You are on page 1of 102

High Voltage Surge Arresters:

Design & Application


HVSA: Design & Application
Agenda
Purpose of Surge Arresters in Electrical Systems
Overvoltage Conditions – Short Review
Proper selection of Surge Arresters for protection of the Electrical System
• Selection of the Arrester’s Characteristics
• Insulation Withstand Level: Selection and Evaluation
• Evaluation of the Insulation Coordination: Insulation Coordination using
Deterministic Method - Short Review
Surge Arresters application
• Transmission Line Arresters
• Station Arresters
Station Arresters for substations: Design & Technology
• Classification of the arresters design
• Design A - porcelain and tube design
• Design B – wrapped and cage design
Purpose of Surge Arresters in electrical
systems
Arresters are used to protect
electrical equipment and power
systems against transient
overvoltages (lightning and
switching) by reducing their
electrical stress to values lower than
the withstand voltage of the
equipment / power systems.

This protects the equipment / power


system from damage and / or
failures in the insulation of the
equipment / power systems after the
overvoltage condition’s occurrence.
Overvoltage conditions: short review

Definition – IEC 60.071-1 – Edition 8.0 / 2006:


• Any voltage between one phase conductor and earth or across a longitudinal
insulation having a peak value exceeding the peak of the highest voltage of the
system divided by 3 or between phase conductors having a peak value
exceeding the peak of the highest voltage of the system.

Classification:
• According to their shape and duration, voltage and overvoltages are divided in the
following classes:
• Continuous
• Temporary Overvoltage
• Transient Overvoltage
Overvoltage conditions: short review

Temporary Overvoltage:
• An oscillatory phase-to-ground or
phase-to-phase overvoltage of
relatively long duration. May be
undamped or weakly damped and
in some cases its frequency may be
several times smaller or higher than
power frequency.

• Temporary overvoltages usually


originate from:
• Switching Operations
• Faults (Short Circuit)
• Load Rejection
• Ferro resonance Effects
• Ferranti Effect
Overvoltage conditions: short review

Transient Overvoltages:
• Short Duration Overvoltage of few milliseconds or less, oscillatory or non-
oscillatory, usually highly damped.
• Slow-Front Overvoltage (usually associated with switching)
• Fast-Front Overvoltage (usually associated with lightning)
• Very Fast-Front Overvoltage (GIS and very fast events)
• Combined Overvoltage
Overvoltage conditions: short review

Continuous (Power Frequency) Temporary Transient (Slow, Fast and Very Fast Fronts)

Combined
Purpose of Surge Arresters in electrical
systems
Proper selection of Surge Arresters for
the protection of the electrical systems
Selection of the Arrester’s Characteristics

Selection and Evaluation of the Insulation Withstand Levels for proper


Equipment Protection

Evaluation of the Insulation Coordination


Insulation Withstand Levels
Selection and Evaluation
Selection of the Arrester’s Characteristics
• Steady State Condition – MCOV and Rated Voltage
• Protective Characteristics – Residual Voltage Levels
• Energy Requirements
• Environmental Conditions
• Short-circuit requirements
• Mechanical requirements

Selection and Evaluation of the Insulation Withstand Levels for proper


Equipment Protection

Evaluation of the Insulation Coordination


Insulation Withstand Levels
Selection and Evaluation
Lightning Impulse Withstand Voltage (BIL)
Switching Impulse Withstand Voltage (BSL)
LIWV & SIWV may be expressed as either Statistical or Conventional

Conventional Withstand Voltage: the peak voltage that an insulation system


is capable of withstanding without failure or disruptive discharge under
specified test conditions being applicable specifically to non-self-restoring
insulations.

Statistical Withstand Voltage: the peak voltage that an insulation is capable


of withstanding with a given probability of failure being applicable specifically
to self-restoring insulations.
Insulation Withstand Levels
Selection and Evaluation
Insulation Withstand Levels
Selection and Evaluation

IEC 60071-1 – Edition 8.0 / 2006


Insulation Withstand Levels
Selection and Evaluation

ANSI IEEE Std. 1313.1 / 1996


Evaluation of the Insulation Coordination

Selection of the Arrester’s Characteristics


• Steady State Condition – MCOV and Rated Voltage
• Protective Characteristics – Residual Voltage Levels
• Energy Requirements
• Environmental Conditions
• Short-circuit requirements
• Mechanical requirements

Selection and Evaluation of the Insulation Withstand Levels for proper


Equipment Protection

Evaluation of the Insulation Coordination


Insulation Coordination
Deterministic method: short review

Distance → VT
Maximum magnitudes of the transient overvoltages on the terminals of the
equipment protected are calculated taking into account the Surge Arrester’s
protective levels and the distance effect (electrical distance) among the
arrester and the protected equipment.
Insulation Coordination
Deterministic method: short review
Insulation Coordination is the process of bringing the insulation strengths of
electrical equipment into the proper relationship with expected overvoltages
and with the characteristics of surge-protective devices.

Consists in the
selection of insulation
strength consistent
with the expected
overvoltages to
obtain an acceptable
risk of failure.
Insulation Coordination
Deterministic method: short review
Protective Margin:
CWV LIWV SIWV
PM 1  PM 2  PM 3 
FWPL  V1 LIPL  V2 SIPL

CWV Chopped Wave Voltage of the equipment


FWPL Front of Wave Protective Level of the arresters
LIWV Lightning Impulse Withstand Voltage of the equipment (BIL)
LIPL Lightning Impulse Protective Level of the arrester
SWIV Switching Impulse Withstand Voltage of the equipment (BSL)
SIPL Switching Impulse Protective Level of the arrester

V Additional voltage due to the electrical distance between the


arrester and the protected equipment
Insulation Coordination
Deterministic method: short review
Methods for evaluating the Distance Effect

• Simplified Method

• IEC Method: IEC 60.099-5

• ANSI IEEE Std. Method: ANSI C62.22

• Computational Simulation Method: Usually more realistic, but the final results
depend strongly on the models and the parameters used
Insulation Coordination
Deterministic method: short review

LIWV - BIL
PM ≥ 1,20
VMAX
LIPL SA
SIWV - BSL
PM ≥ 1,15
VMAX
SIPL SA

VMAX t   VRES t   V t 
Proper selection of Surge Arresters for
protection of the electrical systems
To reduce the electrical distance among surge arresters and the protected
equipment in special power transformers, place the surge arresters as closer
as possible to the protected equipment.

• Possibility of increasing the Protective Margin (MP).

• Possibility of reducing the Insulation Withstand Voltage.

Arrester as an integral part of the Protected Equipment


Proper selection of Surge Arresters for
the protection of the electrical systems
Proper selection of Surge Arresters for
the protection of the electrical systems

CHESF – Brazil
245 kV System
Proper selection of Surge Arresters for
the protection of the electrical systems

Kazakhstan
242kV System
Surge Arresters: application
Substations Distribution Networks Transmission Lines
Station Arresters

Installed to protect both self-restored and non-self-restored equipment from


the substation against transient overvoltages due to lightning and switching
events preventing damage in the insulation of those equipment.

Usually specified with lower protective levels as compared with Transmission


Line Arresters.

Energy requirements for station arresters usually higher than the


requirements for Transmission Line Arresters.
Station Arresters for substations
Design & Technology

Porcelain Polymeric
Station Arresters for substations
Design & Technology
Classification of arresters designs
Design A:

• Arresters have a design in which a gas channel runs along the entire
length of the arrester unit and fills ≥ 50 % of the internal volume not
occupied by the internal active parts.

• Typically, “Design A” arresters are porcelain housed arresters and polymer


housed arresters with a composite hollow insulator, which are usually
equipped with pressure relief devices.
Station Arresters for substations
Design & Technology – Design A

Porcelain Polymeric
ZnO Arresters: design and technology
Porcelain arresters
ZnO Arresters: design and technology
Porcelain arresters
ZnO Arresters: design and technology
Porcelain arresters – Short-circuit test
ZnO Arresters: design and technology
Porcelain arresters – Short-circuit test
ZnO Arresters: design and technology
Porcelain arresters – Short-circuit test
ZnO Arresters: design and technology
Porcelain arresters
MAA: up to 198 kV rating
• IEC Class 2 – 4.5 kJ / kV rating

MCA: up to 360 kV rating


• IEC Class 3 – 8.75 kJ / kV rating

MDA: up to 420 kV rating


• IEC Class 4 – 11.0 kJ / kV rating

MEA: up to 640 kV rating


• IEC Class 5 – 13.0 kJ / kV rating
ZnO Arresters: design and technology
Porcelain arresters
ZnO Arresters: design and technology
Porcelain arresters
ZnO Arresters: design and technology
Polymeric arrester: tube design

1 Polymeric housing
(Silicone, EPDM or
blends
EPDM/Silicone)
2 Fiber Reinforced
Tube (FRT)
3 Mettalic flanges
4 ZnO disks
5 Air spacing inside
the arrester
Station Arresters for substations
Polymeric arrester: tube design
Station Arresters for substations
Polymeric arrester: tube design

420 kV rating - EnBW - Germany


Station Arresters for substations
Design & Technology
Classification of arresters designs
Design B:

• Arresters are of a solid design with no enclosed volume of gas or having


an internal gas volume filling < 50 % of the internal volume not occupied by
the internal active parts.

• Typically, “Design B” arresters are polymer housed arresters which do not


have any pressure relief device and are of a solid type with no enclosed
volume of gas.
Station Arresters for substations
Design & Technology – Design B

Porcelain Polymeric
ZnO Arresters: design and technology
Polymeric arrester: wrapped design

1 Polymeric housing
(Silicone, EPDM or
blends
EPDM/Silicone)
2 Fiber Reinforced
Tube (FRT)
3 Mettalic flanges
4 ZnO disks
5 Air spacing inside
the arrester
ZnO Arresters: design and technology
Polymeric arrester: wrapped design

Slipped over process molded on process


ZnO Arresters: design and technology
Polymeric arrester: wrapped design
FRP material directly wrapped onto MO stack

Outer housing slipped over or molded on (SR, EPDM, EPDM/SR blends)

Most economical design: lowest market prices


Short-circuit performance better than for porcelain
Lightweight; easy to handle

Limited mechanical strength (diameter of housing, wall thickness)


Big differences in performance (e.g. with regard to moisture ingress, short-
circuit performance) depending on design variants and implementation
Multi-unit arresters even for lower system voltages (radial fields)
ZnO Arresters: design and technology
Polymeric arrester: wrapped design

110 kV Sytem - Estonia SGD&E - USA – 69 kV System


ZnO Arresters: design and technology
Polymeric arrester: cage design

1 Polymeric housing
(Silicone, EPDM or
blends
EPDM/Silicone)
2 Fiber Reinforced
Tube (FRT)
3 Mettalic flanges
4 ZnO disks
5 Air spacing inside
the arrester
ZnO Arresters: design and technology
Polymeric arrester: cage design

Loops + bondage Rods


ZnO Arresters: design and technology
Polymeric arrester: cage design
FRP rods or loops form an open cage around the MO stack
Outer housing directly molded onto the MO stack (silicone rubber)
The cage design is a higher performance arrester as compared with wrapped
design.

Economical design; low market prices


Short-circuit performance better than for porcelain
Mechanical strength usually higher than for wrapped design
Lightweight; easy to handle

Limited mechanical strength (diameter; mechanical strength of MO blocks) as


compared with tube design.
ZnO Arresters: design and technology
Polymeric arrester: cage design
ZnO Arresters: design and technology
Polymeric arrester: cage design
ZnO Arresters: design and technology
Polymeric arrester: cage design
Short-circuit performance

1. Arrester has failed and gas begins to


be expelled through the housing.

2. The gas streams trigger an external


flashover and the internal arc is
commutated to the outside
ZnO Arresters: design and technology
Polymeric arrester: cage design
Short-circuit performance
ZnO Arresters: design and technology
Polymeric arrester: cage design
Short-circuit performance
Station Arresters for substations
Design & Technology – Design B

55
ZnO Arresters: design and technology
Polymeric arrester: cage design
Bending Moment Test: 1,000 cycles - SLL
ZnO Arresters: design and technology
Polymeric arrester: cage design
Bending Moment Test: 1,000 cycles - SLL
ZnO Arresters: design and technology
Polymeric arrester: cage design
Bending Moment Test: SLL Application
ZnO Arresters: design and technology
Polymeric arrester: cage design
Bending Moment Test: SLL Application
ZnO Arresters: design and technology
Polymeric arrester: cage design
Bending Moment: Thermal cycle 96 h
ZnO Arresters: design and technology
Polymeric arrester: cage design
Bending Moment: Thermal cycle 96 h
ZnO Arresters: design and technology
Polymeric arrester: cage design
Bending Moment: Thermal cycle 96 h
ZnO Arresters: design and technology
Polymeric arrester: cage design
Bending Moment: Boiling test - 42 h
ZnO Arresters: design and technology
Polymeric arrester: cage design
Seismic test: shake table – PCA3-120
ZnO Arresters: design and technology
Polymeric arrester: cage design
PAA: up to 132 kV rating
• IEC Class 2 – 4.5 kJ / kV rating
• IEEE – Intermediate Class – 5.2 kJ / kV MCOV – Energy Class B

PBA: up to 230 kV rating


• IEC Class 2 – 6.4 kJ / kV rating
• IEEE – Station Class – 7.5 kJ / kV MCOV – Energy Class D

PCA: up to 360 kV rating


• IEC Class 3 – 7.8 kJ / kV rating
• IEEE – Station Class – 9.5 kJ / kV MCOV – energy Class E
ZnO Arresters: design and technology
Series parallel HVSA
ZnO Arresters: design and technology
Surge counters
Selection of the arrester’s characteristics

Selection of the Arrester’s Characteristics


• Steady State Condition – MCOV and Rated Voltage
• Protective Characteristics – Residual Voltage Levels
• Energy Requirements
• Environmental Conditions
• Short-circuit requirements
• Mechanical requirements

Selection and Evaluation of the Insulation Withstand Levels for proper


Equipment Protection

Evaluation of the Insulation Coordination


Surge arrester’s characteristics
Lightning and switching
Contamination and overvoltages
environmental condition
Voltage

U rw
Temporary
overvoltages
Up
Continuous operating
voltage

Uc

t1
Time
Surge arrester’s characteristics
Surge arrester’s characteristics
MCOV and duty rating
Condition 1 - Selection of MCOV based on the Highest System Voltage

U max
Uc1 
3
Surge arrester’s characteristics
MCOV and duty rating
Condition 2 - Selection of MCOV based the Amplitudes of the Temporary
Overvoltages (TOV) and their Duration
• Temporary Overvoltage versus Time Capability for Surge Arrester

TOV
Uc2 
K2
TOV
K2 
MCOV
Surge arrester’s characteristics
MCOV and duty rating - Example
System Voltage (Phase-to-Phase)
• Rated Voltage: 230 kV
• Highest Voltage of the System: 242 kV
• Case 1 - Grounded System: TOV = 181.6 kV (1.3 pu) at 1 s
• Case 2 – Non-effectively Grounded System: 193.6 kV at 1 s
• Case 3 - High Impedance System: TOV = 216.6 kV (1.55 pu) at 1 s
• Case 4 – Ungrounded System: TOV = 242 kV (1.73 pu) at 1 s
Surge arrester’s characteristics
MCOV and duty rating - Example
System Voltage (Phase-to-Phase)
• Rated Voltage: 230 kV
• Highest Voltage of the System: 242 kV

Um
Uc1  MCOVmin 
3

242
Uc1   139.7kV
3
Surge arrester’s characteristics
MCOV and duty rating - Example
System Voltage (Phase-to-Phase)
• Rated Voltage: 230 kV
• Highest Voltage of the System: 242 kV
• Case 1 - Grounded System: TOV = 181.6 kV (1.3 pu) at 1 s

TOV
Uc2 
K2
181.6
Uc2   122.7kV
1.48
Surge arrester’s characteristics
MCOV and duty rating - Example
System Voltage (Phase-to-Phase)
• Rated Voltage: 230 kV
• Highest Voltage of the System: 242 kV
• Case 2 - Non-effectively Grounded System: 193.6 kV at 1 s

TOV
Uc2 
K2

193.6
Uc2   130.8kV
1.48
Surge arrester’s characteristics
MCOV and duty rating - Example
System Voltage (Phase-to-Phase)
• Rated Voltage: 230 kV
• Highest Voltage of the System: 242 kV
• Case 3 - High Impedance System: TOV = 216.6 kV (1.55 pu) at 1 s

TOV
Uc2 
K2
216.6
Uc2   146.4kV
1.48
Surge arrester’s characteristics
MCOV and duty rating - Example
System Voltage (Phase-to-Phase)
• Rated Voltage: 230 kV
• Highest Voltage of the System: 242 kV
• Case 4: Ungrounded System: TOV = 242 kV (1.73 pu) at 1 s

TOV
Uc2 
K2
242
Uc2   163.5kV
1.48
Surge arrester’s characteristics
MCOV and duty rating - Example
Summary of the Results:

System Voltage (Phase-to-Phase)


• Rated Voltage: 230 kV
• Highest Voltage of the System: 242 kV
• Case 1 - Uc1 = 139.7 kV / Uc2 = 122.7 kV ▬ Uc = 144 kV
• Case 2 - Uc1 = 139.7 kV / Uc2 = 130.8 kV ▬ Uc = 144 kV
• Case 3 - Uc1 = 139.7 kV / Uc2 = 146.4 kV ▬ Uc = 152 kV
• Case 4 - Uc1 = 139.7 kV / Uc2 = 163.5 kV ▬ Uc = 180 kV
Surge arrester’s characteristics
MCOV and duty rating - Example
System Voltage (Phase-to-Phase): 230 kV
Highest Voltage of the System: 242 kV

• Grounded System: Uc = 144 kV / Ur = 180 kV


• Non-effectively Grounded System: Uc = 144 kV / Ur = 180 kV
• High Impedance System: Uc = 152 kV / Ur = 192 kV
• Unearthed System: Uc = 180 kV / Ur = 228 kV

Higher MCOV and rated voltage means higher residual voltage across the
surge arrester.
Surge arrester’s characteristics
MCOV and duty rating - Example
Grounded System: PCA33-180

High Impedance System: PCA33-192

Unearthed System: PCA33-225


Surge arrester’s characteristics
MCOV and duty rating - Example

• For same arrester design, it is


URATED possible to reduce the surge
arrester’s protective levels by
reducing the arrester’s MCOV and
rated voltage.
MCOV

TOV SA TOV 2
TOV 1
MCOV
VMAX
Surge arrester’s characteristics
Arrester classification
ANSI IEEE Std. 62.11
• Intermediate Class Arrester - Classifying current: 5 kA
These arresters are designed for moderate-duty and for maximum system voltages of
169 kV and below.
• Station Class Arrester – Classifying current: 10 kA / 15 kA / 20 kA
These arresters are designed for heavy-duty applications. They have the widest range
of ratings, the lowest protective characteristics, and the most durability.

IEC 60.099-4
• Transmission Line Discharge Class: 1 - 5
• Nominal Discharge Current 10 kA: Class 1, 2 & 3
• Nominal Discharge Current 20 kA: Class 4 & 5
Surge arrester’s characteristics
Energy requirements
To define Surge Arrester Energy Capability
• ANSI IEEE Std. C62.11: Station or Intermediate Class
• IEC 60.099-4: Transmission Line Discharge Class

Lightning Requirements

Switching Requirements
• Closing and Re-closing of Long Lines
• Switching of Capacitor Banks and Cables
• Switching of reactors
Surge arrester’s characteristics
Energy requirements
Closing and reclosing of TL
Surge arrester’s characteristics
Energy requirements
Closing and reclosing of TL

 2 U ps  U L  U ps 
Td
E ARR
Z0

EARR Energy absorbed by the arrester (kJ)


Ups Residual voltage for swtching impulse (kV)
UL Overvoltage along the transmisison line (kV)
Td Propagation time of the electromagnetic waves (µs)
Z0 Transmission Line Surge Impedance (Ω)
Surge arrester’s characteristics
Energy requirements
Closing and reclosing of TL

Highest System Surge Impedance Overvoltage


Voltage (kVrms) (Ω) (pu)
Um ≤ 145 450 3.0
145 < Um ≤ 362 400 3.0
362 < Um ≤ 525 350 2.6
Um > 525 300 2.2
Surge arrester’s characteristics
Energy requirements
Closing and reclosing of TL
Example:
• 72.5 kV transmission line with 200 km length
• Surge Impedance: 450 Ω
• Overvoltage: 3.0 p.u. = 177.6 kVpeak
• Arrester model: PCA3-72
• Residual voltage at 250 A: 133 kV
• Propagation time: 666.7 µs

E ARR  2 U ps  U L  U ps   2 133  177.6  133 


Td 666.7
 17.58kJ
Z0 450
Surge arrester’s characteristics
Energy requirements
Closing and reclosing of TL
Example:
• 230 kV transmission line with 450 km length
• Surge Impedance: 400 Ω
• Overvoltage: 3.0 p.u. = 592.8 kVpeak
• Arrester model: PCA33-192
• Residual voltage at 500 A: 372 kV
• Propagation time: 1,500 µs

 U  T  2  372  592.8  372 


1,500
E ARR  2 U ps L  U ps d
 616.0kJ
Z0 400

616.0 kJ
E ARR  616.0kJ   4.05
152 kV MCOV
Surge arrester’s characteristics
Energy requirements
Closing and reclosing of TL

From the graphic: Ups = 128 kV and Idischarge = 105 A E = 17.92 kJ


Surge arrester’s characteristics
Energy requirements
Closing and reclosing of TL
600000

500000
Residual Voltage (V)

400000

300000

200000

100000

0
0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200
Discharge Current (A)

From the graphic: Ups = 375 kV and Idischarge = 550 A E = 618.8 kJ


Surge arrester’s characteristics
Energy requirements
Reevaluate the real conditions for the surge arresters regarding the energy
requirements during the occurrence of transient overvoltages.

Detailed studies have shown that in some cases is possible to reduce the
energy absorption capability required for the surge arresters, reducing costs
and optimizing the cost – benefit relationship.

Surge arresters must be defined based on the energy absorption capability


required instead of transmission line dicharge class.
Surge arrester’s characteristics
Protective Levels – Residual Voltages
To obtain the Surge Arrester Protective Levels

• ANSI IEEE Std. C62.11


• Normalized lightning impulse discharge voltage
• Normalized switching impulse discharge voltage
• Normalized front-of-wave discharge voltage

• IEC 60.099-4
• Steep Current Residual Voltage: 1 µs / Nominal Discharge Current - In
• Lightning Impulse Residual Voltage: 8/20 µs / 0.5.In, In, and 2.In
• Switching Impulse Residual Voltage: 30/60 µs / Discharge Current based on TLD Class
and Nominal Discharge Current
Surge arrester’s characteristics
Protective Levels – Residual Voltages
ANSI IEEE C62.11
• Normalized front-of-wave discharge voltage: 1 µs
• Lightning impulse classifying current value
Surge arrester’s characteristics
Protective Levels – Residual Voltages
ANSI IEEE C62.11
• Normalized lightning impulse discharge voltage - 8/20 µs
• 1.5 kA / 3.0 kA / 5.0 kA / 10.0 kA and 20.0 kA
• Classifyng current if different
Surge arrester’s characteristics
Protective Levels – Residual Voltages
ANSI IEEE C62.11
• Normalized lightning impulse discharge voltage - 8/20 µs
Surge arrester’s characteristics
Protective Levels – Residual Voltages
ANSI IEEE C62.11
• Normalized switching impulse discharge voltage
• Current impulse with a magnitude equal to the appropriate switching surge classifying
current(s)
Surge arrester’s characteristics
Other parameters to be selected
Environmental Conditions (Especially for Polymeric Arresters)
Contamination Issues
• Define the minimum leakage distance required
Short-Circuit Capability
• At Low Current
• At High Current
Mechanical considerations
• Bending Moment requirements
• Seismic requirements
Surge arrester’s characteristics
Pollution issues – Leakage distance
Highest system voltage: 242 kV

Arrester model PCA33-192


• Leakage distance: 285.4 inches or 7,250 mm

Contamination level 3 – IEC 60815:


• 1.705 in / kV or 43.3 mm / kV (phase-to-earth)
• 0.984 in / kV or 25.0 mm / kV (phase-to-phase)

Minimum leakage distance required: 0.984 * 242 = 238.1 inches


Surge arrester’s characteristics
Pollution issues – Leakage distance
Highest system voltage: 72.5 kV

Arrester model PBA3-72


• Leakage distance: 143 inches or 3632 mm

Contamination level 3 IEC 60.815:


• 43.3 mm / kV (phase-to-earth)
• 25.0 mm / kV (phase-to-phase)

Minimum leakage distance required: 43.3 * 41.9 = 1,812 mm (71.4 in)


Proper selection of Surge Arresters for
the protection of the electrical systems
VMAX t   VRES t   V t 
LIWV - BIL
MP ≥ 1,20
VMAX
LIPL SA
SIWL - BSL
MP ≥ 1,15
VMA
SIPL SA X

TOV capability
TOV SA
TOV system
1.3 – 2.0 pu
MCOV MCOV SA
1.0 pu VMAX
Proper selection of Surge Arresters for
the protection of the electrical systems
VMAX t   VRES t   V t 
825 kV - BIL
MP ≥ 1,20
687 kV
LIPL SA
685 kV - BSL
MP ≥ 1,15
595 kV
SIPL SA
382 kV – 1 kA

225 kV – 1 s
TOV SA
193.6 kV – 1 s
1.3 – 2.0 pu
MCOV 152 kV
1.0 pu 139.7 kV

You might also like