschnittstelle
Adresse: 31
Frame: 8 E(ven) 1
Baudrate: 38400
Max. Telegramm-Lücke (0...50): 0
IP-Adresse: 192.168.2.1
Subnetzmaske: 255.255.255.0
Linkschicht: PPP (Punkt zu Punkt, seriell)
Zugriffsberechtigung an der Schnittstelle für Parametrierung: Aktiviert
Zugriffsberechtigung an der Schnittstelle für Test und Diagnose: Aktiviert
Web Monitor-Bedienung: Lesen
IP-Adresse: 0.0.0.0
Subnetzmaske: 0.0.0.0
Page 18 of 27
+71_-F28_7SD522 V4_7_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:41
Standardgateway: 0.0.0.0
Linkschicht: Ethernet
Zugriffsberechtigung an der Schnittstelle für Parametrierung: Aktiviert
Zugriffsberechtigung an der Schnittstelle für Test und Diagnose: Aktiviert
Web Monitor-Bedienung: Lesen
SNMP (Simple Network Management Protocol): Ein
Web Server (http): Ein
Web Server (https): Aus
IEC 61850: Ein
Zusatzprotokoll EN100-Modul: Ein
DIGSI über EN100-Modul: Ein
3.6 Redundanz
Betriebsart: Line
3.7 Ethernet am PC
IP-Adresse:
Subnetzmaske: 255.255.254.0
Page 19 of 27
+71_-F28_7SD522 V4_7_prn
General Device Settings
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:41
Gruppe Device
Nr. Parameter Wert Gruppe
0610 Fault Display on LED / LCD Display Targets on every Pickup alle
0625A Minimum hold time of latched LEDs 0 min alle
0640 Start image Default Display image 1 alle
Page 20 of 27
+71_-F28_7SD522 V4_7_prn
Power System Data 1
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:41
Page 21 of 27
+71_-F28_7SD522 V4_7_prn
Parametergruppen
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:41
6 Parametergruppen
Page 22 of 27
+71_-F28_7SD522 V4_7_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:41
Gruppe Intertrip
Nr. Parameter Wert Gruppe
Page 23 of 27
+71_-F28_7SD522 V4_7_prn
Gruppe Measurement Supervision; Gruppe I/U-Monitoring
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:41
Page 24 of 27
+71_-F28_7SD522 V4_7_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:41
Page 25 of 27
+71_-F28_7SD522 V4_7_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:41
Page 26 of 27
+71_-F28_7SD522 V4_7_prn
Shuweihat_S3 /
SIMATIC +71CHA_COM3_BACK / +71CHA02 / 13.08.14 12:11:41
Page 27 of 27