Auto Recloser Function
≡ Auto Recloser is an inbuilt function of REC650 ( Bay Control Unit)
Fucntion Description IEC 61850 Identification IEC 60617 Identification ANSI/IEEE C37.2 Device Number
Auto Recloser for 3 Phase
SMBRREC O->l 79
Operation
Operation Description Value Used Logic Gate Description
Open time/ Dead Time 1 Sec And Gate (&) :- The AND gate is an electronic circuit
Reclaim Time 25 Sec that gives a high output (1) only if all its inputs are
Max Wait time for Sync check OK 30 Sec high.
Min time that CB must be Closed before new
5 Sec
sequence allows OR Gate:- The OR gate is an electronic circuit that
Max Trip Pulse Duration 0.2 Sec gives a high output (1) if one or more of its inputs are
Number of Shots 1 high
Auto Recloser Start Logic when Bay is in Normal Condition
REL 650 (Line Distance Prot. Relay)
Zone -1 Fault REC 650( Bay Control Unit)
Zone 2 Start
OR
Carrier Received
Carrier Selector &
Switch 'IN' Position
Carrier Channel
Healthy
Auto Recloser Start
&
REC 650( Bay Control Unit)
CBREADY( CB Ready for Reclosing Cycle i.e.
operating gear/mechanism charged)
CBPOS(Ensure that the CB was closed when line
fault occurred)
Blocking or Inhibit Signal shall notbe present &
Bay on Normal (NIT Switch is in Normal Position)
Synchocheck OK
Avik Bhattacharya 19/03/2019 15:20Hrs.
Auto Recloser Function
≡ Auto Recloser is an inbuilt function of REC650 ( Bay Control Unit)
Fucntion Description IEC 61850 Identification IEC 60617 Identification ANSI/IEEE C37.2 Device Number
Auto Recloser for 3 Phase
SMBRREC O->l 79
Operation
Operation Description Value Used Logic Gate Description
Open time/ Dead Time 1 Sec And Gate (&) :- The AND gate is an electronic circuit
Reclaim Time 25 Sec that gives a high output (1) only if all its inputs are
Max Wait time for Sync check OK 30 Sec high.
Min time that CB must be Closed before new
5 Sec
sequence allows OR Gate:- The OR gate is an electronic circuit that
Max Trip Pulse Duration 0.2 Sec gives a high output (1) if one or more of its inputs are
Number of Shots 1 high
Auto Recloser Start Logic when Bay is in Transfer Condition
REL 650 (Line Distance Prot. Relay)
Zone -1 Fault REC 650( Bay Control Unit)
Zone 2 Start
OR
Carrier Received
Carrier Selector &
Switch 'IN' Position
Carrier Channel
Healthy
Auto Recloser Start
&
REC 650( Bay Control Unit)
CBREADY( CB Ready for Reclosing Cycle i.e.
operating gear/mechanism charged)
CBPOS(Ensure that the CB was closed when line
fault occurred)
Blocking or Inhibit Signal shall notbe present &
Bay on Transfer (NIT Switch is in INTER/TRANSFER
position)
Synchocheck OK
Avik Bhattacharya 19/03/2019 15:20 Hrs.
Auto Recloser Blocking Logic
A/R Unsuccessful under these conditions:
REL 650 (Line Distance Prot. Relay) - Permanent fault
- During dead time faults
SOTF Trip - Out of synchronism
CB Open
Permit 3 PH Trip
Carrier Out/Fail
OC/EF Trip
GR A/B Trip relay
optd
Overvoltage Trip
OR
UndervoltageTrip
Manual CB Trip
Manual CB close
Distance Delayed Trip
(Z3,Z4)
Line REC 650
DT Received ( Bay Control Unit)
Z1,Z2,Z3,Z4
(PH-PH) Trip
Auto Recloser Block
&
Line Panel REC 650( Bay Control Unit) Bay in Normal
OR
GR A/B Trip relay
faulty
SF6 Gen Lockout
Loss of SF6 Alarm
TBC REC 650
TBC Panel ( Bay Control Unit)
REB 670
Busbar prot Trip
&
Auto Recloser Block
REC650 Bay in Transfer
OR
SF6 Gen Lockout
Loss of SF6 Alarm
Avik Bhattacharya 19/03/2019 15:20 Hrs.