5110

AUTO START
DEEP SEA ELECTRONICS RECOGNISED TO UL 508

DESCRIPTION Issue 1
VH 10/01/03
The Model 5110 is an Automatic The 5110 module provides engine and
Engine Control Module. The electrical metering facilities via the
module is used to automatically start LCD display with the following
and stop the engine, indicating the instrumentation displays, accessed via
operational status and fault the SCROLL push-button:
conditions, automatically shutting
Generator Volts L1-N, L2-N, L3-N
down the engine and indicating the
Generator Volts L1-L2, L2-L3, L3-L1
engine failure by means of a
Generator Amps L1,L2, L3
graphical LCD display and a flashing
Generator Frequency Hz
LED on the front panel. Selected
Engine Speed RPM
operational timers and alarms can be
Engine Oil Pressure (PSI & Bar)
altered by the customer. o o
Engine Temperature ( C & F)
Adjustments are made by using the
Plant Battery Volts
integral front panel editor allowing
Engine Hours Run
changes in the field, with no
specialist equipment required. DESCRIPTION (continued)
e.g.
Engine analoge inputs are provided
Operation of the module is via
for Oil Pressure and Engine
pushbuttons mounted on the front
Temperature. These connect to
panel with STOP, AUTO and
conventional engine mounted
MANUAL modes.
resistive sender units (such as VDO
A further pushbutton provides an
or Datcon Type) to provide accurate
LCD DISPLAY SCROLL function to
monitoring and protection facilities.
view the instrumentation.
Alternatively they can be configured
The module features microprocessor to interface with digital switch type
control and provides a The instrumentation displays are inputs for Low oil pressure and high
comprehensive list of timers and pre- supplemented further by LCD icon engine temperature shutdowns.
configured sequences. This allows displays for various engine alarms.
Relay outputs are provided for Fuel
complex specifications to be
Uncommitted LCD icons allow the user Solenoid Output, Start Output and
achieved.
to configure the module to provide three configurable outputs.
Multiple alarm channels are other status or alarm indications from
provided to monitor for the following either internal states or from external A range of different functions,
conditions: digital inputs. conditions or alarms can be selected
► Under/Overspeed
for the three configurable relay
The module accepts the following outputs. These outputs supply
► Charge alternator failure
digital inputs; positive plant supply out.
► Emergency stop
► Low oil pressure ► Emergency Stop - A N/C DC Refer to appropriate manuals for
► High engine temperature positive input details.
► Fail to start (overcrank) ► 5 fully configurable warning or
► Fail to come to rest shutdown inputs. FEATURES
► Loss of speed sensing signal
With the exception of the Emergency ► Micro-processor based design
Additionally any configurable input Stop Input, these are configurable to
► Automatic engine starting and stopping
alarms that have been configured as be either N/C or N/O contacts,
► Automatic shutdown on fault condition
indication, warning or shutdown. switched to the -Ve DC.
The five fully configurable auxiliary ► Custom graphical icon type display
Alarms are indicated by an LCD Icon
inputs can be selected to be indication, ► Provides engine and generator
and LED illumination. instrumentation
warning or shutdown inputs either
The 5110 series modules have been immediate or held off during start up to ► Provides engine alarms alarm and status
designed for front panel mounting. information
allow for use as protection expansion
The module is fitted into the cut-out ► “Front panel” configurable inputs,
inputs. Alternatively they may be outputs, alarms and timers.
with the fixing clips removed. These configured to control extra functions
are then fitted from the rear. ► LED & LCD alarm indication
such as lamp test or Remote start
Connection is via locking plug and ► Compatible with 5200 series modules for
input - refer to appropriate manuals easy upgrade path.
socket connectors. for details.
SPECIFICATION

DC Supply: Max. Operating Current:


8 to 35 V Continuous. 420mA at 12V, 270mA at 24V
Cranking Dropouts: Max. Standby Current:
Able to survive 0 V for 50mS, providing supply was at least 10V 250mA at 12V, 140mA at 24V
before dropout and supply recovers to 5V. This is achieved Alternator Input Range:
without the need for internal batteries. 75(ph-N) to 277(ph-N) 3 Phase 4wire AC (+20%)
Start Relay Output: Alternator Input Frequency:
10 Amp DC at supply voltage. 50 - 60 Hz at rated engine speed (Minimum: 15V AC Ph-N)
Fuel Relay Output: Magnetic Pick-up Voltage Input Range:
10 Amp DC at supply voltage. +/- 0.5 V to 70 V Peak
Auxiliary Relay Outputs: Magnetic Input Frequency: 10,000 Hz (max) at rated engine
2 Amp DC at supply voltage. speed.
Charge Fail / Excitation Range: Dimensions:
0 V to 35 V 240mm x 172mm x 57mm (9½’’ x 6¾’’ x 2¼’’ )
Operating Temperature Range: Panel Cutout:
0
-30 to +70 C 220mm x 160mm ( 8.7” x 6.3”)
Environment Maximum Panel Thickness:
Pollution Degree 2 8mm (0.31”)
Overvoltage Category III
Deep Sea Electronics plc reserve the right to change specification without notice.

TYPICAL W IRING DIAGRAM


LOAD
L1 L2 L3 N

L1
CT
Earth
L2

L3

N
F2A F2A F2A
Transient Voltage Supressors
400V XUHT2 (R/C) (6kV Withstand)
Recommended fitted across terminals
CT 35-37 to terminal 38
common

39 40 41 42 43 35 36 37 38
Not connected

MPU
17
18

5110 controller
Not connected

internal emergency stop


Not connected
Not connected

To plant supply +ve Ground screen


at one end only
Supply for
controller
16
1 2 3 5 4 9 44 45 46 47 10 11 12 13 14 15 19 6 7 8
Functional
Earth
Configurable auxiliary input 2

Configurable auxiliary input 3

Configurable auxiliary input 5


Configurable auxiliary input 1

Configurable auxiliary input 4


stop
Emergency

Configurable auxiliary output 1

Configurable auxiliary output 2

Configurable auxiliary output 3


Coolant temp. sender
Oil pressure sender

F F

These ground connections must be


Crank Fuel on the engine block and must be
Starter a sound electrical connection
motor + to the sender bodies.
Charge WL The ground connection to terminal 47
Battery alt. must not be used to provide a ground
connection to any other device.

Deep Sea Electronics Plc. Deep Sea Electronics inc.


Highfield House, Hunmanby Industrial Estate, 5301 E. State St. – Suite 202
North Yorkshire. YO14 0PH. ENGLAND Rockford, Illinois 61108 U.S.A.
Tel +44 (0)1723 890099. Phone +1 (815) 316-8706
Fax +44 (0)1723 893303. Fax +1 (815) 316-8708
Email - sales@deepseaplc.com Email – dsesales@deepseausa.com
Web - www.deepseaplc.com Web – www.deepseausa.com