POWER SUPPLY 15.1 DC / DC CONVERTER 15.3
QUINT PS-1AC/24DC/10 QUINT PS-24DC/24DC/10
INPUT OUTPUT INPUT OUTPUT
230V-50Hz 24V-D.C. 10A 24V-D.C. 24V-D.C. 10A
L N PE + - + - + -
2 4 2 4 1 3
1F1 1F2 1F3
1 3 S202 1 3 S202 2 4 S202
10A (B) 16A (B) 6A (B)
EARTH - 1x6
DISTRIBUTIONBOARD 3x230VAC "13EL"
SUPPLY 24V-D.C.
22.26002 - 4x0,75
14.210061 - 2x4
NO PART OF THIS WORK MAY BE COPIED, STORED OR PUBLISHED,
WITHOUT PRIOR WRITTEN PERMISSION OF ALEWIJNSE.
APPROVED :
=24SP12/10 11
IN PA IS Name: LNG FLEXITANKER YARD NBR. : 803
BODEWES SHIPYARDS HOOGEZAND
CL SFI-DOC_NO: 815
CO2 ALARM INSTALLATION "26CO2" PROJECT NBR. : 11000334
= 26C02
* NO DELIVERY ALEWIJNSE
PANEL JOBNBR. :
D 26.11.2015 HDJ 10
MARINE SYSTEMS PAG.
R 06.10.2016 HDJ HET GANGBOORD 18 9206 BJ DRACHTEN HOLLAND INSPECT./CLASS. : I.V.W./B.V.
NO PART OF THIS WORK MAY BE COPIED, STORED OR PUBLISHED,
WITHOUT PRIOR WRITTEN PERMISSION OF ALEWIJNSE.
APPROVED :
IN
10
0
PA
R
D
IS
CL
2X1
21
1 1
1
26.20001 F.R. 4x1,5
LIMIT SWITCH CO2 VALVE
22
1
2 2
04.10.2016
26.11.2015
ENGINE ROOM
CO2 ALARM INSTALLATION "26CO2"
13
CO2 ROOM
3 3
HDJ
HDJ
14
4 4
*
26CO2-16
21
1 1
5
26.20003 F.R. 4x1,5
LIMIT SWITCH EMERGENCY RELEASE STATION
SFI-DOC_NO: 815
22
2
2 2
6
ENGINE ROOM
CO2 ALARM INSTALLATION "26CO2"
13
CO2 ROOM
3 3
* NO DELIVERY ALEWIJNSE
14
4 4
*
3X1
21
1 1
1
26.30001 F.R. 4x1,5
LIMIT SWITCH CO2 VALVE
22
3
2 2
2
LNG AUX. ENGINE ROOM
CO2 ALARM INSTALLATION "26CO2"
13
26CO2-17
CO2 ROOM
3 3
3
14
4 4
4
MARINE SYSTEMS
*
4X1
21
1 1
1
22
4
2 2
2
SWITCHBOARD ROOM
CO2 ALARM INSTALLATION "26CO2"
13
26CO2-18
CO2 ROOM
3 3
3
14
4 4
4
*
5X1
21
1 1
1
22
5
2 2
2
COMPRESSOR ROOM
CO2 ALARM INSTALLATION "26CO2"
13
26CO2-19
CO2 ROOM
3 3
3
14
4 4
4
*
6
YARD NBR.
PROJECT NBR.
PANEL JOBNBR.
INSPECT./CLASS.
:
8
: 803
: 11000334
: I.V.W./B.V.
=
PAG.
9
11
26C02
12
NO PART OF THIS WORK MAY BE COPIED, STORED OR PUBLISHED,
WITHOUT PRIOR WRITTEN PERMISSION OF ALEWIJNSE.
APPROVED :
IN
11
0
PA
R
D
IS
CL
2X2
21
1 1
1
26.20002 F.R. 4x1,5
LIMIT SWITCH CO2 RELEASE STATION
22
1
2 2
04.10.2016
26.11.2015
ENGINE ROOM
CO2 ALARM INSTALLATION "26CO2"
13
26CO2-16
3 3
FIRE STATION
HDJ
HDJ
14
4 4
*
3X2
21
1 1
1
26.30002 F.R. 4x1,5
LIMIT SWITCH CO2 RELEASE STATION
SFI-DOC_NO: 815
22
2
2 2
2
LNG AUX. ENGINE ROOM
CO2 ALARM INSTALLATION "26CO2"
13
26CO2-17
3 3
FIRE STATION
* NO DELIVERY ALEWIJNSE
14
4 4
*
4X2
21
1 1
1
26.40002 F.R. 4x1,5
LIMIT SWITCH CO2 RELEASE STATION
22
3
2 2
2
SWITCHBOARD ROOM
CO2 ALARM INSTALLATION "26CO2"
13
26CO2-18
3 3
3
FIRE STATION
14
4 4
4
MARINE SYSTEMS
*
5X2
21
1 1
1
22
4
2 2
2
COMPRESSOR ROOM
CO2 ALARM INSTALLATION "26CO2"
13
26CO2-19
3 3
3
FIRE STATION
14
4 4
4
*
3X3
21
1 1
1
22
5
2 2
2
13
26CO2-17
3 3
3
PLATFORM DECK
NEAR ENTRANCE
14
4 4
4
*
4X3
21
1 1
1
2 2
2
SWITCHBOARD ROOM
CO2 ALARM INSTALLATION "26CO2"
13
DECK 9800
3 3
3
4 4
4
*
5X3
21
1 1
1
2 2
2
COMPRESSOR ROOM
CO2 ALARM INSTALLATION "26CO2"
13
26CO2-19
3 3
MAIN DECK
3
NEAR ENTRANCE
14
4 4
4
YARD NBR.
PROJECT NBR.
PANEL JOBNBR.
INSPECT./CLASS.
EEX .. II.. T..
:
8
: 803
: 11000334
: I.V.W./B.V.
=
PAG.
9
12
26C02
13
NO PART OF THIS WORK MAY BE COPIED, STORED OR PUBLISHED,
WITHOUT PRIOR WRITTEN PERMISSION OF ALEWIJNSE.
APPROVED :
IN
12
0
PA
R
D
IS
CL
2X4
1
1
26.20004 F.R. 2x1,5
*
SIREN CO2 ALARM
1
04.10.2016
26.11.2015
DECK 9800 ENGINE ROOM STBD AFT.
2
26.20005 F.R. 2x1,5
HDJ
HDJ
SIREN CO2 ALARM
PLATFORM DECK ENGINE ROOM STBD AFT.
*
SIREN CO2 ALARM
PLATFORM DECK ENGINE ROOM PORT FORE
SFI-DOC_NO: 815
2
*
SIREN CO2 ALARM
TANKTOP ENGINE ROOM STBD FORE
* NO DELIVERY ALEWIJNSE
26.20008 F.R. 2x1,5
*
SIREN CO2 ALARM
MGO. AUX ENGINE ROOM
26CO2-16
26.20009 F.R. 2x1,5
*
SIREN CO2 ALARM
3
PURIFIER ROOM
*
SIREN CO2 ALARM
WORKSHOP STORE
MARINE SYSTEMS
26.20011 F.R. 2x1,5
*
SIREN CO2 ALARM
WORKSHOP
*
SIREN CO2 ALARM
STEERINGGEAR ROOM
*
SIREN CO2 ALARM
DECK FF ROOM
3X4
1
1
*
SIREN CO2 ALARM
5
26CO2-17
EEX d IIB T4
4X4
1
1
*
SIREN CO2 ALARM
26CO2-18
SWITCHBOARD ROOM 2
2
5X4
6
1
1
2
BODEWES SHIPYARDS HOOGEZAND COMPRESSOR ROOM
2
EEX d IIB T4
7
YARD NBR.
PROJECT NBR.
PANEL JOBNBR.
INSPECT./CLASS.
:
8
: 803
: 11000334
: I.V.W./B.V.
=
PAG.
9
13
26C02
14
NO PART OF THIS WORK MAY BE COPIED, STORED OR PUBLISHED,
WITHOUT PRIOR WRITTEN PERMISSION OF ALEWIJNSE.
APPROVED :
IN
13
0
PA
R
D
IS
CL
2X5
1
1
26.20020 F.R. 2x1,5
=10P/711.3
CO2-2/20
MAINSWITCHBOARD 3x440VAC "10P"
1
04.10.2016
26.11.2015
CO2 RELEASE ENGINE ROOM
STOP VENTILATION
1
3
26.20021 F.R. 2x1,5
=10P/711.7
HDJ
HDJ
CO2-2/21
MAINSWITCHBOARD 3x440VAC "10P"
2
4
CO2 RELEASE ENGINE ROOM
STOP VENTILATION
26CO2-16
1
5
26.20022 F.R. 2x1,5
CO2-2/22
ENGINE CONTROL ROOM DESK "40DE"
=40DE/1410.8
2
6
24V DC DISTRIBUTIONBOARD "14E21"
CO2 RELEASE ENGINE ROOM
SFI-DOC_NO: 815
2
7
8
* NO DELIVERY ALEWIJNSE
3X5
1
1
26.30020 F.R. 2x1,5
=10P/711.3
CO2-3/20
MAINSWITCHBOARD 3x440VAC "10P"
2
2
CO2 RELEASE LNG AUX. ENGINE ROOM
STOP VENTILATION
3
1
3
26.30021 F.R. 2x1,5
=10P/711.8
CO2-3/21
MAINSWITCHBOARD 3x440VAC "10P"
2
4
1
5
MARINE SYSTEMS
CO2-3/22
ENGINE CONTROL ROOM DESK "40DE"
=40DE/1410.7
2
6
8
4X5
1
1
=10P/711.4
CO2-4/20
MAINSWITCHBOARD 3x440VAC "10P"
2
2
=10P/711.8
CO2-4/21
MAINSWITCHBOARD 3x440VAC "10P"
5
2
4
1
5
CO2-4/22
ENGINE CONTROL ROOM DESK "40DE"
=40DE/1410.9
2
6
5X5
26CO2-19
1
5
2
6
YARD NBR.
8
PROJECT NBR.
PANEL JOBNBR.
INSPECT./CLASS.
:
8
: 803
: 11000334
: I.V.W./B.V.
=
PAG.
9
14
26C02
15
0 1 2 3 4 5 6 7 8 9
ALARM
24V-D.C.
10.4/CO2-1F3/+ CO2-1F3/+/16.1
13 11 13 11
1E1 1K1 1E2 1K2
10.1 15.1 10.3 15.3
14 14 14 14
FAULT MAIN FAULT BACK-UP
ALARM SUPPLY ALARM SUPPLY
24V-D.C.
1X1 1
21 1K1
15.1
24 MAIN
SUPPLY
21
1K2
15.3
24
BACK-UP
SUPPLY
1X1 2
NO PART OF THIS WORK MAY BE COPIED, STORED OR PUBLISHED,
A1 A1
1K1 1H1 1K2 1H2
A2 MAIN A2 BACK-UP
SUPPLY SUPPLY
WITHOUT PRIOR WRITTEN PERMISSION OF ALEWIJNSE.
(GREEN) (GREEN)
10.5/CO2-1F3/- CO2-1F3/-/16.1
NO NC NO NC
APPROVED :
15.2 15.4
15.6 15.6
14 16
IN PA IS Name: LNG FLEXITANKER YARD NBR. : 803
BODEWES SHIPYARDS HOOGEZAND
CL SFI-DOC_NO: 815
CO2 ALARM INSTALLATION "26CO2" PROJECT NBR. : 11000334
= 26C02
* NO DELIVERY ALEWIJNSE
PANEL JOBNBR. :
D 26.11.2015 HDJ 15
MARINE SYSTEMS PAG.
R 04.10.2016 HDJ HET GANGBOORD 18 9206 BJ DRACHTEN HOLLAND INSPECT./CLASS. : I.V.W./B.V.
0 1 2 3 4 5 6 7 8 9
21 * 21 * 21 * 13 * 11
LIMIT SWITCH LIMIT SWITCH LIMIT SWITCH LIMIT SWITCH 2K1
CO2 VALVE CO2 EMERG. CO2 RELEASE STATION 16.1
22 22 22 14 CO2 VALVE 14
ENGINE ROOM RELEASE STATION ENGINE ROOM ENGINE ROOM CO2 ALARM
ENGINE ROOM ENGINE ROOM
2X1 2 6 2X2 2 2X1 4
230V-60Hz 230V-60Hz 24V-D.C. 24V-D.C.
2X1 7 2X5 1 3 5 7
13 * 11 21 31 41
LIMIT SWITCH 2K2 2K2 2K2 2K2
16.4 16.4 16.4 16.4
14 CO2 EMERG. 14 24 34 44
RELEASE STATION STOP STOP CLOSE CLOSE
ENGINE ROOM VENTILATION VENTILATION FIRE DAMPERS FIRE DAMPERS
2X1 8 2X5 2 4 6 8
2X2 3
13 *
LIMIT SWITCH
14 CO2 RELEASE STATION
ENGINE ROOM
2X2 4
2X4 1
10/2A
ENGINE ROOM
NO PART OF THIS WORK MAY BE COPIED, STORED OR PUBLISHED,
A1 A1
2X4 2
2K1 2K2
A2 A2 10/2A
WITHOUT PRIOR WRITTEN PERMISSION OF ALEWIJNSE.
15.4/CO2-1F3/- CO2-1F3/-/17.1
NO NC NO NC
APPROVED :
16.5 16.6
16.7
16.7
16.8
15 17
IN PA IS Name: LNG FLEXITANKER YARD NBR. : 803
BODEWES SHIPYARDS HOOGEZAND
CL SFI-DOC_NO: 815
CO2 ALARM INSTALLATION "26CO2" PROJECT NBR. : 11000334
= 26C02
* NO DELIVERY ALEWIJNSE
ENGINE ROOM PANEL JOBNBR. :
D 26.11.2015 HDJ 16
MARINE SYSTEMS PAG.
R 04.10.2016 HDJ HET GANGBOORD 18 9206 BJ DRACHTEN HOLLAND INSPECT./CLASS. : I.V.W./B.V.
0 1 2 3 4 5 6 7 8 9
21 * 21 * 21 * 13 * 11
LIMIT SWITCH LIMIT SWITCH LIMIT SWITCH LIMIT SWITCH 3K1
CO2 VALVE CO2 RELEASE STATION CO2 RELEASE STATION 17.1
22 22 22 14 CO2 VALVE 14
LNG AUX. ENG. ROOM LNG AUX. ENG. ROOM LNG AUX. ENG. ROOM LNG AUX. ENG. ROOM CO2 ALARM
LNG AUX. ENG. ROOM
3X1 2 3X2 2 3X3 2 3X1 4
230V-60Hz 230V-60Hz 24V-D.C. 24V-D.C.
3X2 3 3X5 1 3 5 7
13 * 11 21 31 41
LIMIT SWITCH 3K2 3K2 3K2 3K2
17.4 17.4 17.4 17.4
14 CO2 RELEASE STATION 14 24 34 44
LNG AUX. ENG. ROOM STOP STOP CLOSE CLOSE
VENTILATION VENTILATION FIRE DAMPERS FIRE DAMPERS
3X2 4 3X5 2 4 6 8
3X3 3
13 *
LIMIT SWITCH
14 CO2 RELEASE STATION
LNG AUX. ENG. ROOM
3X3 4
3X4 1
10/1,25A
A1 A1
3X4 2
3K1 3K2
A2 A2 10/1,25A
WITHOUT PRIOR WRITTEN PERMISSION OF ALEWIJNSE.
16.6/CO2-1F3/- CO2-1F3/-/18.1
NO NC NO NC
APPROVED :
17.5 17.6
17.7
17.7
17.8
16 18
IN PA IS Name: LNG FLEXITANKER YARD NBR. : 803
BODEWES SHIPYARDS HOOGEZAND
CL SFI-DOC_NO: 815
CO2 ALARM INSTALLATION "26CO2" PROJECT NBR. : 11000334
= 26C02
* NO DELIVERY ALEWIJNSE
LNG AUX. ENGINE ROOM PANEL JOBNBR. :
D 26.11.2015 HDJ 17
MARINE SYSTEMS PAG.
R 04.10.2016 HDJ HET GANGBOORD 18 9206 BJ DRACHTEN HOLLAND INSPECT./CLASS. : I.V.W./B.V.
0 1 2 3 4 5 6 7 8 9
21 * 21 * 21 * 13 * 11
LIMIT SWITCH LIMIT SWITCH LIMIT SWITCH LIMIT SWITCH 4K1
CO2 VALVE CO2 RELEASE STATION CO2 RELEASE STATION 18.1
22 22 22 14 CO2 VALVE 14
SWITCHBOARD ROOM SWITCHBOARD ROOM SWITCHBOARD ROOM SWITCHBOARD ROOM CO2 ALARM
SWITCHBOARD ROOM
4X1 2 4X2 2 4X3 2 4X1 4
230V-60Hz 230V-60Hz 24V-D.C. 24V-D.C.
4X2 3 4X5 1 3 5 7
13 * 11 21 31 41
LIMIT SWITCH 4K2 4K2 4K2 4K2
18.4 18.4 18.4 18.4
14 CO2 RELEASE STATION 14 24 34 44
SWITCHBOARD ROOM STOP STOP CLOSE CLOSE
VENTILATION VENTILATION FIRE DAMPERS FIRE DAMPERS
4X2 4 4X5 2 4 6 8
4X3 3
13 *
LIMIT SWITCH
14 CO2 RELEASE STATION
SWITCHBOARD ROOM
4X3 4
4X4 1
10/1,25A
SWITCHBOARD ROOM
NO PART OF THIS WORK MAY BE COPIED, STORED OR PUBLISHED,
A1 A1
4X4 2
4K1 4K2
A2 A2 10/1,25A
WITHOUT PRIOR WRITTEN PERMISSION OF ALEWIJNSE.
17.6/CO2-1F3/- CO2-1F3/-/19.1
NO NC NO NC
APPROVED :
18.5 18.6
18.7
18.7
18.8
17 19
IN PA IS Name: LNG FLEXITANKER YARD NBR. : 803
BODEWES SHIPYARDS HOOGEZAND
CL SFI-DOC_NO: 815
CO2 ALARM INSTALLATION "26CO2" PROJECT NBR. : 11000334
= 26C02
* NO DELIVERY ALEWIJNSE
SWITCHBOARD ROOM PANEL JOBNBR. :
D 26.11.2015 HDJ 18
MARINE SYSTEMS PAG.
R 04.10.2016 HDJ HET GANGBOORD 18 9206 BJ DRACHTEN HOLLAND INSPECT./CLASS. : I.V.W./B.V.
0 1 2 3 4 5 6 7 8 9
21 * 21 * 21 * 13 * 11
LIMIT SWITCH LIMIT SWITCH LIMIT SWITCH LIMIT SWITCH 5K1
CO2 VALVE CO2 RELEASE STATION CO2 RELEASE STATION 19.1
22 22 22 14 CO2 VALVE 14
COMPRESSOR ROOM COMPRESSOR ROOM COMPRESSOR ROOM COMPRESSOR ROOM CO2 ALARM
COMPRESSOR ROOM
5X1 2 5X2 2 5X3 2 5X1 4
230V-60Hz 230V-60Hz 24V-D.C. 24V-D.C.
5X2 3 5X5 1 3 5 7
13 * 11 21 31 41
LIMIT SWITCH 5K2 5K2 5K2 5K2
19.4 19.4 19.4 19.4
14 CO2 RELEASE STATION 14 24 34 44
COMPRESSOR ROOM STOP STOP CLOSE CLOSE
VENTILATION VENTILATION FIRE DAMPERS FIRE DAMPERS
5X2 4 5X5 2 4 6 8
5X3 3
13 *
LIMIT SWITCH
14 CO2 RELEASE STATION
COMPRESSOR ROOM
5X3 4
5X4 1
10/1,25A
COMPRESSOR ROOM
NO PART OF THIS WORK MAY BE COPIED, STORED OR PUBLISHED,
A1 A1
5X4 2
5K1 5K2
A2 A2 10/1,25A
WITHOUT PRIOR WRITTEN PERMISSION OF ALEWIJNSE.
18.6/CO2-1F3/-
NO NC NO NC
APPROVED :
19.5 19.6
19.7
19.7
19.8
18 =27ES1/10
IN PA IS Name: LNG FLEXITANKER YARD NBR. : 803
BODEWES SHIPYARDS HOOGEZAND
CL SFI-DOC_NO: 815
CO2 ALARM INSTALLATION "26CO2" PROJECT NBR. : 11000334
= 26C02
* NO DELIVERY ALEWIJNSE
COMPRESSOR ROOM PANEL JOBNBR. :
D 26.11.2015 HDJ 19
MARINE SYSTEMS PAG.
R 04.10.2016 HDJ HET GANGBOORD 18 9206 BJ DRACHTEN HOLLAND INSPECT./CLASS. : I.V.W./B.V.