You are on page 1of 4

Is it the drive, the

motor, or the load?


Application Note

Where do you start balanced, the cause could be


internal to the motor (deterio-
when troubleshooting rating stator insulation, for
problems? example), or it could be the
In troubleshooting situations result of voltage imbalance. So
involving a motor, more than if there is any problem with
half the battle is simply isolat- current imbalance, make the
ing the problem. Whenever voltage imbalance measure-
there’s a working motor, ment (less than three percent)
there’s a load and there’s some at the output of the ASD. The
sort of motor controller, which following calculation works
is increasingly going to be an for either voltage or current
adjustable speed drive (ASD). imbalance.
So when problems arise, how Voltage and current imbal-
can you tell if it is the drive, ance measurements should also
the motor, or the load? Here be taken at the line side of the
are a few tips to tackle the drive. Drives are extremely
problem in a quick, systematic sensitive to voltage imbalance,
way, making a few key meas- even more so than motors.
urements as you go. Drives are using the peak volt-
ages of each phase to charge
Imbalance measurements internal capacitor banks. If one
A good place to start is with a of these phases is even a bit
measurement of current drawn low, it will make it hard for the
by the motor. When we talk drive to draw current from that
about motors here, we are phase. So voltage imbalance
referring to three-phase induc- will cause current imbalance.
tion motors, the workhorse of The drive may still function, but
industry. Motors are balanced the charge cycle of the capaci-
loads: the current that they tors, and their ride-through
draw on each phase should be time in the event of voltage
about the same (less than sags, will be diminished.
ten percent, as measured In addition to imbalance
below). If they are not measurements, voltage drops should also be checked. This
across loose connections can be done with direct volt-
age measurements or with
infrared thermometers. Read-
ings that are much higher than
Percent imbalance = maximum deviation from average / the ambient temperature, or that
average of three phases X 100% are higher than other phases,
Example: can indicate loose or otherwise
1. As measured: Phase A = 449 A; Phase B = 470 A; bad connections.
Phase C = 462 A
2. Calculate Average = (449 + 470 + 462) / 3 = 460 A
3. Calculate Max Deviation = 460 – 449 = 11 A
4. Calculate Imbalance = (11 / 460) x 100 % = 2.4 %
Note: New three phase power quality analyzers perform these calculations automatically.

Continued on next page

From the Fluke Digital Library @ www.fluke.com/library


Continued from previous page

ASD overvoltage and problems. Studies have shown Overloading is always relative to
undervoltage trips that these low-cost compo- time: a high overload will trip the
nents are the first to drop out motor in a short time, while a
Drives have diagnostic codes when voltage sags occur. So lower level of overload will take
which identify the cause of don’t forget to look at any longer to trip the motor.
trip. Generally speaking, they external control circuit while When we want to evaluate the
can be classified as overvolt- you’re troubleshooting intermit- impact of a load on the motor-
age, undervoltage, or overload tent system shutdowns. drive system, we have to
(overcurrent). Note that Overvoltage could be a measure the current it draws. Of
mechanical starters only have symptom of problems in the course, this current draw typi-
overload trips. They’re not capacitors or reactor. Or it could cally varies over time as the load
concerned with over or under- be caused by line-related volt- varies. The measurement of
voltage. What makes drives age transients. At one point, current over some period of time
different? utility capacitor switching tran- is called load profiling. For load
Drives turn sine wave ac sients were notorious for profiling, the power-record func-
into dc (converter section), and causing overvoltage trips in tion of Fluke power quality
then turn the dc back into ac drives. Overvoltage could also analyzers is ideal for capturing a
(inverter section). However, the be caused by regenerative trend line of current consumption
ac at the output is not a sine loads. Loads such as cranes (and kW too, if you want it). A
wave. It is a special waveform and elevators feed back voltage cursor enables you to identify the
known as the pulse-width when they decelerate. Dynamic current values at different points
modulated (PWM). The PWM, braking circuits are installed to on the trend line, along with a
from the motor’s point of view, shunt off this energy from the time stamp for those points. It is
is accepted as if it were a sine drive, where they would other- not necessary to measure all
wave — almost (see Advanced wise show up as overvoltage three phases of the induction
motor measurements below). on the dc link. Problems such motor because the motor is a
For now, though, let’s focus on as improper installation can balanced load. Before load
the drive internals, specifically result in overvoltage trips. profiling, first make the current
on what’s commonly referred Overload problems are imbalance measurement to make
to as the dc link. The dc link is usually load related and will be sure the motor is healthy. If your
nothing but a capacitor bank, addressed below. concern is nuisance tripping,
usually with a series link then pick the high leg and
inductor (reactor) thrown in for Load profiling measure that (an overload on
filtering and protection. The dc one leg will trip all three legs).
link is carefully monitored by To troubleshoot the interaction When load profiling, we are
the drive; overvoltage or between the load and the looking for periods of especially
undervoltage refers to the volt- motor, you have to understand high current, relative to the full
age of the dc link. the relationship between load amps of the motor. Full load
Undervoltage can be caused torque and current. A motor is amp information is available on
externally by voltage sags on nothing but a device to turn the nameplate of the motor. If
the drive input. The Sags and electrical energy (current) into there is a service factor, the
Swells function on Fluke power rotational mechanical energy range calculation should be made
quality analyzers can help to (torque), via the magical effects on the basis of full load amps
identify line-related undervolt- of magnetism. What a load times service factor.
age problems. Problems could demands of a motor is torque. While high current is the main
also exist internally with the dc For all practical purposes, this concern, low current should also
link capacitors and/or reactor. torque is directly proportional be avoided. A motor is most effi-
In many drives, there are test to current used by the motor. cient, and has the best power
points to measure the dc link This should make perfect factor, in the 60 to 80 percent
voltage. To check the capaci- sense, because we all know range of its full load amps. There
tors, use the min/max function that for constant-speed motors is no immediate penalty for
of a digital multimeter, or, — which include all motors underloading — the motor will
preferably, the trend function of started across the line (with not trip. In fact, many motors are
a Fluke power quality analyzer electro-mechanic starters) — routinely oversized for the load,
or ScopeMeter® test tool. Check voltage is, or should be, stable, on the theory that the motor is
if voltage regulation is within and current is the variable. less likely to trip from overload.
the manufacturer’s specifica- When a load demands more However, as is most often the
tion. To check the reactor, torque and current than a case, there is no free lunch. In
check the waveform on both motor can supply, the result is the case of underloading, the
sides — there should be no an overload condition. Over- energy company sends a higher
change. loading will cause overheating bill.
When troubleshooting a of the motor. Motor controllers
system, the tendency is to view will shut down the motor (and
the drive or PLC as the most thereby the load) rather than
susceptible to voltage sags. The allow permanent winding insu-
ice-cube control relay is most lation damage to occur.
often the source of sag-related

Continued on next page

2 Fluke Corporation Is it the drive, the motor or the load?


Continued from previous page

Two different loads: measure heat indirectly by These overvoltages are


variable torque and measuring current (there are clearly visible on the scope
constant torque motors with heat sensors waveform. Solutions fall into
embedded in their stators, but three categories: shorten the
Most drive systems are used these are obviously more drive-motor cable length;
with variable torque or expensive). Here we have a use a motor with higher
constant torque loads. Variable situation where normal current grade insulation, so-called
torque loads include fans and draw at low speed can cause inverter duty motors; use
rotary pumps. These are by far overheating. The common solu- filters.
the majority of loads, from an tion is to install externally
energy consumption point of powered fans to cool the motor.
• Motor shaft voltages and
bearing currents. Measure
view. When ASDs are used Before we leave the subject voltage rotor-to-frame
with these loads, dramatic of load troubleshooting, it (ground), using stranded
energy savings can be realized. should be noted that there is a wire or a carbon brush.
For example, a fan at half- whole area of expertise having Motors run by sine waves
speed (30 Hz) ideally uses only to do with the mechanical link- have a "normal" shaft/bear-
one-eighth of the power of the age of the motor and load. ing-to-frame voltage of 1 to
same fan at 60 Hz (we say These include vibration, shaft 2 V. The PWM waveform can
ideally, because there is always alignment, motor mounting, cause breakdown voltages of
some level of loss due to ineffi- etc. These are obviously impor- 8 to 15 V to occur between
ciencies in the drive-motor- tant issues, but they are the shaft (more specifically,
load system). From a trou- outside of the scope of this arti- the bearing) and the frame.
bleshooting point of view, the cle. This damages bearings,
important thing to realize is causing pitting and scarring.
that these variable torque loads Advanced motor Many solutions have been
rarely cause overload-related measurements proposed, but the most
problems for drives (assuming common is the shaft ground-
the load has been sized In ASD motor systems, there
are a few measurements that ing device.
correctly). That is because they
spend a lot of their time need to be taken that would • Leakage current. Measure
running at lower speeds (less not be taken in mechanical with a current clamp around
than 60 Hz) and drawing less starter (across the line) motor all three phase conductors.
current. If this were not the systems. This is because the High frequencies cause
case, that is, if the load fast switching, high-frequency increased leakage between
demanded full speed (and element of the PWM output stator windings and the
torque) most or all of the time, waveform causes special prob- frame. This ground or leak-
there would be no economic lems that the sine wave age current can interfere
justification; i.e., energy doesn’t. At first glance, the with control and communi-
savings, to install an ASD in motor as a current-drawing cation signals. Common
the first place. Sometimes these load looks like nothing but a solutions are the use of EMI
loads will cause a trip at start- big set of inductors or coils suppression cables or a
up, but that is usually an (stator windings), and the common mode choke.
indication that the load has not nature of inductors is that they What about harmonics at the
been sized correctly to the filter out the high frequency output of the drive? Wouldn’t
drive. Another possibility is that current elements. That is why the PWM-turned-into-sine-
the load has changed. For the current waveform looks like wave current-waveform
example, a bearing starting to a sine wave. But unfortunately, contain a lot of harmonics?
seize up demands more initial those high-frequency elements Absolutely. But we don’t have
torque to get the load going. of the voltage waveform do not to measure these. First of all,
Constant torque loads can get filtered out, and are capa- they don’t get into the rest of
be more challenging. Frictional ble of causing some mischief. the power distribution system;
or gravitational loads are The first two of these meas- they only affect the motor.
constant torque loads. The key urements should be made with Specifically, they cause addi-
thing to understand about a ScopeMeter or with the Scope tional heating in the motor.
these loads is that they require function of a Fluke power However, motor and drive
the same level of current (more quality analyzer: manufacturers have addressed
or less) at lower speeds. This • Overvoltage reflections. this problem by supplying
can be dangerous for the Measure phase-to-phase at higher grades of motor insula-
motor. Motors are usually the motor terminals. The tion. In those cases where an
cooled by fans built onto the leading edges of the PWM older motor is retrofit with an
rotor; when the motor slows, pulses can have peak values ASD, the recommendation is
the fan cools less. Therefore much higher (up to 200 that the motor full load amp be
excessive heating can occur. percent in theory) than derated.
The danger is that motor over- normal. These overvoltage
load circuits are built to reflections can cause
damage to motor windings.
Continued on next page

Is it the drive, the motor or the load? Fluke Corporation 3


Continued from previous page

Summary Work safely


To determine whether it’s the The high voltage and currents
load, the motor, or the drive present in electrical power
that is causing problems, it systems can cause serious
helps to proceed systematically. injury or death by electrocution
Start with the basic motor and burns. Consequently, only
measurements (imbalance) to trained, experienced electri-
check the health of the motor cians who have knowledge of
itself. Then do some simple electrical systems in general
drive measurements to check and the equipment under test
for causes of over or undervolt- should perform testing and
age trips. Profile the load to modification of electrical
find the cause for intermittent systems.
overload trips. Finally, for Fluke cannot anticipate all
premature motor bearing or possible precautions that you
winding failures, as well as must take when performing the
control signal interference, use measurements described here.
a Fluke ScopeMeter test tool to At a minimum, however, you
make additional motor meas- should:
urements. This by no means • Use appropriate safety
exhausts all the possible equipment such as safety
sources of problems, but it will glasses, insulated gloves,
certainly identify a lot of the insulating mats, etc.
most common ones. • Be sure that all power has
been turned off, locked out,
and tagged in any situation
where you will be in direct
contact with circuit compo-
nents. Be certain that the
power can’t be turned on by
anyone but you.
• Read and understand all of
the applicable manuals
before applying the informa-
tion in this application note.
Take special note of all
safety precautions and
warnings in the instruction
manuals.
• Do not use instruments on
applications for which they
are not intended, and
always be aware that if the
equipment is used in a
manner not specified by the
manufacturer, the protection
provided by the equipment
may be impaired.
Fluke. Keeping your world
up and running.

Fluke Corporation
PO Box 9090, Everett, WA USA 98206
Fluke Europe B.V.
PO Box 1186, 5602 BD
Eindhoven, The Netherlands
For more information call:
In the U.S.A. (800) 443-5853 or
Fax (425) 446-5116
In Europe/M-East/Africa (31 40) 2 675 200 or
Fax (31 40) 2 675 222
In Canada (800)-36-FLUKE or
Fax (905) 890-6866
From other countries +1 (425) 446-5500 or
Fax +1 (425) 446-5116
Web access: http://www.fluke.com/
©2004 Fluke Corporation. All rights reserved.
Printed in U.S.A. 10/2004 1989052 A-US-N Rev B

You might also like