Breaker Analyzer
Programma Products
User’s Manual
USER’S MANUAL
for
Breaker Analyzer
EGIL
Subject to change without notice. Printed matter No. ZP-BM01E R06A 2004 Doc:xxxxxx
EGIL
Contents
About this manual................................... 6 5.5 Serial communication terminal (op-
tion)......................................................... 23
1 Safety .................................................... 8
5.6 Other ................................................. 23
1.1 General ............................................... 8
5.7 Indicators .......................................... 24
1.2 Warnings ............................................ 8
5.8 Operation knobs .............................. 24
2 Quick instructions .............................. 10
5.9 Function keys ................................... 25
2.1 Preparing Egil for time
measurement ......................................... 10 6.1 Parameter values ............................. 26
3 System components .......................... 14 6.5 Menu tree for the MAIN menu ....... 43
Programma Electric AB
4 ZP-BM01E R07A
EGIL
Programma Electric AB
ZP-BM01D R07A 5
EGIL
Egil’s components
Chapter 3 (System components) contains a list of the
components that are included in Egil and the accessories
that can be ordered.
Chapter 4 (Description of Egil) presents an overview of
the different control panel blocks.
Chapter 5 (Control panel) presents the control panel in
detail.
Printing results
Chapter 12 (The printer) describes the different parts of
the printout and how to change paper in the printer.
Troubleshooting
Chapter 10 (Troubleshooting) presents many of the most
frequently encountered errors made by users and explains
how to fix them. The error messages that are shown in the
display window are also explained here.
Calibration
Chapter 11 (Calibration) explains how to calibrate Egil.
Programma Electric AB
6 ZP-BM01E R07A
EGIL
Programma Electric AB
ZP-BM01D R07A 7
EGIL
1 Safety
1.1 General 1.2 Warnings
IMPORTANT WARNING
• Read the manual and comply with the • Always make certain that the DC
following instructions before using Egil. system in the substation is disconnected
• Always comply with local safety regula- before connecting Egil.
tions. • Always ground Egil.
• Before connecting Egil, turn off its
master ON/OFF switch.
Symbols on the instrument • Only connect Egil to an outlet pro-
tected with max 16 A overcurrent protec-
Caution, refer to accompanying tion.
• Unplug Egil from the mains supply
documents when it is left unattended or not in use.
• Do not attempt to service Egil yourself.
Opening or removing covers may expose
Protective connector terminal
you to dangerous voltage. If you attempt
to service Egil yourself the warranty is no
longer valid.
• Do not use any accessories that are
not intended for use together with Egil.
• Unplug Egil from the wall outlet before
cleaning. Use a damp cloth for cleaning.
Do not use liquid cleaners or aerosol
cleaners.
CAUTION
• Use only approved mains detachable
cable set with Egil. Main supply cables
shall be rated for the maximum current
for the equipment and the cable shall
meet the requirements of IEC 60227 or
IEC 60245. Mains supply cables certi-
fied or approved by a recognized testing
authority are regarded as meeting this
requirement.
• Polarity on AUX 1&2 must be red to +
and black to -.
• Refer all servicing to qualified service
personnel.
• If you need to return Egil, please use
either the original crate or one of equiva-
lent strength.
Programma Electric AB
8 ZP-BM01E R07A
EGIL
Programma Electric AB
ZP-BM01D R07A 9
EGIL
2 Quick instructions
2.1 Preparing Egil for 6. Connect the breaker trip coil to Egil trip coil
output.
time measurement 7. Make sure a jumper (if the trip and close
coil have the same voltage source) is
connected between the trip coil input and
the close coil input.
IMPORTANT
• Read the chapter “Safety” before 8. Connect the battery + (plus) to Egil coil
using Egil. input.
• Always comply with local safety regula- 9. Remove the ground connections from one
tions. side of the breaker as shown in the picture
below.
1. Check that Egil and the breaker are
grounded as illustrated below:
Programma Electric AB
10 ZP-BM01E R07A
EGIL
red
yellow
main
supply _
+ trip coil
EGIL Programma red black
yellow/green
earth
IMPORTANT
When only one side of the breaker is
grounded while making the test, special
precautions must be observed to protect
service personnel and the test equip-
ment from harmful voltages.
Programma Electric AB
ZP-BM01D R07A 11
EGIL
Programma Electric AB
12 ZP-BM01E R07A
EGIL
Programma Electric AB
ZP-BM01D R07A 13
EGIL
3 System components
3.1 Standard items 3.2 Accessories
Egil standard unit includes the following The following accessories can be ordered
Item Art. No. Accessory Art. No.
Basic unit Egil, ................................................................... BM-19070 Extension cable Timing & AUX 1&2, 10 m (33 ft) ........ GA-00150
Mains cable, 2.5 m (8.2 ft) ............................................... 04-00XXX Transducer TLH 500, 500 mm (19.6") stroke .................. XB-30020
Breaker control cables, black, 2x2 m (6.6 ft) ............... 04-35030 Transducer TS 150, 150 mm (5.9") stroke ...................... XB-30030
Breaker control cables, red, 2x2 m (6.6 ft) ................... 04-35032 IP6501, rotates through 357° ........................................... XB-31010
Fuse, 12A F, 6.3 x 32 mm ................................................... 33-07147 Assembly kit for TLH, TS or IP6501 ................................ XB-39010
Cable, Extend, 10 m (32.8 ft) ............................................ GA-00150 For other lengths of TLH, TS: Contact GE Energy
Cable, TIMING, 5 m (16.4 ft) ............................................ GA-00160
Cable, AUX1&2, 2 m (6.6 ft) .............................................. GA-00170
Protective cable, 2.5 m (8.2 ft) ........................................ GA-00200
Thermal printer paper, 2 rolls ......................................... GC-00030
Transport case .................................................................. GD-00190
Egil User’s guide ............................................................... ZP-BM01E
Egil Quick guide ................................................................. ZO-BM01E
Programma Electric AB
14 ZP-BM01E R07A
EGIL
Programma Electric AB
ZP-BM01D R07A 15
EGIL
4 Description of Egil
Breaker Analyzer Egil is intended for use in medium-
voltage substations and industrial environments and is 4.1 Fields of
designed to test medium-voltage circuit breakers with no
more than one main contact per phase. If the main con- application
tacts are equipped with parallel pre-insertion resistor
contacts, Egil automatically records the difference be- Egil is primarily intended for:
tween main and resistor contacts. Auxiliary contact timing • Time measurement
as well as coil current traces are recorded.
• Automatic coil current measurement
As option, Egil can be equipped for travel motion record-
ing and with a serial interface for PC-communication. • Travel motion measurement
Time measurement
There are two time measuring connections:
The TIMING connection with three time channels. Signals
can be measured at both main contacts and pre-insertion
resistor contacts on the same channel. Egil automatically
senses if there is a pre-insertion resistor connected. No
specific settings are necessary.
The AUX1&2 connection with two independent auxiliary
inputs. These inputs can be used for contact-sensing or
voltage-sensing.
The time for contact operations is measured in several
different sequences (open/close).
The maximal measurement time for Egil is 100 seconds.
Other functions
The keyboard is used for entering control parameters via
the menu system.
The display window shows the settings and can also be
used for result read-out.
Test reports can be printed after each measurement
sequence.
Programma Electric AB
16 ZP-BM01E R07A
EGIL
Option - End
Sequencer
The sequencer block is equipped with fuses for breaker
control outputs and close and trip coil inputs/outputs.
There is also a built-in galvanically isolated analog current
transducers to measure the current in the trip and the close
circuit. AC and DC current up to 50 A is measured.
Time/motion/serial inputs
The time/motion/serial input block is equipped with inputs
for measuring time and motion and a serial communica-
tion terminal.
Printer
The printer block is equipped with a built-in printer for
printing results and test conditions, numeral and graphical.
Programma Electric AB
ZP-BM01D R07A 17
EGIL
Programma Electric AB
18 ZP-BM01E R07A
EGIL
Programma Electric AB
ZP-BM01D R07A 19
EGIL
5 Control panel
Programma Electric AB
20 ZP-BM01E R07A
EGIL
3 8
7
1 11 12
5
Programma Electric AB
ZP-BM01D R07A 21
EGIL
15 16
17
Programma Electric AB
22 ZP-BM01E R07A
EGIL
19
18
19. Printer.
20. Display window.
Programma Electric AB
ZP-BM01D R07A 23
EGIL
23 21
24 25
22
21. Auxiliary input 1 mode button. 24. OPERATE knob. Runs a breaker operation
22. Auxiliary input 2 mode button. sequence without measurement.
The Light Emitting Diode (LED) on the AUX1 DRY or 25. MEASURE knob. Runs a breaker operation
AUX2 DRY buttons show if the auxiliary contact senses sequence, measuring and recording the
contact or voltage (“dry” or “live”). results.
The LED is lit if Egil is in contact mode and delivers 24
V, 25 mA. The LED is off if Egil is in voltage mode and
senses a voltage from 20 V to 250 V independent of the
polarity.
Programma Electric AB
24 ZP-BM01E R07A
EGIL
26 27 28
29
30
Programma Electric AB
ZP-BM01D R07A 25
EGIL
Programma Electric AB
26 ZP-BM01E R07A
EGIL
SEQUENCES
OPEN OL1
OPEN
CLOSE
CLOSE
CL
CD CL
CLOSE
CD CL
CLOSE
CLOSE
CD CL
Programma Electric AB
ZP-BM01D R07A 27
EGIL
The sequence starts when you turn the MEASURE or You can choose between the following parameters on the
OPERATE knob. The BREAKER CLOSED indicator, SEQUENCE menu:
shows the state of the breaker.
During the measurement process the following messages
Menu heading Available Explanation
appear in the display window:
settings
Be Ready ... Close pulse length time in s or cy Length for close pulse
Open pulse length time in s or cy Length for open pulse
Delay C-O1 time in s or cy Open pulse delay at CO
(Egil prepares for operation)
Delay O1-C time in s or cy Close pulse delay at OC
Programma Electric AB
28 ZP-BM01E R07A
EGIL
Next Sequence
You can choose between the following menu headings.
O OC OCO
Menu heading Function
Setup General parameters and options
Opn Pulse Length Pulse Delay Pulse Delay
Print Print parameters
0.20s 0.00s C:0.00s O:0.01s C:0.30s O:0.10s
Save Save configuration in memory
Opn Pulse Length Opn Pulse Length blocks
0.29s 0.00s 0.10s 0.29s Recall Recall configuration from memory
Calibration Calibration of current/voltage
Cls Pulse Length Cls Pulse Length
measurements and motion
0.29s 0.10s
channel
Option - >
Next Sequence Analog Channel Settings for motion channel
C CO
Open Speed Speed calculation points
Cls Pulse Length Pulse Delay
Close Speed Speed calculation points
0.30s C:0.00s O:0.01s Option - End
Opn Pulse Length
0.29s 0.00s Display Show data/time on the display
Cls Pulse Length
Monitor Show on-line measurement
values
0.10s
Setup
Here you set general parameters and options for:
Measure Time
Here you can choose between the measure times 1, 2, 5,
10, 20, 50 and 100 seconds. At 1 s, the time resolution is
0.1 ms and at 100 s, the resolution is 10 ms. You choose
the unit for measure time in the TIME BASE section.
Language
Here you choose between English, German, French,
Spanish or Swedish. If you select another language than
English and want Egil to “remember” this next time you
start the instrument you must save the setting in memory
“0”.
Programma Electric AB
ZP-BM01D R07A 29
EGIL
Printouts
Here you set parameters for printouts. The maximum Time Time base selection Unit
length for a printout is 20 squares.
Auto ms/div
1s 1 2 5 10 20 50
Region
Auto Printouts
Here you choose whether or not you want a report auto- Auto ms/div
2s 2 5 10 20 50 100
matically printed out after every measurement. If you not Region
activate this function, you must press the PRINT button Auto ms/div
5s 5 10 20 50 100 250
after every measurement to get a printed report. Region
Auto ms/div
Contents 10s 10 20 50 100 250 500
Region
Here you can choose whether or not you want all pages
Auto s/div
printed out or just those pages containing graphs. 20s
Region
0.02 0.05 0.1 0.25 0.5 1
Auto s/div
Compress Time 50s
Region
0.05 0.1 0.25 0.5 1 2.5
Here you choose if you want to activate time scale
Auto
compression during the interval when something can 100s
Region
0.1 0.25 0.5 1 2.5 5 s/div
happen on the channels.
Supress Bounces The table will look different if you choose the time unit
Here you choose whether or not you want bounces (10 cycle instead.
ms) to be filtered when printing numeric values. This Example: 1 ms/div corresponds to 0.05 cy/div at 50 Hz or
setting does not apply to the graphic printout. Note: All 0.06 cy/div at 60 Hz.
raw data is stored in Egil’s memory. Only the values that
are printed are filtered. If the function is activated, the If you choose AUTO, the interesting parts of the time
system gives you the time for the first contact connection scale measurement is automatically enlarged as much as
at circuit closure and the time for last contact separation at possible.
circuit disconnection. If the function is not activated, all If you choose REGION, you can enlarge a part of the
registered bounces are printed. measurement around a chosen midpoint. The system
enlarges 10 squares before and 10 squares after the chosen
midpoint. The time scale is automatically set to 1/1000 of
the measure time you use. For example: 1 s corresponds to
1 ms/division.
Programma Electric AB
30 ZP-BM01E R07A
EGIL
Centre Point memory but are written over by the next measurement or
The system displays this menu only when you have chosen erased when Egil’s power is switched off.
the setting REGION from the TIME SCALE menu. Here
you enter the midpoint of the area you want to print out. 0
Refer to the section above. Save setting in memory area 0. The array of settings
stored in memory area 0 are always activated when you
turn on Egil.
(I) Current Scale( internal current
measuring) 1...9
Here you set the scaling factor for the internal current Save settings in memory areas 1 - 9. You choose the
axis. If you choose AUTO, the system automatically sets memory area where you will store the settings and press
the scale so that axis becomes as large as possible. If you ENTER to save..
choose not to activate this function, the axis will not be
displayed on the printout. Recall
Here you recall the settings that you have saved in Egil’s
memory.
Option - >
0...9
Motion Scale Recall settings that have been saved in memory area 0 - 9.
Memory 0 is recalled automatically at power on.
Here you enter the scaling factor for the motion axis. You
can only use this setting if you have chosen to measure Default
motion in the ANALOG CHANNEL menu. If you choose Recall default settings.
AUTO, the system automatically sets the scale so that axis The default settings are set at the factory. They are stored
becomes as large as possible. If you choose not to activate in memory 0 - 9. If you want to use the default settings
this function, the axis will not be displayed on the print- every time Egil is switched on do as follows. Choose
out. RECALL, DEFAULT and SAVE choosing memory 0.
Option - End
Save in memory
Here you can save the settings in Egil’s memory. You can
store an array of settings in each of the 10 storage areas.
All of the parameters that can be set in Egil’s menus can
be stored in memory with the exception of channel
calibration for internal current axis and motion channel.
However, the actual measurement results are not stored in
Programma Electric AB
ZP-BM01D R07A 31
EGIL
Example:
First you choose which type of measurement you want to 1. Choose MOTION and TRANSD LENGTH
perform. Choose between MOTION, CURRENT and 2. Enter the transducer’s length when Egil
VOLTAGE. prompts you to do so. Press ENTER. The
value you enter will be valid until you enter
Note! If you are not using the analog channel, a new estimated stroke, change measure-
it is important that you deactivate the ment method, calibrate a transducer or turn
function by selecting the position “Off”. off Egil.
Otherwise, there is a risk that you will 3. Perform a measurement. The first measure-
get the error message “Not calibrated” ment that is taken must be an single
since the motion channel expects events
operation.
during a recording
CALIBRATING
Choice MOTION We recommend that you calibrate the transducer, because
If you choose MOTION from the ANALOG CHANNEL the length that is printed on a transducer does not always
menu, you have three alternatives: STOKE, CALIBRAT- correspond to the electrical length. To calibrate, choose
ING or TRANSD LENGTH. Options STROKE and the option CALIBRATE. After calibration, Egil automati-
TRANSD LENGTH represent two different measurement cally measures according to the TRANSD LENGTH
methods. These are described below. method and the result from the calibration as transducer
length.
Programma Electric AB
32 ZP-BM01E R07A
EGIL
Programma Electric AB
ZP-BM01D R07A 33
EGIL
Tip
Programma Electric AB
34 ZP-BM01E R07A
EGIL
Example:
Choose OPEN SPEED from the main menu. Define the
speed calculation:
MAIN MENU
<Open speed>
Choose the reference for the upper point speed calcula-
tion:
Programma Electric AB
ZP-BM01D R07A 35
EGIL
Programma Electric AB
36 ZP-BM01E R07A
EGIL
Example:
Choose CLOSE SPEED from the main menu. Define the
speed calculation:
MAIN MENU
<Close speed>
Choose the reference for the upper speed calculation point:
Cls:Upper speed
<Below Cls. Pos>
Define the distance between the upper point and stable
closed position.
Programma Electric AB
ZP-BM01D R07A 37
EGIL
Programma Electric AB
38 ZP-BM01E R07A
EGIL
Close
Closing Time L1
62.4 ms
Open
Opening Time L1
42.1 ms
During an OCO operation, the first and second opening
times are shown according to the windows below:
1:Opn Time L1
43.0 ms
Programma Electric AB
ZP-BM01D R07A 39
EGIL
2. Difference between the phases 4. Close - open (trip-free) time (only during
CO and OCO operations)
This parameter is calculated as the largest difference
between the three phases’ main contacts. This parameter is calculated as the time difference
between the first contact touch of the main contact of the
Close fastest phase and the last contact separation of the main
contact of the slowest phase.
Cls Phase Diff
2.2 ms Time O-C
24.4 ms
Open
Open Phase Diff 5. Open - close (dead) time (only during OC
1.4 ms and OCO operations)
This parameter is calculated as the time difference
During an OCO operation, the difference between the between the last contact separation of the main contact of
phases at the first and the second opening operations are the slowest phase and the first contact touch of the main
shown, see below: contact of the fastest phase.
Programma Electric AB
40 ZP-BM01E R07A
EGIL
Programma Electric AB
ZP-BM01D R07A 41
EGIL
Status: O = open
R = resistive
C = close
Example:
Adjusting a rotating transducer
When you use a rotating transducer like a motion trans-
ducer, it is important that it is mounted so that the zero
crossing is not exceeded during an operation. Complete
the following steps:
1. Mount the rotating transducer on the
breaker.
2. Select the MONITOR menu. If a percentage
is not shown in the lower left corner, restart
Egil (turn off/turn on) and select the MONI-
TOR menu again.
3. Gently loosen the transducer from its
holder and turn it until about 50% is shown
on the display. Now the transducer is in the
middle of the measure region which means
that it can rotate almost half way around in
each direction without passing the zero
crossing.
4. Make a measurement.
Programma Electric AB
42 ZP-BM01E R07A
EGIL
Programma Electric AB
ZP-BM01D R07A 43
EGIL
To/from To/from
Recall Open speed
MAIN MENU
<- Analog channel ->
Analog channel
Motion Current Voltage Off
Trans Position 2
4.000V
Transd. Length
0105.0mm
Programma Electric AB
44 ZP-BM01E R07A
EGIL
To/from To/from
Analog channel Display
MAIN MENU MAIN MENU
<- Open Speed -> <- Close Speed ->
Dist. Below Upper Time After Upper Dist. Below Upper Time Before Upp.
0010.0mm 010ms 0010.0mm 010ms
Programma Electric AB
ZP-BM01D R07A 45
EGIL
To/from To/from
Close speed Setup
MAIN MENU MAIN MENU MAIN MENU
<- Display -> <- Monitor -> <- Calibration ->
Programma Electric AB
46 ZP-BM01E R07A
EGIL
Programma Electric AB
ZP-BM01D R07A 47
EGIL
Next Sequence
<C> CO
1. To select parameters, use the buttons for
left-arrow and right-arrow.
2. Press ENTER to confirm your choice and to
proceed to the next menu level.
3. Press ESC to return to the previous menu
level.
4. Change a numeric value
5. In some menus a value can be set. Select
the digit to be changed by the left and right
arrow key.
Programma Electric AB
48 ZP-BM01E R07A
EGIL
Programma Electric AB
ZP-BM01D R07A 49
EGIL
WARNING
• Do not short-circuit or touch the
auxiliary voltage. Use of “touch-proof”
connectors is recommended.
• Both breaker sides must be grounded
when making connections to the
breaker.
• Always disconnect the breaker control 2. Connect the power supply cable to Egil (2).
circuit from Egil control output, before 3. Connect Egil to the breaker.
doing any work on the breaker. Connect the time measurement cable to
• To avoid unintentional breaker opera- the breaker main contacts and to Egil
tions while working on the breaker,
TIMING contact (15).
connect the breaker control circuit to Egil
blind terminals (13 and 14) as illustrated 4. Connect the auxiliary contact measurement
below. cable to the auxiliary contacts in the operat-
ing mechanism and to Egil AUX1&2 contact
(16).
+
4a. If the measurement is on wet (AC voltage)
auxiliary contacts, set the timing auxiliary
inputs to wet mode (LED is off).
close coil
4b. If the measurement is on wet (DC voltage)
auxiliary contacts, set the timing auxiliary
inputs to DRY mode (LED is on). The red
EGIL Programma
trip coil cable must be connected to the positive
side of the auxiliary contact
4c. If the measurement is on dry auxiliary
contacts, set the timing auxiliary inputs to
DRY mode (LED is on).
5. Connect the breaker close coil to Egil close
coil output (10).
6. Connect the breaker trip coil to Egil trip coil
output (12).
Programma Electric AB
50 ZP-BM01E R07A
EGIL
red
yellow
main
supply _
+ trip coil
EGIL Programma red black
yellow/green
earth
IMPORTANT
When only one side of the breaker is
grounded while making the test, special
precautions must be observed to protect
service personnel and the test equip-
ment from harmful voltages.
Programma Electric AB
ZP-BM01D R07A 51
EGIL
Programma Electric AB
52 ZP-BM01E R07A
EGIL
Programma Electric AB
ZP-BM01D R07A 53
EGIL
WARNING
• Do not short-circuit or touch the
auxiliary voltage. Use of “touch-proof”
connectors is recommended.
• Both breaker sides must be grounded
when making connections to the
breaker.
• Always disconnect the breaker control
circuit from Egil control output, before
doing any work on the breaker.
• To avoid unintentional breaker opera-
tions while working on the breaker,
connect the breaker control circuit to Egil
blind terminals (13 and 14) as illustrated
below.
close coil
EGIL Programma
trip coil
Programma Electric AB
54 ZP-BM01E R07A
EGIL
Programma Electric AB
ZP-BM01D R07A 55
EGIL
Switch to maintain
battery life 4V supply
8.2 Setting
Screen
OUT Reference
input
parameters
R IN
0 Egil reads the status of the breaker (closed or open). The
Max 4 V Cable Input
built-in sequence module is automatically set to the next
Moving slider logical single operation.
If multiple operation is requested, perform the following
Measuring current with a external steps:
current shunt 1. Select a sequence operation from the
Current shunt: SEQUENCE menu by pressing the arrow-
1.. Choose a current shunt (resistor) with keys.
appropriate current capacity. Low resist- 2. Press ENTER to set pulse delay times and
ance gives low voltage drop. High resist- pulse length values if needed and press
ance gives higher resolution because of ENTER to confirm your settings.
higher measuring voltage. For more information about parameters, see Chapter 6
2.. Connect voltage sensor wires to the IN (Menu options and parameter settings).
terminal and to the 0 terminal.
Current path
Input
Shunt Screen
OUT
R
IN
0
Cable
Transducer
power
source
Input
4 - 20 mA
Pressure OUT
Trans-
ducer Resistor R IN
or other 0
quantity
Programma Electric AB
56 ZP-BM01E R07A
EGIL
1. Connect the breaker as shown in section The second part of the printout shows the result in nu-
meric and graphic form.
8.1 above.
2. Run a breaker operation without measure- You can also view the results on the display if you activate
the DISPLAY option on the MAIN menu.
ment by turning the OPERATE knob. This
tests the connection. Run the operation Option - End
with measurement by turning the MEASURE
knob.
Running an Open-Close-
Open (O-C-O) operation.
1. Connect the breaker as shown in section
8.1 above.
2. Select O-C-O (open-close-open) operation in
the SEQUENCE menu by using the arrow
keys.
3. Press ENTER to set the close and open
delay values. The default value is 300 ms
(0.30 s) for close pulse delay and 10 ms
(0.01 s) for opening pulse delay. Press
ENTER to continue.
4. Set the pulse length values if needed.
Press ENTER to confirm your settings.
5. Run a breaker operation without measure-
ment by turning the OPERATE knob. This
tests the connection. Run the operation
with measurement by turning the MEASURE
knob.
Programma Electric AB
ZP-BM01D R07A 57
EGIL
9 Connecting Egil to a
computer (option)
Programma Electric AB
58 ZP-BM01E R07A
EGIL
9.2 Operating Egil 4. Turn the MEASURE knob in the usual way
to execute the measurement, whereupon
while running CABA Egil takes measurements and sends the
results to the computer.
For detailed information and guidance, see the CABA
User’s Manual.
Connected to PC
Next sequence
< C > CO
3. If the breaker is in the wrong state (open or
closed) it can now be operated with the
OPERATE knob. In Egil’s SEQUENCE menu,
you can select the desired sequence, set
pulse duration and set delay times for the
close and trip pulses using the same
procedures as those set forth in Chapter 6
(Menu options and parameter settings),
see sections 6.2 and 6.3.
Programma Electric AB
ZP-BM01D R07A 59
EGIL
Option - End
Programma Electric AB
60 ZP-BM01E R07A
EGIL
Programma Electric AB
ZP-BM01D R07A 61
EGIL
10 Troubleshooting
10.1 General 10.2 Displayed values
The display does not show anything Reading: Strange result
Possible cause: Fuse F1 may be broken. Possible cause: Something is wrong with your
Remedies: Check that the mains voltage settings.
selector switch is set in an The settings are correct, but you
accurate position. Also check the have started the preparations for
mains voltage with a volt meter. the next measurement too soon.
Reset the fuse. Remedies: Check the parameter settings.
Breaker control circuits malfunctions Restore the old settings. For
Possible cause: The 12 A F fuses are broken. more information about
parameters, see Chapter 6
Remedy: Check the fuses and replace them. (Menu options and parameter
The printer does not print and no message on the settings).
display Reading: Dashed lines instead of values
Possible causes: Problems with the paper Possible cause: In DISPLAY mode: The time set
(incorrectly turned paper roll, the exceeds the established
thermo sensitive side - outside of measuring time.
roll - must face towards the On the motion part of the test
operator, bad quality, wrong size, report: Egil was not able to
etc.). Internal fault in Egil. compute the speed because the
Remedies: Use the paper recommended by points were not located. (The
Programma Electric AB, and turn difference between the time
it correctly. Contact Programma values is too short, for example).
Electric AB or your Egil service Remedies: Set a new value located inside
representative. the measurement interval. Check
When CABA is started with Egil connected, CABA your settings and change them if
displays a message reading necessary.
“Communication error”. Reading: Motion: Speed calculation failed
Possible cause: Wrong cable used for connection. Possible cause: Egil was not able to find the
Wrong communication port set in points specified by your settings.
CABA.
Remedy: Change your settings. For more
Remedy: Use the cable delivered with CABA information about parameters,
for Egil as described in Chapter 9 see Chapter 6 (Menu options and
(Connecting Egil to a computer). parameter settings).
Check the CABA menu headed
“6.2 Computer Configurations”, to
see if the correct communication
port has been set (normally
COM1) and that the baud rate
setting is correct (normally
19200).
You are unable to print from CABA on Egil’s
internal printer
Possible cause: Wrong printer port set in CABA.
Wrong printer selected in CABA.
Remedy: Set the printer port to TM1600/
EGIL in the CABA menu headed
“6.2 Computer Configurations”.
Select one of the TM1600/EGIL
printers in the CABA menu
headed “6.3 Printer List”.
Programma Electric AB
62 ZP-BM01E R07A
EGIL
Programma Electric AB
ZP-BM01D R07A 63
EGIL
Option - End
Programma Electric AB
64 ZP-BM01E R07A
EGIL
Programma Electric AB
ZP-BM01D R07A 65
EGIL
11 Calibration
You can calibrate Egil by adjusting the current and the
voltage measurement. The zero adjustment is made 11.1 Coil current
automatically at the start-up of Egil. The scale adjustment
is defined as described below. measurement
Confirm that you want to continue calibrating the current
Note! Only qualified personnel should perform scale.
the calibration function.
Select CALIBRATION in the MAIN menu: Adjust Current
<Yes> No
MAIN MENU
Note! Only qualified personnel should perform
< Calibration >
the calibration function.
Test Current
xx A
4. Press ENTER to continue.
Source Current
xx A
2. Press ENTER to finish the current calibra-
tion.
Programma Electric AB
66 ZP-BM01E R07A
EGIL
Test Voltage
xx V
3. Press ENTER to continue.
Source Voltage
xx V
2. Press ENTER to finish the calibration
process.
Egil as a timer
1. Connect the start input of a calibrated
frequency counter to the close coil input/
output of Egil.
Programma Electric AB
ZP-BM01D R07A 67
EGIL
12 The printer
12.1 General 12.2 Printouts
information The page of the printout is divided in 4 main parts:
• The general text part (part 1, 2, 3)
The printer is a highspeed text/graphic thermal printer.
This technology gives a silent operation, long life, and a • The test conditions part (part 4, 5)
good contrasted printing.
It uses heat sensitive paper with a width of 114 mm (4.488 • The test results part (part 6, 7)
in.) maximum.
• The graphical printout (part 8)
Programma Electric AB
68 ZP-BM01E R07A
EGIL
Parameters you
have selected for
travel (motion)
measurement.
Tabular printout of
time measurements
at main contacts.
Tabular printout
of time measurements
at auxiliary contacts.
Tabular printout of
travel (motion)
calculations.
Programma Electric AB
ZP-BM01D R07A 69
EGIL
Graphical
printout
Auxiliary contact,
close circuit
Main contacts
Auxiliary contact,
trip circuit
Programma Electric AB
70 ZP-BM01E R07A
EGIL
IMPORTANT
Make sure that the cables are properly
connected
4. Push the lever from ”2” to position ”3”. 8. Put the printer back into its holder and
make sure that it is securely locked.
Programma Electric AB
ZP-BM01D R07A 71
EGIL
13 Specifications
Contact characteristics: Non bouncing, Closing time
13.1 EGIL maximum 0.1 ms.
Make/Break capacity: 25 A, 250 V (AC or DC) per
contact function.
General Start breaker operation: By rotary switch.
Specifications are subject to change without notice.
Pulse length: Adjustable in steps of
Application field: The instrument is intended 10 ms
for use in medium voltage Pulse delay: Adjustable in steps of
substations and industrial 10 ms
environments up to 130 kV
Working voltage: 250 V AC/DC
Mains voltage: 115/230 V AC
(switchable), 50-60 Hz
TIMING
Languages: English, German, French, Number of channels: 3 with common ground
Spanish or Swedish
Operating temperature: 0 to +50°C (+32 to +122°F) Status thresholds
Closed: < 10 Ω ±20%
Storage temperature: -40 to +70°C (-40 to +158°F)
Resistor: 10 Ω ±20% to 3 kΩ ±20%.
Humidity: 5% to 95% RH, Non-
condensing Open: > 3 kΩ ±20%
Dimensions: 360 x 210 x 190 mm (14.2" Open Circuit voltage: 24 V ±20%
x 8.3" x 7.5") Short circuit current: 100 mA ±20%
Dimensions transport case:
420 x 300 x 230 mm AUX 1&2
(16.5" x 11.8" x 9.0") Number of channels: 2, galvanically isolated
Weight: 6.3 kg (14 lbs). 10 kg
(22 lbs) with accessories Contact-sensing (Dry)
and carrying case Status Threshold:
Closed: < 600 Ω ±30%
CE-marking
Open: > 600 Ω ±30%
EMC: EMC Directive 89/336/EEC
am. by 91/263/EEC, Open Circuit voltage: 20 V ±20% DC
92/31/EEC and 93/68/ Short circuit current: 25 mA ±20%
EEC
Voltage sensing (Wet)
LVD: Low Voltage Directive 73/ Status Threshold: 8 – 13 V
23/ EEC am. by 93/68/ < 8 V – Open Indication
EEC > 13 V – Close Indication
Measurement time: 1 to 100 s Polarity insensitive
Resolution: 0.1 to 10 ms Working voltage: 250 V AC/DC
Time base accuracy: 0.05% of the reading
± resolution MOTION (Optional)
Number of channels: 1 independent
Current measurement Max Cable length: 10 m
Range: ±25 A per channel, sum of
currents is measured Input
Range: -4 to +4 V
Resolution: 25 mA
Resolution: 2 mV
Accuracy: 1% of the reading ±100 mA
Accuracy: 1% of the measurement
Working voltage: 250 V AC/DC
range
Transducer resistance: 1 kΩ to 5 kΩ
Breaker operation
Input impedance: 150 kΩ
Sequences: C, O, C-O, O-C, O-C-O.
Continuous current: 5A Output
Max current: 25 A during 300 ms, rest Open circuit voltage: 4,092 V ±4 mV
time 1 min Short circuit current: 115 mA
Contact function: Two independent control
functions.
Programma Electric AB
72 ZP-BM01E R07A
EGIL
SERIAL (Optional)
Type: V24, RS232C
13.2 Cables
Format: 8 bits, 1 stop bit, no parity
Mains power supply
Speed: 1200 - 19200 baud
Suited for respectively region/
Protocol: Xon/Xoff country
Standard cable length
Printout
Type of printout: Graphic and numeric Earth (ground)
Art. No. GA-00200
Printer: Thermal printer with fixed
print head Cable length 3 m (9.8 ft) green/
yellow cable with round or U-end
Graphic resolution: 8 dots/mm - 203 dpi
terminal
Paper width: 114 mm (4.5")
Programma Electric AB
ZP-BM01D R07A 73
EGIL
AUX1&2 inputs
1: Channel AUX1 ground .................................................. GND1
2: Channel AUX1 signal .................................................... AUX1
3: Channel AUX2 ground .................................................. GND2
4: Channel AUX2 signal .................................................... AUX2
5: Not connected
Extension cable for above cables (TIMING and
AUX1&2), (extra accessories) The XLR5 plug, used for both TIMING and AUX1&2
Art. No. GA-00150 inputs is illustrated below:
Cable length 10 m (32.8ft)
5-pin XLR contact (female) to
5-pin XLR contact (male).
Programma Electric AB
74 ZP-BM01E R07A
EGIL
Programma Electric AB
ZP-BM01D R07A 75
EGIL
Index
A G
Analog channel ................................................... 31 graphical printout ............................................... 70
Auto Printouts ..................................................... 30
I
B Indicators ............................................................. 24
Breaker control outputs ...................................... 21 inputs ............................................................. 17, 22
Breaker operation sequence .............................. 16 internal printer .................................................... 60
C K
CABA ................................................................... 59 keyboard .............................................................. 18
Cables .................................................................. 73 knobs ................................................................... 24
Calculated parameters ....................................... 38
CALIBRATING ..................................................... 32 L
Calibration ..................................................... 31, 66 Language ............................................................. 29
Centre Point ......................................................... 31
M
Change measurement parameters .................... 13
MAIN menu ................................................... 29, 43
chronogram ......................................................... 27
main power supply ............................................. 17
Close - open ........................................................ 40
Measure Time ..................................................... 29
coil current measurement .................................. 16
Measurement ...................................................... 12
Compress Time ................................................... 30
Measuring current ............................................... 56
computer ............................................................. 58
Measuring other quantities ................................ 56
Connect the transducer ...................................... 55
memory ............................................................... 31
Connections ........................................................ 74
Monitor ................................................................ 41
Contact penetration ............................................ 40
MOTION .............................................................. 32
Control panel ....................................................... 20
Motion input ....................................................... 22
CURRENT ............................................................ 33
motion measurement ................................... 12, 54
Current peak ........................................................ 40
Motion Scale ....................................................... 31
Current Scale ....................................................... 31
current shunt ....................................................... 56 O
Open - close ........................................................ 40
D
Open speed ......................................................... 33
Default ................................................................. 31
Operation knobs ................................................. 24
Description of Egil .............................................. 16
Options and accessories .................................... 14
Display ................................................................. 18
outputs ................................................................ 21
E Over travel ........................................................... 40
Egil as a timer ..................................................... 67
P
Egil as a Volt meter ............................................. 67
Paper reload ........................................................ 71
Egil as an Ampere meter .................................... 66
Parameter values ................................................ 26
external current shunt ......................................... 56
Power supply ...................................................... 21
F Printer ............................................................ 17, 68
Fields of application ........................................... 16 Printing ................................................................ 12
front panel ........................................................... 17 Printouts ................................................. 13, 30, 68
Function keys ................................................ 25, 48 pulses .................................................................. 28
Function time ...................................................... 39
Programma Electric AB
76 ZP-BM01E R07A
EGIL
Q
Quick instructions ............................................... 10
R
Rebound .............................................................. 41
Running a measurement .................................... 57
running CABA ..................................................... 59
S
Save ..................................................................... 31
Scale .................................................................... 31
Select a menu item ............................................. 48
Select measurement method ............................. 55
SEQUENCE ......................................................... 26
SEQUENCE menu ............................................... 29
Sequencer ........................................................... 17
Serial communication ........................................ 23
Set pulses ............................................................ 28
Setting parameters ............................................. 56
Specifications ...................................................... 72
Speed .................................................................. 41
Standard items .................................................... 14
STROKE ............................................................... 32
Supress Bounces ................................................ 30
System components ........................................... 14
T
Time ..................................................................... 29
Time Base ........................................................... 30
Time measurement ............................................ 16
time measurement ....................................... 10, 50
Time Scale .......................................................... 30
Timing inputs ...................................................... 22
transducer ........................................................... 55
TRANSDUCER LENGTH ..................................... 32
Travel Unit ........................................................... 30
trip-free ................................................................ 40
Troubleshooting .................................................. 62
V
VOLTAGE ............................................................. 33
Voltage Scale ...................................................... 31
Programma Electric AB
ZP-BM01D R07A 77
EGIL
Programma Electric AB
78 ZP-BM01E R07A
EGIL
Programma Electric AB
ZP-BM01D R07A 79
Subject to change without notice. Printed matter No. ZP-BM01E R07A Doc:BM0087JE