Professional Documents
Culture Documents
Annex 11 PDF
Annex 11 PDF
ANNEX 11
Extract of Design Summary Report for Tank Farm at Les Grandes Salines
10.2 Recommendations
The following are general principles and recommendations in relation to fire fighting at tank farms:
�Skilled personnel should be available at short notice 24 hours a day
�Personnel should be experienced in the operation of similar installations
�Operation of the tank farm should not to be interrupted due to false alarms and failures in automatic
systems
�Regular training of personnel in correct operating procedures should be provided
�Plant shall be well maintained and kept in good order
�Maintenance work including welding and cutting shall be done with appropriate precautions and
instructions (hot work permits and fire watch)
�Installed fire protection equipment shall be properly maintained and periodically tested
Page 1 of 5
Extract of Design Summary Report for Tank Farm at Les Grandes Salines
complete bunded area is extinguished. NFPA 11 recommends fixed foam pourers for common bunds
surrounding multiple tanks with poor access or less than 0.5 tank diameter spacings.
2
BS 5306 states a minimum application rate of 4 l/min/m and at least one 2600 l/min discharge device
2
(low or medium expansion foam) for each 450 m of bund area Discharge time is to be 60 minutes.
2
For the proposed bund size of 3851 m , nine discharge devices will be required.
In line with the principle that bund fires should be tackled in sections, the flow rate required for
tackling 25% of the bund surface area is we estimate that three of these would operate
3
simultaneously giving a maximum total flow rate of 231 m /h.
It is not recommended that tank cooling should be applied at the same time that bund fires are being
tackled, since the cooling water will interfere with the proper action of the foam.
Page 2 of 5
Extract of Design Summary Report for Tank Farm at Les Grandes Salines
The total number of site area hydrants shall be determined as part of the detailed design. An
appropriate number of them shall have spool pipe for monitor connection
10.13 Buildings
Page 3 of 5
Extract of Design Summary Report for Tank Farm at Les Grandes Salines
The fire alarm system shall consist of the following main components:
� a fire alarm centre including a supervision unit, a display unit, input and output terminal units, a
power supply unit, and a message transfer unit
�fire detectors and manual call points connected to the fire alarm centre
�alarm devices (bells, sirens, flashing lights) connected to the fire alarm centre
When designing the fire alarm system, the following basic principles shall be considered:
�The fire alarm centre shall be placed in, or the signals relayed to, a continuously manned room
�The supervised rooms should be divided into alarm zones to ease locating the fire
�
� Alarm bells, sirens and flashing lights must be situated so that they can be heard or seen
everywhere inside and where needed outside the buildings
�An average ambient sound level greater than 105 dBA shall require the use of a visible notification
appliances.
Page 4 of 5
Extract of Design Summary Report for Tank Farm at Les Grandes Salines
a line break or short circuit on the loop, the faulty section is isolated at the two closest disconnecting
devices. The other detectors on the loop will stay in contact with the fire centre along either end of the
loop Cable with copper wires (2x0.8 mm indoors and 4x0.8 mm in outdoor circuitries) that fulfil the fire
condition requirements of IEC 332-1 should be used.
Page 5 of 5