1.General
1.1 Two (2) sets of (1 working + 1 stand-by) motor driven boiler initial filling
pumps will be provided for start boiler.
Frequency: 50 HZ
B) Pressure
SI.no Description Unit Quantity
2
1 Static head kg/cm 6
2
2 Filling line control valve pressure drop kg/cm 4
2
3 Other losses kg/cm 2
2
4 Head kg/cm 12
5 Selected Head [(12×1.05×10000)/density] mwc 126.38