Paper 0403
Nagu N. Srinivas
UtilX Corporation, USA
nsrinivas@utilx.com
Paper 0403
Partial
discharge
Partial
discharge
Partial
discharge
Partial
discharge
Partial
discharge
Level 4: The system has moderate probability of failure.
It is recommended to replace the cable in 2 years.
Electrical trees Further discussion is required to determine the viability of
FAILURE
rejuvenation for extruded cables.
Figure 1- Defects in extruded cable that can be detected. Level 5: The system has a high probability of failure
within the next two years. Consider immediate
replacement.
IN SITU CABLE ASSESSMENT TECHNOLOGY
A review of historical CableWISE test data results has been
Data acquisition begins by placing an RF sensor over the performed by an independent research organization.
exterior of an energized shielded cable. RF signals emitted Substantial data is available where such tested cables had
by the cable system while in service are detected, amplified, remained energized and in service for many years after the
and then recorded on a laptop computer for later testing was completed. This analysis has suggested that
transmission to be analyzed by the specialists.(Ref3) The recommendations regarding future performance are justified
analysis involves reading the signals both in frequency and as being reliably related to the probability of failure, rather
time domains The frequency spectra are used to locate the than absolute values for any specific tested segment. It is
deterioration which emits RF signals, and the time domain also concluded that the analysis provides guidance on the
traces are then used to determine the significance of accuracy of the diagnostic test method. This provides a new
deterioration The assessed condition of each cable approach for guidance to the utilities regarding asset
component also depends on the type of cable insulation, management decisions.
influence of installation conditions, and previous condition
assessments (when available). Improved data analysis
CASE HISTORIES
software permits detection of minute signals with the help
of correlation software such as Fast Fourier transform. The
Case History A: The assessment levels discussed above
ratio between the main frequency and the first harmonic is
were used while evaluating cable systems in a major
also used to further identify signals of concern.
Western Utility in US and serve as an example of how to
apply the predictive technology. Overall, the analysis
allowed this utility to evaluate the potential of utilizing this
Level 3 predictive condition assessment technology (CableWISE) as
Le
ak
Paper 0403
Paper 0403
(again for the purpose of improving cable life). However, technology to improve system reliability. Over 99% of
there were several drawbacks in this approach also. those cables remain in failure-free service today.
Acetophenone is a solid at room temperature and the cables
had to be warm prior to injection. It also diffuses out of SUMMARY
cable over time and thence the improvement in the
insulation properties vanish. These factors made use of Asset managers in electric utilities and industrial plants can
Acetophenone unsuitable for life extension in the field. In use novel technologies to improve the reliability of their
the late 1980’s a new fluid based on silicone technology electrical distribution system. Cost savings can be realized
was developed and has been in use in the field effectively by making proper engineering judgements based on In situ
since then. This life enhancement fluid offers superior cable system condition assessment (CableWISE) and by
speed of treatment, increased cable life under harsh increasing the remaining life of the aged extruded cables by
conditions of elevated temperature and many other fluid injection ( CableCURE) .These two technologies have
advantages (Ref 7). Additional research conducted over been in use for many years with proven success in the field.
several years has led to the development of a new fluid
especially suited for larger, hotter-running cables such as Acknowledgments
feeder cables.
The fluid (CableCURE) is injected directly into the
The author acknowledges the contributions made by UtilX
interstitial region of the electrical cable. Initially cable is
personnel, Dr. Oscar Morel, CableWISE Technology
deenegized and special elbows are attached to the cable
Specialist and Dr. Wayne Chatterton, Director, Technology.
which is then re-connected to the transformer. The fluid is
then pumped into the conductor through the elbow’s
injection port while the cable is energized. From the REFERENCES
interstices the fluid diffuses into the polymer insulation of
the cable seeking out the polar (degraded) regions that may 1) EPRI report EL 3154 – Estimation of Life Expectancy of
contain water. CableCURE is made up of 100% water PE insulated cables - Nagu Srinivas, Principal Investigator
reactive cable treatment fluids and via molecular
interaction, eliminates water from the void as well as water 2)N.N. Srinivas and B.S, Bernstein “Effect of DC Testing
diffusing through the cable. When the fluid comes in on XLPE Insulated Cables” Proceedings Jicable 95,
contact with water it oligomerizes (increasing in molecular Versailles France,(June 1995),pages 139-144; EPRI Reports
weight), filling the cavities containing the water tree with a TR-101245 V 1 and V2. “Effect of DC Testing on Extruded
more viscous water resistant fluid, thus, preventing further Cross linked Polyethylene Insulated Cables Phase 1
tree growth. As it reacts with the water in the void it (January 1993) and Phase 2 (October 1995);
undergoes ongoing oligomerization. This monomeric
starting material slowly polymerizes in the water tree 3) N. Ahmed and N. Srinivas, “Partial Discharge
regions. Hence the overall process involves a monomeric Measurement in Distribution Class Extruded Cables, 1999
starting material that reacts with water and itself, IEEE T&D Conference, pp 46-51, New Orleans, 1999
polymerizes, fills the voids as the water is removed and
slows down the diffusion of the material. Since the 4) S. Boggs, The Case for Frequency Domain PD Testing in
molecules of the resulting oligomer are many times larger the Context of Distribution Cable, IEEE Electrical
than water molecules, they lock into place and retard the Insulation Magazine, Vol. 19, No. 4, 2003
growth of future water trees. The entire process dries out the
electrical cable restoring the dielectric strength, thus 5) N. Srinivas, T. Nishioka, K. Sanford and B. Bernstein
increasing the service life of the cable. The diffusion occurs “Non-Destructive Condition Assessment of Energized
at a rate which is fast compared to the aging process and the Cable Systems “paper presented at 2005/2006
diffusion of water. Transmission and Distribution Conference, Dallas Texas