You are on page 1of 5

Building: Office Building XYZ

Date of Lighting Audit: 15-Aug-16

Basement W QTY Aug-16


CFL 13 4 no. of saturdays 4
Flood Lights 57 14 no. of working days 23
4 Ft Linear T8 32 250
8 Ft Linear T8 59 80

Stairwells W QTY Peak Lighting Demand


4 Ft Linear T8 32 64 lights W
CFL 13
First Floor W QTY flood lights 57
4 Ft Linear T8 32 698 2 ft linear T8 17
Pot Lights 50 40 4 ft linear T8 32
8 ft linear T8 59
Second Floor W QTY pot lights 50
4 Ft Linear T8 32 962 peak demand(kW)
2 Ft Linear T8 17 256

Third Floor W QTY


4 Ft Linear T8 32 690

Fourth Floor W QTY


4 Ft Linear T8 32 1038

Monthly
Total
Fixture Type Usage W Quantity savings(kWh)
(kWh)
(hrs)
pot lights 269 23 40 247.48 437

Peak Lighting Demand


lights W
CFL 7
flood lights 27
2 ft linear T8 9
4 ft linear T8 15
8 ft linear T8 28
pot lights 23
peak demand(kW)
Base Model

Basement W QTY Tot Watts hours/day


CFL 13 4 52 11
Flood Lights 57 14 798 11
4 Ft Linear T8 32 250 8000 11
8 Ft Linear T8 59 80 4720 11

ak Lighting Demand Stairwells W QTY Tot Watts hours/day


quantity demand(kW) 4 Ft Linear T8 32 64 2048 11
4 0.05
14 0.8 First Floor W QTY Tot Watts hours/day
256 4.35 4 Ft Linear T8 32 698 22336
3702 118.46 Pot Lights 50 40 2000 24
80 4.72
40 2 Second Floor W QTY Tot Watts hours/day
mand(kW) 130.38 4 Ft Linear T8 32 962 30784 11
2 Ft Linear T8 17 256 4352 11

Third Floor W QTY Tot Watts hours/day


4 Ft Linear T8 32 690 22080 11

Fourth Floor W QTY Tot Watts hours/day


4 Ft Linear T8 32 1038 33216 11

Peak Demand 130386

vings(kWh)

Retrofit Model
Basement W QTY Tot Watts hours/day
ak Lighting Demand CFL 7 4 28 11
quantity demand(kW) Flood Lights 27 14 378 11
4 0.03 4 Ft Linear T8 15 250 3750 11
14 0.38 8 Ft Linear T8 28 80 2240 11
256 2.3
3702 55.53 Stairwells W QTY Tot Watts hours/day
80 2.24 4 Ft Linear T8 15 64 960 11
40 0.92
mand(kW) 61.4 First Floor W QTY Tot Watts hours/day
4 Ft Linear T8 15 698 10470
Pot Lights 23 40 920 24
Second Floor W QTY Tot Watts hours/day
4 Ft Linear T8 15 962 14430 11
2 Ft Linear T8 9 256 2304 11

Third Floor W QTY Tot Watts hours/day


4 Ft Linear T8 15 690 10350 11

Fourth Floor W QTY Tot Watts hours/day


4 Ft Linear T8 15 1038 15570 11

Peak Demand 61400


days/week hours/week monthly usage(hours) monthly usage(kwh)
5 55 253 13.156
5 55 253 201.894
5 55 253 2024
5 55 253 1194.16

days/week hours/week monthly usage(hours) monthly usage(kwh)


5 55 253 518.144

days/week hours/week monthly usage(hours) monthly usage(kwh)


59 269 6008.384
7 168 744 1488

days/week hours/week monthly usage(hours) monthly usage(kwh)


5 55 253 7788.352
5 55 253 1101.056

days/week hours/week monthly usage(hours) monthly usage(kwh)


5 55 253 5586.24

days/week hours/week monthly usage(hours) monthly usage(kwh)


5 55 253 8403.648
Total Monthly Estimated Lighting (KWh ) = 34327.034

Total Yearly Estimated Lighting (KWh ) = 411924.408

days/week hours/week monthly usage(hours) monthly usage(kwh)


5 55 253 7.084
5 55 253 95.634
5 55 253 948.75
5 55 253 566.72

days/week hours/week monthly usage(hours) monthly usage(kwh)


5 55 253 242.88

days/week hours/week monthly usage(hours) monthly usage(kwh)


59 269 2816.43
7 168 744 684.48
days/week hours/week monthly usage(hours) monthly usage(kwh)
5 55 253 3650.79
5 55 253 582.912

days/week hours/week monthly usage(hours) monthly usage(kwh)


5 55 253 2618.55

days/week hours/week monthly usage(hours) monthly usage(kwh)


5 55 253 3939.21

Total Monthly Estimated Lighting (KWh ) = 16153.44

Total Yearly Estimated Lighting (KWh ) = 193841.28