You are on page 1of 1

580 370

Fresh Air Opening


Sand Trap
motorized louver optional
115
25
270 100
32 96 90 394 95 180 95

ng
Diesel Generator Foundation 140 370 75 75

ni
pe
90

O
Air
ot
H
150 150

cable trench
Detail A
Fresh Air Opening
Sand Trap

A 115 A
150
motorized louver optional
Panel
50 SEE note h. 50

Diesel Generator Room Lay Out Right Side View


Left Side View

Detail A:
a a

b b
FOUNDATION DETAIL:
EXHAUST DUCT

140 LOUVRED OPENING


HOT AIR &

flexible duct d1:PROFILE THICKNESS


MESH BAR (4Cm x 4Cm) d2:DISTANCE BETWEEN 2 PROFILE
at list20Cm d2
EFFECTIVE AREA = %97 (a x b) EFFECTIVE AREA = (a x b)
d1+d2

14
0
25

F.F: 0.
00
Sand Trap Detail:
270 240 5 10
Fresh Air
Opening 11 14@25cm Top
POWER CABLE
UNP14 6 10@25 cm Top
UNP10 Weld Connection Weld Connection Weld Connection
B B
F.F= 0.00 FOUNDATION

25 90 25 5 25
7 10@20 cm Bottom
SECTION:A-A (schematics)
SAZAND
14 14@20 cm Bottom

SECTION B-B Eng. & Mfg. Co.


Notes:
CLIENT: MATBA
a: The outlet opening hot air in front of radiator has to have an area of 25% e: in case of there was an obstacle in front of radiator
more than area of radiator matrix. Sp No. :
opening has to be considered a way to conduct and draft
the hot air out let upward by a 45 degree slope CONSULTANT:
b: The fresh air opening on the back of set has to have an area of at least
preferable round duct.
equal to hot air opening.
File Na. : MATBA-ROOM LAYOUT-rev2
c: The mentioned areas are "effective area" i.e net opened FREE f: closing plate around the out let exhaust is necessary to
FLOW AREA area which air can pass without any restriction avoid entrance of hot air to machine room because of Dwg.Title:Diesel generator Room Drawing &
through doors and windows to put any damper or grilled it has radiator fan suction. Recommendation
to be added the area as efficiency of grillage or louvre damper g: if exhaust duct is longer than normal for diameter of Project: PERKINS 1103-33G
manufacturer . exhaust coordinate with sazand eng co.
d: Radiator opening has to be fitted firmly to the body of the radiator h: free area is 25% open area. Design By : Z-Farzane
MECHANICAL
as no return of hot air to the machine was possible. ELECTRICAL Drawn By : Z-Farzane
CIVIL Approved By :K-Dor
ALL DIMENSION ARE IN Cm. OTHER WISE MENTIONED.
Date : 94/02/07 Page : 1/1