Professional Documents
Culture Documents
POWER SYSTEMS
Ned Mohan
Oscar A. Schott Professor of Power Electronics and Systems
Department of Electrical and Computer Engineering
University of Minnesota
Minneapolis, MN 55455
USA
Bus-1 Bus-3
200km
P + jQ
Pm1 Pe1 150km
150km
Bus-2
Pe 2
Pm 2
10 Chapter 11: Transient Stability Lab 10: Transient Stability using MATLAB
11 Chapter 12: Interconnected Lab 11: AGC using Simulink, and Economic
Systems, Economic Dispatch Dispatch using PowerWorld
12 Chapter 13: Short-Circuit Lab 12: Transmission Line Faults using
Faults, Relays, Circuit Breakers PowerWorld and MATLAB
13 Chapter 14: Transient Over- Lab 13: Over-voltages and Surge Arrestors
Voltages, Surge Arrestors, using PSCAD-EMTDC
Insulation Coordination
Generator
Transmission 13.8 kV
line
Feeder
Load
(a) ( b)
REVIEW OF BASIC
ELECTRIC CIRCUITS AND
ELECTROMAGNETIC
CONCEPTS
V = V ∠0 Real
−φ
I = I∠ − φ
Fig. 2-3 A circuit (a) in time-domain and (b) in phasor-domain; (c) impedance triangle.
− j5 Ω 2Ω
+
I1
V1 7.0Ω
j15 Ω
Im I2
−
Subcircuit 1 v (t ) Subcircuit 2
−
p (t ) = v (t ) i (t )
0 t 0
t
v (t )
i (t ) i (t )
(a ) ( b)
Subcircuit 1 V Subcircuit 2
−
S = P + jQ
(a)
Im
Im S
V = V ∠φv Q
φ Re
φ
I = I ∠φi P Re
(b) (c)
Fig. 2-8 (a) Circuit in phasor-domain; (b) phasor diagram; (c) power triangle.
+
V1 − jQC
PL + jQL
− j13.963 Ω
−
Generator
Transmission 13.8 kV
line
Feeder
Load
Vbn ( b)
2π 2π
3 3
(a )
Fig. 2-11 Three-phase voltages in time and phasor domain.
(a) (b)
Fig. 2-12 Balanced wye-connected, three-phase circuit.
c C
(a) ( b)
30 o
Van
Vbn
Vbc
ZΥ
ZΔ I ab Z Δ
I ca
Ibc ZΥ ZΥ
c b c
ZΔ b
(a) (b)
Fig. 2-16 Delta-wye transformation.
(a )
Fig. 2-17 Power transfer between two ac systems.
0.5
0 0 0
δ
90 180
Fig. 2-18 Power as a function of δ .
Pbase ,Qbase ,(VA)base =Vbase Ibase (in Watt, VAR, or VA) (2-50)
actual value
Per-UnitValue = (2-51)
base value
Pin Power Po
System
Apparatus
Ploss
Fig. 2-19 Energy Efficiency η = Po / Pin .
i2
rm
ID ID
OD OD
(a) (b)
Fig. 2-21 Example 2-9.
μm
μo
Hm Hm
(a) (b)
φm
(a) (b)
Fig. 2-24 Coil inductance.
r
w
i (t )
+
e (t ) N
−
0 t
e +
e φl
−
−
(a) (b)
Fig. 2-28 Including leakage flux.
− −
(a) (b)
Fig. 2-29 Analysis including the leakage flux.
(a) (b)
Fig. 3-1 Production and consumption of energy in the United States in 2004 [1].
Fig. 3-2 Electric power generation by various fuel types in the U.S. in 2005 [1].
Heat in
Boiler Turbine Gen
Combustion
Compressor Chamber
Turbine
Air in Exhaust
(a ) ( b)
Fig. 3-6 (a) BWR and (b) PWR reactors [5].
Fig. 3-8 c p as a function of λ [7]; these would vary based on the turbine design.
AC DC
Wind
Turbine DC AC
Generator-side Grid-side
Converter Converter
Fig. 3-10 Doubly-fed, wound-rotor induction generator [9].
Utility
Utility
Max. Power- 1φ
point Tracker
Voltage E=
2F
1.2 -
Activation - 1000
Cell Power ( PC in mW )
Losses
Cell Voltage ( VC in Volts )
1-
- 800
Ohmic
0.8 - Losses
- 600
0.6 -
Cell Power
PC= VC x i Mass - 400
0.4 - Transport
Losses
- 200
0.2 -
0 -| | | | | -0
0 500 1000 1500 2000
Current Density ( i in mA/cm2 )
Fig. 3-14 Fuel cell v-i relationship and cell power [12].
1
5
2
3
4 1
4
3 5
6
2
Fig. 3-17 Electric power industry fuel costs in the U.S. in 2005 [1].
AC TRANSMISSION LINES
AND UNDERGROUND
CABLES
(b)
C
neutral (zeroimpedance)
D
surface towards center
(a ) ( b)
Fig. 4-4 (a) Cross-section of ACSR conductors, (b) skin-effect in a solid conductor.
ic
a b a b b
r D
ia r ib ia x
dx a x
ib
D D dx
(a ) (b) (c)
x
x1 1 2
q
x2
c c
qc
C hypothetical
neutral
qa qb C n C
a b
a b
D
(a ) ( b)
Fig. 4-7 Shunt capacitances.
Nominal Voltage R (Ω / km ) ω L (Ω / km ) ωC ( μ / km )
x 0
0 - 80 Thermal >3
POWER FLOW IN
POWER SYSTEM
NETWORKS
150km 150km P + jQ
Slack Bus PQ Bus
PV Bus
Bus 2
I1 I3
Bus 2 V2
I2
Fig. 5-2 Example system of Fig. 5-1 for assembling Y-bus matrix.
2
x (2) x (1)
x (0)
0
0.5 1.0 1.5 2 3.0 3.5 4.0 x
−2
−4
−6
−8
−10
−12
( 0.69 - j1.11) pu
P1 + jQ1 = (3.08 - j 0.82) pu ( 5.0 + j1.0 ) pu
( 2.68 + j1.48) pu
V2 = 1.05∠-2.07 0 pu
P2 + jQ2 = ( 2.0 + j 2.67) pu
TRANSFORMERS IN POWER
SYSTEMS
(a) (b)
Fig. 6-1 Principle of transformers, beginning with just one coil.
μm
μo
Hm Hm
(a) (b)
Fig. 6-2 B-H characteristics of ferromagnetic materials.
e2 Ideal
− Transformer
(a) (b)
Fig. 6-3 Transformer with the open-circuited second coil.
Ideal
Transformer
(a) (b)
Fig. 6-4 Transformer with load connected to the secondary winding.
+ im
+ + +
Rhe jX m
V1 E1 E2 V2
− − − −
N1 N2
Ideal Transformer
Real Transformer
Fig. 6-5 Transformer equivalent circuit including leakage impedances and core losses.
(a) (b)
Fig. 6-6 Eddy currents in the transformer core.
Fig. 6-8 Transferring leakage impedances across the ideal transformer of the model.
© Copyright Ned Mohan 2006 89
Transformer Equivalent
Circuit in Per Unit
I (pu) I (pu)
Z tr (pu)
+ +
V p (pu) Vs (pu)
− −
(a ) (b)
Fig. 6-10 Winding connections in a three-phase system.
+ + + +
⎛ 1⎞
⎜ 1 − ⎟ YA
⎝ t⎠ V2
V1 V2 V1 ⎛ 1 1⎞
⎜ 2 − ⎟ YA
− − − ⎝t t⎠ −
1: t
(a ) (b)
Fig. 6-17 Transformer with an off-nominal turns-ratio or taps in per unit; t is real.
Thyristor
Power (VA)
IGCT
106
IGBT
104
Auto-
101 motive
Lighting
100
101 102 103 104
Device blocking voltage [V]
(a ) ( b)
Figure 7-2 Power semiconductor devices: (a) ratings (source: Siemens), (b) various
applications (source: ABB).
HVDC Line
AC1 AC2
Fig. 7-3 HVDC system – one-line diagram.
−
AC1 AC2 AC1 AC2
(a ) (b)
320MW
2000MW
150MW 350MW
1620MW 2138MW
312MW
370MW 200MW 690MW
500MW 1000MW
2000MW
200MW 1000MW
330MW
200MW
3100MW
100MW
200MW
1920MW
210MW
200MW 200MW
200MW 600MW
36MW
Fig. 7-5 HVDC projects, mostly current-link systems, in North America [source: ABB]
A P pn1
N pn2
(a) (b) G
G P
pn3
K N
+ Ls
+
(a ) vs vd R
−
−
vd
Vd
0
ωt
α is α
vs
( b)
0
iG ωt
0
ωt = 0 ωt
Fig. 7-8 Thyristor circuit with a resistive load and a series inductance.
+ van ia
ia − + 1
van 1 3 5
− + 3 P
Ls 5
vbn +
n − +
vd n Id vd
4 −
vcn
− + 6
+
2 N
4 6 2
−
−
(a) (b)
Fig. 7-9 Three-phase Full-Bridge thyristor converter.
Vdo 0
0 t ωt
(b) (c)
Aα
0 ωt
α
v Nn
ia
1 1
0 ωt
4 4
ib
3
0 ωt
6 6
ic
5 5
0 ωt
2
0 ωt
α
vPn
ia 1
1
0 ωt
4 4
ib 3
3
0 ωt
6
ic
5
0 ωt
2
2
© Copyright Ned Mohan 2006Fig. 7-12 Waveforms in the inverter mode. 112
DC-Side Voltage as a
Function of Delay Angle
Vd Vd Rectifier
P = Vd I d = +
1800
0 0
90 0 0 α Id
160
Inverter
P = Vd I d = −
(a ) ( b)
Fig. 7-13 Average dc-side voltage as a function of α .
0 ωt
u v Nn
ia
1 1
0 ωt
4 4
−φ1
I a1 −φ1
I a1
(a ) (b)
Fig. 7-15 Power-factor angle.
ia (Y − Δ )
(a ) ( b)
Fig. 7-17 Six-pulse and 12-pulse current and voltage waveforms [2].
+ Rd Ld −
AC 1 vd 1 vd 2 AC 2
− +
Rectifier characteristic
in a current-control mode
0
I d , ref Id
Fig. 7-19 Control of an HVDC system [3].
Fig.Mohan
© Copyright Ned 7-20 Voltage-link
2006 HVDC transmission system [source: ABB]. 120
Voltage-Link HVDC
System Block Diagram
+
−
AC1 AC2
P1 , Q1 P2 , Q2
(a ) ( b) (c)
Fig. 7-22 Block diagram of a voltage-link converter and the phasor diagram.
0 ωt
vaN
Vd
Vˆa
0.5Vd
0 ωt
Fig. 7-24 Sinusoidal variation of turns-ratio d a .
+
ida ia
+
ia Vd
Vd
a +
+ vaN
vaN
− − − −
N
qa
qa qa−
(a) (b)
Fig. 7-26 Realization of the ideal transformer functionality.
0 vaN
vaN
0 vaN ωt
0
Ts
(a )
Vh
f1 fs 2 fs 3 fs
( b)
Fig. 7-27 PWM to synthesize sinusoidal waveform.
© Copyright Ned Mohan 2006 127
CHAPTER 8
13.8kV ±120V
House2
Transformer
±120V
House 3
kW Load
(MW)
12 6 12 6 12
AM NOON PM percentage of the time
Time 0 100%
(a) (b)
(a ) ( b)
Fig. 8-3 Utility loads.
Load
Vd
Utility −
Fig. 8-4 Voltage-link-system for modern and future power-electronics based loads.
Fig. 8-5 Per-phase, steady state equivalent circuit of a three-phase induction motor.
f5 f4 f3 f2 f1
Load
Torque
0 ωm
ωslip ωsyn
3 3
ωslip ωsyn
1 1
− HF transformer
Energy
Storage
Load
Feeder 2
STATCOM
Fig. 8-13 STATCOM [4].
+ Vs
vs φ
−
Is
(b)
(a)
Figure 8-14 Voltage and current phasors in simple R-L circuit.
0 t 0 t
φ1 / ω
( b)
T1
(a )
Figure 8-15 Current drawn by power electronics equipment without PFC.
(b) 0 t
idistortion
I
(c) t
0
−I
© Copyright Ned Mohan 2006 Figure 5-4 Example
Figure 8-16 5-1.
Example 8-1. 145
Influence of Distortion on
Power Factor
1
0.9
0.8
0.7
PF
DPF 0.6
0.5
0.4
+ +
Vs Vs
− −
(a) (b)
Figure 8-185-6
Figure (a)(a)Utility
UtilitySupply, (b)short
supply; (b) Short-Circuit Current.
circuit current.
SYNCHRONOUS
GENERATORS
Heat in Water
Boiler Turbine Gen
H Penstock
Generator
Turbine
Pump Condenser Heat out
(a ) (b)
Fig. 9-1 Synchronous generators driven by (a) steam turbines, and (b) hydraulic turbines.
(a) (b)
N S N N S S
2π / 3 2' 6' ia
θ
a − axis
2π / 3 ia 1' 7'
7 1 ia
ic
6 2
c − axis 5 3
4
(a) (b)
a − axis
a ∠0 o ia
a ' ia a
c'
ic
c ic
c
c − axis (a) (b)
∠240 o
Fig. 9-5 Connection of three phase windings.
ωsyn
a-axis
a-axis
ea
ωsyn
S
−
Fig. 9-7 Current direction and voltage polarities; the rotor position shown induces
maximum ea .
2π / 3
e j0
2π / 3
a − axis Re a-axis
2π / 3
ia
900 θ θ
ic G
Ea , AR
Ia B AR (at t = 0)
c − axis
4π
j
e 3
(a ) (b ) (c)
Fig. 9-9 Armature reaction due to phase currents.
Ea
−
− −
Ia
(a) (b )
0 δ1 δ 2 90 o δ 0 90 o δ
(a ) (b)
Fig. 9-12 Steady state stability limit.
δ δ Va I aq { δ Ia
⎧
Ia Va ⎪ Va
I aq ⎨ Ia
⎪⎩
90 o
(a ) ( b) (c)
Fig. 9-13 Excitation control to supply reactive power.
Synchronous
Condenser
Fig. 9-14 Synchronous Condenser.
ac input output
Generator
slip rings
ac regulator
(a ) ( b)
Fig. 9-17 Armature (a) and field current (b), after a sudden short circuit [source: 4].
Eaf' jX s I a
− +
Im + jX s I a
+
Eaf'' jX s' I a
jX s' I a Eaf jX s'' I a
Eaf' Ea
jX s'' I a
Re Eaf''
Ea −
−
(a ) Ia
(b)
Fig. 9-18 Synchronous generator modeling for transient and sub-transient conditions.
VOLTAGE REGULATION
AND STABILITY IN
POWER SYSTEMS
− − −
x Vx
(a) (b)
Fig. 10-3 Voltage profile along the transmission line.
jX L PF = 1
0.8
PF = 0.9
0.6
(lagging) PF = 0.9
(leading)
PR + jQR 0.4
(a )
0.2
0
0 0.5 1 1.5 2 2.5 3 3.5
PR / SIL
( b)
Fig. 10-4 Voltage collapse in a radial system (example of 345-kV line, 200 km long).
0
P
VTh Vbus
Vbus
− Vbus jX Th I
−
VTh
(a)
(b)
Fig. 10-6 Effect of leading and lagging currents due to the shunt compensating device.
1 IC
jωC
IC 0
(a ) ( b)
Fig. 10-7 V-I characteristic of SVC.
IL iL
iL
α ≤ 900
α > 900
0 IL
(a ) ( b) (c )
(a ) ( b)
Fig. 10-10 STATCOM.
Linear
Range
capacitive 0 inductive I
conv
(a ) (b) (c)
Fig. 10-12 Thyristor-Controlled Series Capacitors (TCSC) [source: Siemens Corp.].
TRANSIENT AND
DYNAMIC STABILITY OF
POWER SYSTEMS
Pm
during-fault
XL
δ Pm Pe
0 δ 0 δ1 π
(a ) (b)
Fig. 11-2 Power-angle characteristics.
5 0
4 5
4 0
3 5
3 0
2 5
2 0
0 0 .2 0 .4 0 .6 0 .8 1 1 .2 1 .4
Pre-fault
post-fault
C
Pe = Pm
D
0 δm π
δ2
δ1 δ
0 δ 0 δ1 δ crit δ max π δ
Fig. 11-6 Critical clearing angle.
25
20 B post-fault
Pe = Pm 15
10 A
during fault
5
0
0 20 40 60
δ 0 = 22.470 δ cA =80750 100
δ m 120 1400
= 115.28 160 180
Fig. 11-7 Power angle curves and equal-area criterion in Example 11-2.
Pm , k = Pe, k
ωk and δ k
Pm , k and Ek' held constant Phasor Calculations
Electro-dynamic Pe , k using Ek' ∠δ k
differential (load may be assumed
Equations as a constant impedance)
Fig. 11-8 Block diagram of transient stability program for an n-generator case.
Pm1 Pe1
Bus-2
Pe 2
Pm 2
7 0 0
6 0 0
5 0 0
4 0 0
3 0 0
δ1
2 0 0
1 0 0 δ2
0
0 0 .2 0 .4 0 .6 0 . 8 1 1 .2 1 .4 1 .6
Fig. 11-11 Growing Power Oscillations: Western USA/Canada system, Aug 10, 1996 [4].
CONTROL OF
INTERCONNECTED
POWER SYSTEM AND
ECONOMIC DISPATCH
ac input output
Generator
slip rings
ac regulator
(a ) ( b)
Fig. 12-2 (a) The Interconnections in North America, (b) Control Areas [Source: 2]
Turbine G
Pm
Pm Pe PLoad
0 ΔPm Pm
(a ) (b)
Pm 2
Pm1
0 Pm
Pm1 Pe1 PLoad ΔPm1 ΔPm 2
(a ) (b)
Fig. 12-4 Response of two generators to load-frequency control.
1
B
R
Supplementary
Controller
+ −
k − Change in Steam Valve Position
Governor
s
+ ACE
(Area Control Error)
Fig. 12-6 Area Control Error (ACE) for Automatic Generation Control (AGC).
Area 1 Area 2
Pm1 Pe1 Load
P1− 2 M
Bus-2
Pe 2
Pm 2
Fig. 12-7 Two control areas in the example power system with 3 buses.
1
B1 ΔPLoad 1
R1
+ − −
K1 1 − 1 1 + ωsyn sΔδ1
ACE1 s Ts1s + 1 ΔPs1 TG1s + 1 ΔPv1 TS 1s + 1 M 1s + D1
+ Regulator Governor Steam Turbine
ΔPm1 − Area 1 1
s
Δδ1 +
ΔP12 = T12 ( Δδ1 − Δδ 2 ) ( Δδ 1 − Δ δ 2 )
T12
Δδ 2 −
1
− + s
K2 1 ΔPs 2 1 ΔPv 2 1 ΔPm 2 ωsyn
ACE 2 s Ts 2 s + 1 − TG 2 s + 1 TS 2 s + 1 + − M 2 s + D2 s Δδ 2
+ −
Regulator Governor Steam Turbine Area 2
1
B2 ΔPLoad 2
R2
1/ ωsyn
Fig. 12-10 Two-area system with AGC. Source: adapted from [6].
© Copyright Ned Mohan 2006 204
Results of Simulink
Modeling Following a Step
Load Change in Control
Area 1
1.5
ΔPm1
ΔPm 2
0.5
-0.5
ΔP12
-1
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000
Fig. 12-11 Simulink results of the two-area system with AGC in Example 12-3.
9.0
0 20 40 60 80 100 P [ MW ]
ΔCi
ΔPi
0 0
(a ) Pi [ MW ] Pi [ MW ]
( b)
Fig. 12-13 (a) Fuel cost and (b) Marginal cost, as functions of the power output.
0 0 0
P1 P P2 P P3 P
TRANSMISSION LINE
FAULTS, RELAYING AND
CIRCUIT BREAKERS
I c0 I
Ic I c1 b0
I a1 Ia2 Ia0
I b2
Ib
Ic2
I b1
Fig. 13-2 Sequence components.
+ + I a1 + Ia2 + Ia0
Ea1 Va1 Va 2 Va 0
− − − −
Zf Ia0
g Z0 +
Va 0
(a )
−
( b)
(a) ( b) (c)
Fig. 13-8 Path for zero-sequence currents in transformers.
Zn 3Z n Va 0
−
(a ) ( b)
Fig. 13-9 Neutral grounded through an impedance.
X Line1 = 0.10 pu
′′ 1 = 0.12 pu
X gen Bus-1 X Line 2 = 0.10 pu PLoad = 1 pu
Bus-3
X gen 2 = 0.12 pu X tr1 = 0.10 pu X Line 0 = 0.20 pu QLoad = 0
X gen 0 = 0.06 pu X tr 2 = 0.10 pu
X tr 0 = 0.10 pu
Fig. 13-10 (a) One-line diagram of a simple power system and bus voltages.
−
−
Fig. 13-12 Sequence networks for calculating fault current due to SLG fault on bus-2.
Pm1 Pe1
Bus-2
Pe 2
Pm 2
PT R
Burden
(b)
(a)
Fig. 13-15 Current Transformer (CT) [5].
(a) (b)
CT
CT
Relay
PT R
instantaneous
A B C
+ i (t ) 0 .5
vs ( t ) v (t ) 00
− - 0 .5
−
-1
0 0 .05 0.1 0 .15 0 .2
(a ) (b)
Fig. 13-26 Current in an RL circuit.
TRANSIENT OVER-VOLTAGES,
SURGE PROTECTION AND
INSULATION COORDINATION
0.5I peak
t[ μ s ]
t1 t2
(a ) (b)
vc L
C
(a )
( b)
Fig. 14-3 Over-voltages due to switching of transmission lines.
Fig. 14-4 Frequency dependence of the transmission line parameters [Source: 2].
0.5 V pe ak
0 1 .2 μ s 40 μ s t