Professional Documents
Culture Documents
Spaj 110 C Earth-Fault Relay: User S Manual and Technical Description
Spaj 110 C Earth-Fault Relay: User S Manual and Technical Description
Earth-fault relay
User´s manual and Technical description
B
I
2
I n = 1A 5A ( I ) f n = 50Hz Io IRF
5
60Hz
SPAJ 110 C
STEP 0.35
80...265V –
~ Io>
18...80V – U aux In STEP
0.1 0.8
SPCJ 1C8
0.5
REGISTERS
t > [ s] SG1
0 0 0 0 k
1
0.05 1.0 2
3
1 I o /I n 4
5
2 n (I o> ) 2.5 6
3 n (I o>> ) SGR I o >> 7
4.0 8
4 t / t >[ %] 1 In 0 1
2 0.5
5 t / t >> [ % ] 3
4
5 RESET
6 0.5
7
8
t >> [ s ]
0 1
0.05 1.0
I o > I o >>
1043B
1311
The complete manual for the earth-fault relay SPAJ 110 C includes the following partial manuals:
Features Low-set neutral overcurrent stage with definite Serial interface for connecting the relay to a fibre
time or inverse time characteristic optic object bus and substation and network
control systems
High-set neutral overcurrent stage with definite
time characteristic Digital display of setting values, neutral current
measured, memorized fault values, etc.
Output relay functions to be freely configured
Continuous self-supervision with auto-diagnos-
Flexible adaptation to different types of applica- tics of hardware and software
tion
Application The earth-fault relay SPAJ 110 C is designed to definite-time characteristic or with inverse-time
be used for selective earth-fault protection, ei- characteristic, while the high-set stage operates
ther primary or back-up protection, in solidly with definite time characteristic only. The earth-
earthed or low-resistance earthed power sys- fault relay is used both as primary and back-up
tems. earth-fault protection relay for feeders, trans-
formers, generators and motors. The relay can
The relay has two protection stages: a low-set be configured to cooperate with a residual volt-
overcurrent stage I0> and a high-set overcurrent age relay used for blocking/deblocking the op-
stage I0>>. The low-set stage operates with eration of the earth-fault relay.
2
Description of The earth-fault relay SPAJ 110 C is a secondary starts once its set start value I0>> is exceeded
operation relay that is connected to the current transform- and, when the set operate time t>> expires, the
ers of the object to be protected. The earth-fault relay operates.
current can be measured either via a set of three
phase current transformers in a residual current The low-set stage of the earth-fault relay can be
connection or a window-type core-balance cur- given either definite-time or inverse-time char-
rent transformer. When a core-balance current acteristic. At inverse time characteristic four
transformer is used, it should be secured that the inverse time curve sets with different degrees of
repeatability of the current transformer is suffi- inversity are available: Normal inverse, Very
cient also at high earth-fault currents. When an inverse, Extremely inverse and Long-time in-
earth-fault occurs, the relay delivers an alarm verse. These curve sets comply with the BS 142
signal, trips the circuit breaker or starts an and IEC 60255 standards.
external auto-reclose relay, depending on the
application and the configuration of the relay. The start signal from the earth-fault relay is
received as contact function. The start signal can
When the energizing current exceeds the set be used, for instance, for blocking cooperating
start value I0> of the low-set stage, the earth- protection relays.
fault relay starts. When, at definite time opera-
tion, the set operate time t> or, at IDMT opera- The relay contains one optically isolated logic
tion, the calculated operate time t>, expires, the input for incoming external control signals,
relay operates. In the same way the high-set stage generally blocking signals.
TRIP 1
Io NON-DIRECTIONAL DEFINITE TIME
OR INVERSE TIME EARTH-FAULT 51N
TRIP 2
PROTECTION STAGE Io>
SIGNAL 1
NON-DIRECTIONAL DEFINITE TIME
EARTH-FAULT PROTECTION 50N
STAGE Io>>
START 1
IRF
Fig. 1. Protection functions of the earth-fault relay SPAJ 110 C. The encircled numbers refer to the
ANSI (=American National Standards Institute) number of the concerned protection function.
3
Connections
L1
L2
L3
0 -
I - I
+
Rx Tx
0
SPA-ZC_
+
+ (~) Uaux
- (~)
BS IRF START2 START1 SIGNAL1 TRIP2 TRIP1
+
SERIAL
PORT
25 26 27 10 11 61 62 70 71 72 73 74 75 77 78 80 81 68 69 65 66
≅_
5A
1A
E F D C B A
+ - U3
1 1 1 1
SGR/1
U3
SGR 3 2 4 7 5 8 6
IRF
SS1
t >,k TS1
Io>
SGB
4
5
SS2
t >> TS2
Io>>
U1 I/O
SPAJ 110 C U2
4
25 61
Rx 26 62
TTL
Tx 27 65
66
68
69
Made in Finland
73 80
74 81
75 77
70 78
71 10
72 11
B470498
Contacts Function
The earth-fault relay SPAJ 110 C is connected The bus connection module is fitted to the D-
to the fibre optic data communication bus by type connector (SERIAL PORT) on the rear
means of the bus connection module SPA-ZC panel of the relay. The opto-connectors of the
17 or SPA-ZC 21. optical fibres are plugged into the counter con-
nectors Rx and Tx on the bus connection mod-
ule.
5
Configuration of The start signal of the I0> stage is firmly/solidly following functions can be selected with the
output relays wired to output relay F and the trip signal to switches of the SGR switchgroup on the front
output relay A. The trip signal of the I0>> stage panel:
is wired to output relay A. In addition, the
SGR/1 Routes the external blocking signal to the neutral current module 1
The circuit breakers can be operated directly relay or two separate circuit breakers can be
both with output relay A or output relay B. Thus operated with the same protection relay.
either operation stage may have its own output
6
Start and B
2. The yellow LED (I0) on the upper black part
operation 2
I of the front plate indicates, when lit, that the
indicators I n = 1A 5A ( I ) f n = 50Hz
5
Io IRF value of the neutral current I0 is currently
60Hz
being displayed.
SPAJ 110 C
80...265V –
STEP 0.35 3. The red IRF indicator of the self-supervision
~ Io>
18...80V – U aux In
0.1 0.8
STEP system indicates, when lit, that a permanent
SPCJ 1C8 internal relay fault has been detected. The
REGISTERS
t > [ s]
0.5
SG1
fault code appearing on the display once a
0 0 0 0 k
0.05 1.0
1
2
3
fault has been detected should be recorded
1
2
I o /I n
n (I o> ) 2.5
4
5
6
and notified when service is ordered.
3 n (I o>> ) SGR I o >> 7
4.0 8
4 t / t >[ %] 1 In 0 1
5 t / t >> [ % ]
2
3
4
0.5
4. The green Uaux LED on the front panel is lit
RESET
5
6
7
0.5 when the power supply module operates prop-
0 1
8
t >> [ s ]
0.05 1.0
erly.
I o > I o >>
1311
RS 421 Ser.No. SPCJ 1C8
indicates, when lit, that the setting value is
being displayed.
1. Either current stage has its own operation
indicator (I0> and I0>>), located in the right 6. The LED of the SG1 switchgroup indicates,
bottom corner of the front plate of the relay when lit, that the checksum of the switch-
module. Yellow light indicates that the con- group is being displayed.
cerned stage has started and red light that the
stage has operated (tripped). The start and operation indicators, the function
of the SG2 software switchgroup and the func-
With the SG2 software switchgroup the start tions of the LED indicators during setting are
and trip indicators can be given a latching described more detailed in manual for the non-
function, which means that the LEDs remain directional earth-faut relay module SPCJ 1C8.
lit, although the signal that caused operation
returns to normal. The indicators are reset
with the RESET push-button. An unreset
indicator does not affect the operation of the
relay.
Combined power The combined power supply and I/O module The power supply and I/O module is available
supply and I/O (U2) is located behind the system front panel of in two versions which have different input volt-
module the protection relay and can be withdrawn after age ranges:
removal of the system front panel. The power
supply and I/O module incorporates a power - type SPTU 240 S1 Uaux = 80...265 V ac/dc
unit, five output relays, the control circuits of - type SPTU 48 S1 Uaux = 18...80 V dc
the output relays and the electronic circuitry of
the external control input. The voltage range of the power supply and I/O
module inserted in the relay is marked on the
The power unit is transformer connected, that system front panel of the relay.
is, the primary side and the secondary circuits
are galvanically isolated. The primary side is
protected by a slow 1 A fuse F1, placed on the
PC board of the module. When the power
source operates properly, the green Uaux LED
on the front panel is lit.
7
Technical data Energizing inputs 1A 5A
(modified 2002-04) Terminals 25-27 25-26
Rated current In 1A 5A
Thermal withstand capability
Carry continuously 4A 20 A
Make and carry for 10 s 25 A 100 A
Make and carry for 1 s 100 A 500 A
Dynamic current withstand capability,
half-wave value 250 A 1250 A
Input impedance <100 mΩ <20mΩ
Rated frequency fn acc. to order 50 Hz or 60 Hz
Signalling contacts
Terminals 70-71-72, 73-74-75, 77-78, 80-81
Rated voltage 250 V ac/dc
Carry continuously 5A
Make and carry for 0.5 s 10 A
Make and carry for 3 s 8A
Breaking capacity for dc, when the signalling
circuit time constant L/R ≤ 40 ms,
at the control voltages
- 220 V dc 0.15 A
- 110 V dc 0.25 A
- 48 V dc 1A
8
Non-directional earth-fault relay module SPCJ 1C8
Low-set stage I0>
Start current I0>, setting range 0.1...0.8 x In
Selectable modes of operation
- definite time characteristic
- operate time t> 0.05...100 s
- inverse definite minimum time (IDMT) characteristic
- curve sets acc. to IEC 60255-3 and BS 142 Normal inverse
Very inverse
Extremely inverse
Long-time inverse
- time multiplier k 0.05...1.00
Data communication
Transmission mode Fibre optic serial bus
Data code ASCII
Selectable data transfer rates 300, 1200, 2400, 4800 or 9600 Bd
Fibre optic bus connection module,
powered from the host relay
- for plastic fibre cables SPA-ZC 21 BB
- for glass fibre cables SPA-ZC 21 MM
Fibre optic bus connection module with
a built-in power supply unit
- for plastic fibre cables SPA-ZC 17 BB
- for glass fibre cables SPA-ZC 17 MM
Insulation Tests *)
Dielectric test IEC 60255-5 2 kV, 50 Hz, 1 min
Impulse voltage test IEC 60255-5 5 kV, 1.2/50 µs, 0.5 J
Insulation resistance measurement IEC 60255-5 >100 MΩ, 500 Vdc
Environmental conditions
Specified ambient service temperature range -10...+55°C
Long term damp heat withstand acc. to IEC 60068-2-3 <95%, +40°C, 56 d/a
Relative humidity acc. to IEC 60068-2-30 93...95%, +55°C, 6 cycles
Transport and storage temperature range -40...+70°C
Degree of protection by enclosure
for panel mounted relay IP 54
Weight of relay including flush mounting case 3.0 kg
*) The tests do not apply to the serial port, which is used exclusively for the bus connection module.
9
Examples of
application L1
L2
Example 1. L3
Feeder earth-fault 0 -
protection
I - I
+
Rx Tx
0
SPA-ZC_
+
+ (~) Uaux
- (~)
1) 2)
BS IRF START2 START1 SIGNAL1 TRIP2 TRIP1
+
SERIAL
PORT
25 26 27 10 11 61 62 70 71 72 73 74 75 77 78 80 81 68 69 65 66
≅_
5A
1A
E F D C B A
+ - U3
1 1 1 1
SGR/1
U3
SGR 3 2 4 7 5 8 6
IRF
SS1
t >,k TS1
Io>
SGB
4
5 SS2
t >> TS2
Io>>
U1 I/O
SPAJ 110 C U2
Fig. 4. Earth-fault relay SPAJ 110 C used for the earth fault protection of a feeder.
The earth-fault relay SPAJ 110 C is used for levels, current transformers with high accuracy
two-stage non-directional earth fault protection limit factors are recommended especially if the
of a feeder. The neutral current can be measured high-set stage is to operate instantaneously.
either via a set of three phase current transform-
ers in residual current connection or a core- The residual current connection can be used in
balance current transformer. cases with high earth-fault current magnitudes,
moderate sensitivity requirements and low cur-
The residual current connection is obtained by rent transformer ratios. In solidly earthed net-
parallelling the secondary sides of the phase works or networks earthed over a low-resistance
current transformers. The accuracy of the re- resistor or low-impedance coil, the earth-fault
sidual current connection depends on electrical current is high enough to guarantee a sufficient
similarity of the current transformers. To secure accuracy of the residual current connection for
selectivity and stability at high fault current measuring the earth-fault current.
10
Generally, the earth-fault relay SPAJ 110 C relay, for instance, due to partial saturation of a
requires no blocking from a cooperating re- phase current transformer.
sidual voltage relay. However, when required,
the stability of the earth-fault relay can be se- The low-set stage of the earth-fault relay module
cured with a blocking signal obtained from the can be given definite-time or inverse-time char-
residual voltage relay of the busbar system. Then, acteristic. The high-set stage can be used for
during a no-fault situation, the earth-fault relays instantaneous operation. In the above example
of the feeders are blocked by the residual voltage the start signal of the low-set stage is used for
relay. When an earth-fault arises on a feeder the blocking the earth-fault relay of the infeeder,
feeder earth-fault relay starts but does not oper- also functioning as busbar earth-fault relay, see
ate until deblocked by the residual voltage relay, also example 2.
when it starts. This blocking function is used to
prevent spurious operation of the earth-fault The function selector switches of the earth-fault
relay SPAJ 110 C can be set as follows:
∑ 5
Contact Function
11
Example 2.
Earth-fault protec-
tion of infeeder and 0 -
busbar system, back-
up protection of
feeders
- I
I
+
0
+
0 -
- I
I
+
I
II
0
+ Rx Tx
SPA-ZC_
+ (~) Uaux
- (~)
1)
BS IRF START2 START1 SIGNAL1 TRIP2 TRIP1
+ +
SERIAL
PORT
25 26 27 10 11 61 62 70 71 72 73 74 75 77 78 80 81 68 69 65 66
≅_
5A
1A
E F D C B A
+ - U3
1 1 1 1
SGR/1
U3
SGR 3 2 4 7 5 8 6
IRF SS1
t >,k TS1
Io>
SGB
4
5 SS2
t >> TS2
Io>>
U1 I/O
SPAJ 110 C U2
Fig. 5. Earth-fault relay SPAJ 110 C for the earth-fault protection of an infeeder and back-up
protection of outgoing feeders.
12
The low-set stage of the earth-fault relay serves cuit on the LV side of the power transformer.
as back-up protection for the outgoing feeders
and the high-set stage as primary earth-fault On operation the high-set stage of the earth-
protection of the busbar system. If the earth- fault relay trips the circuit breaker on the HV
fault occurs on an outgoing feeder, the earth- side of the power transformer. Thus an earth-
fault relay of the outgoing feeder delivers a fault on the busbar system is rapidly discon-
blocking signal to the earth-fault relay of the nected. The low-set stage trips the circuit breaker
infeeder on starting. Should the earth-fault oc- on the LV side of the power transformer. This
cur on the busbar system or in the infeeder allows operate times of down to 100 ms at
cubicle, no blocking signal is obtained and the busbar earth-faults.
earth-fault relay of the infeeder operates. The
incoming blocking signals are linked to the In the above example the trip relay has been
high-set stage of the earth fault relay of the given a latching function (SG1/4=1). The trip
infeeder with the SGB/5 switch on the PC board relay can be manually reset from the front panel
of the earth-fault relay module SPCJ 1C8 of the of the relay, or via a command over the serial
infeeder earth-fault relay. bus.
The neutral current is measured via a current The function selector switches of the earth-fault
transformer located in the neutral earthing cir- relay SPAJ 110 C can be set as follows:
∑ 45
Contact Function
13
Recorded data The data recorded in the registers of the relay on the occurrence of earth-faults and informa-
and fault analysis can be used both to analyze an earth-fault situ- tion on the distribution of earth-faults in respect
ation and to study the behaviour of the protec- of the fault resistance. Frequent starts may be a
tion equipment. sign of an imminent earth-fault or some kind of
disturbance apt to cause an earth-fault.
Register 1 stores the maximum measured neu-
tral current of the relay as a multiple of the rated Registers 4 and 5 show the duration of the latest
current of the energizing input used. If the relay start situation of the stages, expressed in per cent
operates, the current measured at the moment of the set operate time or, at inverse time opera-
of operation is memorized. A new relay opera- tion the calculated operate time. Any new start
tion erases the previous value from the register resets the counter, which restarts from zero. If
and updates the register contents. The register is the stage operates, the register value will be 100.
also erased and updated whenever the measured
current exceeds the currently recorded value. The registers 4 and 5 give information on the
duration of an earth-fault, or, if a final trip has
The level of the neutral current value recorded been performed, the safety margin of the grad-
in a fault situation shows the degree of develop- ing times of the selective protection. If, for
ment of the earth fault. The data of register 1 instance, the value of register 4 of the busbar
also show how close the relay’s start current is to earth-fault relay operating as feeder back-up
the actual fault current value. protection is 75 when the earth-fault relay of the
feeder has operated, the safety margin between
Correspondingly the ratio between the set start the primary protection and the back-up protec-
current and the current values during normal tion is 25%.
operation can be determined by reading the
normal current values via the display of the relay. The registers 1...5 are reset either by pressing the
STEP and RESET push-buttons simultaneously
The number of times the different stages have or with a command, V102, over the SPA bus.
started, registers 2 and 3, provides information
As switch positions and setting values have to be - adjustable voltage transformer 0...260 V, 1 A
altered during the test procedure the correct - current transformer
positions of switches and the setting values of - ammeter, accuracy ±0.5%
the relay during normal operation conditions - stop watch or counter for time measurement
have to be recorded, for instance, on the refer- - dc voltage source
ence card accompanying the relay. - switches and indicator lamps
- supply and pilot wires
To enable secondary injection testing the relay - calibrated multimeter
has to be disconnected, either through discon-
nectable terminal blocks or a test plug fitted on
the relay.
14
The secondary current of the current trans- to be tested. The energizing inputs are specified
former is to be selected on the basis of the rated under the heading "Technical data, Energizing
current, 1 A or 5 A, of the relay energizing input inputs".
U2
6
A
1
TRIP1
65 66
TIMER
STOP
8
START2 START1 SIGNAL1 TRIP2
68 69
+ (~)
- (~)
5
C
7
80 81
L4
4
D
3 2
1
77 78
SGR
L3
SS1
SS2
TS1
TS2
73 74 75
L2
I/O
t >,k
t >>
E
IRF
70 71 72
IRF
L1
U3
Io>>
Io>
61 62
≅_
Uaux
+ -
SGB
SGR/1
U1
4
5
S2
10 11
BS
TIMER START
25 26 27
1A
SPAJ 110 C
5A
A
U3
S1
L1 N
Fig. 6. Secondary injection test connection for earth-fault relay SPAJ 110 C.
When the test connection has been completed The operation of the test connection can be
and the selector switches properly set, the auxil- verified by using a multimeter.
iary voltage is connected to the relay.
15
Testing of internal Apply a pure sinusoidal voltage to the relay and instance, at the rated current of the relay. Note
matching trans- compare the current value indicated on the that the relay shows the measured current as a
formers display of the relay with that shown by the multiple of the rated current In of the energizing
ammeter. The measurements can be made, for input used.
Testing of the low- Set the switches of the SGR switchgroup as Operate time
set stage I0> follows before starting the test:
Definite-time characteristic
Switch Position
Set the test current at 2 x the set start value of
1 1 stage I0>. The clock is started by the closing of
2 0 switch S1 and stopped via contact 65-66, when
3 0 output relay A picks up.
4 0
5 0 The operation of output relay C is indicated by
6 0 L4.
7 1
8 0 When the relay starts, the I0> LED in the right
bottom corner of the front panel is lit with
When the switches are set as above, the output yellow light. When the relay operates, the indi-
relays have the following functions. cator LED turns red.
Blocking
Starting
Set switches 4 and 5 of switchgroup SGB and
Carry out the test according to Fig. 6. Close the switch SGR/1 in position 1 (ON).
S1 switch and increase the test current slowly
until the relay starts (L2 is lit). Then read the Apply a control voltage on the auxiliary voltage
start current value indicated by the ammeter. level to the external control input of the relay by
closing switch S2. Increase the test current until
the low-set stage I0> starts. After the set operate
time the low-set stage is not allowed to operate
as long as the blocking is active.
16
Testing of the high- Set the switches of the SGR switchgroup on the The test procedure is the same as for the low-set
set stage I0>> front panel as follows before starting the test of stage, but with the exception that, when the
the high-set stage: operate times are measured, the clock is stopped
via contact 68-69, output relay B.
Switch Position
Note!
1 1 The current carrying capacity of the wiring,
2 1 terminals and matching transformers of the
3 0 relay is limited, see chapter "Technical data".
4 0 The test wires should have an cross-section of 4
5 1 mm2. Then 100 A is allowed to be connected for
6 0 max. 1 s to a 1 A energizing input and for max.
7 0 10 s to a 5 A energizing input.
8 0
Testing of self- The self-supervision system and the function of document "General characteristics of C-type
supervision output the IRF LED and the output relay E can be relay modules". The operation of output relay E
relay (IRF) tested in the Trip test mode described in the is indicated by L1.
17
Maintenance When used under the conditions specified in If the relay fails in operation or if the operation
and repair the section "Technical data", the relay requires values considerably differ from those stated in
practically no maintenance. The relay includes the relay specifications, the relay should be given
no parts or components that are sensitive to a proper overhaul. Minor measures, such as
abnormal physical or electrical wear under nor- exchange of a faulty module, can be taken by
mal operating conditions. personnel from the customer’s instrument work-
shop, but major measures involving the elec-
If the environmental conditions on site differ tronics are to be taken by the manufacturer.
from those specified, as to temperature and Please contact the manufacturer or his nearest
humidity, or if the atmosphere around the relay representative for further information about
contains chemically active gases or dust, the checking, overhaul and calibration of the relay.
relay should be visually inspected during the
relay secondary testing. The visual inspection Note!
should focus on: The protection relays contain electronic circuits
which are liable to serious damage due to elec-
- Signs of mechanical damage on relay case and trostatic discharge. Before removing a module,
terminals ensure that you are at the same electrostatic
- Dust accumulated inside the relay cover or potential as the equipment by touching the case.
case; remove carefully with compressed air or
a soft brush Note!
- Signs of corrosion on terminals, case or com- Static protection relays are measuring instru-
ponents inside the relay ments and should be handled with care and
protected against damp and mechanical stress,
especially during transport and storage.
The two last letters of the ordering number designate the rated frequency fn and
the Uaux voltage range of the relay as follows:
18
Dimensions and The relay case is basically designed for flush- by 40 mm, type SPA-ZX 112 by 80 mm and
instructions for mounting. The mounting depth can be reduced type SPA-ZX 113 by 120 mm. The relay can
mounting by the use of a raising frame: type SPA-ZX 111 also be mounted in a case for surface mounting,
reduces the depth behind the mounting panel type designation SPA-ZX 115.
250
142
216 34
30 186
136
162
129 ±1 a b
139 ±1
Panel cut-out
Raising frame a b
SPA-ZX 111 176 74
SPA-ZX 112 136 114
SPA-ZX 113 96 154
The relay case is made of profile aluminium and along the edge of the cover provides an IP54
finished in beige. degree of protection between the case and the
cover.
A rubber gasket fitted on the mounting collar
provides an IP54 degree of protection between All input and output wires are connected to the
relay case and mounting panel, when the relay is screw terminal blocks on the rear panel. Each
flush mounted. terminal is dimensioned for one max. 6 mm2
wire or two max. 2.5 mm2 wires. The D-type
The hinged cover of the relay case is made of a connector connects to the serial communica-
clear, UV stabilized polycarbonate, and pro- tion bus.
vided with a sealable fastening screw. A gasket
19
SPCJ 1C8
Non-directional earth-fault relay module
User´s manual and Technical description
B
I
Io IRF
STEP 0.35
Io>
In STEP
0.1 0.8
0.5
t > [ s] SG1
k
1
0.05 1.0 2
3
4
5
2.5 6
I o >> 7
4.0 8
In 0 1
0.5
RESET
0.5
t >> [ s ]
0.05 1.0
I o > I o >>
1311
SPCJ 1C8
1MRS 750603-MUM EN
SPCJ 1C8
Issued 1996-12-31
Modified 2002-05-15
Version B (replaces 34 SPCJ 3 EN1)
Non-directional
Checked MK
Approved OL
earth-fault relay module
Data subject to change without notice
Features Low-set neutral overcurrent stage I0> with Both neutral overcurrent stages can sep-arately
selectable definite time or inverse definite mini- be blocked with an external control signal
mum time (IDMT) operation characteristic
Memory controlled function of start and opera-
High-set neutral overcurrent stage I0>> with tion indicators selectable
definite time operation characteristic
Digital display of measured and set values as well
Automatic doubling feature of the set start value as data recorded at the moment a fault occurs
of the high-set stage I0>> on sudden rise of the
energization current can be selected Constant self-supervision of hardware and soft-
ware. At a permanent fault the alarm output
The high-set stage I0>> can be set out of opera- relay picks up and the operation of tripping and
tion if not needed signalling outputs is blocked
2
Description of The non-directional earth-fault relay module characteristic. The operation characteristic is
function SPCJ 1C8 is a single-pole neutral overcurrent selected with switch SG1/3. At definite time
relay module. It contains two neutral overcur- characteristic the operate time t> is chosen from
rent stages, i.e. a low-set overcurrent stage I0> one out of three operate time setting ranges. The
and a high-set overcurrent stage I0>>. setting range is selected with switches SG1/1
and SG1/2. When the inverse time characteris-
The low-set or high-set overcurrent stage starts tic (IDMT) is used four time/current curve
if the input energizing current exceeds the set groups, referred to as "Normal, very, extremely
start value of the stage concerned. When start- and long-time inverse" are available. The re-
ing, the stage provides a start signal SS1 or SS2 quired operation characteristic is selected with
and simultaneously the operation indicator of switch SG1/1 and SG1/2.
the stage is lit with yellow colour. If the overcur-
rent situation lasts long enough to exceed the set The operate time t>> of the high-set overcurrent
operate time, the stage that started also operates stage I0>> is set separately. The setting range,
and provides a tripping signal, TS1 or TS2. At one of three available alternatives, is selected
the same time the operation indicator of the with switch SG1/7 and SG1/8.
concerned stage turns red. The start and opera-
tion indicators can individually be given self- The two overcurrent stages are provided with a
reset or manual reset mode of operation. If the so called latching facility, which means that the
self-reset mode of operation is selected, the tripping output remains energized, although
indicator is automatically turned off when the the signal which caused the operation disap-
stage resets. If the manual reset mode is selected pears. The latching function is selected with
the indicators are reset with the RESET push- switch SG1/4 and the stages are reset by pressing
button on the front panel of the relay module or the push-buttons STEP and RESET simultane-
via the serial port by means of the command ously.
V102 or V101.
The set start value I0>> of the high-set over-
The operation of the low-set overcurrent stage current stage may be automatically doubled on
I0> can be blocked by routing a blocking signal starting. Thus the start value of the high-set
BTS1 to the stage. Similarly, the starting of the overcurrent stage can be set lower than the
high-set current stage I0>> can be blocked by a connection inrush current. The doubling fea-
blocking signal BTS2. The blocking signals are ture is selected with switch SG1/5. A start situ-
routed by means of switchgroup SGB on the ation is defined as a situation where the energiz-
PC-board of the relay module. ing current rises from a value below 0.12 x I0>
to a value exceeding 3.0 x I0> in less than 60 ms.
If the protection relay incorporates an auto- The start situation ceases when the current falls
reclose module, switchgroup SGB is additionally below 2.0 x I0>.
used for the purpose of selecting proper start
signals for the auto-reclose module. The in- The start current setting range of the high-set
structions for setting the switchgroup are given overcurrent stage is selected with switch SG1/6.
in the general description of the protection Two setting ranges are available, 0.5...4 x In and
relay, in the diagram illustrating the signal inter- 0.1...0.8 x In.
change between the relay modules.
The operation of this stage may be totally blocked
The operation of the low-set overcurrent stage by selecting the setting value ∞, infinite.
I0> can be based on definite time or inverse time
3
Block diagram
NOTE!
All input and output signals of the relay module diagram illustrating the signal interchange be-
are not necessarily wired to the terminals of tween the relay modules of the protection relay
every protection relay using this module. The or feeder terminal in question.
signals wired to the terminals are shown in the
4
Front panel
B
I Simplified device symbol
SPCJ 1C8
relay module
5
Start and Both overcurrent stages have their own yellow/ An unreset operation indicator does not affect
operation red LED indicators. Yellow light indicates start- the protective functions of the relay module.
indicators ing of the concerned overcurrent stage and red The relay module is constantly operative, re-
light indicates that the overcurrent stage has gardless of the indicators have been reset or not.
operated.
The self-supervision alarm indicator IRF indi-
The four LED indicators can, independently of cates that the self-supervision system has de-
one another, be given self-reset or manual reset tected a permanent internal relay fault. The
mode of operation. The manual reset mode indicator is lit with red light shortly after the
means that the indicator remains lit after being fault has been detected. At the same time the
switched on, although the earth-fault stage, relay module puts forward a control signal to the
which controls the indicator, resets. If, for in- self-supervision system output relay of the pro-
stance, the yellow start indication is given the tection relay unit.
self-reset mode and the red indicator the manual
reset mode, the yellow indicator is lit, when the Additionally, in most fault cases, a fault code
stage starts, turning red if and when the stage showing the type of the relay fault appears on the
operates. When the earth-fault stage resets only display of the module. The fault code consists of
the red indication remains lit. The indicators, a red number one (1) and a green three-digit
which have been given the manual reset mode, code number. When a fault message appears on
are reset locally by pushing the RESET push- the display, the code number should be noted
button on the front panel or by remote control down to facilitate the subsequent fault finding
over the SPA bus using the command V101 or and repair work.
V102.
Relay settings The setting values are shown by the three which setting value is currently being shown on
rightmost digits of the display. An LED indica- the display.
tor below each setting knob shows, when lit,
I0>/In Start current of stage I0> as a multiple of the rated current of the used relay energizing
input. Setting range 0.10...0.80 x In.
t> [s] Operate time of stage I0>, expressed in seconds, when the definite time operation
characteristic (SG1/3 = 0). The setting range, i.e. 0.05...1.00 s, 0.5...10.0 s or 5...100 s,
is determined by the position of the switches SG1/1 and SG1/2.
I0>>/In Start current of stage I0>> as a multiple of the rated current of the used relay energizing
input. The setting range, i.e. 0.5...4.0 x In or 0.1...0.8 x In, is selected with switch
SG1/6. Addi- tionally, the setting infinite "∞" (dis- played as - - -) can be selected,
which means that stage I0>> is ot of function.
t>> [s] The operating time of the I0>> stage, expressed in seconds. The setting ranges,
0.05...1.00 s, 0.5...10.0 s or 5...100 s, are determined by the position of switches
SG1/7 and SG1/8.
Further, the checksum of the function selector that the switches themselves work properly. An
switchgroup SG1 is indicated on the display example of calculating the checksum is given in
when the indicator under the switchgroup is lit. the description "General characteristics of C
In this way a check can be carried out to prove type relay modules".
that the switches have been set as planned and
6
Selector switches Additional functions required by individual the front panel. The numbering of the switches,
applications are selected by means of the program 1...8, as well as the switch positions 0 and 1 are
selector switches of switchgroup SG1 located on marked on the front panel.
Switch Function
SG1/1 Switch SG1/3 is used for selecting the operation characteristic of the low-set current
SG1/2 stage I0>, i.e. definite time characteristic or inverse definite minimum time (IDMT)
SG1/3 characteristic. At definite time characyeristic the setting range of the operate time t>
is selected by means of switches SG1/1 and SG1/2 whereas, at inverse definite
minimum time characteristic the switches are used for selecting the time/current
characteristic of the low-set stage I0>.
SG1/4 Selection of mode of operation for the operate signals TS1 and TS2.
When SG1/4 = 0, the operate signals returns to the initial state (= the output relay
drops off), when the energizing signal causing the operation falls below the set start
level.
When SG1/4 = 1, the operate signals remain on (= the output relay operated), although
the energizing signal falls below the set start level. Resetting with command V101 via
the serial interface or by pressing the push-buttons STEP and RESET simultaneously,
which also erases the recorded information.
SG1/5 Selection of automatic doubling of the set start value of the high-set current stage I0>>
when the protected object is connected to the network.
When SG1/5 = 0, no doubling of the set start value of stage I0>> is obtained.
When SG1/5 = 1, the set start value of the stage I0>> doubles automatically.
This makes it possible to give the high-set current stage a setting value below the
connection inrush current level of the protected object.
SG1/6 Selection of the setting range of the high-set overcurrent stage I0>>.
7
Switch Function
SG1/7 Selection of setting range of the operate time t>> of the high-set overcurrent stage I0>>.
SG1/8
SG1/7 SG1/8 Operate time t>>
0 0 0.05...1.00 s
1 0 0.5...10.0 s
0 1 0.5...10.0 s
1 1 5...100 s
Switchgroup SG2 is a so called software switch- be separately set for each indicator. The mode of
goup, which is located in the third submenu of operation is set by means of the checksum,
switchgroup SG1. The mode of operation, i.e. which can be calculated from the following
self-reset or manually reset, of the LED indica- table. Normally the start indications are self-
tors I0> and I0>> is determined by the switches reset and the operation indications manually
of switchgoup SG2. The mode of operation can reset.
Checksum 15 10
The PC board of the relay module contains a ule, whereas switches 4...8 are used for routing
switchgroup SGB including switches 1...8. The external control signals to the neutral overcur-
switches 1...3 are used for selecting start initia- rent stages of the relay module in various protec-
tion signals to a possible auto-reclose relay mod- tion relays.
Measured The measured values are displayed by the three neutral current is indicated with a LED indica-
information rightmost digits of the display. The measured tor on the front panel.
I0 Neutral current measured by the relay module as a multiple of the rated current In
of the used energizing input of the protection relay.
8
Recorded The leftmost digit of the display shows the
information address code of the register and the other three
digits the value of the register.
1 Maximum current measured as a multiple of the rated current of the protection. The
register is updated when one of the following criteria is fulfilled:
I) The measured current exceeds the value currently recorded
II) The relay module operates. On operation the current value at operation is recorded.
4 Duration of the latest start situation of stage I0> as a percentage of the set operate time
t> or at IDMT mode of operation the calculated operate time. A new start resets the
counter which then starts counting from zero. When the concerned stage has
tripped, the counter reading is 100.
5 Duration of the latest start situation of stage I0>> as a percentage of the set operate
time t>>. A new start resets the counter which then starts counting from zero. When
the concerned stage has tripped, the counter reading is 100.
0 Display of blocking signals and other external control signals. The rightmost digit
indicates the state of the blocking inputs of the module. The following states may be
indicated:
0 = no blockings
1 = tripping of the low-set current stage I0> blocked
2 = tripping of the high-set current stage I0>> blocked
3 = tripping of both operation stages blocked
On this module the middle digit of the register is always a zero. The third digit from
the right indicates the state of the remote reset input, if the protection relay is
provided with a control input. The following states may be indicated:
0 = remote reset control input not energized
1 = remote reset control input energized
From this register it is possible to move on to the Trip test mode. For further details,
see the description "General characteristics of C-type relay modules".
A Address code of the protection relay module, required by the serial communication
system. Register A has three subregisters with the following contents:
1) Selection of data transfer rate for the serial communication. Selectable values 300,
1200, 2400, 4800 or 9600 Bd. Default value 9600 Bd.
2) Communication interruption counter. If the relay module is connected to a
communication system, which is in operation, the value of the communication
interruption counter is 0 (zero). If the communication system is disturbed, the
numbers 0…255 are scrolling in the communication interruption counter.
3) Password required for remote setting of relay module parameters.
– Display dark. By pressing the STEP push-button the beginning of the display menu
is re-entered.
The registers 1...5 are set to zero by pressing the of the serial communication and the password
push-buttons STEP and RESET simultaneously are not erased by a voltage failure. The instruc-
or via the SPA bus with the command V102. tions for setting the address and the baud rate are
The registers are also cleared if the auxiliary described in the "General characteristics of C-
power supply to the module is interrupted. The type relay modules".
address code of the relay module, the baud rate
9
Main menu and
submenus of
settings and MAIN MENU SUBMENUS
Normal state. Display switched off = value that can be set in the setting mode
S
T
E STEP BACKWARD 0,5 s STEP FORWARDS 1 s
P Measured residual current Io SUBMENUS
B
A
C Remotely set Remotely set
Set start current Io> 1 2
K percentage p1 value Io> x p1
W
A
R Set operate time t> or time Remotely set 2 Remotely set value
1
D multiplier k percentage p2 t> x p2 / k x p2
.5
s
Remotely set Remotely set
Set start current Io>> 1 2
percentage p3 value Io>> x p3
M
A
I 1 Remotely set 2 Remotely set
Set operate time t>>
N percentage p4 value t>> x p4
Communication
A Relay module address
code for communication 1
Data transfer
rate [Bd]
2 counter 0...255 s 3 Password
The measures required for entering a submenu Data Sheet "General characteristics of C-type
or a setting mode as well as how to perform the relay modules".
settings and use the TEST mode are described in
10
Time/current The operation of the low-set current stage I0> of The degree of inversity is determined by the
characteristic the earth-fault relay module is based on either values of the constants α and β:
(modified 2002-05) definite time or inverse time characteristics. The
mode of operation is selected with switch 3 of Degree of inversity of α β
switchgroup SG1 (see page 7). the characteristic
When the IDMT mode of operation is selected, Normal inverse 0.02 0.14
the operate time of the low-set current stage I0> Very inverse 1.0 13.5
will be a function of the current; the higher the Extremely inverse 2.0 80.0
current, the shorter the operate time. The rela- Long-time inverse 1.0 120.0
tionship between current and time complies with
the standards BS 142.1966 and IEC 60255-3
and may generally be expressed as: According to the standard BS 142.1966 a nor-
mal current range is defined as 2...20 times the
k x β setting. Additionally the relay must start at the
t= α [s] latest when the current exceeds a value of 1.3
( ) I
I0>
–1 times the setting, when the time/current charac-
teristic is normal inverse, very inverse or ex-
where tremely inverse. When the characteristic is long-
t = operate time in seconds time inverse, the normal range in accordance
k = time multiplier with the standard is 2...7 times the setting and
I = current value the relay is to start when the current exceeds 1.1
I0> = set current value times the setting.
The module includes four characteristics with The following requirements with regard to op-
different degrees of inversity. The characteristic erate time tolerances are specified in the stand-
to be used is selected with switches 1 and 2 of ard (E denotes accuracy in per cent, - not speci-
switchgroup SG1 (see page 7). fied):
11
t/s
70
60
50
40
30
20
10
9
8
7
6
5
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
k
0.2 1.0
0.8
0.6
0.1 0.4
0.09
0.08 0.3
0.07
0.2
0.06
0.05
0.1
0.04
0.05
0.03
0.02
1 2 3 4 5 6 7 8 9 10 20 I/I>
12
t/s
70
60
50
40
30
20
10
9
8
7
6
5
1
0.9
0.8 k
0.7 1.0
0.9
0.6
0.8
0.5 0.7
0.6
0.4
0.5
0.3 0.4
0.3
0.2
0.2
0.1
0.09 0.1
0.08
0.07
0.06
0.05
0.05
0.04
0.03
0.02
1 2 3 4 5 6 7 8 9 10 20 I/I>
13
t/s
70
60
50
40
30
20
10
9
8
7
6
5
3 k
1.0
2 0.9
0.8
0.7
0.6
0.5
1
0.9 0.4
0.8
0.7 0.3
0.6
0.5
0.2
0.4
0.3
0.1
0.2
0.05
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.03
0.02
1 2 3 4 5 6 7 8 9 10 20 I/I>
14
t/s
700
600
500
400
300
200
100
90
80
70
60
50
40
30
20
10
9
8
k
7
1.0
6 0.9
5 0.8
0.7
4
0.6
0.5
3
0.4
2
0.3
0.2
1
0.9
0.8
0.7
0.1
0.6
0.5
0.4
0.05
0.3
0.2
I/I>
1 2 3 4 5 6 7 8 9 10 20
15
Technical data Low-set current stage I0>
Start current I0> 0.1...0.8 x In
Start time, typically 60 ms
Operate time t> at definite time operation 0.05...1.00 s,
0.5...10.0 s or
5...100 s
Operation characteristic at IDMT
mode of operation Extremely inverse
Very inverse
Normal inverse
Long-time inverse
Time multiplier k 0.05...1.00
Reset time, typically 60 ms
Drop-off/pick-up ratio, typically 0.96
Operate time accuracy at
definite time mode of operation ±2% of set value or ±25 ms
Operation time accuracy class E at
inverse time mode of operation 5
Operation accuracy ±3% of set value
16
Event codes The substation level control data communica- The event codes E1...E8 are represented by the
tor is able to read, over the SPA serial bus, the numbers 1, 2, 4...128. The event mask is formed
event data of the module, e.g. starts and trip- by multiplying above numbers either with 0
pings, from the non-directional earth-fault relay (event not included in reporting) or 1 (event
module SPCJ 1C8. Event information called included in reporting) and adding up the num-
for are printed out in the format: time (ss.sss) bers received (compare calculation of checksum).
and event code. The event codes of the module
are E1...E8 and E50 and E51. Furthermore, the The event mask may have a value in the range
substation level control data communicator is 0...255. The default value of the non-direc-
able to form event codes relating to e.g. the data tional earth-fault module SPCJ 1C8 is 85, which
communication. means that all startings and trippings are in-
cluded in the reporting, but not the resetting.
The codes E1...E8 and the events represented by The codes E50...E54 and the events represented
these can be included in or excluded from the by these cannot be excluded from the reporting.
event reporting by writing an event mask (V155)
to the module over the SPA bus. The event mask Event codes of non-directional earth-fault mod-
is a binary number coded to a decimal number. ule SPCJ 1C8:
Note!
The codes E52…E54 are formed by the sub-
station level data communication equipment.
17
Data to be Apart from the event codes the substation level recorded in the memory (V data), and some
transferred control data communicator is able to read, over other data. Further, part of the data can be
remotely the SPA bus, all input data (I data), output data altered by commands given over the SPA bus.
(O data) , setting values (S values), information All the data are in channel 0.
18
Data Code Data Values
direct.
19
Data Code Data Values
direct.
The data transfer codes L, B, C and T have been To be able to write the password (V160) for the
reserved for the event data transfer between the remote setting must be opened and the poten-
module and the station level control data com- tionmeter settings must be activated (V150=0).
municator. The variables S31...S35 contain the remote
setting values.
The event register can be read by the L-com-
mand only once. Should a fault occur e.g. in the When changing the remote setting percentages
data transfer, it is possible, by using the B- S21...S24, these variables can be given a per-
command, to re-read the contents of the event centage factor within the range 0...999. Then it
register read by means of the L-command. When is also possible to alter the setting value beyond
required, the B-command can be repeated. the limits specified in the technical data of the
module. However, the validity of the setting
The setting values S1...S5 are the setting values values are guaranteed only within the limits
used by the protection programs. These values specified in the technical data.
are set either remotely or by means of the setting
knobs. The values S11...S15 are settings set with Activation of the self-supervision input (V165)
setting knobs or switches. S21...S25 are knob prevents the protection from operating as long
setting percentage factors to be set remotely. as the self-supervision input is active and the
The settings S21...S25 allow reading or writing. IRF indicator is on.
20
Fault codes Shortly after the self-supervision system has detected the fault code should be recorded for
detected a permanent internal fault the red IRF further use when the relay module is to be
indicator is lit. Simultaneously the relay module repaired.
puts forward a control signal to the output relay
of the self-supervision system. In most fault Some of the fault codes that may appear on the
situations an autodiagnostic fault code appears display of the non-directional earth-fault relay
on the display of the module. The fault code module SPCJ 1C8 are shown in the following
consists of a red number 1 (one), and a green, list:
one to three digit code number. When a fault is
21
General characteristics of
C-type relay modules
User´s manual and Technical description
B
I >
I >>
I L1 I L2 I L3 IRF
Self-supervision alarm indicator
Indicators for measured values (Internal Relay Fault)
Display, 1 + 3 digits
STEP 1.5
I>
Setting knob 1 In STEP
with indicator 0.5 2.5
Step push-button (STEP)
Stage 1 0.5
t > [ s] SG1
Setting knob 2 k
1
with indicator 0.05 1.0 2
3
4
5
Programming switches SG1
13 6
7
I >>
Setting knob 3 20 8
In
with indicator 2.5
0 1
Switchgroup indicator
RESET
Stage 2
0.5
Reset push-button (RESET)
Setting knob 4 t >> [ s ]
with indicator 0.04 1.0
I> I >>
Start/operation indicators
1309
SPCJ 3C3
1MRS 750328-MUM EN
General characteristics of
Issued 96-02-19
Version A (replaces 34 SPC 2 EN1)
Checked L-W U
C-type relay modules
Approved TK
Push-buttons The front panel of the relay module contains settings, e.g. for setting the address of the relay
two push-buttons. The STEP button is used for module and the data transfer rate for the serial
stepping forward in the display and the RESET communication when the modules are used in
button for resetting the red indicators. Addi- relay packages provided with this quality. (See
tionally, the push-buttons are used for certain section Display).
Programming Part of the settings and the selections of the checksum of the switchgroup is shown on the
switches SG1 operating characteristics for the relay modules display. The checksum can be used for checking
in various applications are made with the pro- that the switches are properly set. Fig. 2 gives an
gramming switches SG1 on the front panel. The example of calculating the checksum.
indicator of the switchgroup glows when the
When the checksum calculated according to the The function of the programming switches of
example is equal to the checksum indicated on the individual measuring relay modules is speci-
the display of the relay module, the switches are fied in the description of the module concerned.
properly set.
2
Setting knobs Most of the operating values and operating In addition to the settings made with the setting
times are set by means of the setting knobs on knobs, most modules allow so called remote
the front panel of the relay module. Each setting setting. This means that the settings made by
knob has its own (LED) indicator which glows means of the setting knobs of the module and
when the concerned setting value is shown on the checksum of the programming switchgroup
the display. may be altered through an instruction over the
serial communication bus. Remote setting is
If a setting knob is turned while the display is possible if the password in the register A is
showing another measured or set value, the known, and the remote settings are not acti-
value being set automatically appears on the vated, i.e. parameter V150=0. The circumstance
display. Simultaneously, the indicator for the that the remote settings are activated is shown
concerned setting starts glowing. with a flashing light of the indicator of the
setting knob, the value of which currently is
being displayed.
Display The measured and set values as well as the data When the auxiliary voltage is connected to a
recorded are shown on the display of the meas- measuring relay module, the module initially
uring relay module. The display consists of four tests the display by stepping through the digits
digits. The three digits (green) to the right 1...9 for about 15 seconds. When the test is
indicate the measured, set or stored value and finished the display turns dark. The testing can
the digit at the extreme left (red) the number of be interrupted by pressing the STEP button.
the register. The measured or set value displayed The protective functions of the module are
is indicated by a yellow LED indicator. The operative throughout the testing.
number of the register glows only when a stored
value is displayed.
Display main menu All the data required during normal operating From a dark display only forward movement is
conditions are accessible from the main menu possible. When keeping the STEP button de-
which presents the measured values in real-time, pressed, the display is continuously moving in
the normal setting knob settings as well as the forward direction stopping for a while at the
most important memorized data. dark point.
The data to be shown in the main menu are Unless the display is switched off by stepping to
selected to the display in a certain sequence by the dark point, it remains activated for about 5
means of the STEP button. When pressing the minutes from the last pressing of the STEP
STEP button for about one second, the display button and then goes out.
moves forward in the display sequence. When
pressing it for about 0.5 seconds, the display
moves backwards in the display sequence.
3
Display submenu Less important values and values not very often display moves forward when pressing the STEP
set are displayed in the submenus. The number button for one second and backward when
of submenus varies with different relay module pressing it for 0.5 seconds. The return to the
types. The submenus are presented in the de- main menu has taken place when the red STEP
scription of the concerned module. display turns dark.
A submenu is entered from the main menu by When entering a submenu from a measured or
pressing the RESET button for about one sec- set value indicated by a LED indicator, the
ond. When the button thereafter is released, the indicator remains glowing and the address win-
red digit (STEP) of the display starts flashing, dow (STEP) of the display starts flashing. A
indicating that one is in a submenu. Going from flashing address window when no LED indica-
one submenu to another or back to the main tor is lit indicates that the submenu of a register
menu follows the same principle as when mov- has been entered.
ing from the main menu display to another; the
Fig. 3. Example of the main and submenus for the settings of the overcurrent relay module SPCJ
3C3. The settings made with the setting knobs are in the main menu and they are displayed by
pressing the STEP button. In addition to the setting knob settings the main menu contains the
measured current values as well as the registers 1…5, as well as 0 and A. The remote setting
percentage and remote setting value are located in the submenus for the settings and are activated
on the display by pressing the RESET button.
Setting mode The registers of the main menu and the submenus pressed slightly in excess of the STEP button.
also contain parameters to be set. The settings Return from the setting mode to the main menu
are made in the so called setting mode, which is or submenu is possible by pressing (for about 10
accessible from the main menu or a submenu by s) the RESET button until the green digits on
pressing the RESET button, until the digit at the display stop flashing. If the module is left in
the extreme right starts flashing (about 10 s). the setting mode, it will return automatically to
The flashing digit is set by means of the STEP the start condition after about 5 minutes.
button. The flashing is moved on from digit to
digit by pressing the RESET button. The values to be set in the setting mode are for
instance the address code of the relay module
A set value is stored in the memory by pressing and the data transfer rate for the serial commu-
the push-buttons STEP and RESET simultane- nication. Further the percentage values for the
ously. In practice the RESET button must be remote settings can be changed.
4
Example 1: Function in the setting mode. Manual setting of g)
the address code of a relay module and the data Set the digit by means of the STEP button.
transfer rate for the serial communication. The
initial value for the address code is 146.
a)
Press push-button STEP until register address A
appears on the display. h)
Store the set address number in the memory of
the relay module by pressing the RESET and
STEP button simultaneously. At the moment
the information enters the memory, the three
green dashes flash in the display, i.e. A—.
b)
Press the RESET button for about 10 s until the
right most digit starts flashing.
i)
Leave the setting mode by pressing the RESET
button for about 10 s, until the display stops
flashing.
c)
Press the STEP button repeatedly to set the digit
to the value desired.
j)
Then enter submenu 1 of register A by pressing
the RESET button for approx. one second. The
d) register address A is then replaced by a flashing
Press the RESET button to make the middle of 1. This submenu is used for setting the data
the green digits flash. transfer rate of the serial communication.
e) k)
Set the middle address digit by means of the The data transfer rate for the serial communica-
STEP button. tion is set and stored in the same way as the
address, see sections b...i, except that the con-
tinuously glowing register address has been re-
placed by a flashing 1.
l)
After storing the data transfer rate for the serial
f) communication you may return to the main
Press the RESET button to make the left most menu of register A by pressing the STEP button
green digit flash. for about 0.5 second.
5
Stored information The parameter values measured at the moment Register A contains the address code of the relay
when a fault occurs are recorded in the registers, module as required by the serial communication
in some modules also the setting values. The system. Example 1 on page 4 shows how the
recorded data, except for some setting param- address code is altered. Submenu 1 of register A
eters, are set to zero by pressing the push- contains the data transfer rate value expressed in
buttons STEP and RESET simul-taneously. kilobaud for the serial communication.
The data in normal registers are erased if the
auxiliary voltage supply to the relay is disrupted, Submenu 2 of register A contains a bus traffic
only the set values and the number of monitor for the SPACOM system. If the protec-
autoreclosings are maintained in the registers at tive relay, which contains the relay module, is
a voltage failure. linked to a system including the control data
communicator and the data communication
The number of the registers varies with different system is operating, the counter reading of the
module types. The function of the registers are monitor will be zero. Otherwise the digits 1...255
illustrated in the descriptions of the separate are continuously rolling in the monitor.
relay modules. Additionally, the system panel
contains a simplified list of the data recorded by Submenu 3 contains the password required for
the various relay modules of the relay assembly. changing the remote settings. The address code,
the data transfer rate for the serial communica-
All C-type relay modules are provided with two tion and the password can be set manually or via
general registers: register 0 and register A. the serial communication bus. For manual set-
ting see example 1.
Register 0 contains, in coded form, the informa-
tion about e.g. external blocking signals and The start value for the address code and the
status information for the circuit breaker. The password is 001 and that for the data transfer
codes are explained in the descriptions of the rate 9.6 kilobaud.
relay modules.
6
Trip-test mode Register 0 also allows access to the so called The selected starting or tripping is activated by
Trip-test function, which allows the output simultaneous pressing of the push-buttons STEP
signals of the relay module to be activated one by and RESET. The signal remains activated as
one. If the auxiliary relay module of the protec- long as the two push-buttons are being pressed.
tion assembly is in place, the auxiliary relays will
be included in the testing. The self-supervision output is activated by press-
ing the STEP button once when no setting knob
When pressing the RESET button for about 10 indicator is flashing. The IRF output is acti-
seconds, the three green digits to the right start vated in about 5 seconds after pressing of the
flashing to indicate that the relay module is in STEP button, and resets after that. Simultane-
test position. The indicators of the setting knobs ously, the display returns to the main menu and
indicate by flashing which output signal can be performs the initial testing indicated by rolling
activated. The required output function is se- digits 0...9 in the display several times.
lected by pressing the RESET button for about
1 second, until the following LED indicator The signals are selected in the order illustrated in
starts flashing. fig. 4.
Fig. 4. Sequence order for selecting the output signals in the Trip-test mode.
If e.g. the indicator of the setting knob 2 (second Trip-test sequence scheme, by pressing the
from the top) is flashing, and the push-buttons RESET button for about 10 seconds. If the
STEP and RESET are being pressed, the signal module is left in the Trip-test mode, it will
TS1 (tripping of stage 1) is activated. Return to return automatically after approx. 5 minutes.
the main menu is possible at any stage of the
7
Example 2: Trip-test function. Forced activation of the out- d)
puts is made as follows: Press the RESET button for about 1 second
until the indicator of the second setting knob
starts flashing.
a)
Step forward on the display to register 0.
e)
Press the push-buttons RESET and STEP si-
multaneously to activate tripping of stage 1 (e.g.
b) the I>-stage of the overcurrent module SPCJ
Press the RESET button for about 10 seconds 3C3). The indicator of the concerned stage
until the three green digits to the right and the starts glowing red.
LED indicator of the uppermost setting knob
start flashing.
f)
Starting and tripping of the second stage is
c) activated in the same way as stage 1. The indica-
Press the push-buttons RESET and STEP si- tor of the third or fourth setting starts flashing to
multaneously. Then the starting of stage 1 (e.g. indicate that the concerned stage has been acti-
the I>-stage of the overcurrent module SPCJ vated.
3C3) is activated and, simultaneously, the indi-
cator of the stage starts glowing yellow. g)
To activate the self-supervision output step to-
wards the test position, where no indicator is
flashing. Press the STEP button once. In about
5 seconds the red IRF indicator starts glowing
and the IRF output is activated. Shortly thereaf-
ter the indicator goes out and the output auto-
matically resets. At the same time the module
leaves the test position.
h)
It is possible to leave the trip test mode at any
step of the sequence scheme by pressing the
RESET button for about 10 seconds until the
three digits to the right stop flashing.
8
Operation A measuring relay module is provided with two The operation indicator starts glowing yellow
indicators separate operating stages, each of which with its when the operating stage starts and red when a
own yellow/red operation indicator on the lower delayed tripping operates. The functions of the
part of the front plate of the relay module. start and operation indicators are described in
detail in the different protection relay module
manuals.
Fault codes In addition to the protective functions the relay In most fault situations a fault code, indicating
module is provided with a self-supervision sys- the nature of the fault, appears on the display of
tem which continuously supervises the function the module. The fault code, which consists of a
of the microprocessor, its program execution red digit (1) and a three digit green code number,
and the electronics. cannot be removed from the display by reset-
ting. When a fault occurs, the fault code should
When the self-supervision system has detected a be recorded and stated when service is ordered.
permanent fault in the relay module, the red
IRF indicator on the panel starts glowing soon
after the fault was discovered. At the same time
the module puts forward a signal to the self-
supervision contact of the relay assembly.
9
1MRS 750801-MUM EN
ABB Oy
Substation Automation
P.O.Box 699
FIN-65101 VAASA
Finland
Tel. +358 (0)10 22 11
Fax.+358 (0)10 22 41094
www.abb.com/substationautomation