Automatic Voltage Regulator R610 Instruction Manual
Automatic Voltage Regulator R610 Instruction Manual
2006 / a
GS
3Ø
ou
GS GS
3Ø 3Ø
or or
AVR AVR
NOTE
THE ELECTRICAL CONNECTION DIAGRAM ARE ONLY GIVEN
AS AN INDICATION. PLEASE REFER TO THE SPECIFIC DIAGRAMS
OF YOUR ALTERNATOR
WARNING
TO PREVENT PERSONNAL INJURY OR EQUIPMENT DAMAGE,
ONLY QUALIFIED TECHNICIANS/OPERATORS SHOULD
INSTALL AND OPERATE THIS DEVICE
CAUTION
MEGGERS AND HIGH POTENTIAL TEST EQUIPMENT MUST NOT BE
USED. INCORRECT USED OF SUCH EQUIPMENT COULD
DAMAGE THE SEMICONDUCTORS CONTAINED IN THE AVR
2 2
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
TABLE OF CONTENT
CARDS REFERENCE 4
GENERAL DESCRIPTION 5
CONNECTICS 9
SUPPLY CARD 16
SENSING CARD 18
DRIVER CARD 23
START - UP 43
3 3
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
CARDS REFERENCE
DESIGNATION N° printed N° N° instruction REMARKS
circuit board card manual
= Basic
= Optional
NOTE :
- 1F = Solo or parallel operation between machines (Voltage regulation + reactive load sharing (droop))
- 2F = 1F + parallel operation with the mains (P.F or KVAR regulation)
- 3F = 2F + automatic voltage matching between the generator and the mains. (For synchronizing)
IMPORTANT : The informations given on this sheet will be used to order spare parts. Take care of it.
4 4
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
GENERAL DESCRIPTION
1) APPLICATION 5) SPECIFICATIONS :
- The AVR model R600 can be used with brushless self- - Sensing voltage
excited type generators, "SHUNT", "SHUNT with BOOSTER" : 100/110Vac 50Hz
or "PMG" or “AREP” excitation. In case of "SHUNT with : 120/130Vac 60Hz
BOOSTER” the booster current is totally monitored by the : 380/420Vac 50Hz
AVR. : 430/450Vac 60Hz
- The AVR is able to ensure, depending of its constitution,
solo operation, parallel operation between equivalent - Power supply
generators or parallel operation with the mains with cosØ or (maximum 180Vac 50/60Hz)
KVAR regulation. Shunt+Booster = power transformers
AREP = auxiliary windings
2) DESCRIPTION PMG = external generator
- The AVR model R610 is composed of electronic cards which - Field output
are included in a half rack 19" . : 8 Amperes nominal, 20Amp maximum during 10s on
- An empty slot located on the left of the rack allows future 6§Ù minimum
optional cards to be added without any internal wiring - Accuracy
modification. : +/-1% of the means of the three phases on linear load
- The rear flat cable (BUS 64 points) is given more long as it and without droop
can be connected to an optional interface terminal block
which gives all the internal test points or in the future the - Voltage setting range
possibility to connect another rack if the cards number will : +/-5% of the nominal voltage by means of external
become too important. optional potentiometer .
- Droop setting range
3) INTERCONNECTIONS : - 7% of the nominal voltage at cosØ =0
- External interconnections are located on the top of the rack
- Under-frequency protection
in form of two terminal blocks:
: Adjustable threshold and slope from V/Hz to 2V/Hz
- A power / voltage terminal block (16 terminals, two with
fuses ) - Field ceiling
- A command / control terminal block (24 terminals) : 110% of If nominal permanently, unlocked in case of
- A conventional wiring connect this terminal blocks to the voltage decrease
power block fitted on a heat sink and also to the "generator
I/O" and "mains I/O" to give an interface with the flat cable - Protection
BUS 64 points. : Heat sink overheating, exciter short-circuit
- In the same manner a 8 points connector connects directly - Alarm output
the driver card to the power block. : Heat sink overheating, too much ceiling unlocked time
4) OPTIONAL CARDS - Environment
: Maximum ambient temperature -10°C to +50°C
- Basically the AVR allows voltage regulation with reactive : Fitting in control panel without excessive vibrations
sharing when paralleling with other machines.
The following cards can be plugged into the AVR without 6) SCHEMATICS AND DRAWINGS
internal wiring modification :
- CosØ / KVAR regulation (2F) (// with the mains) - Following schematics give all the usual information on the
- Voltage equalisation with the mains (3F) (Synchro) interconnections between the terminal block, the I/O
Only one is possible with the following cards connectors and the power block.
- Voltage and P.F digital potentiometers
- Manual operation
- I stator limitation
- Mains P.F or KVAR regulation from 4-20mA converter.
-
2 or 3
Power 2 or 3 measure VT
VT measure VT Out of
supply
Optional
Booster
board
De-energizing or
or
(Power) (Control)
Mains measure
Out of supply
A VR
Rotating
diode
failure
detector
(OPTION)
Command Potentiometer
Fault output Alarm output inputs inputs
POWER TERMINALS
17
17 18 19
Power supply
18
Power supply
19
Power supply
5
5
+ Field +VDC
Power su pply
4 7 5 5
4
+ Field flash R
Free
wh eeli ng
8 8
dio de
- Field flash
8
+
HALL 8
se nsor 5
6 6 60 60 Thermocontact
- Field
6
8 E2 8
OVDC
69
70
1
2
3
4
5
6
8
7
Power su pply
1 2 3 4 5 6 8 7 P4 9c 10c
To LMI 8 points connector To 32 points connector
on driver card P4 on "MAINS I / O"
8 1
6 6
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
2 or 3
2 or 3 measure VT
measure VT Out of
supply
or
De-energizing
(Power) (Control)
Mains measure
Out of supply
A VR
Rotating
diode
failure
detector
(OPTION)
Command Potentiometer
Fault output Alarm output inputs inputs
POWER TERMINALS
17
17 18 19
Power supply
18
Power supply
19
Power supply
5
5
+ Field +VDC
4 7 5 Power su pply 5
4
+ Field flash R
Free
wh eeli ng 8
8
dio de
8
- Field flash
+
HALL 8
5
se nsor
6 6 60 60 Thermocontact
6
3
4
5
6
8
7
ON HEATSINK
8 E2 8
69
70
OVDC
1
2
3
4
5
6
8
7
Power su pply
1 2 3 4 5 6 8 7 P4 9c 10c
To LMI 8 points connector To 32 points connector
on driver card P4 on "MAINS I / O"
8 1
7 7
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
PMG
2 measure 2 or 3 measure
De-energizing or
(Power) (Control)
Mains measure
Out of supply
A VR
Mains P.F measure
Out of supply
Rotating
diode
failure
detector
(OPTION)
Command Potentiometer
inputs inputs
Fault output Alarm output
POWER TERMINALS
17
17 18 19
Power supply
18
Power supply
19
Power supply
+VDC
Power su pply
5 5 5
5
+ Field
Free
wh eeli ng
8 8
dio de
8
+
HALL
8
se nsor 5
6 6 60 60 Thermocontact
- Field
6
8 E2 8
OVDC
69
70
1
2
3
4
5
6
8
7
Power su pply
1 2 3 4 5 6 8 7 P4 9c 10c
To LMI 8 points connector To 32 points connector
on driver card P4 on "MAINS I / O"
8 1
8 8
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
(*) in case of SHUNT + booster excitation : there are fuses in terminals 14 & 16 and nothing interminal 15
9 9
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
10 10
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
11 11
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
12 12
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
VOLTAGE INPUTS :
Reference Generator sensing voltage
C5 195 0230 100V - 120V 50/60Hz
C5 195 0232 400V - 450V 50/60Hz
13 13
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
6c 1
1 U alt 7a
8c 3
2 V alt 8c
TP 3
10 c 5
3 W alt 8a
23
5c 7c
2,2¦ RB60 25
9 CT // 9a
R0 D1 to 6
PT3
7c 1 1 1 00 V TP 2 2c ,2a
10 CT //- GND 1 20 V
}
16a,17c
Te rmi nal N° 2 2 1 20 V PT2
}
1 00 V TP 1 3c ,3a
7a 3 3
D7 to 12
20 Sh ie lds
R2 6
4a
D1 3
to 18
1a 6 D1 9
C1 C2 4 to 24
Q1 2
10 a
P.F/ kvar K1 PT1 15
37 38 CR1 +Vc c 1c
R1 4 14 20a
R1 7
DS1 13
11 c
P.F Cmd K2
31 30 CR2
R1 3 16
24a
15 c R1 8
+U K3 DS2
37 35 CR3
R1 2 12
23a
16 a
-U K4 DS3
37 36 CR4
R1 1 10
24c
Internal te st p oi nts
DS4
0V +Vcc 0V meas
1c 19
21 Pot U R8 11a
9a 26
22 Pot U 21a
2c
23 Pot U R7
2a
24 P.F pot R6
8a 24
25 P.F pot 20c
P.F pot 3c R5 17
26 -Vcc 32a
3a
27 KVAR pot R4
6a 22
28 KVAR pot 21c
KVAR pot 4c
29 R3
R2
14 a
33 Inf o Ala rm CR6 R1 5
13 a K8
34 Inf o Ala rm DS7 8 31a
9c
Thermostat
5a 20 26c
Thermostat
4a 21
39 Measure If R1 6 17a
}
14 14
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
R610 potentiometers position. For adjustments, refer to specific card technical manual
15 15
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
SUPPLY CARD
1) FUNCTIONAL 2) ADJUSTMENTS
- None
- This card, from not regulated symetrical voltage,
generates +15Vdc and -15Vdc voltages with 0V common to
both named +Vcc for +15V and Vdd for -15V in the 3) INPUTS / OUTPUTS
following.
- 2a, 2c : Input +30Vdc not regulated
- The non régulated voltages are first filtered (C01, C02), - 3a,3c : Input -30Vdc not regulated
pre-régulated to 20dc with ballast stages Q01 et Q02 and - 1a,1c : Output +15Vdc regulated (Vcc)
finally decreased to15V by means of RG01 et RG02 - 32a,32c : Output -15Vdc regulated (Vdd)
régulators. - 16a,17c : Common electronic ground
- Its permanent current capability is 0,5 Amp on both
polarity.
16 a,17c 16 a,17c
0v 0V
LED
-15V
16 16
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
BDX85C
TP1 RG01
Q01
2a,2c 1a,1c
7815
R03
3,3KΩ
R01 330Ω C03 C05
0,33µF 63v CR03 0,33µF 63v
C01
CR01 1N4007
1000µF 40V
BZX85C20 DS1
16a,17c
TP2
R04
1000µF 40V 3,3KΩ
CR02
C02 CR04 C06
BZX85C20
R02 330Ω C04 1N4007 0,33µF 63v
0,33µF 63v
DS2
3a,3c 32a,32c
7915
Q02
TP3 RG02
17 17
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
SENSING CARD
2) ADJUSTMENTS
1) FUNCTIONAL - P1 : Reactive droop adjust for parallel operation
- This card elaborates from the three phases voltage image between equivalent machine.
of the generator given by the "ALTERNATOR I/O" : - P2 : Vm adjust for nominal voltage. (9Vdc at Un)
-A rectified, calibrated, filtered voltage Vm proportional to - P3 : Underfrequency threshold adjust (normally Fn -
the stator voltage of the generator. Vm could be affected by 5%) signaled by LED.
droop depending of adjustment. - P4 : Underfrequency slope adjust ( k ) in kVolt / Hz
- A voltage function of the generator frequency, a part of mode
which gives the reference set point named Vref. - P5 : Voltage set point Vref for the nominal voltage
(9Vdc at Un and Fn)
- Vref is a constant above the underfrequency threshold set
point (signaled by LED) and decreases below this threshold 3) INPUTS / OUTPUTS
following a function depending of the position of the strap
CV1: - 7a, 8a, 8c : Voltage inputs image of the generator (3 x
- In fixed V/Hz mode 21Vac between each and the GND)
-In adjustable kVolt / Hz (see curve below) - 9a : Current input image of the generator stator
current (1Vac pour In)
Volt - 1a,1c : +15Vdc regulated (Vcc)
- 32a,32c : -15Vdc regulated (Vdd)
Un - 16a,17c : Common ground (GND or 0V)
- 11c : Voltage output image of the generator (Vm)
9Vdc at Un
- 11a : Voltage set point output (Vref) 9Vdc at Un
Mode Volt / Hz and Fn
Mode k x Volt / Hz
Fn - 5% Fn Hz
9a
TI // AC / DC
Reactive
droop
7a
Um
Σ
8c 11 c
Vm AC / DC Filter Vm
8a
Wm
1c,1 a AC / DC Threshold
+Vcc k U/F
16 a,17c
0V
32 c,32a
-Vdd
11 a
F -> kV Vre f
Voltage
set point
LED
18 18
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
19 19
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
- Parallel operation with the mains with power factor 3) INPUTS / OUTPUTS
(COSØ) or KVAR regulation (2 Fonction)
( Only if COSØ / KVAR card is fitted) - 11a : Voltage reference set point input. Vref
- 13c : Added signal to voltage reference set point
- Operation in voltage equalization mode between input (option )
machine and mains before coupling (3 Fonction) - 22c : Added signal to voltage reference set point
( Only if "MAINS I / O" card is fitted) input (external voltage option )
1F : Machine image Vmis compared with the sum of - 21a : Added signal to voltage reference set point
Vref, Pext, etc voltages depending of used options and the input (external potentiometer option )
resultant voltage (error voltage ) feeds the PID. - 13a : Added signal to voltage reference set point
input (differential droop option; with
2F : When cosØ cmd input is activated (+Vcc), the cosØ/KVAR card )
machine voltage Vm is compared to the voltage given from - 19a : Integrator short-circuit command input
the cosØ/KVAR card and the result (error voltage ) feeds - 10a : Mains image voltage input (3F) ( with "MAINS
the PID. I / O" card only)
- 14c : CosØ error voltage input (2F) (with
3F : When U/U cmd input is activated (+Vcc), the
cosØ/KVAR card )
machine voltage Vm is compared to the voltage given from
- 25c : Voltage equalization command input (3F)
the "MAINS I / O" card and the result (error voltage ) feeds
(with "MAINS I / O" card only)
the PID.
- 24a : CosØ regulation command input (2F) (with
A compensation external input, given for specific cosØ/KVAR card )
applications is added to the error voltage and the resultant - 1a,1c : +15Vdc regulated (Vcc)
voltage is the real PID input. Each branch (P, I, D) of the - 32a,32c : -15Vdc regulated (Vdd)
PID, independently adjustable from the others, set the time - 16a,17c : Common electronic ground
constants of the AVR in regard to the generator. The - 14a : Minimum field limitation, active power
integrator branch can be short-circuited, for example when correction input
starting-up. - 15c : Field current voltage control output "AUTO"
channel
These three outputs are added, limited to 10Vdc and
then give the field current set voltage of the "automatic
channel" which is the driver card input.
The minimum value of this signal can be limitated to avoid
total loss of excitation of the generator. In case of parallel
operation with the mains (cosØ/KVAR card), this limitation
is a function of the active power supply by the generator,
this information is given by the COSØ / KVAR card.
A separate stage detect if the generator voltage is
below an adjustable value to unlock the normal field ceiling
voltage from 110% of nominal to 160% (adjustable).
20 20
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
11 a
Vre f
13 c static
Vpot dig +
+ relay
13 a static
Vstat - + relay
+
22 c + P
Cde U + - -
21 a
Pe xt
10 a
Vre s
25 c
Cde U/U I
11 c
Vm
14 c
CosØ
static
24 a
Cde CosØ relay
12 c
V Exte rn
19 a
Cct inte g D
9c
Vm -10% M in If
+
11 c
Vm - +
LED +
11 a
Vre f + 10 V AUTO output15 c
14 a If min M in If 19 c
IcosØ
limit
21 21
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
22 22
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
DRIVER CARD
1) FUNCTIONAL 2) ADJUSTMENTS
This card controls from "AUTO" and "MANU" voltage - P1 : Integrator time constant adjust.
reference and some additional informations detailed in the - P2 : Unlocked ceiling time delay adjust. (generally 5s)
following, the exciter field current supply by the regulator - P3 : Alarm time delay adjust after ceiling unlock.
and the booster (if used). - P4 : Permanent ceiling value adjust
- Three operating mode are possible, depending of external (generally 1,1If nominal)
informations : - P5 : HALL sensor range adjust.
- Normal mode with 110% ceiling of If nominal. - P6 : Initial ramp-up adjust
- Ceiling unlocked mode (160% minimum Ifield - P7 : Maximum field current adjust (machine short-circuit
nominal) depending of the command input from the PID )
card with limited delay and alarm output in case of - P8 : Maximum fieeld current in case of heatsink
sustained undervoltage. overheating.
- Maximum ceiling mode if the synchronisation voltage
desappears ( machine short-circuit) with limited (adjustable) 3) INPUTS / OUTPUTS
field current.
- The "AUTO" or "MANU" reference voltage depending Flat cable (BUS 64points)
of the associated command input and also of the active
limitations, is compared to the field current measurement - 15c : If reference set point input "AUTO" channel
and gives the error voltage which is after integration, - 15a : If reference set point input "MANU" channel
compared to a sawtooth feed by the synchronisation - 25a : "AUTO / MANU" command input
voltage. The output of this stage is a variable duty cycle (0V = "AUTO")
signal which controls the power transistors throught - 9c : Unlocking ceiling command input
isolating optocouplors. - 4a, 4c : Synchronisation voltage input
- 26c : Heatsink thermocontact input
- This card can be supplied in three manners : - 1a,1c : +15Vdc regulated (Vcc)
- From the general supply of the rack in normal operation - 32a,32c : -15Vdc regulated (Vdd)
- Throught an isolated supply taken from the field voltage - 16a,17c : Common ground (GND or 0V)
during start-up or generator short-circuit. (Rack supply not - 17a : Field current measure output
present) - 19a : End of ramp-up output signal
- Directly from the field voltage for power transistor - 31a : Alarm output
command. Card connector (8 points)
The permanent limitation (110% de Iexc nominal) can -1 : Field voltage
be modified by the following conditions: -2 : Main transistor drain
- Field ceiling unlocking on machine undervoltage -3 : Main transistor gate
condition. It inccreases from 110% (normal operation) to a -4 : Booster transistor gate
minimum of 160% of the nominal field current during an -5 : Power ground
adjustable time delay and then go back to 110%. An alarm -6 : +Vcc HALL sensor
is activated if this undervoltage is sustained afterward. -7 : -Vcc HALL sensor
- Field ceiling unlocking on synchronisation voltage -8 : HALL sensor measure output
abcence. It increases to the maximum given by the setting
of P7.
-Field ceiling limitation caused by power heatsink
overheating. On thermocontact action the ceiling is reduced
to a value given by the setting of P8.
A separate circuit monitors the instantaneous current of the
power transistor and reduces immediatly the command
signal if its value increases above a fixed value. (Exciter or
wiring short-circuit protection ).
23 23
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
9c
Ce il i ng Ts Ipl + Ra mp
un lo ck -
31 a Lim 1
Outpu t al arm
Lim max
18 a
Li mi t If
19 a
Ramp e nd
26 c
Th ermoco ntact
he atsi nk
24 24
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
25 25
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
- First the current image of the stator current is filtered Nota : If the droop is used from this card, potentiometer P1
and used directly for KVAR measure. Then it is derivated of the sensing card must be set to zero.
and used for KW measure. And then it is amplified to obtain
square waves and integrated to give a sawtooth used to Ø 3) INPUTS / OUTPUTS
measure.
- The voltage image is phase-shifted to compensate the Flat cable (BUS 64points)
phase shift of the current input filter and after amplification - 8c : Generator voltage image input
is fed to a monostable which gives the pulse signal (about - 9a : Generator current image input
100µs) used by all the sample and hold circuits. - 20a : Command input "cosØ / KVAR" (0V = "cosØ")
- KVAR and Ø values are compared with an internal - 21c : External KVAR setting input
and external (if used) setting and the difference is send to - 20c : External cosØ setting input
the PID card as an error signal. An external contact control - 1a,1c : +15Vdc supply (Vcc)
an analog switch to select what information between KVAR - 32a,32c : -15Vdc supply (Vdd)
and Ø will be regulated. - 16a,17c : Common electronic ground
- 14c : Error signal output to PID card
- Three informations (Ø, ΔØ, ΔKVAR) can be used as - 13a : Droop signal output to sensing card
an alternative droop for solo operation. - 14a : KW signal output to PID card
- Ø gives no droop at cosØ=1 and the voltage - 12a : KVAR signal output
decreases at lagging PF. - 10c : Ø signal output
- ΔØ gives no droop at the cosØ setting and the voltage
decreases at more lagging PF and opposite for more
leading PF.
- ΔKVAR gives no droop at the KVAR value setting and
the voltage decreases with more KVAR and increases if
less.
- The selection between these is made by mean of
jumper (CAV) on the card. (internal)
26 26
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
Isi nØ
12 a
Co sØ
10 c
set p oi nt kV Ar
exte rn al
21 c
Vac set p oi nt co sØ
Ph ase shi ft Mon osta ble exte rn al
8c
20 c
co mmand
KVA R Co sØ/KVAR
20 a
Gai n
TI // Isi nØ KVA R
Fi l te r sampl e & hol d Isi nØ
9a
KVA R
Ø
14 c
Gai n Co sØ
x(fx) dt
sampl e & hol d COS Ø
+V cc d(fx)/d t Ø di ffé re ntia l
1c,1 a droo p
2
-Vcc 3
32 c,32a 1 13 a
CAV
0V
16 a, 1 7c sampl e & hol d IcosØ
IcosØ
14 a
27 27
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
28 28
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
VOLTAGE INPUTS :
Reference Generator sensing voltage Mains sensing voltage
C5 195 0233 100V to 120V 50/60Hz 100V to 120V 50/60Hz
C5 195 0235 400V to 450V 50/60Hz 400V to 450V 50/60Hz
C5 195 0234 400V to 450V 50/60Hz 100V to 120V 50/60Hz
29 29
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
16a,17c
2 2 1 20 V PT2
Te rmi nal N° 1 00 V TP 1 3c ,3a
}
7a 3 3
D7 to 12
20 Sh ie lds
R2 6
4a
D1 3
to 18
1a 6 D1 9
C2 4 to 24
C1
Q1 2
10 a PT1
P.F/ kvar K1 15
37 38 CR1 +Vc c 1c
R1 4 14
20a
R1 7
DS1 13
11 c
P.F Cmd K2
31 30 CR2
R1 3 16
24a
R1 8
+U 15 c
K3 DS2
37 35 CR3
R1 2 12
23a
16 a
-U K4 DS3
37 36 CR4
R1 1 10
24c
U/U Cmd 13 c
K5 DS4
31 32 CR5
R1 0 18
25c
R9 DS5
Internal te st p oi nts
0V +Vcc 0V meas
12 c 7
11 U réseau 5a
14 c 9
12 V réseau 6c
TP 4
16 c 11
13 W rés eau 6a
AC
10a
0¦ DC
1c 19
21 Pot U R8 11a
9a 26
22 Pot U 21a
2c
23 Pot U R7
0¦
2a
24 P.F pot R6
8a 24
25 P.F pot 20c
P.F pot 3c 17
26 R5 -Vcc 32a
KVAR pot 3a
27 R4
6a 22
28 KVAR pot 21c
KVAR pot 4c
29 R3
R2
14 a
33 Inf o Ala rm CR6 R1 5
13 a K8
34 Inf o Ala rm DS7 8
31a
9c
Thermostat
5a 20 26c
Thermostat
39 Measure If 4a 21
R1 6 17a
}
30 30
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
2 11
C R1
1
MA 1/1
3 4
R02 R22 R07 C01
PT7
R14
PT10
6 C R2
C R14 R10 R16 C02
7 9
16a MA 1/2 R25 R17 13
8 10a
C R15 MA 2/3 14
5 MA 2/4 Ur
17c 10 P01
C05 12
0V
1c,1a R13 R18
9 R15
+Vcc 0V C R3
8 R11
32c,32a
MA 1/3
-Vcc R01 R21
10
R23 R08 0V
PT4 R03
PT8
PT5 C R16
R04 13 C R4
PT6 14
R05 C R17 MA 1/4
12
+V cc
R12
0V
C R13
2 11 R20
C R5
R24 1
MA 2/1
3 4 L1
C R18 R09
0V PT9
R06
TP4 C R19 6 C R6 Q01
7
MA 2/2
5
U V W R19
0V
31 31
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
32 32
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
UP U/D M ax
23 a
Cmd +
INC Digital M in
Logic pot U M ax Pos
DOWN static CS 30 a
24 c relay
Cmd -
0V
SW1
24 a
Cmd P.F
-Vre f SW2
U/D
M ax
P01 INC Digital
Cloc k Spe e d pot P.F / M in
CS
KVAR
U r ange
static
P.F / Kv ar
relay
range P.F Output
20 c
- Kv ar Output
21 c
Kv ar Cmd 20 a
DIGITAL
SETTINGS
HAUT
UP
BAS
DOW N
FACE AVANT MA X
Volt age
MIN
Pot Digital U / cosØ
MA X
CosØ - Kvar
MIN
P1
SPEED
33 33
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
34 34
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
-NOTE:
For the R610, the switching between AUTO ÅÆ MANU is
only possible by the switch command in front of the card,
and the setting by the front potentiometer. It is not possible
to use remote commande or control
35 35
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
4c -
24Vac AC / DC Filte r Ampli PI - Manu out
+ 15 a
+
Exte rnal Cmd
27 c
Voltage
Limitation
Se t point
Ifie ld
Limitation
9c
Inte gr al ET +
short cmd Se t point
- too hight
25 a
Cmd
auto/manu Manu out + Se t point
Auto out - too low
12 c
Corr ec t
relais
PID
statique
Gain +
16 c ET Se t point OK
Cmd Ie xc - -
15 c
Auto out +
MANUA L
MODE
A M
FRONT VIEW LIMIT
HAUT
HIGH
Manual Mode 2
LOW
BAS
OK
P3
Seuil
P2
Iexc
P1
Gain
36 36
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
37 37
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
38 38
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
13
Gain
Chan 1 4 -20mA 10Hz K5 CV5 Corr PID
25
Filter
- R
12 c
4 -20mA / 0-10V - A A
12 Exter nal se tting 1 +
B CV3
20
Pot e xt +1 2V Int se tting
24
Re f 1 0V channe l 1
CV6 Corr PID
11 12 c
Gain M A9 A R
Chan 2 4 -20mA 10Hz Exter nal se tting 2
23 - Re f U 21 a
B
CV2
fa ilure
L2 A
21
K1
4 - 20mA 9 K1
16 a, 1 7c
fa ilure 8 0V
1c,1 a
+V cc
-Vcc 32 c,32a
15
K2 K2 30 a
Pot dig 3 Adapt
at max K5 30 c
2
position
Ope n : reg K1 23 a
ge nerator 7
P.F L3 24 c
+V cc Limitation 14 c
Clos ed : reg 19
mains P.F Ifie ld 2 24 a
14
0V 0V
Ifield 26 c
Limit
L4
2 1
aux I / O
FRONT VIEW 13
25
MA IN
P .F O N
MAINS P.F REG
4 -20 mA
1
OFF
2
Limit 2
14 1
ON
Main
P2 P .F
set
Ref 2
P5 set
Limit
P7 2
set
39 39
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
40 40
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
Ref
9a Istator
TI // AC / DC Filter
1c,1 a
+Vcc
16 a,17c
0V T
32 c,32a
-Vdd GAIN
+ 12 c
Ampli PI Limitation
RAMP -
LED
41 41
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
C01 2 11
9a R01 C R3
R04 1
MA 1/1
R02 3 4
9 R05 R07 R10
R06 C03
8 R11
MA 1/3 R09 13
14
10 6 P01 MA 1/4
C R01 C R4
7 C02
MA 1/2 12
R03
C R02 5 R08 R12
0V 0V
16a
L1
C04
-Vcc R19 C06
Q01
R25
R14 2 11
R16 C R06
1 R17 6 9
MA 2/1 C R07
7 8
MA 2/2 R22 MA 2/3 C R08
3 4
P02 R18 5 P03 10
R15 C05
R13 C R05 R20 R24
R21 R26
0V
LIMIT
I STATOR
LIMIT
P2
Ramp
P3
GA IN
42 42
LEROY-SOMER Installation and Maintenance 4008 en – 01.2006 / a
START - UP
- E02 must short-circuit the booster output (if used)
1) STARTING WITH MANUAL MODE CARD (terminals 7 and 8 of AVR) and is closed for de-energizing.
4) ADJUSTMENTS
CAUTION - Refer also to card descriptions.
Never energize the AVR when the driver card - The AVR is normally preset in factory.
is removed. An overvoltage can appear and - The nominal voltage can be set by Vref (P5) on sensing
the power transistor can be damaged card. Fine adjustment can be made by an external voltage
potentiometer (10K§Ù), (terminals 21,22,23)
- For initial start-up, the best is to use the manual mode for
-If an adjustment must be moved, note carefully the
testing the sensing wires between the generator and the
original setting for resetting in case of problems.
AVR.
- If the strap V/Hz of sensing card is on kV/Hz position, the
- For this it is necessary to have a manual mode card
original setting is V/Hz and can be changed between V/Hz
plugged in the AVR. If not, see directly §2.
and 2V/Hz by potentiometer P4.
- Switch the manual card on ON (switch in front of card).
-The stability is adjusted with the machine in factory . If
- Set the potentiometer P2 on manual card maximum CCW, necessary, the response time can be changed by the
start the prime mover up to the nominal speed. setting of potentiometer P4 of PID card.
- Turn slowly the potentiometer CW to obtain the nominal - Other settings are difficult to adjust without specific
voltage. electronics equipments. It is better to not change them.
- Check the presence and the value of the three phases at 5) FIELD FLASHING
the AVR terminal block ( terminals 1, 2, 3 )
- Generally, field flashing is not necessary, but in some
- Set the voltage to 5% above the nominal voltage. cases like long stop time or fault trip, it can be possible that
- Check that the voltage between terminal 39 and 20 of the the voltage does not appear naturally.
AVR terminal block is about one volt. In this case, connect a 12Vdc to 24Vdc voltage source to
the terminals 4 and 8 of AVR terminal block, + to 4 for a
- If yes, switch off the manual operation in the front of short time and remove it when the voltage increases.
manual card.
6) PARALLEL OPERATION(1F)
- The voltage must reach the nominal value.
- The generator voltages must be as equal as possible.
- Go to §3
- Same for the droop. If it is not possible to measure it, set
2) STARTING WITHOUT MANUAL MODE CARD the potentiometers P1 of the sensing cards all in the same
position. (middle set for example). If the droop setting is
- start the prime mover up to the nominal speed.. made from cosØ/KVAR card (when used), see notice NT
1950080.
- If the voltage does not appear, check wires between AVR
and the generator field (terminals 5 and 6 of AVR),and the - The reactive currents (KVAR) must be shared, immediatly
also the wires between AVR and power transformer after coupling, even the KW are not shared.
(terminals 14,15 (and 16 if used) of AVR. Check also the
- If, immediatly after coupling, the current increases
fuse inside the terminal 14,16 of AVR terminal block.
abnormally, check if the parallel CT wires are not reversed.
- If the voltage is too hight, check that the sensing voltages ( 9 et 10 of AVR terminal block)
at the terminals 1, 2, 3 of the AVR terminal block are
- If the coupling is OK but if when the load increases, the
present.
cosØ or the current have an abnormal value, check that
- Adjust the nominal voltage with Vref (P5) of the sensing the sensing phases at the input of the AVR are right
card for the middle position of the external voltage connected. (U, V, W respectively to the terminals 1, 2, 3 if
potentiometer (if used). clockwise rotation or W, V, U, if counter clockwise rotation)
3) DE-ENERGIZING (optional)
- External contacts E01 and E02 must be used.
- E01 must be serie with terminal 14,15 of AVR (power
input) and is opened for de-energizing.