You are on page 1of 2

RESULT

Table 1 : Result of Heat Pump, SOLTEQ Mechanical Heat Pump (Model: HE165)

Test 1 2 3 4 5
Cooling % 78.6 45.5 32.8 43.6 19.0
Water
Flowrate,
FT2
Cooling LPM 3.9 2.3 1.6 1.2 1.0
Water
Flowrate,
FT2
Cooling ˚C 29.8 30.0 30.2 30.4 30.5
Water Inlet
Temperature,
TT5
Cooling ˚C 34.4 37.6 40.6 43.6 46.8
Water Outlet
Temperature,
TT6
Compressor W 310 321 330 339 349
Power Input
Heat Output W 1249.8200 1217.7733 1159.2533 1103.5200 1135.5667
COPH - 4.0317 3.7937 3.5129 3.2552 3.2538
Performance Curve of Heat Pump Vs Cooling
Water Outlet Temperature (o C)
1400 4.5
1200 4
3.5
1000
3
800 2.5
600 2
1.5
400
1
200 0.5
0 0
34 36 38 40 42 44 46 48

Heat Output Compressor Power Input COPH

Figure 1 : Performance Curve of Heat Pump Vs Cooling Water Outlet Temperature (˚C)