Features • GD is specifically developed for refrigeration • Optional NO or NC and different delay setting
applications. for both Low and High Alarm Level.
• Interchangeable precalibrated sensor board • Manual or Auto reset optional.
means reduced costs of recalibration and • Low and High Alarm levels and delays setting,
maintenance. can be changed by the user.
• Optional models: LCD display, IP 65 • GD can be connected directly to a Danfoss m2,
models, Exd (Explosion Protected), Exd Low Micromon or AK-SM 350 monitoring unit.
temperature, Models with remote sensor, • Available with a range of different sensor
Models with remote Exd sensor, Models with technologies to monitor industrial refrigeration
remote display, Models for Low temperature gases:
down to –40°C (–40°F). – Electro-Chemical (EC)
• Can operate as stand alone product. – Semi-Conductor (SC)
• Linear analog outputs, current (mA) / volt (V) – Catalytic (CT)
proportional to the gas concentration. – Infra-Red (IR)
• Two digital outputs. Low Level and High Level • Calibration Certificates available.
Alarm.
Contents Page
Features........................................................................................................................................................................................ 1
Technical data............................................................................................................................................................................ 3
Electrical connection............................................................................................................................................................... 4
Design........................................................................................................................................................................................... 5
Sensor technology................................................................................................................................................................... 6
Calibration / test methods............................................................................................................................................. 6
Electrochemical Sensors - EC........................................................................................................................................ 6
Semi-conductor – SC....................................................................................................................................................... 6
Catalytic - CT....................................................................................................................................................................... 6
Infrared - IR.......................................................................................................................................................................... 6
Calibration test methods....................................................................................................................................................... 6
Bump test............................................................................................................................................................................. 7
Product range............................................................................................................................................................................ 7
Functions - all models............................................................................................................................................................. 8
Normalization Period............................................................................................................................................................... 8
Mother PCB................................................................................................................................................................................. 9
GD connected to Danfoss monitoring............................................................................................................................10
Reference material.................................................................................................................................................................11
Ordering.....................................................................................................................................................................................12
GD sensor PCB..................................................................................................................................................................13
Accessories........................................................................................................................................................................14
Dimensions...............................................................................................................................................................................15
Ammonia (R 717)
Type GDA: HFC ( R134A)
– 0-100 ppm Type GDHF-R3
– 0-300 ppm – 0-1,000 ppm
– 0-1,000 ppm
– 0-10,000 ppm Hydro-carbon (R 290, R 600, R 600A, R 1270)
– 0-30,000 ppm Type GDH
– 0-5,000 ppm
Carbon Dioxide (R 744)
Type GDC Reference temperature conditions for factory
0-10,000 ppm calibration:
0-20000 ppm Ambient temperature
0-40000 ppm For increased accuracy the unit must be calibrated at
the temperature of operation.
Halo-Carbon - HCFC (R 22, R 123)
Type GDHC Response times may vary based on temperature of
– 0-1,000 ppm operation, enclosure, and environmental conditions
HFC (R 404A, R 507) Alarm thresholds should be set accordingly based on
Type GDHF the environment of operation and the application in
– 0-1,000 ppm which they are being used
Technical data
(Continued)
Models Standard Basic Standard IP 65 with IP 65 enclosure Exd model Exd model IP 66 enclosure IP 66 enclosure Remote LCD
Basic with LCD stainless steel Low 5 m remote 5 m remote display
display sensor head Temperature IP 65 sensor IP 65 Exd IP 41
Sensor sensor 5 m cable 3)
Temperature range
EC 1) –20°C/+40°C 0°C/+40°C –20°C/+40°C –20°C/+40°C –40°C/+40°C –20°C/+40°C –40°C/+40°C –20°C/+40°C –20°C/+40°C 0°C/+40°C
(–4°F/104°F) (32°F/104°F) (–4°F/104°F) (–4°F/104°F) (–40°F/104°F) (–4°F/104°F) (–40°F/104°F) (–4°F/104°F) (–4°F/104°F) (32°F/104°F)
SC, CT –20°C/+50°C 0°C/+50°C –20°C/+50°C –40°C/+50°C –20°C/+50°C –40°C/+50°C –20°C/+50°C –20°C/+50°C 0°C/+50°C
(–4°F/122°F) (32°F/122°F) (–4°F/122°F) (–40°F/122°F) (–4°F/122°F) (–40°F/122°F) (–4°F/122°F) (–4°F/122°F) (32°F/122°F)
IR 0°C/+50°C 0°C/+50°C –20°C/+50°C –40°C/+50°C –20°C/+50°C not available not available not available 0°C/+50°C
(32°F/122°F) (32°F/122°F) (–4°F/122°F) (–40°F/122°F) (–4°F/122°F) (32°F/122°F)
Electrical data
EC 12-24 V d.c., 0.23A 12-24 V d.c., 0.23A 12-24 V d.c., 0.23A 12-24 V d.c., 0.23A Supplied from
SC, CT 12-24 V a.c. 4 W 12-24 V a.c. 4 W 12-24 V a.c. 4 W 12-24 V a.c. 4 W connector on GD
IR 12- 24 V d.c 0.3 A 12- 24 V d.c 0.24 A not available not available not available motherboard
Enclosure
EC IP 65 2
) IP 66 2
) IP 66
IP 30 IP 30 IP 65 IP 65 IP 65 (~NEMA 4) (~NEMA 4x) (~NEMA 4x) IP 41
SC, CT
(~NEMA 1) (~NEMA 1) (~NEMA 4) (~NEMA 4) (~NEMA 4) (~NEMA 1)
IR not available not available not available
) Two models.
1
Sensor head
Models Standard Basic Standard IP 65 for High IP 65 enclosure Exd model Exd model IP 66 enclosure IP 66 enclosure
Basic with LCD RH and Fast Low 5 m remote 5 m remote IP
display response Temperature IP 65 sensor 65 Exd
Sensor sensor
Electrical connection All terminals will accept 0.5-1.5 mm2 (20-15 AWG) Digital output – volt free contacts
Load: 1 A, 24 V a.c/d.c
Analog output
4-20 mA Max. 400Ω
0-10 V Min. 10 kΩ
0-5 V Min. 10 kΩ
RS 485 Communication
To Danfoss Monitoring System:
Danfoss m2
Danfoss Micromon
Danfoss AK SM 350
Design The GD product range is designed in a very flexible The sensor PCB is always precalibrated and dedicated
way with a mother PCB (Print Circuit Board) and an to the actual refrigerant and ppm range. Danfoss has in
interchangeable precalibrated sensor PCB. advance selected the most appropriate sensor making
it easy to optain safe detection and avoid false alarms
The mother PCB is the same for all GD models from other gases present.
independent of the refrigerant or sensor Because of the interchangeable precalibrated
technology. On the mother PCB individual settings sensor PCB, it is very easy to replace the sensor
(Alarm levels, delays e.t.c) can be set to meet local when service or a calibration procedure is required
legislation or application requirements. (see the below drawings).
Mother PCB
Sensor PCB
Sensor head
Mother PCB
n IP 65 enclosure
M148D0002_1
Danfoss
Mother PCB
Sensor
head
Sensor technology Danfoss has, depending on actual ppm range and GD product range makes it easy to pick out the right
refrigerant, selected the most appropriate sensor for product.
the target refrigerant gas. When the refrigerant and
actual ppm range has been decided, the Danfoss Below is a brief introduction to the GD sensor types.
For further information - please contact Danfoss.
Annual Test
To comply with the requirements of EN378 and the F GAS regulation sensors must be tested annually.
However local regulations may specify the nature and frequency of this test. If not the Danfoss
recommended bump test procedure should be followed. Contact Danfoss for details.
For increased accuracy the unit must be calibrated at the temperature of operation.
After exposure to a substantial gas leak, sensor should be checked and replaced if necessary.
Check local regulations on calibration or testing requirements.
Method I This method requires that Danfoss offers factory Danfoss recommends that the calibration / test
Calibration / test by means of calibrated PCB sensor boards with calibration certificate procedure is done by means of replacing the Sensor
replacing Sensor PCB and traceability codes. Additionally an electrically PCB, because:
simulation is required to verify the output signals and
alarm settings. • No need to purchase calibration gases in several
different concentrations
The PCB sensor board, which is the essential measuring • Simpler and quicker than gas calibration
element of the gas detector, is produced, calibrated, • Danfoss guarantees the correct calibration and
tested and certified by Danfoss. functioning of the new sensor PCB, which is supplied
with a calibration certificate.
After the main PCB of the gas detector has been tested
with the GD tester, the new calibrated Sensor PCB can • No problems with sensor deterioration or end-of-life
be installed. • Price competitive, compared to the gas calibration
carried out on site.
Test and calibration of GD Main
Board by the use of GD tester
Certificate
XXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXX
Certificate:
XXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXX
Gas / calibration levels etc.
XXXXXXXXXXXXXXXXXXXXX Traceability
Exchange of PCB
sensor board + Electrical
test of alarm Gas sensor
tested
Bump test A Bump Test consists of exposing the sensor to a gas. The objective is to establish if the sensor is reacting to the
gas and all the sensor outputs are working correctly. A qualified bump test is a test carried out using ampoules or
similar of known concentration.
Bump test of gas sensors (this test is a function test - it is not a calibration)
SC EC CT IR
Semi- Electro- Catalytic Infrared
Method Refrigerant conductor chemical
Ampoules Ammonia
Lighter gas HCFC, HCF
Lighter gas HC - Hydro Carbon
Ampoules or (Breath on sensor) CO2
Ammonia water Ammonia
M148D0003_1
Danfoss
Standard LCD display IP 65 with stainless steel sensor head Exd Exd Low temperature for CO2
Exd Low temperature
IP 65 enclosure
IP 66 enclosure 5 m remote IP 65 sensor
IP 66 enclosure 5 m remote IP 65 Exd sensor
• Standard • Exd
Basic standard model for machine/engine rooms and Like Standard but applicable in explosive areas Zone
cold rooms 1 and 2 and higher IP(NEMA).
• Standard with LCD display The sensor is mounted in an external Stainless Steel
Basic standard model for machine/engine rooms head.
with the actual reading of present ppm level in the • Remote LCD (accessory)
room and Alarm messages. Remote LCD display with 5 m cable
• IP 65
Two models with IP 65 available: • Remote sensor
- IP 65 with stainless steel sensor head. Models with 5 m cable. Can be used in connection
Temperature down to –20°C(–4°F) with safety valves/vent pipe applications.
- IP 65 enclosure. Temperature down to Also available with remote Exd sensor
–40°C(–40°F)
Functions - all models All GD models shown above have the same basic With the option Auto reset selected, the release of the
functions. All settings are done by means of jumper Low or High Level Alarm is done automatically.
settings on the mother PCB. All GD models are factory set to Auto Reset.
See the section “Mother PCB” for more details.
For detailed information on how to adjust Alarm The factory preset values can be adjusted, with a
setting - please see the instruction PI.S00.A. voltmeter measuring a 0-5 V d.c output.
0 V corresponds to the min. ppm range (e.g. 0 ppm)
Alarm 5 V corresponds to the max. ppm range (e.g. 1000)
All GD models can detect 2 alarm levels and give
alarm via 2 volt free contacts. When an alarm has been Example:
detected a yellow LED (Low Level Alarm) or a red LED If a setting of 350 ppm is required the voltage shall be
(High Level Alarm) will go ON. All GD sensors have set to 1.75 V (35 % of 5 V)
been preset by the factory, to realistic Low/High values
related to the actual ppm range of the GD model. The Analog Output
actual Low and High Alarm ppm values can be read on All GD will continuously generate a linear analog
the external GD label. output, proportional to the gas concentration. The
signal is available as 4-20 mA, 0-10 V and 0-5 V.
The 2 volt free contacts can be set individually to either All are available at the same time (see next page).
Normally Open (NO) or Normally Closed (NC).
All GD models are factory set to NO LCD display
The model with the LCD display will continuously
display the actual present ppm level in the room and
the Alarm messages.
Both Low and High Level Alarm can be delayed Lower Line:
individually before the 2 volt free contacts are Alarm status.
activated. This is useful when cross interference from 4 text messages are possible - only one at a time:
other gasses may occur. The delayed response time can “No Alarm” Neither Low Level Alarm nor
be set to 0, 1, 5 or 10 minutes. High Level Alarm active.
All GD models are factory set to 0 minutes. “Lo Alarm on” Low Level Alarm active.
When the GD sensors have detected a Low or High “Lo,Hi Alarm on” Both Low Level Alarm and
Level Alarm an option for having these alarms with High Level Alarm active.
Manual reset or Auto Reset is possible. With the option “Hi Alarm on” High Level Alarm active.
Manual reset selected, a push button on the mother
PCB must be activated to release the Low or High Level
Alarm.
Mother PCB
Mother PCB
(Continued)
GD connected to Danfoss offers the possibility of connecting every GD, assigned an address. See next page.
Danfoss monitoring independent of model, via the built-in RS 485 Bus A conversion chart between channel number of the
communication, directly to the Danfoss monitoring Danfoss monitoring system and the hexadecimal
unit. address of the GD is attached. Power must be removed
when setting the addresses on the GD sensor.
Up to 31 GD sensors can be connected via a two- If more than 31 units are needed, a GD Repeater
core screened communication cable (see the below (amplifier) must be installed (see Accessories).
drawing).
Every GD sensor needs a unique address number which Contact Danfoss for further information.
must be selected. The address of GD is set by S2 and
S3. By setting S2 and S3 between 0 and F, the GD will be
Danfoss
m2
Micromon
AK-SM 350
GD connected to
Danfoss monitoring
(Continued)
Ordering
IP 65 sensor IP 65 Exd sensor
–40°C/+50°C (–40°F/122°F)
–40°C/+40°C (–40°F/104°F)
Type Danfoss Type Range Alarm Resp. Sensor Complete Sensor Complete Sensor Complete Sensor Complete Sensor Complete Sensor Complete Sensor Complete Sensor Complete Sensor Complete Sensor
of gas [ppm] limits Delay type PCB PCB PCB PCB PCB PCB PCB PCB PCB
Low/ [s]”
High
[ppm]
10000/
R 744 GDC IR 20000 0-20000 0 Infrared 1) - 1) - - - 148H5082 148H5219 1) - 1) - 1) - 1) -
18000
20000/
GDC IR 40000 0-40000 0 Infrared 1) - 1) - - - 148H5092 148H5220 1) - 1) - 1) - 1) -
36000
Halo-Carbon
HCFC
500/ Semi-
R 22, GDHC SC 1000 0-1000 0 148H5100 148H5205 148H5101 148H5205 148H5102 148H5212 148H5109 148H5223 1) - 1) - 148H5107 148H5262 1) -
900 Conductor
R 123
HFC
500/ Semi-
R 404A, GDHF SC 1000 0-1000 0 148H5110 148H5206 148H5111 148H5206 148H5112 148H5213 148H5119 148H5217 148H5113 148H5243 1) - 148H5117 148H5263 1) -
900 Conductor
R 507
Hydro-Carbon
R 290,
R 600, 800/ Semi-
R 600A, GDH SC 5000 0-5000 148H5190 148H5267 148H5191 148H5267 - - - - - - 148H5193 148H5260 - - - - - -
2500 Conductor
R 1270
1) Contact Danfoss
DKRCI.PD.S00.A9.02 | 520H2142 | 12
Data sheet | Gas detecting sensor, types GDA, GDC, GDHC, GDHF, GDH
GD Tester
GD Mother PCB
Beaker
Ampoules
EC/SC/CT-Adaptor
M35 Adaptor
Dimensions
152
M148D0004_1
Danfoss
75 122
122
168
14
7
Mounting Holes
2 x Clearance for M6
IP 65 Enclosure