For the short-circuiting transfer mode of the gas metal-arc process, when the qualification test

coupon
thickness is less than 1/2”, an increase in thickness beyond 1.1 times that of the qualification test
coupon. For thicknesses of ½” & greater, use Table QW-451.1 or Table QW-451.2, as applicable

miniature boiler pressure vessel shall be inspected while being tested at a hydrostatic pressure
equal to three times the maximum allowable working pressure.

A minimum metal temperature of 60°F is permitted during the hydrostatic test in

PMB-21.1, provided the shell thickness is 3/8 in. or less .

Miniature boilers shall have the lowest visible part of the water gage located at least 1 in. above
the lowest permissible water level specified by the Manufacturer.

Each miniature boiler shall be equipped with a blowoff connection, not less than NPS 1/2”.

miniature boiler exceeding 12 in internal diameter shall be fitted with not less than three brass
washout plugs of 1 in