Professional Documents
Culture Documents
Input parameters
Hot water temperature 40.5 C
Cold water temperature 29.5 C
Wet bulb temperature 26 C
Range of cooling tower 11 C
Approach 3.5 C
Diameter of fan 3.8 m
Diameter of fan hood 3.9 m
Avarage air velocity at exit 6 m/s
Density of water 1000 Kg/m^3
Density of air 1.2 Kg/m^3
Specific heat capacity of water 4.178 kj/kgK
0.1 bar at
45.8 C
29.5 C
COOLING TOWER DESIGN
Second method
1 BTU/Lb F
T has
85.1 53.1
87.08 55.13
71.766864 m^3/sec 95 63.04
880966.3645 lb/hr/cell 0.111 m^3/sec/cell 399.6 m^3/hr/cell 96.98 64.83
102.92 70.94
104.9 73.02
1.411616
78.63327 Kg/s
ate tower characteristic by the simpsion rule
13 kj/kg 5.59 BTU/lb
ha has-ha 1/(has-ha)
34.4 18.7 0.053476
37.195 17.935 0.055757
48.375 14.665 0.06819
51.17 13.66 0.073206
59.555 11.385 0.087835
62.35 10.67 0.093721
0.071247
1.41069
tic Graph cooling water temperature 10°F above wet bulb temperature
Determine the tower dimentions
Tower hight 15.67981 ft 4.779207 m
Area of tower 121345.6 ft^2 11273 m^2