You are on page 1of 51

Safety Codes Council Conference

Banff 2014

90°C Panel Discussion

Tim Driscoll – OBIEC Consulting Ltd.


George Morlidge – Fluor Canada Ltd.
Scott Basinger – Eaton Canada
René Leduc – Marex Canada Limited
Safety Codes Council Conference Banff 2014

Perspectives

• Regulatory Compliance
• René Leduc
• Manufacturing
• Scott Basinger
• Engineering Design
• George Morlidge
• Owner / User
• Tim Driscoll

Slide 2 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

Perspective:

REGULATORY COMPLIANCE

Slide 3 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

New 2012 Canadian Electrical Code


Requirement

4-006 Temperature limitations (see


Appendix B)
(1) Where equipment is marked with a
maximum conductor termination
temperature, the maximum allowable
ampacity of the conductor shall be
based on the corresponding
temperature column from Table 1, 2,
3, or 4.
(2) Where equipment is not marked with
a maximum conductor termination
temperature, 90 °C shall be used by
default.

Slide 4 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

Why a Temperature Limitation?

• Part 2 standards require


that testing be conducted
using conductors with an
insulation rating of 60°C
and 75°C.

• Why no Temperature
limitation Rule in 2009
and prior?

Slide 5 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

Why a Temperature Limitation?

Slide 6 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

Impact – Terminating on equipment with


temperature limitation

• None
Choosing from the
75°C column now will
achieve the same
results (in terms of
conductor sizing) as
having selected from
the 90°C column prior
to 2012

Slide 7 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

Impact – Termination on equipment with


no temperature limitation

• Smaller sizes

• Less Copper

• Can use JB to
transition to
equipment with
temp limitation

Slide 8 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

Benefits of harmonizing conductor ampacities

• What benefits can be realized?

1. Cable spacing correction factors???:

Example: 3-cond #14 TC cable each loaded to 12 A in 150 mm


tray

– 2009 Code – T5D not less than 25% spacing


.82(cf) x 15A = 12.3A

– 2012 Code – T5C no spacing (random fill)


.50(cf) x 25A = 12.5A

Slide 9 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

Perspective

ENGINEERING DESIGN

Slide 10 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

Engineering design

Effect of additional ampacity to temperature


1-Al-90

60

1-Cu-90
Heat Loss for 1m Conductor - Tables 1-4
50
1-Al-75
Watt

40
1-Cu-75

30 3-Al-90

3-Cu-90
20

3-Al-75
10

3-Cu-75

0
0 100 200 300 400 500 600 700 800 900 1000
Cross Section (mm2)

Slide 11 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

Engineering design

Its all about heat production and temperature


Heat production is a squared function - i2r
Most of our conductors end up operating at well below, lets
conservatively say, 80 % of rated (Many are closer to 50 % in
reality). That means they only produce less than 64 % of the
heat (or 25 % of the heat at 50% rated).
Our ambients are rarely anywhere near rated ambients
We often put space heaters in these enclosures to drive off
moisture.
I really question whether utilizing 90 o C ampacity rated wire is
really an issue because in reality, we will likely never see
anywhere near the ideal conditions where this will be an issue.

Slide 12 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

Engineering design

Change the codes and standards to simplify and eliminate the need
for 4-006 (why would anyone buy 75 oC rated equipment if 90 oC
equipment were available
Most equipment that is presently manufactured will likely pass
a 90 oC wire test
The problem is that in many standards the only test is for 75 oC
wire so therefore there is no test and the equipment is
marked as 75 oC wire rated.
The Technical Committee on Industrial Products (TCIP) has
been approached to update all standards to add an
additional optional test requirement for 90 oC wire
Progressive manufacturers will test and mark to this standard.

Slide 13 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

Engineering design

Standards are changing


– In a recent standard voted on at CSA, the following clauses
were included:
• C22.2 No. 76-13 Splitters
– 5.1 Information to be marked …

Slide 14 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

Engineering design

M) where required by clause 4.2.3.4, the splitter


shall be marked to indicate the conductor
ampacity permitted with the following words or
equivalent: 75 oC CONDUCTOR AMPACITY
PERMITTED
N) ) where required by clause 4.2.3.4, the splitter
shall be marked to indicate the conductor
ampacity permitted with the following words or
equivalent: 90 oC CONDUCTOR AMPACITY
PERMITTED

Slide 15 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

Engineering design

These are the clauses that will be added to all CSA standards in
time giving the manufacturer the opportunity to test to the new
90 oC wire ampacities and mark his equipment accordingly

In time, to be competitive, all equipment will be marked to meet the


90 oC conductor temperature requirement.

The next step will be to move to 105 oC conductor temperature


requirements.

Slide 16 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

Perspective

OWNER / USER

Slide 17 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

Conductor Ampacities

 For many years, conductor ampacity was very limited in


the CEC compared to the IEC world and also due to
temperature constraints on insulation
 For several decades, 90oC wire & cable has been available
 Today, you have to go out-of-the-way to buy 75oC wire & cable
 90oC columns were introduced into the CEC Ampacity
Tables many years ago
 However, they were essentially the same as the 75oC columns
 So it didn’t really matter what columns were used for sizing

Slide 18 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

Conductor Ampacities (cont.)

 For the 2012 CEC, a major Ampacity harmonization effort


with the NEC was performed
 Resulting in large increases for 90oC over the 75oC columns
 NEC had previously updated/uprated Ampacities

Slide 19 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

Equipment Termination Ratings

 However, CEC Part ll Equipment standards have not kept


up with Wire & Cable – majority use 75oC in the testing
 Some use 60oC and very few use 90oC
 Rule 4-006 was also introduced in 2012 CEC along with Ampacity
Table increases, to ensure Users size Wire & Cable per the rating of
Equipment Terminations, generally 75oC
 Net effect – Wire & Cable ampacities essentially have not
changed !
 One possible solution is to use a Jct. Box to splice in a
larger conductor prior to Equipment termination
 Caution – many Terminal Blocks / Wire Connectors are 75oC rated
 This adds more equipment, time, space and cost to a termination
 Note – much of this discussion applies to <1000V equipment, but not all
Slide 20 / 90°C Panel Discussion/ Mar. 2014
Safety Codes Council Conference Banff 2014

Other

 4-006(2): termination temperatures default to 90oC if not


marked
 Many manufacturers think this was in error and should be changed
 Rule 14-104(2) also introduced in 2012 CEC to
 Restrict #14, 12 and 10 conductors to be fed from 15, 20 and 30A
max. Overcurrent protection respectively, regardless of ampacity
 Wire temperature ratings
 90oC is the standard available today
 However, 105 and 110oC are starting to become readily available

Slide 21 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

E.g. Supplemental CEC Sections

 Specific CEC sections may modify general sections Rules


4-006 and 14-104
 Example – Section 62 Electrical Heating
 Rule 62-108(1) for Branch conductors and 62-116(1) for Service
and Feeder conductors
• Allow Ampacity Tables to be used directly
 Rule 62-114(7)
• Allows protection to be sized above the conductor ampacity rating
• On #14 conductor, can be up to 25A Load and 30A Overcurrent

Slide 22 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

Conductor Rating Changes from 2009 CEC


2012 CEC
2009  Current ratings ~5A above
Cond Amp, Cu Adder over
CEC 2009 CEC ratings in smaller
Size Conductor 2009 CEC
conductor sizes and 5-10A
75/90oC 75oC 90oC 75oC 90oC lower for larger conductor
14 15 20 25 5 10 sizes
12 20 25 30 5 10  Not a big change from 2009
10 30 35 40 5 10 on average
8 45 50 55 5 10
6 65 65 75 0 10  If 90oC column was available
4 85 85 95 0 10 for sizing, current ratings
3 105 100 115 -5 10 average 10A higher for all
2 120 115 130 -5 10 conductor sizes
1 140 130 145 -10 5  A significant increase
0 155 150 170 -5 15 from 2009 !
00 185 175 195 -10 10
Slide 23 / 90°C Panel Discussion/ Mar. 2014
Safety Codes Council Conference Banff 2014

Cost Examples for 90oC vs 75oC


 To take a look at a few 3 Conductor Approx. Cost Savings
examples E.g. 600V Cable (in using 90oC Table)
 600V, 3 Cond. Cable Load
75/90oC Type 100m 300m 1000m
 Teck and Tray
 Small, medium and higher 25A 12 / 14 Tray $ 184 $ 551 $ 1,837
loads Teck $ 53 $ 158 $ 528
 Ignoring Voltage Drop issues
70A 4/6 Tray $ 734 $ 2,201 $ 7,337
(many Users have Variances
allowing more flexibility with Teck $ 386 $ 1,158 $ 3,861
Voltage Drop) 160A 00 / 0 Tray $ 1,466 $ 4,399 $ 14,663
 Can be some Large Cost Teck $ 586 $ 1,759 $ 5,863
Savings, especially Tray cable
 Reduced by Users’ voltage  MV Cable constructions will also reduce
drop criteria net savings
Significant cost savings are available, depending on design !
Slide 24 / 90°C Panel Discussion/ Mar. 2014
Safety Codes Council Conference Banff 2014

Voltage Drop

 If voltage drop CEC criteria followed completely, little $


savings available
 However, since the voltage drop criteria is very restrictive, many Users
have Variances to allow higher voltage drops
 Using examples from previous slide, 600V, 3 Phase
• #14 Cu good for 90m @ 3%, and 230m @ 8%
• #6 Cu good for 200m @ 3%, and 530m @ 8%
• 1/0 Cu good for 350m @ 3%, and 930m @ 8%
• Note – lower voltages see higher % volt drop, as does 1 Phase Loads
 From these E.g.’s, it can be seen that smaller conductors
have more issues with volt drop constraints

Slide 25 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

Summary – A User’s View

 Conductor Ampacities - very restrictive


 Some progress starting to be made
 Base ratings increased
 But many restrictions still in place – net effect is little change so far
 Actions needed
 Change Part ll standards to allow 90oC testing / marking
 Change Part ll standards to require 90oC testing / marking
 Remove restrictions on Overcurrent Protection, CEC Rule 14-104(2)
 Then Users will start to see some $ savings
 Some premium may need to be paid for higher temperature 90oC
equipment, but wire & cable cost savings will more than offset
 Gives Users choice !

Slide 26 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

Perspective

MANUFACTURING

Slide 27 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

CSA C22.1-12, Section 4 — Conductors

4-006 Temperature limitations (see Appendix B)


(1) Where equipment is marked with a maximum
conductor termination temperature, the maximum
allowable ampacity of the conductor shall be
based on the corresponding temperature column
from Table 1, 2, 3, or 4.
(2) Where equipment is not marked with a maximum
conductor termination temperature, 90 °C shall
be used by default.

Slide 28 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

CSA C22.1-12, Appendix B — Notes on Rules

Rule 4-006
The intent of this Rule is to correlate the temperature
rating of conductors where the ampacity is selected
from Tables 1 to 4 with the lowest temperature rating of
electrical equipment or any wire connector (terminal
connector, lug, etc.). It is intended by this Rule that the
ampacity of conductors be selected from the
temperature column in Table 1, 2, 3, or 4 that
corresponds to the temperature rating marked on the
electrical equipment.

Slide 29 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

CSA C22.1-12, Appendix B — Notes on Rules

Rule 4-006 (cont’d)


As an example, where a conductor is terminated on a
breaker with a 75 °C rating, the maximum conductor
ampacity would be based on the 75 °C column of the
Tables.
It should be noted that the temperature rating of a wire
connector or lug that is connected to the equipment
may be higher than that of the equipment itself; it is the
equipment rating that determines the conductor size,
not the lug.

Slide 30 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

CSA C22.2 Product Safety Standards

LET’S LOOK AT SOME PART 2


STANDARDS…

Slide 31 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

CSA C22.2 No. 4: Enclosed and Dead-


Front Switches

7.2.4 A new switch shall be mounted as in actual


service, with the door and other openings closed. The
switch shall be wired with not less than 1.2 m (4 ft) of
Type RH, TW, TW75, or THW copper wire per terminal,
the wire size corresponding to the current rating of the
switch. For a switch rated 30, 60, or 100 A, the wire size
shall be based on the temperature rating of the wire as
indicated by the marking on the switch (see 9.2.47).

Slide 32 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

CSA C22.2 No. 4: Enclosed and Dead-


Front Switches
7.2.4 (cont’d)
Where a dual temperature rating is marked 60/75°C wire, the test
shall be conducted with 75°C wire. The test shall be made at any
convenient voltage. A temperature shall be considered to be
constant when three successive readings taken at 15-minute
intervals do not indicate any change.

9.2.47 A switch shall be marked in a readily visible location to


indicate the required temperature rating of all field-installed
conductors.

Slide 33 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

CSA C22.2 No. 5: Molded-Case Circuit Breakers,


Molded Case Switches, and CB Enclosures
7.1.2.1.5 Except as specified in 7.1.1.14, the conductors used in making
the connections to a circuit breaker for the calibration tests of 7.1.2.2
shall be of copper of the size indicated in Table 6.1.4.2.1 (CEC Table 2
and 4 75°C column amperage) and no less than 1.219 m (4 feet) in
length, except that an accommodating fixture may be used for circuit
breakers rated 100 A or less. For a circuit breaker or a circuit breaker
frame with an interchangeable trip unit rated more than 30 A but not
more than 125 A, the wire size shall be based on the temperature rating
of the wire as indicated by the marking on the circuit breaker or trip unit.
Where a dual wire temperature rating is marked, 60/75°C (140/167°F),
the test shall be conducted with both size wires or the most adverse one,
if it can be clearly determined.

Slide 34 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

CSA C22.2 No. 5: Molded-Case Circuit Breakers,


Molded-Case Switches, and CB Enclosures

7.1.1.14 If a circuit breaker is marked for use with aluminum


conductors only, all tests shall be conducted using aluminum
conductors.
9.1.2.14 A circuit breaker that is intended to be operated
continuously at 100 percent of its rating and that has a temperature
rise on a wiring terminal exceeding 50°C (90°F), see 7.1.4.3.1 and
7.1.4.3.2, shall be marked, Location Category B:
a) For use with 90°C (194°F) wire and the wire size. The wire size
shall be based on the ampacity of 75°C rated conductors as
indicated in Table 6.1.4.2.1.

Slide 35 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

CSA C22.2 No. 14: Industrial control equipment

5.1 General marking requirements


5.1.1 A permanent-type nameplate shall be attached to the individual
component or complete assembly and provide
(a) the manufacturer’s name, trademark, or other
descriptive marking;
(b) the electrical rating;
(c) the catalogue number or equivalent identifier; and
(d) the temperature rating for the field-installed
conductors for which the unit has been investigated,
as follows:

Slide 36 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

CSA C22.2 No. 14: Industrial control equipment

(i) the rating shall be 60 °C only, 60/75 °C, or 75 °C only; and


(ii) a marking shall not be required for devices rated 30 A or
less, or for horsepower-rated devices having an equivalent
current rating of 24 A or less (see Tables 18A and 19), that
have been tested when wired with 60 °C or 60/75 °C
conductors.
Note: For open-type equipment or in cases where it is not
practical to place a mark on the device, this information may be
placed on the smallest carton or on an instruction sheet included
with the device.

Slide 37 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

CSA C22.2 No. 29: Panelboards and


enclosed panelboards
5.11.1 Except as permitted in Clause 5.12, panelboards shall be
provided with main and branch circuit wiring terminals suitable for
the connection of conductor sizes selected from the 75/90 °C
column of Table 3 (CEC Table 2 and 4 75°C column amperage);
for circuit breakers rated at 125 A or less and marked for use with
60 °C wire only, the conductor sizes shall be selected from the 60
°C column of Table 3.
Example: 225A panel CSA spec 29 table specifies 4/0
corresponding to 75C table. 2012 CEC 90C table 2 corresponding
to this would be to test at 3/0 cable size.

Slide 38 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

CSA C22.2 No. 31: Switchgear


Assemblies
This section is complicated somewhat by the fact that it covers both
MV and LV assemblies. It allows for a temperature rise of 45C
over a 40C ambient.
The temperature requirement is similar in the ANSI C37.20.1 (Metal
Enclosed LV Gear), 2 (Metal Clad MV) and 3 (Metal Enclosed MV)
showing 90C cables as being specifically tested.
MV gear is ok with 90C cables sized per 90C tables.
NEC and manufacturer’s labels can provide some guidance on the
LV “grey area”, some labelling 75C.
NEC 110.14(C)(1)(b)(2) is clear that this is to be 75C for LV.
(which makes sense since it will connect to 75C equipment)

Slide 39 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

CSA C22.2 No. 244: Switchboards

6.2.6.18 A switchboard shall be provided with a marking readily visible


prior to wiring to indicate the required temperature rating of field-
installed conductors.
6.2.6.19 If a circuit breaker is to be installed in the field, the marking
shall indicate that the circuit breaker is to be marked either 60/75°C or
75°C if conductors sized for 75°C ampacity are to be used.
6.2.6.20 A switchboard or field wiring circuit rated more than 125 A
shall be marked for use with conductors sized for 75°C ampacity.
6.2.6.21 With respect to 6.2.6.18, a switchboard that is marked to
indicate that only 60°C field-installed conductors are to be used shall
not reference a field-installed unit that has been investigated for 75°C
conductors only.

Slide 40 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

CSA C22.2 No. 244: Switchboards

6.2.6.23 If the temperature rise exceeds 50°C on a wiring


connector as covered in item 6 of Table 13, a marking shall be
provided near the wiring connector indicating that 90°C wire
shall be used and it shall be sized based on the ampacity of
wire rated 75°C. If the switchboard is marked for use with
aluminum or copper-clad aluminum conductors, there shall be
a marking to indicate that the wire connectors shall be
identified AL9, AL9CU, or CU9AL. The marking shall be:
a) provided by the switchboard manufacturer if not already
provided on the switch or circuit breaker and
b) visible after installation.

Slide 41 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

CSA C22.2 No. 254: Motor Control Centres

6.3.27 Motor control centres shall be marked to indicate


the temperature rating (60 °C only, 60/75 °C, or 75 °C
only) of the field-installed conductors for which the
equipment has been investigated unless the field wiring
terminal is only intended for the connection of a control
circuit conductor.

Slide 42 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

The Issue….

Where equipment is not marked with a maximum


conductor termination temperature, 90°C shall
be used by default (4-006)
For electrical equipment rated for 600V and less,
terminations are typically rated 60°C, 75°C or
60°/75°C
No distribution or utilization equipment is
approved for the use of 90°C wire at its 90°C
ampacity.

Slide 43 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

The US Has Already Been Here

Slide 44 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

Importance of temperature ratings

“One of the most common misapplications of conductor


temperature ratings occurs when the established
temperature rating of the equipment termination is
ignored. This is particularly true for equipment rated for
600 V and lower, since it is tested as a complete system
using conductors sized by NEC rules. Reduced
conductor sizes result in the system having less ability
to dissipate heat, and therefore increases the operating
temperature of the equipment terminations. Conductors
must be sized by considering where they will terminate
and how that termination is rated.

Slide 45 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

Importance of temperature ratings

“Frequently, manufacturers are asked when


distribution equipment will be available with
terminations that will permit 90°C conductors at
90°C ampacity. This would require not only
significant equipment redesign (to handle the
additional heat), but also coordination of
downstream equipment … where the other end of
the conductor terminates. Significant changes in the
product testing/listing standards also would have to
occur.

Slide 46 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

Cable Temp Ampacity Experiment

Purpose:
– to determine the effect of using 90oC ampacity sized cable
on circuit breakers designed to use 75oC ampacity sized
cable
Method:
– Install breaker into an enclosure and conduct a heat run test
with:
• 1) 75oC sized, min. 4ft of cable line and load, and
• 2) 90oC sized min. 4ft of cable line and load
Measure resulting temperature rise

Slide 47 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

Cable Temp Ampacity Experiment

Slide 48 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

Cable Temp Ampacity Experiment

600A

600A

Slide 49 / 90°C Panel Discussion/ Mar. 2014


Safety Codes Council Conference Banff 2014

Results (Preliminary / Simple Testing


Only)

Temp Margin
Breaker Size Cu size Diff Rise Diff Diff
-65.5%
800 -16.4% 11.0% (Fail)
-65.5%
600 -14.1% 21.1% (Fail)
-32.9%
225 -20.6% 12.3% (Pass*)
-57.3%
225L -20.6% 24.0% (Pass*)
* Preliminary Heat Rise Pass Only. Additional Tests would be req’d.
Slide 50 / 90°C Panel Discussion/ Mar. 2014
Safety Codes Council Conference Banff 2014

Panel Discussion

Slide 51 / 90°C Panel Discussion/ Mar. 2014

You might also like