SEQUENTIAL

FUNCTIONAL EXTRACTION

POWDER SKID
PWD 2 x 1000 Kg
Ref. dwg. Nr. 9434-1 & 9434 – 2

Job N°9434
Customer : ENTRAC
P.O. N° 06 / 21

Ready to operate conditions

The READY TO OPERATE conditions are the following :

- Vessel filled with 1000 Kg of powder extinguisher


- N2 cylinders filled with 200 bar of nitrogen
- All the manual operated ball/butterfly valves, and the valves on the
cylinders CLOSED
- Pressure gauges at “ZERO”
- Flat hoses (pos.31) connected to the dedicated outlets of the vessel
OPERATION RESULT

Use the pull command device The high pressure fills the HP
(pos.34) manifold and the pressure
PROCEDURE
DETASSAGE

To open the N2 27 Lt (pos.1) reducer (pos.5) lowers the


cylinder valve pressure at max 10 bar.

Open the 3/4” valve (pos.27) N2 flows inside the vessel for
the detassage procedure

Pull the lever (pos.3) The high pressure fills the HP


manifold and the pressure
Or open the 1/4” valve (pos.28) reducer (pos.6) lowers the
pressure at max 12 bar.
To open the N2 50 Lt (pos. 2) The system is ready to
FIRE FIGHTING USE

cylinder valve pressurize the vessel

Open the pressurizing valve N2 flows inside the vessel


manually operated (pos.12) reaching the operating pressure

Open the delivery valve 11/2” Powder flows from the vessel
(pos.25) manually operated and feeds the flat hose (pos.31)

Open the delivery valve 3” Powder flows from the vessel


(pos.26) manually operated and feeds the monitor (pos.33)

Close the pressurizing valve


(pos.12)
Close the delivery valves
(pos.25/26)
CLEANING

Depressurize the vessel with 1/2”


valve (pos.21)

Clean the delivery pipes using an


external source through the external
flushing coupling under the 1/4”
check valves (pos.23)
Once the operational activities are completed, bring the powder system
back to "ready to operate” conditions

WARNING:

the powder is delivered at high pressure from the gun.


It is forbidden to shoot powder against people