EMUA Solution in 3900 Series Site Internal Open

EMUA Solution for 3900 Series BTS


00102313 Xiao Fei
2009-6-10
1. Alarm Assignment: .....................................................................................................................1
1.1 Define EMUA alarms and port: .......................................................................................1
1.2 Map BTS alarm to BSC alarm: .......................................................................................2
2. Configure BSC Alarm: ...............................................................................................................3
3. EMUA Board Configuration......................................................................................................4
3.1 Slot Number: .....................................................................................................................4
3.2 Configure EMUA Board Attributes: ...............................................................................4
3.3 Binding BTS alarm with BSC alarm:..............................................................................5
Bind Alarm ..............................................................................................................................5
4. Trouble Shooting .........................................................................................................................5

In 3900 series BTS, UEIU/UPEU are used to provide environmental alarm connections,
however, the total number of alarms of these 2 boards are only 16. If there are over 16 alarms to
be connected, we could use EMUA board which can provide 32 Environmental Alarms.

1. Alarm Assignment:
1.1 Define EMUA alarms and port:

2009-06-19 HUAWEI Confidential Page1, Total6


Security Level:
EMUA Solution in 3900 Series Site Internal Open

1.2 Map BTS alarm to BSC alarm:


The Alarm ID arranges from 6292 to 6354.
In BSC, the available BTS Custom Environment Alarm ID arrange from 65384 to 65533.
For example:
BSC
Monitoring Port Alarm Alarm
Unit Port No. ID Alarm Name ID Alarm Level
S1+/S1- 1 6292 AC Main Alarm 65420 Major
S2+/S2- 2 6294 DC High Voltage Alarm 65422 Major
S3+/S3- 3 6296 DC Low Voltage Alarm 65424 Warning
2009-06-19 HUAWEI Confidential Page2, Total6
Security Level:
EMUA Solution in 3900 Series Site Internal Open

S4+/S4- 4 6298 DC Module Alarm 65426 Major


S5+/S5- 5 6300 65428
S6+/S6- 6 6302 65430
S7+/S7- 7 6304 65432
S8+/S8- 8 6306 65434
Low Voltage Load Disconnect
S9+/S9- 9 6308 Alarm 65436 Warning
S10+/S10- 10 6310 65438
S11+/S11- 11 6312 65440
S12+/S12- 12 6314 65442
S13+/S13- 13 6316 65444
S14+/S14- 14 6318 65446
S15+/S15- 15 6320 65448
S16+/S16- 16 6322 65450
S17+/S17- 17 6324 65452
S18+/S18- 18 6326 65454
S19+/S19- 19 6328 65456
S20+/S20- 20 6330 65458
S21+/S21- 21 6332 65460
S22+/S22- 22 6334 65462
S23+/S23- 23 6336 65464
S24+/S24- 24 6338 65466
S25+/S25- 25 6340 65468
S26+/S26- 26 6342 65470
S27+/S27- 27 6344 65472
S28+/S28- 28 6346 65474
S29+/S29- 29 6348 65476
S30+/S30- 30 6350 65478
S31+/S31- 31 6352 65480
S32+/S32- 32 6354 65482

2. Configure BSC Alarm:


Method 1--Define on M2000 for all BSC
Method 2 Define on BSC for each BSC
NE Alarm Setting-Alarm Definition-Add
Alarm Maintenance-Query Alarm Configuration
Choose BSC, Change Alarm Name and Level
Set Environment Aalrm Configuration
Click "Apply"

2009-06-19 HUAWEI Confidential Page3, Total6


Security Level:
EMUA Solution in 3900 Series Site Internal Open

3. EMUA Board Configuration


In BSC data, EMUA is configured as DEMU board.
3.1 Slot Number:
If we connect RS485 to UPEU MON0, the EMUA should be configured in slot0.
If we connect RS485 to UPEU MON1, the EMUA should be configured in slot1.

3.2 Configure EMUA Board Attributes:


2009-06-19 HUAWEI Confidential Page4, Total6
Security Level:
EMUA Solution in 3900 Series Site Internal Open

In LMT:
9 Board Parameter Configuration Enabled: yes
9 Special Alarm Switch Enabled: not chosen=enabled; chosen=disabled;
9 Common Alarm Switch Enabled: not chosen=enabled; chosen=disabled;
9 Special Alarm Switch Valid Level Configuration: should be “High Level” (not chosen)
9 Common Alarm Switch Valid Level Configuration: chosen= Low Level; not chosen=High
Level
MML Command: “MOD DEMUBP”.

3.3 Binding BTS alarm with BSC alarm:


Bind Alarm
SET ALMPORT: SITENAME="OSV2", CN=0, SRN=2, SN=0, PN=1, SW=OPEN, AID=65420,
PT=BOOL, AVOL=LOW;
SET ALMPORT: SITENAME="PRAB", CN=0, SRN=2, SN=0, PN=2, SW=OPEN, AID=65422,
PT=BOOL, AVOL=LOW;
SET ALMPORT: SITENAME="PRAB", CN=0, SRN=2, SN=0, PN=3, SW=OPEN, AID=65424,
PT=BOOL, AVOL=LOW;
SET ALMPORT: SITENAME="PRAB", CN=0, SRN=2, SN=0, PN=4, SW=OPEN, AID=65426,
PT=BOOL, AVOL=LOW;
SET ALMPORT: SITENAME="PRAB", CN=0, SRN=2, SN=0, PN=9, SW=OPEN, AID=65436,
PT=BOOL, AVOL=LOW;

4. Trouble Shooting
1. Board Communication Alarm, Board Type=70, Alarm ID: 6420.
2009-06-19 HUAWEI Confidential Page5, Total6
Security Level:
EMUA Solution in 3900 Series Site Internal Open

BBU fail to communicate with EMUA board, check:


Power Input and DC Switch of EMUA;
The data configuration of slot number is consistent with Physical Connection of MON Port.

2. Alarm report are opposite with actual alarm status


For example, the door alarm report to BSC when the door is closed and vise versa.
Check: Alarm Switch Valid Level Configuration is consistent with actual voltage level.