Printed Specifications are NOT Controlled Documents. Verify Revision before using.
1/2
ITEM DESCRIPTION YES/NO CORRECTIVE ACTION/
N/A DATE CORRECTED/COMMENTS
P PLUMBING: Inspected By: ___________________________________
Verify all new piping tie-ins to existing plumbing
P1 mains and submains are coordinated with system
owner for capacity and compatibility.
Pipes are labeled in compliance to the current TI
P2
Standard, including direction of flow and content.
Ensure dielectric unions on dissimilar metals installed
P3
where applicable
Chilled water piping, both supply and return, are
P4
insulated per design
Drains are sized properly, in proper location, and
P5
traps installed per design
Ensure all gravity drain piping is sloped a minimum of
P6 1/8" drop per linear ft or greater as required by
system capacity and building code
Plumbing fixtures are vented to correct location with
P7
properly sized vent line as required
Supply water piping includes the properly sized water
P8
arrestor.
New chilled water piping systems are chemically
P9
passivated per current TI Standards
Ensure all pipe weldments are made with silflos,
P10 unless otherwise approved by system owner
REVISION HISTORY:
B a0212366 7/11/2012 Additional updates & formatting.
A x0135739 7/11/2012 Moved plumbing to a separate document
Authored By: x013573, Ken Golden Date: 7/3/2012
2/2
ITEM DESCRIPTION YES/NO CORRECTIVE ACTION/
N/A DATE CORRECTED/COMMENTS
Approved By: a021236, Jeff Miller Inspected
Date: By: ___________________________________
7/11/2012