You are on page 1of 4

Understanding the

Differences Between Bonding,


Grounding, and Earthing

~[JIT/ -,

~ CNC machine
Source transformer

V I I

~ ~
.J
-c
- Earth resistance, typical value = 10 ohms .- -
Ground rod No.1 Ground rod No.2

Fig. 1. Alightning-induced current flowing inthe earth has atypical value of 20,OOOA. The resulting voltage between the ground rods is200kV,

By Larry Rayand S. Frank Waterer,


Avoiding SfJ1I3re 0 ElIg,lllceri llg Servrces/Schneirler Electric
confusion can
help customers he importance of bonding and grounding in commercial,industrial,and
institutional buildings cannot be overstated. The grounded circuits of
manrmze process machines need to havean effective return path from the machinesto the
power source in order tofunction properly. In addition, non-current-

uptime, sa ety, carrying metalliccomponents in a facility,such as equipment cabinets,


enclosures,and structural steel,need to be electrically interconnectedso
voltage potential cannot existbetween them. The benefits for the building owner are
and profits many - maximized equipment protection , elimination of shock hazard potential,
increased process uptime, and reduced costs through avoiding expensive machine
servicing. However,troubles can arise when terms like"bonding," "grounding:' and
"earthing" are interchanged or confused in certain situations.

28 EC&M January 2009


480V grounded source Busway

o Neutral used as ground conductor; no ground wire


e Surge arrester leads too long, coiled at ground bus

e Neutral wire tied to ground bus


L
CNC machine
o Wire strands broken under lug
e
e Vacuum cleaner plugged into step-down
transformer receptacle load side of line isolation,
regulator devices
e Separate ground rod violates NEe; causes shock
hazard, equipment failure
Ground rod

Fig. 2. Wiring and grounding errors (including the isolated ground rod) that contributed to the CNC machine problems at the example manufacturer.
Typically, an isolated ground rod isinstalled to reduce the effects of the errors listed above, but creates new problems during afault orstorm.

Earthing is the attachment of a Called upon to rectify the problem, havediscovered that isolated ground rods
bonded metallic system to earth, typi- personnel from the engineering ser- can decrease the number of nuisance
cally through ground rods or other vices organization of a major electrical problems, such as rebooting, data er-
suitable grounding electrodes.The NEC distribution equipment manufacturer rors, and intermittent shutdowns. This
prohibits earthing via isolated ground observed that although the plant had decrease is due to the reduced amount
rods as the only means of equipment grounded the CNC machine in accor- of voltage transients or "noise" on the
grounding . Nevertheless, some manu- dance with the manufacturer's instal- ground rod, as compared to a common
facturersof sensitivemachinery actually lation manual, the ground was in clear building grounding system. Because of
encourage this practice in their instal- violation of the NEC. This apparent the reduction in data errors attributed to
latiou mauuals, in order to reduce "no contradiction demonstrates a disturb- the ground rod, some manufacturers in-
problem found" service calls associated ing fact: Some grounding practices that clude isolated ground rod~ in their instal-
with machine errors and rebooting. are designed to decrease data errors in lation instructions. Some even imply the
sensitive machines can actually violate machine warranty will not be honored if
An illustration. Understanding the grounding codes and standards, caus- the ground rod is not installed.
differences between bonding/ground- ing equipment damage and introducing During thunderstorms or ground
ing and earthing is best illustrated with safetyhazards. It's also important to note faults, however, an isolated ground rod
an example. A manufacturer of molded that the conflicting requirements can be becomes a liability, creating shock haz-
components wasreplacingfailed printed overcome, but never by compromising ard potential for employees and high
circuit boards in a computerized nu- employee safety. potential riseson sensitive machinecom-
merically controlled (CNC) machine . ponents . Figure 1 on page 28 illustrates
After a thunderstorm. the machine's Key concepts and terms. Under- the extremely large transient voltages
self-diagnostic system occasionally standing the difference between bond- that can develop between driven ground
registered a component problem . The ing/grounding and earthing requires rods due to lightning currents and earth
machine would not start, delaying the implicit understanding of several impor- resistance. Although ground faultsin the
day's production cycle. Plant electronics tant concepts and terms, including those machine itself may not draw enough
techniciansidentifiedand replacedfailed outlined below. current to trip overcurrent protective
circuit boards, then returned the CNC Safety grounding and machine op- devices, they can create touch hazard
machine to operation. However, each eration. The problem experienced by the potential for employees.
occurrence cost thousands of dollars in plant in the example is not uncommon. Article 250.54 of the 2008 NEC
repairs and lost production. Manufacturers of sensitive machines specifically prohibits the use of

January 2009 EC&M 29


480V grounded source Busway

Safety switch

o Add ground wire; re-route neutral

e Shorten leads from arrester to ground bus


e Replace white neutral wire with ground wire
and route properly
CNC machine

e Replace wire connections e


e forProvide different 480V sourceto step-down transformer
receptacles
o Bond ground rod to building ground system
Ground rod

Fig. 3. Corrective actions needed to eliminate the wiring and grounding errors depicted in Fig. 2. Once the spurious ground rod had been con -
nected to the rest of the example manufacturer'sbonded system, including correcting the wiring error shown inFig. 2, operating issues were
addressed by correcting the remaining wiring errors as listed.

isolated ground rods, or earthing, as the electronic equipment is then grounded solidly grounded wye, which is estab-
sole means of equipment grounding, to an earth ground isolated from the lished by connecting a properly rated
although some have used other sections common powersystemground. Isolating conductor (also known as the main or
of the NEC to justify this practice. The equipment in this manner creates a po- system bonding jumper) from the Xo
"NEC Handbook" providesthe following tential difference that is a shock hazard. terminal of the source (usually a trans-
commentary associated with Art. 250.6 The error is compounded because such former) to the grounding system.
(Objectionabl e Currents): isolation does not establish a low-im- • Equipment grounding (bonding).
"An increase in the use of electronic pedance ground-fault return path to the The best means of equipment ground-
controls and computer equipment, powersource,which is necessary to actu- ing is to route a grounding conductor,
which are sensitive to stray currents, has ate the overcurrent protection device." suitably sized, along the same route
caused installation designers to look for Bonding/grounding vs. earthing. Iso- as the power and neutral conductors,
ways to isolate electronic equipment lated connections to earth are not re- from source to machine. The NEC does
from the effects of such stray circulat- quired for sensitive machine operation. allow use of metallic conduit and other
ing currents. Circulating currents on Issues crop up when equipment bonding! substitutes, but some industry experts
equipment grounding conductors, metal grounding and earthing are confused. In believe these systems are less effective
raceways, and building steel develop po- the United States, the term "grounding" and should be avoided.
tential differences between ground and is used to refer to at least five or more • Grounding electrode (earthing).
the neutral of electronic equipment. grounding-related systems,including: This term refersto the method by which
"A solution often recommended by • System type. This refers to the the facility grounding system is con-
inexperienced individuals is to isolate means by which power source voltage nected and referencedto earth. The most
the electronic equipment from all other relationships are established. Power common grounding electrode for small
power equipment by disconnecting it sources fall into four general categories: facilities is a metallic ground rod, but
from the power equipment ground. In Transformers, generators, electric utili- earthing systems for larger buildings can
this corrective action , the equipment ties, and static power converters. These - and should - be more elaborate and
grounding means is removedor nonme- systems may be configured as wye or include the means by which to inspect
tallic spacers are installed in the metallic delta, and the means by which they are and test these systems periodically. A
racewaysystemcontrary to fundamental interfaced with the grounding system grounding electrodesystem that isburied
safety grounding principles covered determines the system type. The most in earth or encased in concrete and then
in the requirements of Art. 250. The common 3-phase system type is the forgotten isoften the sourceofincreasing

30 EC&M January 2009


problems as the building ages and the
grounding electrodes deteriorate.
• Lightning abatement. Some fa-
Knowledge is Power
cilities use air terminals (also known An electrical engineer or contractor who understands the various elements of proper
as lightning rods) to direct lightning grounding, bonding, and earthing systems isbest positioned to counsel customers on
strikes away from power equipment,
appropriate practices inthis area. Akeen understanding of NEG requirements could also
but these devices ilre often connected to
the grounding system in such a way that help you develop areputation as being the one to contact with any bonding/grounding-
they have the opposite effect - unin- related questions. Such expertise could also lead to future business.
tentionally bringing lightning energy
into facility structural steel, low-voltage This connection eliminated the shock sensitive machine.
transformer windings.aud, subsequently, potential during storms by reducing the 3. Install a step-down transformer
sensitive building loads. resistance between the ground rod and (i.e.,a separatelyderivedsource) to serve
• Signal-reference grounding. Sen- the building grounding system. only the process machine. Derive a new
sitive electronic machines rely on the The next step was to eliminate the neutral to the ground bonding point at
ground ing system for reference of low- wiring errors and install a ground wire the load side of the transformer.
magnitude signals. Therefore, it's often from the source to the eNC machine 4. Anyremaining operating problems
crucial to provide multiple grounding (Fig. 3 on page 30). The primary reason are probably caused by communications
paths, rather than relyon a singleequip- that the isolatedground rod waseffective ground loops. Ground loops, which are
ment grounding conductor between the in decreasingoperating problems wasthe introduced by communication wiring
power source and the sensitiveload.This building's bonded system experienced betweensensitive machines fedfrom dif-
ensures that spurio us voltages on the voltage transients, imposed on it due to ferent power sources, may require more
grounding system are maintained well wiring errors. One common error is the elaborate correction schemes, such as
below the level at which they might be improper connection of neutral wires to optical isolation.
confused with sensitive machine refer- ground buses or ground wires to neutral
ence signals. The best guide for signal- buses. This error allows neutral currents Taking the next step. In summary,
reference grounding is IEEE Standard to flow on the bonded system, thereby the plant in the example had installed a
1100-2006, "Recommended Practice creating voltagetransients. Neutral wires CNC process machinein accordance with
for Poweringand Grounding Electronic are only allowed to be connected to the the manufacturer's recommendations.
Equipment." bonded systemat a serviceentrance or at Unfortunately, those recommendations
Note that earthing is not required for a step-down transformer (called a sepa- included the requirement for a separate
sensitive machine operation . Modern ratelyderivedsource bythe NEC). Notice ground rod to serveas the only means of
aircraft, for example, are packed with in Fig. 2 that the plant had installed both equipment grounding.Whilethispractice
sensitive computers and electronic de- a voltage regulator and a noise suppres- may reduce data errors in sensitive pro-
vices, which operate correctly without sion device ahead of the CNC machine. cessmachines,it violatesthe NEC,creates
an attachment to earth. They rely on a These devices are often applied to solve a shock hazard for employees, and causes
bonded metallic system - the airplane the nuisanceoperating problemsbrought a potential difference that may damage
framework, skill, structural supports, on byground systemtransients.Suppres- sensitiveelectronic components .
raceways, and grounding conductors sion devices are not a cure-all, however. Electrical engineers and contractors
- to serve as the ground reference. If In fact, they're sometimes unnecessary can help customers avoid situations like
this bonded system rises in voltage with when wiring and grounding problems this by providingproactivecounselin this
respect to earth, all machines onboard are corrected first. area. The best place to start is to gather
experiencethe increasetogether.The net Once the spurious ground rod had as much information as possible- from
result is that the machines see no volt- been connected to the rest of the bonded the 2008 NEC, seminars/conferences,
age potential differenceswith respect to system, operating issues had to be ad- trusted electrical equipment manufac-
each other. Once the airplane lands, any dressed, which involved correcting the turers, and online sources. With that
voltage potential between the plane and wiring errors identified in the site sur- knowledgein hand, you haveyetanother
earth must be discharged by an electrode vey. For the example facility, these steps reason to call on a customer and resolve
that bypasses the rubber tires. were adequate. For other situations, you an issue of critical importance. EC&M
should refer to the following checklist:
Resolving t he issue. The immediate I. Connect the ground rod to the Ray, P.E., isdirector ojSchueider Electric's
solution to the example plant's illegal bonded system and install a grounding Square D Engineering Services, Raleigh,
ground rod (Fig. 2 on page 29) was to conductor from the power source to the NiC. He can be reached at larry.ray@
removethe shock hazard.This wasdone sensitiveload to eliminate the safetyhaz- us.schneider-electric.com. Waterer is an
by connecting a grounding conductor ard and allow an effective ground-fault Engineer!ngFellowforSchneider Electric's
( I/O copper) from the grou nd rod to the return path. Square D Engineering Services, Norcro ss.
nearest part of the building grounding 2. Correct wiring and grounding Ga. He can be reached at jrank.waterer@
system- in this case,the structural steel. errors on the power system serving the us.schneider-electric.com.

. January 2009 EC&M 31

You might also like