PRODUCED BY AN AUTODESK STUDENT VERSION

SHORT CIRCUIT CALCULATION: PER UNIT METHOD


SINGLE-LINE DRAWING FOR
ASSUMPTIONS:
1. THE BRANCH CIRCUIT MAIN CB SHALL BE CONNECTED
DIAGRAM CALCULATION
TO A TRANSFORMER WITH THE FOLLOWING DATA:
100kVA, 13.8kV/460V, 1PH, 60Hz, %Z = 1.6% SERVICE DROP WIRE, UTILITY
2. MVAUTILITY = 25MVA, VUTILITY = 13.8kV, ZUTILITY = 7.6176Ω 2 - AWG #6
3. MVABASE = 10MVA, kVBASE = 13.8kV 220V, 1PH, 60HZ
4. ZBASE = kVBASE2 / MVABASE = 13.82/100 = 19.044Ω LINE-TO-GROUND M
5. IBASE = MVABASE / kVBASE = 100MVA/13.8kV = 724.6377A 100kVA,

PRODUCED BY AN AUTODESK STUDENT VERSION


13.8kV/460V,
PRODUCED BY AN AUTODESK STUDENT VERSION

CALCULATIONS: 1PH, 60Hz,


Main CB %Z = 1.6%
1. CALCULATE IMPEDANCES: 60A 2-AWG#6
ZUTILITY-NEW = ZUTILITY x MVABASE x kVOLDBASE = 7.6176 x 10 x 13.8 = 3.04704 20m
1 7
MVAOLDBASE x kVBASE 25 x 13.8 15A 20A
FAULT
ZTRANSFORMER-PU = ZTRANSFORMER x MVABASE = 1.6 x 10 = 1.6 2 8
100 LOCATION
MVAOLDBASE 100 (1000) 15A 20A

TOTAL MOTOR LOADS = 11.97kW = 0.01197MW OR 0.014963MVA @80% PF 3 9


15A 20A
ZMOTOR-PU = ZMOTOR x MVABASE = 0.17 x 10 = 113.6174
MVAOLDBASE 0.014963
4 10
15A 20A
TOTAL LIGHTING LOADS = 1.88kW = 0.00188MW OR 0.00209MVA @90% PF
ZLIGHT-PU = ZLIGHT-PU x MVABASE = 0.10 x 10 = 478.723 5 11
MVAOLDBASE 0.00209 20A SPARE 2-AWG#10 2-AWG#12
30m 30m
FOR WIRE #12AWG, Z = 5.6 OHM/km, LENGTH = 30m 6 12
20A SPARE
1 2 3 4 5 12
Z12AWG = 5.6 x 30 = 0.168, FOR 4-PARALLEL CIRCUITS W/ 2 CONDUCTORS, Z12AWG = 0.084
1000
LOADS
Z12AWG-PU = Z12AWG x MVABASE = 0.084 x 10 = 0.0336
MVAOLDBASE 25

FOR WIRE #10AWG, Z = 3.6 OHM/km, LENGTH = 30m IMPEDANCE DIAGRAM EQUIVALENT
IMPEDANCE DIAGRAM
Z10AWG = 3.6 x 30 = 0.108, FOR 6-PARALLEL CIRCUITS W/ 2 CONDUCTORS, Z10AWG = 0.036
1000 1.0V
Z10AWG-PU = Z10AWG x MVABASE = 0.036 x 10 = 0.0144
MVAOLDBASE 25
1.0V
FOR WIRE #6AWG, Z = 1.44 OHM/km, LENGTH = 20m Z12AWG-PU Z10AWG-PU Z6AWG-PU
Z6AWG = 1.44 x 20 = 0.0288 FOR 2 CONDUCTORS, Z6AWG = 0.0576
1000 ZLIGHT-PU ZMOTOR-PU ZTRANSFORMER-PU ZEQ
Z6AWG-PU = Z6AWG x MVABASE = 0.0576 x 10 = 0.02304
MVAOLDBASE 25
ZUTILITY-NEW
2. CALCULATE EQUIVALENT IMPEDANCE:

ZEQ-PU = 4.47537

3. CALCULATE FAULT CURRENT: NOTES:


1. WIRE IMPEDANCES ARE TAKEN FROM NEC 2017, CHAPTER 9 TABLE 9.
IF-PU = VPU / ZEQ-PU = 1 / 4.47537 = 0.223445 PU 2. SEE LOAD SCHEDULE FOR CABLE SIZE, WATTAGE, & CABLE LENGTH.
IFHV = IF-PU x IBASE = 0.223445 x 724.6377 = 161.9168A
IFLV = IFHV x (13.8kV/460) = 161.9168 x (13800
460 ) = 4,857.505A RECOMMENDATION: BASED FROM THE CALCULATION, USE 5kAIC RATING CIRCUIT BREAKER.

DESIGNED BY: RAL PEÑARANDA ENGINEER: REVISIONS: PROJECT TITLE: SHEET CONTENT: PROJECT OWNER: SHEET NO. 2 of 2
RAL PEÑARANDA, REE TWO-STOREY RESIDENTIAL SHORT CIRCUIT MS. JEANY ROSE CABRAL RIMANDO
CHECKED BY: RAL PEÑARANDA
REG. NO. 43234 TIN: 253-963-420
00 BUILDING CALCULATION: DAGUPAN WESTE
DRAWING NO. 18-001-2

DATE: 07 SEP 2018 TABUK CITY NTS


PTR: 2133605 DATE ISSUED: -- TABUK CITY PER UNIT METHOD SCALE: