Project

DESARROLLO DE LA INGENIERÍA PARA


GENERACIÓN DE ENERGÍA ELÉCTRICA Y
VAPOR (COGENERACIÓN) (FASE I)
PARA LA REFINERÍA EN DOS BOCAS,
PARAÍSO, TABASCO

No. DE PROYECTO TMEX: 4151

Customer

PTI INFRAESTRUCTURA DE DESARROLLO,


S.A DE C.V.
EPC

TECHINT
Applique

IP Classification Export Classification


GE Non-Public- (Class II) NLR
GE Project Document Number GE Project Doc Revision
1518288.GTG.CUDS.GE32.0444-EFB-201 4
GE Project Document Description
GTG One-Line Diagram
GE Project Document Type Distribution List
Electrical Circuit Diagrams 1518288_gen_dl
TECHINT No. PTI No. Comments
4151-SGEP-M-VD-002-32001 R2B-CF-216-03-L-DAL-50001
GE Document Number GE Document Revision Disposal Code
138T4962 C Final for construction
GE Document Title
One Line Diagram

(c) 2021 GENERAL ELECTRIC COMPANY


All rights reserved. The Information herein is Proprietary and Technically Exclusive content that is solely owned by General Electric Company and/or its affiliates. Thus, it is being provided with the explicit expectation of
restricted and privileged use. All persons or legal entities receiving this information shall be deemed by the act of its receipt have contractually agreed to make no duplications, reproductions of any nature by any means,
modifications, disclosures, or use any portion of this material; except as is expressly authorized in writing by the General Electric Company, and/or its legitimate affiliates.
Doc Name : 138T4962 Rev C Released Date : 2021/10/26 Page 1 of 9

FOLD
8 7 6 5 4 3 1

FOLD

FOLD
SIZE DWG NO SH REV

.....

.....
D 138T4962

....

....

....

....

....

....
1 C
REV DESCRIPTION DATE APPROVED

C SEE THE FINAL SHEET FOR REVISION DETAILS.


SEE CA000009416.
UPDATED BY : 503255666. 18-10-21 SEE PLM

RELAY & DEVICE NOMENCLATURE EXCITER FUNCTIONS EQUIPMENT LOCATION KEY NOTES:
D GEN-DMM
BUS-DMM
GENERATOR DIGITAL METER
BUS DIGITAL METER
REGULATOR A & B CUSTOMER EQUIPMENT 1. SEE DEVICE SUMMARY MLI 0414 TO VERIFY MOTOR AND HEATER RATINGS. D
27MC MCC UNDER VOLTAGE MONITORING RELAY AVR AUTOMATIC VOLTAGE REGULATOR (AUTO) ACCESSORY BASE DEVICE 2. POWER CABLES:
52G GENERATOR BREAKER FCR FIELD CURRENT REGULATOR
GE EQUIP MTD SEPARATE FROM PKG ALL POWER CABLES FROM CUSTOMER EQUIPMENT TO GE EQUIPMENT AND BETWEEN GE
52L LINE BREAKER FVR FIELD VOLTAGE REGULATOR PROVIDED EQUIPMENT ARE BY CUSTOMER.
PSS POWER SYSTEM STABILIZER GENERATOR PROTECTION PANEL
57 GROUNDING DEVICE
63PR TRANSFORMER OIL PRESSURE RELIEF RCC REACTIVE CURRENT COMPENSATION MOTOR CONTROL CENTER (MCC)
3. GENERATOR PROTECTION REQUIRES, TYPICALLY, NO MORE
63PTX TRANSFORMER FAULT PRESSURE SWITCH RELAY UEL UNDER EXCITATION LIMIT TURBINE BASE THAN (6) NORMALLY OPEN AND (3) NORMALLY CLOSED
63V TRANSFORMER VACUUM ALARM OEL OVER EXCITATION LIMIT TURBINE CONTROL PANEL(TCP) CONTACTS FOR 52G STATUS.
71Q TRANSFORMER LIQUID LEVEL GAUGE V/Hz VOLTS per HERTZ LIMIT C
83LBSX LINE BREAKER SYNCH SELECTION RELAY COOLING WATER SYSTEM
PROTECTION MODULE 4. THE CRITICAL FAILURE OF ANY ONE GENERATOR PROTECTION RELAY WILL
86BFA,86BFB BREAKER FAILURE LOCKOUT RELAY GENERATOR AUXILIARY COMPARTMENT (GAC) RESULT IN AN ALARM TO TCP. SIMULTANEOUS CRITICAL FAILURES OF BOTH
86EX EXCITATION TRANSFORMER DIFF LOCKOUT RELAY 24EX V/Hz ALARM/TRANSFER GENERATOR PROTECTION RELAYS WILL RESULT IN TCP INITIATING A
86G1A,86G2A 26EX BRIDGE OVER TEMPERATURE ALARM / TRIP LOAD SHAFT COMPARTMENT NORMAL SHUTDOWN OF UNIT, AFTER A 60 MIN DELAY.
GENERATOR LOCKOUT RELAY
86G1B,86G2B 27EX AC/DC SOURCE UNDERVOLTAGE ALARM
40EX LOSS OF EXCITER TRANSFER EXCITER COMPARTMENT 5. EACH GPP LOCKOUT RELAY IS PROVIDED WITH A LOSS OF DC ALARM RELAY,
86AT AUX TRANSFORMER DIFF LOCKOUT RELAY
DEVICE NOMENCLATURE IS 74.
89ET EXCITATION TRANSFORMER DIFF LOCKOUT RELAY 47EX BRIDGE AC PHASE UNBALANCE ALARM / TRIP GENERATOR NEUTRAL ACCESSORY COMPARTMENT(GNAC)
86U UNIT DIFF LOCKOUT RELAY 52G/AUX BREAKER POSITION INPUT SIGNAL 6. REFER TO STATION ONE-LINE DIAGRAM (BY CUSTOMER/PARTNER)
86T TRANSFORMER DIFF LOCKOUT RELAY GENERATOR LINE ACCESSORY COMPARTMENT(GLAC)
59EX OVERVOLTAGE ALARM FOR ADDITIONAL RELAYING IN BOP SCOPE.
96G( ) TRANSDUCER (G)=WATTS/VARS (A)=CURRENT, 60EX VT (VTFF) FAILURE ALARM / TRANSFER GENERATOR COMPT DEVICE
(V)=VOLTAGE, (R)=VARS 7. CT ACCURACY FOR RELAYING CLASS ANSI EL : C800
64EX GENERATOR FIELD GROUND PACKAGED ELECTRICAL & ELECTRONIC
CT ACCURACY FOR METERING CLASS ANSI EL : 0.3B-1.8
76EX OVER EXCITATION ALARM / TRIP CONTROL CENTER (PEECC)
8. CT POLARITY MARK IS AT LEAD CONNECTION TO THE CT USER DEVICE.
94EX RELAY TRIP GENERATOR CIRCUIT BREAKER COMPARTMENT (GCBC)
C 96TVM TRANSFER VOLTAGE F FIRE PROTECTION PANEL
9. VTS ARE NON DRAWOUT. ACCURACY ANSI CLASS 0.3 THRU BURDEN X. C
G60A/G60B (GENERATOR MANAGEMENT RELAY)
96FV FIELD VOLTAGE 10. BREAKER FAILURE RETRIP RELAY CONFIGURATION:
21 PHASE DISTANCE T TURBINE AIR INLET COMPARTMENT
96FC FIELD CURRENT DO NOT CONFIGURE FUNCTION 50BF TO ANY TRIP OUTPUT. DOING SO WILL RESULT IN A
24(A), 24(T) VOLTS PER HERTZ
96FT FIELD TEMPERATURE EX EXCITER (EX2100e) NUISANCE ALARM WHENEVER THE BREAKER TRIPS AND INITIATES A BREAKER FAILURE
25 SYNC CHECK RELAY
27DG DEAD GENERATOR PERMISSIVE RETRIP.
27P(A) PHASE UNDERVOLTAGE WW WATER WASH SKID
11. TEST SWITCHES:
32 SENSITIVE DIRECTIONAL POWER DC LOW VOLTAGE DC DISTRIBUTION SYSTEM/PANEL ALL VT AND CT INPUTS TO PROTECTION RELAYS AND ALL TRIP OUTPUTS ARE PROVIDED
40-1,2 LOSS OF EXCITATION T60T/60U/T60AT (TRANSFORMER MANAGEMENT RELAY) WITH TEST SWITCHES.
.... 46(A),46(T) GENERATOR UNBALANCE (NEG SEQUENCE) GAMP GAS AUXILIARY MONITORING PANEL ....
24 VOLTS PER HERTZ 12. MAXIMUM FLUX PROBE CABLE LENGTH IS 2000 FEET.
50/27 INADVERTENT ENERGIZATION
FOLD 50BF BREAKER FAILURE RE-TRIP 50/51 XFMR INSTANTANEOUS/TIME OVERCURRENT GV FUEL GAS COMPARTMENT FOLD

50/62BF BREAKER FAILURE WITH DELAY 13. MAXIMUM DISTANCE BETWEEN THE MARK VIe AND THE BREAKER TO BE
51TN XFMR NEUTRAL OVERCURRENT CRANKING MOTOR CONTROLLER SYNCHRONIZED IS 900 FEET (280 METERS).
51P PHASE TIME OVERCURRENT
59BN BUS GND FAULT PROTECTION ....
59N NEUTRAL OVERVOLTAGE, (GND PROTECTION)
63PTX SUDDEN PRESSURE RELAY GHM GENERATOR HEALTH MONITOR 14. GENERATOR PROTECTION SETTING IS BY GE (MLI: C184).
59P(A) PHASE OVERVOLTAGE
64TN 100% STATOR GROUND PROTECTION VIA 3RD HARMONIC DIFF 87U/87T/87AT UNIT/TRANSFORMER DIFFERENTIAL PROTECTION
BUS VTFF BUS VOLTAGE TRANSFORMER FUSE FAILURE
78 OUT OF STEP (LOSS OF SYNCH)
81O(A) OVERFREQUENCY
81U UNDER FREQUENCY
87S STATOR DIFFERENTIAL T60ET (EXCITATION TRANSFORMER PROTECTION RELAY)
GEN VTFF GEN VOLTAGE TRANSFORMER FUSE FAILURE
26Q LIQUID TEMPERATURE
B 50/51
63PT-4
INSTANTANEOUS/TIME OVERCURRENT
SUDDEN PRESSURE
B
87ET DIFFERENTIAL PROTECTION

SIZE
D
DWG NO
138T4962
GENERATOR SERIAL NO. CUSTOMER UNIT NO.

LEGEND GG10792
GG10793
EXTTRG EXTERNAL TRIGGER
EGD ETHERNET GLOBAL DATA GG10794
FOS FIBER OPTIC SENSOR
GSU GENERATOR STEP-UP TRANSFORMER
HMI TURBINE CONTROL SYSTEM HUMAN
MACHINE INTERFACE

SH
1
IBF INITIATE BREAKER FAILURE
LA LIGHTNING ARRESTER

REV
SC SURGE CAPACITOR

C
SR SPARE
TS TEST SWITCH GE CLASS II (INTERNAL NON - CRITICAL)
A TRIG OSC TRIGGER OSCILLOGRAPHY
CUSTOMER
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES DRAWN
SIGNATURES

LEON, EDGAR
DATE

11-01-2021
GE POWER GENERAL ELECTRIC COMPANY
Schenectady, NY - USA
TERMINATION POINT TOLERANCES ON:
GE 2 PL DECIMALS ± CHECKED SEE PLM N/A
3 PL DECIMALS
ANGLES
FRACTIONS
±
±
±
PROJ ENG HARTMAN, D. 11-01-2021 ONE LINE DIAGRAM
PROJECT
ISSUED SEE PLM N/A GAS TURBINE
THIRD ANGLE PROJECTION C COPYRIGHT "2021" GE POWER (USA), LLC AND/OR ITS AFFILIATES. 3 X GT-7E.03 / GEN - A35 FIRST MADE FOR: GG10792, GG10793, GG10974 MLI:0444
All rights reserved. The information contained herein is GE Power Generator Proprietary Technical Information
that belongs to the General Electric Company, GE Power (USA), LLC and/or their affiliates, which has been SIZE CAGE CODE DWG NO
provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive
such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or
MADE FOR
D 138T4962

DISTR
TO
other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by PEMEX DOS BOCAS - MEXICO
the General Electric Company, GE Power (USA), LLC and/or its affiliates.
SCALE IPS: 1518288 SHEET 1

4 3 2 1
....

....

....
.....
FOLD
FOLD

GE Non-Public- (Class II) - NLR


Doc Name : 138T4962 Rev C Released Date : 2021/10/26 Page 2 of 9

FOLD
8 7 6 5 4 3 1

FOLD

FOLD
SIZE DWG NO SH REV

.....

.....
D 138T4962

....

....

....

....

....

....
2 C

T60T
63
PT SHEET 3 GENERATOR HIGH VOLTAGE CONNECTION
52L1 63 T60U
PT SHEET 3

/ STATUS
__/5 __/5 __/5 BUS DUCT AUX BUS DUCT
115KV TRIP/CLOSE
TO SYSTEM
GSU
D 52L2 W T Y
BUS DUCT
(3)
D
TO T60U TO T60T TO T60T __/5
/ TO BUS DMM
STATUS
TRIP/CLOSE
SHEET 3 SHEET 3 SHEET 3 SHEET 3 R (3)
GCB __/5 F1
BUS 1 BUS 2 RUN 57GL STATUS FOR SAFE ENERGIZATON TO T60U 51AT
SYNCH VT'S SYNCH VT'S SYNCH VT'S 480VAC POWER DISTRIBUTION
CLOSING CKT INTERLOCK FOR SAFE SHEET 3 A2 (3) 51TN H1 86 SEE
TO T60T DC 125VDC 52G CC, TC1
__/5 63PTX AT SHEET 4
(1Ø) (1Ø) (1Ø) CLOSURE OF 57GL
SHEET 3 M
87AT
__KV/120V __KV/120V __KV/120V DC 125VDC 52G TC2
63 ANY TRIP P1 ALARM
__/5 U VT1 TO T60U, T60T UNIT AUX PTX H7a
(3) VT'S A3 SHEET 3 TRANSFORMER -3 P5 TRIG OSC PRIMARY
13,800/ 3 - 120V/ 3 - 120/3 ANY TRIP GEN PROT RELAY (G60A)
VT SELECTION F4
TO T60U, T60T __/5 P6
BY CUSTOMER TO T60U 0.5A
DAMPING
A4 SHEET 3 ANY TRIP TRIG OSC REDUNDANT
L.A. (1) GEN PROT RELAY (G60B)
QQ SHEET 3 15kV DEVICE 87AT
TO G60A, G60B, BUS DMM, TCP 51AT EGD
TO 83LBSX __/5 Z L1 SHEET 3 51TN
ALARM
PP SHEET 3 63PTX
CRITICAL
TO 83LBSX SC FAILURE ALARM
SHEET 3 89G STATUS
0.13 uf 89G IRIG-B
CUSTOMER/BOP M
T60AT M5 125VDC DC
GE
52G CLOSE
/ 52G TRIP 52G __/5 (3)
52G STATUS
TO G60B 52 GE
H SHEET 3 AUX
EX 52G STATUS (3) 6,000/5
CUSTOMER/BOP
CT'S 21A,22A,23A
TO G60A
C (3) 6,000/5
CT'S 21,22,23
G SHEET 3
TO CUSTOMER SYSTEM
C
CUSTOMER/BOP TURBINE
6,000/5 TO EX2100e
(2) CT'S 19A,19C F SHEET 5 GE

6,000/5
SPARE
(3) CT'S 13,14,15
L.A.
15kV
GENERATOR
.... ....
Ø1
TO EX2100 SC C
GNAC Ø2 3 2 1
FOLD
..... SHEET 5 K VT4 0.13 uf .....
FOLD

Ø3
(3) VT'S
VT2 TO EX2100e
TO G60B
13,800/ 3 - 120V/ 3 J SHEET 5
GCBC
.... (3) VT'S ....
SHEET 3 L 13,800/ 3 - 120V/ 3
0.5A GEN DMM, G60A, TCP
L2 SHEET 3
0.5A
TO METERING
SHEET 3
F1
M
PHASE SEQUENCE
STATUS FOR START 57GG Ø1
/ EX PERMISSIVE KEY PHASER (1/REV) SHORTED TURN
Ø3
FLUX PROBE MONITORING SYSTEM
B EX
57G CLOSING CKT
INTERLOCK Ø2 B
120VAC THE VOLTAGE REACHES
NON SEGREGATED GHM A POSITIVE MAXIMUM
BUS DUCT

SIZE
AT THE GENERATOR LINE

D
TERMINALS IN THE
ORDER OF: Ø1, Ø2, Ø3

DWG NO
GHM

138T4962
FLUX PROBE
THIS SHEET
GENERATOR
FROM EX2100e
SHEET 5 RTD'S

GENERATOR 6,000/5
RATING INFORMATION (3) CT'S 1,2,3 TO METERING
E
KVA 112,000 SHEET 3

SH
P.F. 0.8 6,000/5

2
(3) CT'S 4,5,6
FREQ Hz 60 D TO G60A SHEET 3

REV
KV 13.8 6,000/5

C
(3) CT'S 7,8,9
C TO G60B SHEET 3
(3) 6,000/5
CT'S 10,11,12 TO T60U
A B SHEET 3

13kVA A TO G60A/B
12,000-240V 0.21
SHEET 3
DRY TYPE
NEUTRAL GROUND 750A GE CLASS II (INTERNAL NON - CRITICAL)
TRANSFORMER 10S C COPYRIGHT "2021" GE POWER (USA), LLC AND/OR ITS AFFILIATES. SIZE CAGE CODE DWG NO
All rights reserved. The information contained herein is GE Power Generator Proprietary Technical Information GE POWER & WATER GENERAL ELECTRIC COMPANY

D
Schenectady, NY - USA

138T4962
that belongs to the General Electric Company, GE Power (USA), LLC and/or their affiliates, which has been
provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive
such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or DRAWN LEON, EDGAR

DISTR
TO
other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by
the General Electric Company, GE Power (USA), LLC and/or its affiliates. ISSUED SEE PLM SCALE SHEET 2

8 7 6 5 4 3 2 1
....

....

....

....

....

....
.....

.....
FOLD

FOLD
FOLD

GE Non-Public- (Class II) - NLR


Doc Name : 138T4962 Rev C Released Date : 2021/10/26 Page 3 of 9

FOLD
8 7 6 5 4 3 1

FOLD

FOLD
SIZE DWG NO SH REV

.....

.....
D 138T4962

....

....

....

....

....

....
3 C

RELAY PROTECTION

FROM GSU FROM GSU


HIGH SIDE CT'S NEUTRAL CT'S
SHEET 2 SHEET 2

EPM9700 FROM SWITCHYARD T U


NOTE:
D FROM AUX BUS CT's
BUS
1Ø VT
PP
CUSTOMER MUST PROVIDE MATCHING VT SIGNALS FROM BOTH SIDES OF THE
BREAKER(S) USED FOR SYNCHRONIZING IDENTICAL PHASES, VOLTAGE MAGNITUDES
D
SHEET 2
R DMM
AND PHASE ANGLES WHEN BREAKER ARE CLOSED. GE WILL NOT PROVIDE VOLTAGE
FROM SWITCHYARD
MATCHING AND/OR PHASE ANGLE MATCHING AUX VT's FOR THIS PURPOSE. GPP M5 M8
RS232/RS485 BURDEN ON VT INPUTS WILL BE A MINIMUM OF 30VA (NOT INCLUDING CABLE 87T
1Ø VT
RESISTANCE). 50,51,24 H1 FROM GSU FROM GSU
PULSE OUTPUTS 86T SEE SHEET 5
QQ 63PTX, HIGH SIDE CT'S NEUTRAL CT'S
IRIG-B 59BN H3 SHEET 2 SHEET 2
4-20mA OUTPUTS TRIP 52L1 (TC1)
FROM VT1
DC 125VDC 83LBSX POWER SYSTEM FUNCTIONS
SHEET 2 A4 F5 H4 W Z
DISPLAY ON HMI: WATTS,VARS,PF, TRIP 52L1 (TC2)
GEN VOLTS & FREQ,BUS VOLTS & FREQ 83LBSX H5
FROM VT1 IBF 52L1
FROM VT1 L1 G60A
CLOSE
SHEET 2 A3 F8
51TN P2
SHEET 2 52L1/52L2
SYNCHRONIZATION: 25SC TRIP 52L2 (TC1)
AUTO, MANUAL CLOSE P3
EX SYNCH CHECK 52G TRIP 52L2 (TC2) M5 M8
87U
EXCITER P4 H1
83LBSX UDH (EGD) IBF 52L2 50,51,24 86U SEE SHEET 5
SYNCHRONIZATION: 83LBSX P1
63PTX,
AUTO, MANUAL 52L1/52L2 ANY TRIP ALARM 59BN
FROM VT2 SYNCH CHECK STATUS H7a H3
L2 63PTX P5 FROM VT1
SHEET 2 52G ANY TRIP
TRIG OSC PRIMARY
SHEET 2 A4 F5 TRIP 52L1 (TC1)
STATUS GEN PROT RELAY (G60A) H4
P6 TRIG OSC REDUNDANT
ANY TRIP TRIP 52L1 (TC2)
OVERSPEED (FREQ) TRIP 52G GEN PROT RELAY (G60B)
REVERSE POWER (TC1, TC2) 87T FROM VT1 H5
24 SHEET 2 A3 F8 IBF 52L1
51TN P2
50 EGD TRIP 52L2 (TC1)
EPM9700 51 ALARM P3
TRIP 52L1/52L2 FROM AUX TRIP 52L2 (TC2)
59BN
GEN
UNDERSPEED (FREQ)
(TC1, TC2) 63PTX
BUS CT'S A2 M1
P4
SHEET 2 IBF 52L2
DMM GEN VTFF
C 96GG-1
DISPLAY, EXCITER CONTROL IRIG-B
CRITICAL
T60T FAIL
ANY TRIP
P1
ALARM C
FAILURE H7a P5 TRIG OSC PRIMARY
RS232/RS485 DC 125VDC 63PTX ANY TRIP
T60T F1 GEN PROT RELAY (G60A)
P6 TRIG OSC REDUNDANT
PULSE OUTPUTS ANY TRIP
GEN PROT RELAY (G60B)
4-20mA OUTPUTS 87U
24
IRIG-B Y 50 EGD
DC 125VDC 51 ALARM
FROM GSU
P7a 59BN
LV CT'S EXT TRG 63PTX
M5 SHEET 2
....
FROM VT4 59N H1
GEN VTFF
....
SHEET 2 F1 96GW-1
F5
64TN 86
G1A
SEE SHEET 5 IRIG-B
CRITICAL
87S 59N H1 T60U FAIL
FOLD FROM NEUTRAL E 94EX-1 EX 64TN 86 SEE SHEET 5 FAILURE FOLD
..... FROM VT1 G1B DC 125VDC .....
CT'S 1,2,3 SHEET 2 24(T) SHEET 2 L1 M5 87S T60U F1
40-1,2 H2 86 EX
46(T) SEE SHEET 5 94EX-2
.... 50/27 G2A 24(T) ....
FROM GCB FROM GCB LINE SIDE
81U-3 40-1,2
CT'S 21,22,23 G M1 CT'S 21A,22A,23A H M1
46(T)
H2 86 SEE SHEET 5
SHEET 2 21,32
H3
TRIP 52G (TC1)
SHEET 2
50/27 G2B B
50BF,51P 81U-3
H4 FROM NEUTRAL SIDE
78 TRIP 52G (TC2) FROM VT4 H3 CT'S 10,11,12
SHEET 2 L F5 21,32 TRIP 52G (TC1)
SHEET 2
50BF,51P
H5 86 H4
50/62BF BFA SEE SHEET 5 78 TRIP 52G (TC2)
H6 H5
ANY TRIP ALARM 50/62BF 86 SEE SHEET 5
BFB
P1
25 52G CLOSE PERMISSIVE H6
B FROM NEUTRAL 27DG
P2
27DG PERMISSIVE EX
ANY TRIP
P2
ALARM
B
SIDE CT'S 4,5,6 D F1 27DG 27DG PERMISSIVE EX
SHEET 2 P3 FROM NEUTRAL
27DB
DISABLE DEAD BUS SIDE CT'S 7,8,9 C F1 P5
TRIG OSC PRIMARY GEN PROT RELAY (G60A)
P4 SHEET 2
52G DEAD BUS CLOSE

SIZE
ANY TRIP P6

D
TRIG OSC TRANSFORMER PROT RELAY (T60U)
P5
TRIG OSC REDUNDANT GEN PROT RELAY (G60B)

DWG NO
ANY TRIP P6 U1
TRIG OSC TRANSFORMER PROT RELAY (T60U) TRIP 52L1 (TC1)
U1 U2

138T4962
TRIP 52L1 (TC1) TRIP 52L1 (TC1)
U2 U3
TRIP 52L1 (TC1) 81U-2, IBF 52L1
81O-2, U4
81U-2, U3 TRIP 52L2 (TC1)
IBF 52L1 81O-3
U5
52G H7a
81O-2,
81O-3
U4
TRIP 52L2 (TC1) TRIP 52L2 (TC1) NOTES:
U5 52G H7a U6
TRIP 52L2 (TC1) IBF 52L2 1. ALL G60 PROTECTION ELEMENTS (EXCEPT 25, 27DG AND 27DB) ALSO
IBF H7c U6 IBF H7c
IBF 52L2 TRANSMITTED TO TCP VIA EGD FOR HMI DISPLAY.
24A
52G H8a 52G H8a 46A 2. ALL T60 PROTECTION ELEMENTS ALSO TRANSMITTED TO TCP VIA EGD FOR HMI
24A 27P(A) DISPLAY.
52L1 EXT TRG 50BF EGD
P7a 46A U7a ALARM

SH
52L2 27P(A) 59P(A)

3
EGD 52L1 81U-1
50BF P7a
EXT TRG U7a ALARM 52L2 81O-1
59P(A)

REV
GEN VTFF

C
81U-1
IRIG-B 81O-1 IRIG-B CRITICAL G60A FAIL
GEN VTFF FAILURE
DC 125VDC CRITICAL DC 125VDC
A G60A F8 FAILURE
G60A FAIL G60B F8

FROM NEUTRAL GE CLASS II (INTERNAL NON - CRITICAL)


GROUND RES A C COPYRIGHT "2021" GE POWER (USA), LLC AND/OR ITS AFFILIATES. SIZE CAGE CODE DWG NO
SHEET 2 All rights reserved. The information contained herein is GE Power Generator Proprietary Technical Information GE POWER & WATER GENERAL ELECTRIC COMPANY

D
Schenectady, NY - USA

138T4962
that belongs to the General Electric Company, GE Power (USA), LLC and/or their affiliates, which has been
provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive
such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or DRAWN LEON, EDGAR

DISTR
TO
other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by
the General Electric Company, GE Power (USA), LLC and/or its affiliates. ISSUED SEE PLM SCALE SHEET 3

8 7 6 5 4 3 2 1
....

....

....

....

....

....
.....

.....
FOLD

FOLD
FOLD

GE Non-Public- (Class II) - NLR


Doc Name : 138T4962 Rev C Released Date : 2021/10/26 Page 4 of 9

FOLD
8 7 6 5 4 3 1

FOLD

FOLD
SIZE DWG NO SH REV

.....

.....
D 138T4962

....

....

....

....

....

....
4 C

LOCKOUT RELAY CONTACTS ASSIGNMENT CHART

D D

86BF-A CONTACT ASSIGNMENT 86G-1A CONTACT ASSIGNMENT 86U CONTACT ASSIGNMENT 86ET CONTACT ASSIGNMENT

CONTACTS FUNCTION CONTACTS FUNCTION CONTACTS FUNCTION CONTACTS FUNCTION


TRIP TURBINE & ALARM TRIP TURBINE & ALARM TRIP TURBINE & ALARM TRIP TURBINE & ALARM
TRIP EXCITATION EX TRIP EXCITATION EX TRIP EXCITATION EX TRIP EXCITATION EX
TRIP 52G COIL #1 TRIP 52G COIL #1 TRIP 52G COIL #1 TRIP 52G COIL #1
TRIP 52G COIL #2 TRIP 52G COIL #2 TRIP 52G COIL #2 TRIP 52G COIL #2
BLOCK CLOSE 52G BLOCK CLOSE 52G BLOCK CLOSE 52G BLOCK CLOSE 52G
TRIP 52L1 COIL #1 IBF/52G-A (G60A) IBF/52G-A (G60A) IBF/52G-A (G60A)
TRIP 52L1 COIL #2 IBF/52G-B (G60B) IBF/52G-B (G60B) IBF/52G-B (G60B)
BLOCK CLOSE 52L1/52L2 COIL MONITOR ALARM TRIP 52L1 COIL #1 TRIP 52ET COIL #1
IBF/52L1 TRIP 52L1 COIL #2 TRIP 52ET COIL #2
TRIP 52L2 COIL #1 BLOCK CLOSE 52L1/52L2 BLOCK CLOSE 52ET
TRIP 52L2 COIL #2 86G-2A CONTACT ASSIGNMENT IBF/52L1 COIL MONITOR ALARM
IBF/52L2 TRIP 52L2 COIL #1
TRIP 52AUX COIL #1 TRIP 52L2 COIL #2
C TRIP 52AUX COIL #2
CONTACTS FUNCTION
ALARM
IBF/52L2 86AT CONTACT ASSIGNMENT
C
BLOCK CLOSE 52AUX TRIP 52AUX COIL #1
TRIP EXCITATION EX
IBF/52G-B (G60B) TRIP 52AUX COIL #2
TRIP 52G COIL #1 CONTACTS FUNCTION
COIL MONITOR ALARM BLOCK CLOSE 52AUX
TRIP 52G COIL #2 TRIP TURBINE & ALARM
COIL MONITOR ALARM
BLOCK CLOSE 52G TRIP EXCITATION EX
IBF/52G-A (G60A) TRIP 52G COIL #1
IBF/52G-B (G60B) TRIP 52G COIL #2
....
86BF-B CONTACT ASSIGNMENT COIL MONITOR ALARM BLOCK CLOSE 52G ....
86T CONTACT ASSIGNMENT IBF/52G-A (G60A)
FOLD FOLD
..... CONTACTS FUNCTION IBF/52G-B (G60B) .....

TRIP TURBINE & ALARM CONTACTS FUNCTION TRIP 52L1 COIL #1


.... 86G-1B CONTACT ASSIGNMENT TRIP 52L1 COIL #2 ....
TRIP EXCITATION EX TRIP TURBINE & ALARM
TRIP 52G COIL #1 TRIP EXCITATION EX BLOCK CLOSE 52L1/52L2
CONTACTS FUNCTION IBF/52L1
TRIP 52G COIL #2 TRIP 52G COIL #1
BLOCK CLOSE 52G TRIP TURBINE & ALARM TRIP 52G COIL #2 TRIP 52L2 COIL #1
TRIP 52L1 COIL #1 TRIP EXCITATION EX BLOCK CLOSE 52G TRIP 52L2 COIL #2
TRIP 52L1 COIL #2 TRIP 52G COIL #1 IBF/52L2
IBF/52G-A (G60A)
BLOCK CLOSE 52L1/52L2 TRIP 52G COIL #2 TRIP 52AUX COIL #1
IBF/52G-B (G60B)
IBF/52L1 BLOCK CLOSE 52G TRIP 52AUX COIL #2
TRIP 52L1 COIL #1

B TRIP 52L2 COIL #1


TRIP 52L2 COIL #2
IBF/52G-A (G60A)
IBF/52G-B (G60B)
TRIP 52L1 COIL #2 BLOCK CLOSE 52AUX
COIL MONITOR ALARM
B
BLOCK CLOSE 52L1/52L2
IBF/52L2 COIL MONITOR ALARM
IBF/52L1
TRIP 52AUX COIL #1 TRIP 52L1 COIL #1

SIZE
D
TRIP 52AUX COIL #2 TRIP 52L1 COIL #2

DWG NO
BLOCK CLOSE 52AUX
86G-2B CONTACT ASSIGNMENT IBF/52L1
IBF/52G-A (G60A) TRIP 52AUX COIL #1

138T4962
COIL MONITOR ALARM TRIP 52AUX COIL #2
CONTACTS FUNCTION
BLOCK CLOSE 52AUX
ALARM
COIL MONITOR ALARM
TRIP EXCITATION EX
TRIP 52G COIL #1
TRIP 52G COIL #2
BLOCK CLOSE 52G
IBF/52G-A (G60A)
IBF/52G-B (G60B)

SH
4
COIL MONITOR ALARM

REV
C
A

GE CLASS II (INTERNAL NON - CRITICAL)


C COPYRIGHT "2021" GE POWER (USA), LLC AND/OR ITS AFFILIATES. SIZE CAGE CODE DWG NO
All rights reserved. The information contained herein is GE Power Generator Proprietary Technical Information GE POWER & WATER GENERAL ELECTRIC COMPANY

D
Schenectady, NY - USA

138T4962
that belongs to the General Electric Company, GE Power (USA), LLC and/or their affiliates, which has been
provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive
such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or DRAWN LEON, EDGAR

DISTR
TO
other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by
the General Electric Company, GE Power (USA), LLC and/or its affiliates. ISSUED SEE PLM SCALE SHEET 4

8 7 6 5 4 3 2 1
....

....

....

....

....

....
.....

.....
FOLD

FOLD
FOLD

GE Non-Public- (Class II) - NLR


Doc Name : 138T4962 Rev C Released Date : 2021/10/26 Page 5 of 9

FOLD
8 7 6 5 4 3 1

FOLD

FOLD
SIZE DWG NO SH REV

.....

.....
D 138T4962

....

....

....

....

....

....
5 C

EXCITATION PANEL

4.16KV SWITCHGEAR
D D
FROM 52ET
86ET

CUSTOMER
GE
C ET

63
L1 PTX
-5

L2 F1 26Q, 49T,
TO T60-ET (3) 150/5 50, 51, H1
THIS SHEET 86 SEE
L3 EXCITATION
L1 H7a 63PT-4,
87ET
ET SHEET 4
TRANSFORMER P1
L4 26Q 49T 63PR 63V 71Q TYPE OIL, ONAN FROM EXCITATION L2 H7c
ANY TRIP ALARM
4.16KV/550V TRANSFORMER
800kVA, Z=6% THIS SHEET L3 H8a
26Q
49T
C L4 H8c 50 EGD
ALARM
(3) 1000/5 51
DC 125VDC 63PTX M1 63PT-4

C 120VAC SPACE HEATER IRIG-B


87ET
CRITICAL B1a
C
DC 125VDC FAILURE ALARM
T60-ET

ALARM EXCITATION SYSTEM- 2.0 PU CEILING VOLTAGE AND


3.8 PU/SEC RESPONSE RATIO

.... FROM VT4 ....


K
FOLD
SHEET 2 FOLD
..... .....
FROM VT2
J SHEET 2
.... EX ....
FROM CT'S 19A,19C
F SHEET 2
FAN 1 120VAC
CONTROLLER FAN 2 120VAC
FAN 3 120VAC
LIGHT & RECPT 120VAC
CONTROL 120VAC

CONTROL 125VDC DC

B TRIP
86G1A, 1B, 86G2A, 2B,
86BFA, 86BFB, 86U,
B
86T, 86AT, 86ET
MASTER 1
94EX-1 86G-2A
MASTER 2

SIZE
94EX-2 86G-2B

D
EX OFF

DWG NO
ZERO VOLTAGE 27DG (G60A/G60B)
52G

138T4962
52G/STATUS
MDA(+)
52GG/STATUS 57GG
GCB
41E 57GG CLOSE PERMISSIVE

98GFT
C
96FV
4-20mA
96FC
96FTMP C
DE-EXCITATION DEAD BUS L83DBOUT

SH
5
ZERO SPEED L14ESW

UDH (EGD)

REV
C
EX2100e (WBU)

A TO GENERATOR
FIELD SHEET 2

GE CLASS II (INTERNAL NON - CRITICAL)


C COPYRIGHT "2021" GE POWER (USA), LLC AND/OR ITS AFFILIATES. SIZE CAGE CODE DWG NO
All rights reserved. The information contained herein is GE Power Generator Proprietary Technical Information GE POWER & WATER GENERAL ELECTRIC COMPANY

D
Schenectady, NY - USA

138T4962
that belongs to the General Electric Company, GE Power (USA), LLC and/or their affiliates, which has been
provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive
such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or DRAWN LEON, EDGAR

DISTR
TO
other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by
the General Electric Company, GE Power (USA), LLC and/or its affiliates. ISSUED SEE PLM SCALE SHEET 5

8 7 6 5 4 3 2 1
....

....

....

....

....

....
.....

.....
FOLD

FOLD
FOLD

GE Non-Public- (Class II) - NLR


Doc Name : 138T4962 Rev C Released Date : 2021/10/26 Page 6 of 9

FOLD
8 7 6 5 4 3 1

FOLD

FOLD
SIZE DWG NO SH REV

.....

.....
D 138T4962

....

....

....

....

....

....
6 C

FROM
CUSTOMER'S 480V 3Ø
SUPPLY LOW VOLTAGE AC DISTRIBUTION
MCC1-AC
CUSTOMER
GE

D D
480V, 3Ø , 60Hz, 1200A, MOTOR CONTROL CENTER 65KAIC (L1,L2,L3,G)

C C C C C C C
50 40 400 15 15 70 40 50 40

C
2 2 5 1 1 3 2 2 2
27
MC
-1 C

MCC
C FIELD
20 15 200 5 1.5 30
HP HP HP HP HP HP 20kW 30kW 20kW
23BT-1 23QV-2A 23TK-1 23VG-1 23VL-1 23AC-1A
120W 75W 250W 60W 30W XXW
DESCRIPTION ALARM 88BT-1 88QV-1A 88TK-1 88VG-1 LOAD 88VL-1 88AC-1 23HA-1 23QT-1,2 23HT-1
TURBINE COMPT LUBE TURBINE COMPARTMENT GAS TURBINE AIR INLET ACCESORY COMPT LUBE OIL TANK TURBINE COMPT
COOLING AIR FAN MIST EXHAUST COOLING COMPARTMENT EVAPORATIVE SPACE HEATER INMERSION SPACE HEATER
#1 SEPARATOR FRAME COOLING AIR FAN #1 VENTILATION COOLER PUMP HEATERS
#1 BLOWER #1 FAN #1 MOTOR #2
GV T
C C

C C
(1) (2) (3) (4) (5) (6) (7)
35 35 30 60 30 150 30

.... 50A ....

FOLD FOLD
..... .....
15KVA
480-240/120V
.... 60Hz,1PH MCC ....
FIELD
80A DESCRIPTION 88KA-1 88KA-3 BATTERY GENERATOR EXCITATION
23WM-1 SPARE
PEECC PEECC WATER MIST CHARGER BREAKER COMPARTMENT
HVAC #1 HVAC #3 MODULE SPACE #1 COMPARTMENT PANELBOARD
HEATER SHEET 8 POWER
7.5kW DISTRIBUTION

F DC

B 5A 27
MC-1A ALARM C B
240/120V, 100A, 1Ø, 60Hz PANELBOARD 10KAIC

SIZE
C

D
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) (13) (14) (15) (16) BRKR NO.
20 20 20 20 20 20 20 20 20 20 20 20 20 30 20 20

DWG NO
5A

138T4962
MCC
FIELD

DESCRIPTION GPP COMPARTMENT COMPARTMENT 20TW-1,3 WATER MIST WATER MIST GAS AUX GAS AUX 96TD-1A 96TD-1B 96TD-1C GNAC SPARE SPARE 96FM-4 MKVIe GHM 23CR-1
LIGHTS, RECEPTACLE LIGHTS CONVENIENCE WATER WASH FIRE 88WM-1, MONITORING MONITORING SPACE CORIOLIS CONTROL PANEL CRANKING
& SPACE HEATER RECEPTACLES SOLENOID PROTECTION LIGHTS & PANEL PANEL LIGHT & HEATERS FLOW METER POWER MOTOR
VALVES PANEL RECEPTACLES CONTROL HEATER 23HG-20 TRANSMITTER HEATER
1&3 POWER
F F GAMP GAMP GHM

SH
6
(17) (18+19) (20) (21) (22) (23) (24) (25) (26) (27) (28) (29) (30) BRKR NO.

REV
20 60 20 20 20 20 20 20 20 20 20 20 20

C
A MCC
FIELD

DESCRIPTION SPARE INLET PEECC PEECC RECEPTACLE FOR PEECC PEECC NOVEC 1230 SPARE SPARE SPARE SPARE SPARE
COMPARTMENT LIGHTS CONVENIENCE NETWORK BATTERY SMOKE FIRE
(LIGHTS,
RECEPTACLES,
RECEPTACLES SWITCH B AREA TEMP.
CONTROL FAN
DETECTORS PROTECTION
SYSTEM
GE CLASS II (INTERNAL NON - CRITICAL)
34TF-1,88MH-1) C COPYRIGHT "2021" GE POWER (USA), LLC AND/OR ITS AFFILIATES. SIZE CAGE CODE DWG NO
All rights reserved. The information contained herein is GE Power Generator Proprietary Technical Information GE POWER & WATER GENERAL ELECTRIC COMPANY
T
D
Schenectady, NY - USA

138T4962
that belongs to the General Electric Company, GE Power (USA), LLC and/or their affiliates, which has been
provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive
such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or DRAWN LEON, EDGAR

DISTR
TO
other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by
the General Electric Company, GE Power (USA), LLC and/or its affiliates. ISSUED SEE PLM SCALE SHEET 6

8 7 6 5 4 3 2 1
....

....

....

....

....

....
.....

.....
FOLD

FOLD
FOLD

GE Non-Public- (Class II) - NLR


Doc Name : 138T4962 Rev C Released Date : 2021/10/26 Page 7 of 9

FOLD
8 7 6 5 4 3 1

FOLD

FOLD
SIZE DWG NO SH REV

.....

.....
D 138T4962

....

....

....

....

....

....
7 C

FROM
CUSTOMER'S
LOW VOLTAGE AC DISTRIBUTION
480V 3Ø SUPPLY MCC2-AC

CUSTOMER
GE

D D

480V, 3Ø , 60Hz, 1200A, MOTOR CONTROL CENTER 65KAIC (L1,L2,L3,G)

C C C

50 50 150 400 15 15 15 70

1 1
2 2 4 5 F R 1 1 3

C
27
C
MC
-2

MCC
C FIELD

20 20 60 200 0.5 5 1.5 30


HP HP HP HP HP HP HP HP
23BT-2 23HQ-1 23QA-1 23TK-2 23VG-2 23VL-2 23AC-1B
120W 75W 75W 250W 60W 30W XXW

C DESCRIPTION ALARM 88BT-2 88HQ-1 88QA-1 88TK-2 88TM-1 88VG-2 LOAD 88VL-2 GAS 88AC-1B
C
TURBINE HYDRAULIC AUXILIARY TURBINE TORQUE/ COMPT COMPT TURBINE AIR INLET
COMPT PUMP LUBE PUMP SHELL EXHAUST SPEED COOLING AIR VENTILATION AVAPORATIVE
COOLING MOTOR #1 MOTOR #1 FRAME BLOWER ADJUSTER FAN #2 FAN #2 COOLER PUMP
AIR FAN #2 MOTOR #2 DRIVE MOTOR MOTOR #2
GV T

.... ....

FOLD FOLD
..... .....

.... C C C C ....
C
(5) (4) (3) (2) (1)
35 35 25 60 30 15 40 15 40 15

C C

1 2 1 2 1

B B
MCC
FIELD

SIZE
D
DWG NO
6.75kW 20kW 3.6kW 20kW 3.6kW

138T4962
DESCRIPTION 88KA-2 88KA-4 PURAFIL BATTERY SPARE
PEECC PEECC 23HG-1,3,5 23HA-2 23HA-3 23HT-2 23HT-3
POSSITIVE CHARGER GENERATOR ACCESORY COMPT SPACE HTR TURBINE COMPT (88HT-1B)
HVAC #2 HVAC #4 PRESSURIZATION #2 SPACE SPACE HEATER ACCESS COMPT SPACE HEATER TURBINE COMPT
UNIT HEATER #1, 2, 3 HUMIDITY HUMIDITY
SHEET 8 CONTROL #3 CONTROL #3
1 PH 1

DC

SH
7
REV
C
A

GE CLASS II (INTERNAL NON - CRITICAL)


C COPYRIGHT "2021" GE POWER (USA), LLC AND/OR ITS AFFILIATES. SIZE CAGE CODE DWG NO
All rights reserved. The information contained herein is GE Power Generator Proprietary Technical Information GE POWER & WATER GENERAL ELECTRIC COMPANY

D
Schenectady, NY - USA

138T4962
that belongs to the General Electric Company, GE Power (USA), LLC and/or their affiliates, which has been
provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive
such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or DRAWN LEON, EDGAR

DISTR
TO
other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by
the General Electric Company, GE Power (USA), LLC and/or its affiliates. ISSUED SEE PLM SCALE SHEET 7

8 7 6 5 4 3 2 1
....

....

....

....

....

....
.....

.....
FOLD

FOLD
FOLD

GE Non-Public- (Class II) - NLR


Doc Name : 138T4962 Rev C Released Date : 2021/10/26 Page 8 of 9

FOLD
8 7 6 5 4 3 1

FOLD

FOLD
SIZE DWG NO SH REV

.....

.....
D 138T4962

....

....

....

....

....

....
8 C

DC LOW VOLTAGE DC DISTRIBUTION SYSTEM/PANEL DC

ALARM 23
TST-BC
SCR BATTERY
40A CHARGER #1
FROM MCC1-AC DC
SHEET 6 100A
C ~ = V1

D MINOR ALARM D
MAJOR ALARM DC
ELECTRONIC
MIMIC CURRENT
DISPLAY SHARING 64

SRC BATTERY C
40A CHARGER #2
FROM MCC2-AC 125VDC PANELBOARD, 10KA, SCCR
SHEET 7
C
~ = 100A (1) (2) (3) (4) (5) (6) (7) (8) (9) (10)
BKR NO.
100 16 16 20 20 32 32 32 32 20 20
MINOR ALARM
MAJOR ALARM 27 DC
MIMIC QE
DISPLAY 27F

CB1
ALARM AUX
DC BUS
ALARM
DC FIRE
PROTECTION
150A ALARM

27MC-1A
C

125V DC STATUS DC
NI-CAD (ALARM)
C BATTERY
630Ah 7.5
FIELD C
HP
C
88QE-1 DESCRIPTION 45FTX STANDBY GP2100e GP2100e EX2100e MKVIe GENERATOR GENERATOR DIGITAL VALVE EXCITATION
V2
EMERGENCY FIRE PROTECTION RELAY LIGHTS GENERATOR GENERATOR EXCITER TURBINE BREAKER BREAKER CONTROLLER TRANSFORMER
LUBE OIL PROTECTION PANEL PROTECTION PANEL CONTROL CONTROL TRIP COIL #1 TRIP COIL #2 63PTX
DC CLOSE COIL
PUMP SUPPLY #1 SUPPLY #2 POWER PANEL JB 131A CONTROL
GV CONTROL CHARGING POWER
MOTOR DC
POWER
GPP EX ET

.... ....

FOLD
20 20 20 FOLD
..... .....

.... ....
3 X 20A 24V DC POWER SUPPLY
(N+1 REDUNDANCY)

ALARM

24VDC PANELBOARD, 10KA, SCCR DC

(1) (2) (3) (4) (5) (6) (7) (8) (9) FUSE NO.

B 6 6 6 6 6 6 6 6 6 B

SIZE
D
DWG NO
138T4962
DC
FIELD

DESCRIPTION GAS MODULE GAS MODULE


TURBINE COMPT TURBINE COMPT SPARE TURBINE COMPT TURBINE COMPT SPARE HAZGAS HAZGAS SPARE
HAZGAS HAZGAS HAZGAS HAZGAS

SH
MONITORING MONITORING

8
MONITORING MONITORING MONITORING MONITORING 45HA-IR-9A 45HA-IR-9B
45HT-IR-1A 45HT-IR-1B 45HT-IR-2A 45HT-IR-2B 96GDHA-FT-9A 96GDHA-FT-9B
96GDHT-FT-1A 96GDHT-FT-1B 96GDHT-FT-2A 96GDHT-FT-2B

REV
C
GV GV

GE CLASS II (INTERNAL NON - CRITICAL)


C COPYRIGHT "2021" GE POWER (USA), LLC AND/OR ITS AFFILIATES. SIZE CAGE CODE DWG NO
All rights reserved. The information contained herein is GE Power Generator Proprietary Technical Information GE POWER & WATER GENERAL ELECTRIC COMPANY

D
Schenectady, NY - USA

138T4962
that belongs to the General Electric Company, GE Power (USA), LLC and/or their affiliates, which has been
provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive
such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or DRAWN LEON, EDGAR

DISTR
TO
other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by
the General Electric Company, GE Power (USA), LLC and/or its affiliates. ISSUED SEE PLM SCALE SHEET 8

8 7 6 5 4 3 2 1
....

....

....

....

....

....
.....

.....
FOLD

FOLD
FOLD

GE Non-Public- (Class II) - NLR


Doc Name : 138T4962 Rev C Released Date : 2021/10/26 Page 9 of 9

FOLD
8 7 6 5 4 3 1

FOLD

FOLD
SIZE DWG NO SH REV

.....

.....
D 138T4962

....

....

....

....

....

....
9 C
REVISIONS
REV DESCRIPTION DATE APPROVED

MISCELLANEOUS PANELS A SHEET 1:


1. REMOVED WN, APU, BC, CFD AND DF EQUIPMENT
LOCATION KEY.
2. ADDED FIRST MADE FOR:GG10792, GG10793, GG10974.
SHEET 2:
CUSTOMER 1.GENERAL CHANGES.
120VAC SHEET 3:
UPS /
FROM MCC1E-AC 1.GENERAL CHANGES.
D (2 HOURS) SHEET 6
SHEET 4: D
1.GENERAL CHANGES.
SHEET 5:
1.GENERAL CHANGES.
SHEET 6:
60
1.GENERAL CHANGES.
SHEET 7:
1.GENERAL CHANGES.
150 SHEET 8:
C C 1. GENERAL CHANGES.
GAS AUX
MKVIe (1) (2) MONITORING PANEL GAMP HVAC #1 HVAC #2 SHEET 9:
(1800W) (278W) SEE PLM
30 20 35 35 1. GENERAL CHANGES. 29-04-21
GAS HMI + NETWORK A C
(3) (4)
CHROMATOGRAPH EQUIP RECEP C B SHEET 2:
(80W) 20 20 (960W) HVAC #3 PURAFIL POSITIVE 1. ADDED TERMINATION POINT.
GT ENCLOSURE (5) (6) 35 25 PRESSURIZATION UNIT 2. ROTATED GCBC 90 DEGREE.
SPARE SHEET 6:
LIGHTS (450W) 20 20
(7) (8)
1.GENERAL CHANGES.
SPARE SPARE SHEET 7:
20 20 1.CHANGED DESCRIPTION.
(9) (10) SHEET 4:
SPARE SPARE
20 20 40 1.CHANGED DESCRIPTION.
(11) (12) 480V, 3Ø SHEET 5:
SPARE SPARE 225A, 65kA 1. CHANGED DESCRIPTION. 10-06-21 SEE PLM
20 20
PANELBOARD C SHEET 1:
1Ø, 60Hz, 2W 1. UPDATED NOTE 4.
120V SHEET 2:
C PANELBOARD
125A, 10kA
SEE MLI 4108 FOR ANY
ADDITIONAL UPS LOADS
10kVA 1.UPDATED L & L2 LINE. C
ASSOCIATED WITH THE 480-240/120V SHEET 5:
COMMUNICATION NETWORK 1.ADDED 63PTX.
60 SHEET 6:
1. GENERAL CHANGES.
UPS PANELBOARD (1) (2)
SHEET 7:
EX FAN 1 FAN 2 EX 1.GENERAL CHANGES.
20 20 SHEET 8:
(3) (4) COMPARTMENT 1.GENERAL CHANGES.
EX FAN 3 SHEET 9:
20 20 LIGHTS
.... 1.UPDATED EXCITATION PANELBOARD. 18-10-21 SEE PLM ....
COMPARTMENT (5) (6)
NOVEC 1230
FOLD RECEPTACLES 20 20 FOLD
..... .....
(7) (8) LIGHTS &
EX EXCITER CONTROL RECEPTACLES
EX
.... POWER 20 20 ....
(9) (10) EXCITATION
SPARE TRANSFORMER ET
20 20 SPACE HEATER
(11) (12)
SPARE SPARE
20 20
FROM
4160V
SUPPLY 1Ø, 60Hz, 3W
/ 120/240V
PANELBOARD
125A, 10kA
B MOTOR CONTROLLER
(VACUUM LIMIT AMP)
RUNNING STATUS
RUN B
STOP
52CR ALARM & TERMINATE EXCITATION COMPARTMENT PANELBOARD
PROTECTION START

SIZE
D
ALARM

DWG NO
120V AC
SHEET 6

138T4962
FROM CUSTOMER
480V SUPPLY

WW
ONE SKID FOR (3) GT'S
CUSTOMER
FIELD

800 23CR-1
HP
RTD
800W WATER WASH SKID

SH
88CR-1

9
STARTING
MOTOR

REV
C
88TW-1 PUMP MOTOR
23TW-1 PUMP MOTOR HEATER
88WS-1 SKID SPACE HEATER BLOWER MOTOR
A 23WS-1
23WK-1
MODULE SPACE HEATER
INMERSION HEATER
23WK-2 INMERSION HEATER

REFERENCE MLI E025 AND MLI 0414 FOR SKID DRAWINGS AND LOAD DETAILS.
GE CLASS II (INTERNAL NON - CRITICAL)
C COPYRIGHT "2021" GE POWER (USA), LLC AND/OR ITS AFFILIATES. SIZE CAGE CODE DWG NO
All rights reserved. The information contained herein is GE Power Generator Proprietary Technical Information GE POWER & WATER GENERAL ELECTRIC COMPANY

D
Schenectady, NY - USA

138T4962
that belongs to the General Electric Company, GE Power (USA), LLC and/or their affiliates, which has been
provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive
such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or DRAWN LEON, EDGAR

DISTR
TO
other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by
the General Electric Company, GE Power (USA), LLC and/or its affiliates. ISSUED SEE PLM SCALE SHEET 9

8 7 6 5 4 3 2 1
....

....

....

....

....

....
.....

.....
FOLD

FOLD
FOLD

GE Non-Public- (Class II) - NLR