Professional Documents
Culture Documents
a r t i c l e i n f o a b s t r a c t
Article history: Over-current protection is principally intended to counteract excessive current in power systems. In dis-
Received 24 May 2012 tribution systems in Malaysia, non-directional over-current protection is adopted because of the radial
Received in revised form 24 September nature of the power system used. Relay typically used in distribution network are designed to cater
2013
for current flow in one direction, i.e., from transmission network to load. However, with the forecasted
Accepted 9 October 2013
increase in generation from renewable sources, it is important that adequate codes are in place with
regards to their integration to sub-transmission/distribution network. Distribution network dynamically
changes from ‘‘passive’’ to ‘‘active’’ network. With distributed generation connected to distribution net-
Keywords:
Directional overcurrent relay
work, power flows bi-directionally. Hence, directional over-current protection is adopted along the line
Directional earth-fault relay between the transmission grid and the distributed generation. The bi-directional flow of power also com-
Micro grid plicates the earth fault protection. This is due to the presence of the distributed generation that will cause
the line near the delta side of the transformer to be still energized after the operation of earth fault relay
during single-phase-to-ground-fault. This paper investigates the directional over-current and earth fault
protections used to protect the microgrid (biomass generator) in Malaysia. In this study, under-voltage
relays are adopted at the delta side of the transformer to fully clear the single-line-to-ground fault, which
cannot be cleared by earth fault relay. Three-phase-balanced fault and single-line-to-ground-fault at all
possible locations in the network have been simulated. Simulation shows good coordination and discrim-
ination between over-current relays.
Ó 2013 Elsevier Ltd. All rights reserved.
0142-0615/$ - see front matter Ó 2013 Elsevier Ltd. All rights reserved.
http://dx.doi.org/10.1016/j.ijepes.2013.10.004
582 A.H.A. Bakar et al. / Electrical Power and Energy Systems 55 (2014) 581–591
of automatic reclosing and unsynchronized reclosing [8]. Earth discrimination should be done properly to ensure no nuisance trip-
fault happening at the delta side of the transformer will not be fully ping of relays.
cleared by the earth fault relay with the presence of DG because
there are more than one power source in the network. When the
2.1. Need of directional element in over-current relay
main utility service provider is the only sole power source provider
to the customer load, the earth fault that happens between the
Directional over-current protection is used against fault current
utility source substation and delta-wye transformer can be fully
that could circulate in both directions through a system element
cleared or completely isolated by the tripping of the utility-source
and when non-directional over-current protection could produce
line breaker alone. Hence, when there is another generation source
unnecessary of disconnection of circuits [11–13]. This situation
(probably a distributed generator) being added in parallel with the
can happen in a ring circuit and a circuit with a number of infeed
utility power system at the customer load site, beyond a delta-wye
points. When distributed generator (DG) is present, there are mul-
transformer, the transformer becomes a source of fault current for
tiple power sources and the opening of the utility breaker only
faults on the utility source line [9].
does not guarantee that the fault will be cleared. Hence, the nature
This paper examined the use of directional over-current relays
of distribution network changes with multiple DG units and direc-
along the line connecting the two power sources in order to fully
tional relays are needed in the network [6]. Directional relays
clear the fault. Characteristics graph of relays were plotted and should be placed along the line that links the main grid and the
the tripping time of the primary protection and back-up protection
DG. For the branch that does not link the two power sources,
were recorded. The study also investigated the use of under-volt- non-directional relays could be used.
age relay at the delta side of the transformer to fully extinguish
the earth fault.
2.2. Relay characteristics
DIgSILENT
Biomass mechanical load(1)/415V
Biomass Generator ~
G 0.504
Existing 11kV System
1.214
21.593
0.000 -2.72 2.72
0.000 -0.95 0.95
67.94
0.00 0.00
11/0.43kV
50N/51N (Non-Directional E/F Relay M(E)) 0.00 50N/51N (Non-Directional E/F Relay H(E))
Essential and Other load for Gener(1) -0.00
50/51 (Non-Directional O/C Relay M) 11.77 2.72
0.00
0.00
50/51 (Non-Directional O/C Relay H)
2.68 1.03
80.49
0.00
67.94
0.00
50/51 (Non-Directional O/C Relay C)
Biomass substation/11kV FAULT 0.000
0.000
Existing System/11kV
0.000
-0.00
13.481
1.226
0.000
0.000 -0.00 67 (Directional O/C Relay G)
-6.908 0.00
0.000
0.000
9.05
1.65
67 (Directional O/C Relay L) 0.00
27 (Undervoltage Relay G)
50.02
0.00 27 (Undervoltage Relay L) DELTA
33/11kV(3)
33/11kV(2)
TX UTILITY
TX DG WYE
-9.05 67N (Directional E/F Relay De) 0.00 67N (Directional E/F Relay Ie)
-1.35 -0.00
50.02
0.00
67 (Directional O/C Relay D) 0.00
0.00
67 (Directional O/C Relay I)
Line(4)
-8.99 0.00
-2.44 -2.25
44.14
0.00
67 (Directional O/C Relay E) 10.65
0.00
67 (Directional O/C Relay J)
67N (Directional E/F Relay Ee) 67N (Directional E/F Relay Je)
Substation(2)/33kV 39.930
1.210
21.079 8.98
0.000
0.000
4.69
50.70
50/51 (Non-Directional O/C Relay B)
0.00
50N/51N (Non-Directional E/F Relay B(E))
Line(5)
-8.90
-5.75
50.70
0.00
Substation(4)/33kV 39.572
1.199
21.056
8.90
0.000
0.000 5.75 50/51 (Non-Directional O/C Relay A)
44.19
0.00
33/0.43 kV(1)
-8.90
-5.51
44.19
0.00
Substation(5)/0.43kV 0.492
1.185
49.979
0.000 0.00 0.00 4.45 4.45 0.00
0.000 0.00 0.00 2.76 2.76 0.00
3.49 MW
2.47 MW 3.44 MW 2.91 MW(1)
2.91 MW
Fig. 2. Voltage phasor diagram for (a) unfaulted system, (b) faulted system during parallel operation and (c) faulted system during islanded operation.
when being applied in the earth fault protection because earth 4. Unexpected delta sources protection
fault relay is usually set at current setting of 20–40% of the loading
current. Therefore, earth fault relay with definite time characteris- Conventionally, delta-wye transformers are used to connect
tic has faster operation time for back-up protection when the pri- transmission and sub-transmission systems to distribution sys-
mary protection fails to operate. tems to improve a load balance and block zero sequence current
flow. However, when distributed generation is present, delta-wye
2.2.2. Inverse current transformers become the sources of fault current that can be diffi-
These relays are classified based on their characteristic curves, cult to be detected and isolated. In other words, directional over-
which define the speed of operation as inverse, very inverse or ex- current or distance protection at the interconnection point
tremely inverse. IEC 60255 defines a number of standard charac- between the utility system and source of distributed generation
teristics as follows [14]: can detect faults on the utility source line but cannot detect ground
faults on the high side of a delta-wye transformer when the utility
Standard Inverse ðSIÞ : t ¼ TMS 0:14=½ðIf =IS Þ0:02 1 ð16Þ
source breaker is open [9]. Referring to Fig. 1 which shows a micro
grid system in Malaysia, when ground fault occurs at busbar of
Very Inverse ðVIÞ : t ¼ TMS 13:5=½ðIf =IS Þ 1 ð17Þ
‘‘existing system/11 kV’’ (Delta side of the utility transformer),
the directional earth fault relay Je (Wye side of the utility trans-
Extreme Inverse ðEIÞ : t ¼ TMS 80=½ðIf =IS Þ2 1 ð18Þ former) is not able to detect the fault after the breaker of Relay
H(E) is opened.
Long Time Standard Earth Fault : t ¼ TMS 120=½ðIf =IS Þ 1 When earth fault occurs at the delta side of the transformer, the
ð19Þ earth fault relay located between the fault point and the delta side
of the transformer will not be able to operate because there is no
zero sequence current being detected. When earth fault happens
2.2.3. Combined Inverse Definite Minimum Time (IDMT) and high set
at the delta side of the transformer, before the utility source break-
instantaneous over-current relays
er is opened, the faulted phase voltage collapses. The unfaulted
These relays combine both the characteristic of the inverse cur-
phase voltages are held close to their nominal by the effectively
rent and definite time to improve the overall system grading by
grounded utility source. However, when the utility source breaker
allowing the discriminating curves behind the high set instanta-
trips before the distributed generation trips, the faulted phase volt-
neous element to be lowered. The main advantage of relays with
age remains zero in case of a bolted fault while the unfaulted phase
this characteristic is the high-speed protection over a large section
voltages are 1.73 times the nominal when supplied from a delta
of the protected circuit. In this study, this characteristic is used in
source [9]. This is illustrated in Fig. 2.
the phase over-current relays.
Under and/or overvoltage detection on the high side of the delta
transformer winding supplements islanding protection and low-
3. Current setting side fault detection by providing ground fault detection before
and after the utility source breaker opens. Hence, voltage relays
3.1. Phase over-current can be used to solve this issue. Voltage relays that can be used in-
clude under voltage relays, overvoltage relays and zero sequence
In general, for phase over-current protection, the current setting voltage relay. The under voltage element can be set at some frac-
is selected to be above the maximum short time rated current of tion of nominal voltage, 50% and it picks up if the fault is the same
the circuit involved. The pick-up values of phase over-current re- phase as the VT connection [9]. The overvoltage element can be set
lays are normally set at 30% above the maximum load current, pro- above nominal voltage, 130% and it picks up if the fault is on one of
vided that sufficient short circuit current is available [15]. the other two phases [9].
Table 1A Table 2B
Setting of phase over-current relays. Tripping time of relays for sungle-phase-ground-fault (bolted).
Relay Time-overcurrent (TOC) Instantaneous-overcurrent (IOC) Fault location Primary protection Back-up protection
TMS Current setting (A) Current setting (A) Time setting Relay Tripping t (s) Relay Tripping t (s)
(s)
Secondary Primary Secondary Primary Substation (4)/33 kV Be 0.02 Fe 0.4127
Ke 0.2027
A 0.05 5.53 442 18.75 1500 0.02
Line(5) Be 0.02 Fe 0.5128
B 0.11 5.36 429 26.25 2100 0.02
Ke 0.4123
C 0.06 3.6 143 62.5 2500 0.02
Substation (2)/33 kV Fe 0.4128 Ie 0.5128
D 0.10 3.9 156 23.75 950 0.02
Ke 0.4128 De 0.5128
E 0.17 3.9 156 32.5 1300 0.22
Line(4) Fe 0.4130 Ie 0.5130
F 0.17 5.36 429 18 1440 0.23
Je 0.2000 Ke 0.4197
G 0.26 6.44 1287 25 5000 0.235
Substation (3)/33 kV Ie 0.5128 G (U<) 0.5163
H 0.34 6.5 1300 50 10,000 0.24
Je 0.2001 Ke 0.4128
I 0.19 6.5 260 17.5 700 0.02
Existing system/11 kV He 0.2000 – –
J 0.17 4.77 286 13 780 0.2
G (U<) 0.5190 – –
K 0.16 5.69 455 10 800 0.21
Line (3) Ee 0.2000 Fe 0.4126
L 0.20 5.74 1387 11 2640 0.215
Ke 0.4126 De 0.5126
M 0.24 6.34 1521 12 2880 0.37
Substation (1)/33 kV De 0.5124 L (U<) 0.5290
Ee 0.2000 Fe 0.4124
Biomass substation/11 kV Me 0.02 – –
L (U<) 0.518 – –
Table 1B
Setting of earth fault over-current relays.
Table 4D
Fault current detected by earth fault overcurrent relays Je, Ke and De. 6. Simulation results
Relay Fault location Fault current/A
Je Substation (3)/33 kV 920
The results obtained were classified into two groups, the time-
Ke Substation (2)/33 kV 1486 over-current (TOC) – instantaneous over-current (IOC) plot for
De Substation (1)/33 kV 1969 phase over-current relays and the instantaneous over-current
(IOC) plot for earth over-current relays.
The settings for the Inverse Definite Minimum Time (IDMT)
phase over-current relays are based on the fault currents obtained
combinations of relays at different locations are plotted to verify from a three phase balanced fault. The values of these fault cur-
the coordination and discrimination. rents are presented in Tables 3A–D. The setting for IDMT relays
For phase fault protection, coordination and discrimination are presented in Table 1A. From the simulation, it is found that
among relays need to be obeyed as follows: (a) from load up to in primary protection, the shortest tripping time for phase over-
the 11 kV existing grid, i.e., between relays A, B, F, G and H, (b) from current fault takes only 0.02 s while the longest tripping time is
biomass distributed generation up to 11 kV existing grid, i.e., be- 0.3702 s. The tripping time for relays at different locations of fault
tween relays C, D, E, F, G and H, (c) from 11 kV existing grid up is presented in Table 2A.
The settings for the earth fault over-current relays are relays at the existing 11 kV system. In normal radial distribution
based on the fault currents obtained from single line to ground system, the over-current characteristic curves should discrimi-
fault. The values of these fault currents are presented in Tables nate each other by not overlapping with each other. However,
4A–D. The settings for these relays are presented in Table 1B. as shown in Fig. 3A, the characteristic curves for relay A and B
From the simulation, it is found that in primary protection, the are actually overlapping with that from relays F, G and H but
shortest tripping time for over-current earth fault takes only coordination is still achieved. This is because in normal radial
0.02 s while the longest tripping time is 0.519 s. The tripping distribution system (without the distributed generation (DG)),
time for relays at different locations of fault is presented in the fault current increases from downstream towards upstream,
Table 2B. i.e., fault current nearer to the source is bigger. As shown in
Table 3A, the fault current detected by relay downstream, i.e.,
6.1. Phase over-current relay coordination (TOC-high set IOC plot) relays A and B (1663 A and 2334 A respectively) are bigger as
compared to fault current detected by relay upstream, i.e., relay
6.1.1. Coordination between relays A, B, F, G and H F (1636 A). This scenario is due to the fault current detected by
Fig. 3A shows the time-over-current (TOC) – instantaneous- relays A and B are the total contribution from both existing
over-current (IOC) plot for coordination between relays A, B, F, 11 kV system (slack bus) and biomass generator (PV bus).
G and H. These relays are relays from the load side up to the Another key point noted is that relays A, B and H are
A.H.A. Bakar et al. / Electrical Power and Energy Systems 55 (2014) 581–591 587
non-directional phase over-current relay while relays F and G tected by relay upstream relay L is 3104 A. Although the fault cur-
are directional phase over-current relays. The use of directional rent at relay L, 3104 A is bigger than 1663 A, fault current detected
element for relays F and G is needed because these relays are by relay A. However, the 3104 A detected at relay L is after the 33/
placed along the line between the two power sources, that is 11 kV step down transformer (current is stepped up). Therefore,
existing 11 kV system and the biomass generator. Along this line, the equivalent fault current before passing through the trans-
power flows bi-directionally. former should be 3104/3, or 1034 A. Equivalently, this fault value
at upstream is still smaller than the fault downstream at relays A
and B. The relays A, B and M are non-directional phase over-cur-
6.1.2. Coordination between relays A, B, K, L and M
rent relay while relays K and L are directional phase over-current
Fig. 3B shows the time-over-current (TOC) – instantaneous-
relays.
over-current (IOC) plot for coordination between relays A, B, K, L
and M. These relays are relays from the load side up to the relays
at the biomass generator. As shown in Fig. 3B, the characteristic 6.1.3. Coordination between relays C, D, E, F, G and H
curves for relay A, B and K are overlapping with that from relays Fig. 3C shows the time-over-current (TOC) – instantaneous-
L and M but coordination is still achieved. As shown in Table 3B, over-current (IOC) plot for coordination between relays C, D, E, F,
the fault current detected by relay downstream, i.e., relays A and G and H. These relays are relays from the DG up to the relays at
B are 1663 A and 2334 A respectively while the fault current de- the existing 11 kV grid. As shown in Fig. 3C, the characteristic
588 A.H.A. Bakar et al. / Electrical Power and Energy Systems 55 (2014) 581–591
curves are not overlapping with each other and show good coordi- 7. Earth fault over-current relay coordination (TOC-high set IOC
nation. As can be seen from Table 3C, the fault currents value plot)
increases from downstream to upstream. Relays D, E, F and G are
directional relays because they are placed along the line between Fig. 4A shows the instantaneous-over-current (IOC) plot for
the two power sources. coordination between relays Be, Fe and Ie. These relays are from
the load side up to the Y-side of the 33/11 kV transformer near
6.1.4. Coordination between relays I, J, K, L and M the existing system/11 kV busbar. Coordination of relay is done
Fig. 3D shows the time-over-current (TOC) – instantaneous- up to the Y-side of transformer only because it is the source of zero
over-current (IOC) plot for coordination between relays I, J, K, L sequence current flow. The relay Be used is non-directional earth
and M. These relays are relays from the existing 11 kV grid up to fault relay and it is an IDMT relay. Relays Fe and Ie used are direc-
the relays at the DG. As shown in Fig. 3D, the characteristic curves tional earth fault relay which uses only the definite time character-
do not overlap each other and show good coordination. Table 3D istic which enhances the speed of operation during earth fault
shows the fault currents value increases from downstream to up- occurrence. For relay with definite time characteristic, the time de-
stream. Relays I, J, K and L are directional relays. lay setting is the most crucial part. The current setting of earth
A.H.A. Bakar et al. / Electrical Power and Energy Systems 55 (2014) 581–591 589
Fig. 5A. Zero sequence voltage at existing system/11 kV (without undervoltage relay).
fault relay is normally taken to be 20–40% of loading current be- because they are located along the line between two power
cause it only operates for earth fault detection and not for ordinary sources. Fig. 4D shows the instantaneous-over-current (IOC) plot
phase over-current condition. It can be seen that from Fig. 4A, the for coordination between relays Je, Ke and De. All relays Je, Ke
current setting of the relay Ie is smaller than Fe. This is because the and De used are directional earth fault relay with definite time
large setting of relay Ie will cause the tripping of under-voltage re- characteristic.
lay G instead of relay Ie when there is earth fault happening at bus-
bar Substation(3)/33 kV.
Fig. 4B shows the instantaneous-over-current (IOC) plot for 8. Case study: earth fault at the delta side of the transformer
coordination between relays Be, Ke and De. These relays are from
the load side up to the Y-side of the 33/11 kV transformer near When single phase to ground fault occurs at busbar on the
the biomass substation/11 kV busbar. The relay Be used is non- existing system/11 kV system, that is at the delta side of the trans-
directional IDMT earth fault relay whereas relays Ke and De used former TX UTILITY, earth fault relay H(E) will trip to isolate the
are directional earth fault relay with definite time characteristic. earth fault from the transmission grid. The tripping mechanism is
Fig. 4C shows the instantaneous-over-current (IOC) plot for coordi- safe when the system is normal radial without embedded genera-
nation between relays Ee, Fe and Ie. All relays Ee, Fe and Ie used are tion. With the installation of biomass generator, power flows bi-
directional earth fault relay with definite time characteristic directionally and tripping relay H(E) will not fully clear the earth
590 A.H.A. Bakar et al. / Electrical Power and Energy Systems 55 (2014) 581–591
Fig. 5B. Three phase voltage at existing system/11 kV (without undervoltage relay).
Fig. 6A. Zero sequence voltage at existing system/11 kV (with undervoltage relay).
fault. As shown in Fig. 5A, by just tripping the earth fault relay H(E) Therefore, in order to solve the unexpected delta source prob-
when earth fault occurs at busbar on the existing system/11 kV, the lem, under voltage relay G is used to detect the single phase to
earth fault is not fully cleared. The zero sequence voltage at busbar ground fault. As shown in Fig. 6A, after under voltage relay G is
on the existing system/11 kV does not fall to zero after the opera- used, the zero sequence voltage at busbar on the existing sys-
tion of relay H(E). This shows that the line is still energized and tem/11 kV falls to zero, which indicates the complete clearance
poses certain degree of danger. Fig. 5B shows phase A, B and C volt- of the fault. Fig. 6B shows the phase A, B and C voltage at busbar
ages at busbar on the existing system/11 kV, which when single on the existing system/11 kV before, during and after the fault.
phase to ground fault occurs at phase A, voltage at phase A drops After the fault is cleared, voltage of all three phases falls to zero,
but voltage at phases B and C increases. which indicates that the line is totally de-energized.
A.H.A. Bakar et al. / Electrical Power and Energy Systems 55 (2014) 581–591 591
Fig. 6B. Three phase voltage at existing system/11 kV (with undervoltage relay).
The same phenomena happen when earth fault occurs at busbar [4] Jenkins N, Allan R, Crossley P, Kirschen D, Strbac G. Embedded
generation. Herts, United Kingdom: The Institution of Electrical Engineers;
on the biomass substation/11 kV. Under voltage relay L is used to
2000.
fully clear the earth fault. [5] Paz Comech M, Miguel Garcia-Gracia, Samuel Borroy, Teresa Villen M.
Protection in distributed generation. University of Zaragoza, Spain: Centre of
Research for Energy Resources and Consumption (CIRCE); 2010.
9. Conclusion [6] Hadi Zayandehroodi, Azah Mohamed, Hussain Shareef, Marjan Mohammad
Jafari. An overview of protection coordination methods in distributed network
The simulation results obtained in this study shows that direc- with DGs. In: International conference: electrical energy and industrial
electronic systems EEIES2009, 7–8 December, 2009, Penang, Malaysia.
tional over-current and directional earth-fault relays should be [7] Yuping Lu, Lidan Hua, Jian Wu, Gang Wu, Guangting Xu. A study on effect of
used along the line connecting the two power sources because dispersed generator capacity on power system protection. In: Proceedings of
power flows bi-directionally. For the load side that branches out IEEE power engineering society general meeting; June 2007. p. 1–6.
[8] Kimmo Kauhaniemi, Lauri Kumpulainen, Paul Buchanan. Impact of distributed
from the source, non-directional relays may be used. In a micro
generation on the protection of distribution networks. Electric Energy 2013.
grid system, earth fault that happens at the delta side of the trans- <http://www.electricenergyonline.com/?page=show_article&article=173>
former cannot be fully cleared by the use of earth fault relay. This is [9] Behrendt K. Protection for unexpected delta sources. In: 29th Annual western
protective relay conference, Spokane, Washington; 2002.
because the relay at the delta side of the transformer will not be
[10] Enriquez Arturo Conde, Vazquez-Martinez Ernesto, Altuve-Ferrer Hector J.
able to detect the zero sequence current flow. Therefore, proper Time over current adaptive relay. Electr Power Energy Syst 2003;25:841–7.
operation has to be carried out by using an under voltage relay [11] Gers JM, Holmes EJ. Protection of electricity distribution networks 2nd Edition.
to detect the collapse of phase voltage for the earth fault IEE Power & Energy Series 77; 2004.
[12] Urdaneta J, Perez LG, Gomez JF, Feijoo B, Gonzalez M. Resolved analysis and
occurrence. inferior points solution of the linear programming coordination problem of
directional over current relay. Electr Power Energy Syst 2000;23:819–25.
References [13] Bakar AHA, Mokhlis H, Illias HA, Chong PL. The study of directional overcurrent
relay and directional earth-fault protection application for 33 kV underground
cable system in Malaysia. Int J Electr Power Energy Syst 2012;40:113–9.
[1] Bakar Ab Halim Bin Abu et al. Analysis of overload conditions in distance relay
[14] AREVA T&D Automation & Information Systems. Network protection &
under severe system contingencies. Int J Electr Power Energy Syst
automation guide. Overcurrent protection for phase and earth faults; 2005.
2010;32:345–50.
p. 122–51 [chapter 9].
[2] Dugan RC, McDermott TE. Distributed generation. In: IEEE industry
[15] Siemens power engineering guide 4th Edition. Transmission and distribution.
applications magazine, vol. 8(2); March–April 2002. p. 19–25, 1077–2618.
power system protection coordination. Siemens. p. 6/62–/70.
[3] Girgis A, Brahma S. Effect of distributed generation on protective device
coordination in distribution system. In: Proceedings of large engineering
systems conference on power engineering, LESCOPE ’01; July 2001. p. 115–9.