You are on page 1of 33

1 2 3 4 5 6 7 8

A A
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

B B

C C

This Drawing Valid For :


01 14/03/2019 WD As Manufactured
1. X4024122-302 : SORONG-11kV
D
- OUTGOING FEEDER TO TRAFO GT1 00 11/08/2018 AF First Issued
D
- OUTGOING FEEDER TO TRAFO GT2 Rev N° Date Name Modification

- OUTGOING FEEDER TO TRAFO GT3 Project Name

SLD drw no : X4024122-201 PAPUA DFE PROJECT


2. X4024122-302 : MERAUKE 1-11kV 11kV
- OUTGOING FEEDER TO TRAFO GT1 Owner PT. PLN (Persero) Order N° C2030-4024122
SLD drw no : X4024122-203 Client Switchboard
PT. PP (Persero) Tbk 17kV Switchgear
E 3. X4024122-302 : MERAUKE 2-11kV E
Project Ref. Panel =Outgoing Trafo
- OUTGOING FEEDER TO TRAFO GT1 Title
PLOT 4B1-4B2 CIKARANG SELATAN
SLD drw no : X4024122-204 East Jakarta Industrial Park (EJIP)
COVER SHEET
Schematic Diagram
Bekasi - 17550, Indonesia
Outgoing Trafo
Phone - (62-21) 897 02 03
PT. SCHNEIDER INDONESIA Fax - (62-21) 897 02 09
Date Name Sign Drawing Nr. X4024122-302
F Drawn 11/08/2018 AF Customer Doc. Nr. A01 F

Checked 11/08/2018 AYH Document Type A Sheet 1


11/08/2018

Approved 11/08/2018 DTA Format A3 Scale 33 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

CONTROL AND MONITORING


FUNCTION LOCAL LOCAL CONTROL REMOTE CONTROL REMARKS

CONTROL -Q51,-Q30 -Q51 -Q51

STATUS SIGNAL -Q30


BB1

Metering -P50 (PM8240) (V,A,Hz,PF,kW)

B B
PROTECTION -F51 (VAMP 57,50+51+50N+51N+67+67N+25) -Q51
M

CONTROL AND MONITORING

TECHNICAL SWITCH DATA


DESIGNATION MANUFACT. TYPE NOMINAL CURRENT BREAKING CURRENT REMARKS

C -Q51 SCHNEIDER HVX 15-40-20E 40kA 2000A FOR TIMIKA, MERAUKE 1&2 C
-Q30 SCHNEIDER CB: HVX 15-40-12E
-F30L1-3 EFEN HSW 1.4 A FOR SORONG
CB: HVX 15-40-25E (GT 1)
C1L1-3
CB: HVX 15-40-31E (GT 2) XXXX

CB: HVX 15-40-20E (GT 3)


-Q30 -H101

-T61L1-3

-F30L1-3
TECHNICAL TRANSFORMER DATA
D P1 D
DESIGNATION MANUFACT. TYPE RATIO CORE DATA REMARKS -T51L1-3
Protection & Measurement P2
-T51L1 TRAFINDO CTB-24-D2 2000/1-1-1-1 A Cls.X; Cls.X; Cls. 5P20, 15VA; Cls 0.5, 15VA FOR TIMIKA, MERAUKE 1&2 CT*):1250A/1-1-1-1A
-T51L2 TRAFINDO CTB-24-D2 2000/1-1-1-1 A Cls.X; Cls.X; Cls. 5P20, 15VA; Cls 0.5, 15VA FOR SORONG CT : 2500/1-1-1-1A (GT1)
FOR SORONG CT : 3150/1-1-1-1A (GT2)
-T51L3 TRAFINDO CTB-24-D2 2000/1-1-1-1 A Cls.X; Cls.X; Cls. 5P20, 15VA; Cls 0.5, 15VA FOR SORONG CT : 2000/1-1-1-1A (GT3)

-T61L1 TRAFINDO VTB-24 11kV/√3 : 110V/√3 : 110V/√3 Cls 0.5, 30VA ; Cls 3P, 30VA Protection & Measurement
-T61L2 TRAFINDO VTB-24 11kV/√3 : 110V/√3 : 110V/√3 Cls 0.5, 30VA ; Cls 3P, 30VA
-T61L3 TRAFINDO VTB-24 11kV/√3 : 110V/√3 : 110V/√3 Cls 0.5, 30VA ; Cls 3P, 30VA

E E
11/08/2018

F F

Date 11/08/2018 Project Name Title Technical Data Drawing Nr. =Outgoing Trafo A
01 As Manufactured 14/03/2019 WD Drawn AF
PAPUA DFE PROJECT Schematic Diagram
X4024122-302 A02
00 First Issued 11/08/2018 AF Checked AYH 11kV Outgoing Trafo Customer Doc. Nr. Sheet 2
Rev N° Modification Date Name Approved DTA Order N° C2030-4024122 Switchboard 17kV Switchgear PT. SCHNEIDER INDONESIA 33 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Revision N° Document Identification


Customer Document Number Drawing Number Sheet Description
Type Designation Sheet name
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

X4024122-302 00 01 A =Outgoing Trafo A01 1 COVER SHEET Schematic Diagram Outgoing Trafo
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

X4024122-302 00 01 A =Outgoing Trafo A02 2 Technical Data Schematic Diagram Outgoing Trafo
X4024122-302 00 01 B =Outgoing Trafo B01 3 LIST OF CONTENT Schematic Diagram Outgoing Trafo
X4024122-302 00 01 B =Outgoing Trafo C01 4 Legend Schematic Diagram Outgoing Trafo
X4024122-302 00 01 S =Outgoing Trafo D01 5 AC/DC Supply Schematic Diagram Outgoing Trafo
X4024122-302 00 01 S =Outgoing Trafo G01 6 Digital Inputs Schematic Diagram Outgoing Trafo
X4024122-302 00 01 S =Outgoing Trafo M01 7 Closing Circuit Schematic Diagram Outgoing Trafo
X4024122-302 00 01 S =Outgoing Trafo M02 8 Tripping Circuit Schematic Diagram Outgoing Trafo

B X4024122-302 00 01 S =Outgoing Trafo Q01 9 Local Control Indication Schematic Diagram Outgoing Trafo B
X4024122-302 00 01 S =Outgoing Trafo Q02 10 Spare Contacts Schematic Diagram Outgoing Trafo
X4024122-302 00 01 S =Outgoing Trafo Q03 11 Aux. Contacts Spare Schematic Diagram Outgoing Trafo
X4024122-302 00 01 S =Outgoing Trafo Q04 12 Aux. Contacts Spare Schematic Diagram Outgoing Trafo
X4024122-302 00 01 S =Outgoing Trafo Q05 13 Communication Schematic Diagram Outgoing Trafo
X4024122-302 00 01 S =Outgoing Trafo S01 14 Current Circuit Schematic Diagram Outgoing Trafo
X4024122-302 00 01 S =Outgoing Trafo S02 15 Current Circuit Schematic Diagram Outgoing Trafo
X4024122-302 00 01 S =Outgoing Trafo T01 16 Voltage Circuit Schematic Diagram Outgoing Trafo
X4024122-302 00 01 V =Outgoing Trafo V01 17 TERMINAL PLAN Schematic Diagram Outgoing Trafo
C C
X4024122-302 00 01 V =Outgoing Trafo V02 18 TERMINAL PLAN Schematic Diagram Outgoing Trafo
X4024122-302 00 01 V =Outgoing Trafo V03 19 TERMINAL PLAN Schematic Diagram Outgoing Trafo
X4024122-302 00 01 V =Outgoing Trafo V04 20 TERMINAL PLAN Schematic Diagram Outgoing Trafo
X4024122-302 00 01 V =Outgoing Trafo V05 21 TERMINAL PLAN Schematic Diagram Outgoing Trafo
X4024122-302 00 01 V =Outgoing Trafo V05.1 22 TERMINAL PLAN Schematic Diagram Outgoing Trafo
X4024122-302 00 01 V =Outgoing Trafo V05.2 23 Current Circuit Schematic Diagram Outgoing Trafo
X4024122-302 00 01 V =Outgoing Trafo V06 24 TERMINAL PLAN Schematic Diagram Outgoing Trafo
X4024122-302 00 01 V =Outgoing Trafo V07 25 TERMINAL PLAN Schematic Diagram Outgoing Trafo
D X4024122-302 00 01 V =Outgoing Trafo V08 26 TERMINAL PLAN Schematic Diagram Outgoing Trafo D

X4024122-302 00 01 V =Outgoing Trafo V09 27 TERMINAL PLAN Schematic Diagram Outgoing Trafo
X4024122-302 00 01 Y =Outgoing Trafo X01 28 LV Door Layout Schematic Diagram Outgoing Trafo
X4024122-302 00 01 Y =Outgoing Trafo X02 29 LV Box Layout Schematic Diagram Outgoing Trafo
X4024122-302 00 01 Y =Outgoing Trafo X03 30 LV Door Layout Schematic Diagram Outgoing Trafo
X4024122-302 00 01 Y =Outgoing Trafo X04 31 LV Box Layout Schematic Diagram Outgoing Trafo
X4024122-302 00 01 V =Outgoing Trafo Y01 32 BILL OF MATERIALS Schematic Diagram Outgoing Trafo
X4024122-302 00 01 V =Outgoing Trafo Y02 33 BILL OF MATERIALS Schematic Diagram Outgoing Trafo

E E
11/08/2018

F F

Date 11/08/2018 Project Name Title LIST OF CONTENT Drawing Nr. =Outgoing Trafo B
01 As Manufactured 14/03/2019 WD Drawn AF
PAPUA DFE PROJECT Schematic Diagram
X4024122-302 B01
00 First Issued 11/08/2018 AF Checked AYH 11kV Outgoing Trafo Customer Doc. Nr. Sheet 3
Rev N° Modification Date Name Approved DTA Order N° C2030-4024122 Switchboard 17kV Switchgear PT. SCHNEIDER INDONESIA 33 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SWITCHES
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A Description Symbol Designation Symbol Designation Symbol Designation Symbol A


All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

NORMALLY CLOSE RESISTOR SEMAPHORE


THERMOSTAT ( NC ) CONTACT Voltage Dependent INDICATOR
U

IEC S00264 IEC S00229 IEC S00558 IEC S00968

CHANGE-OVER
CIRCUIT BREAKER BREAK BEFORE
MAKE CONTACT MINIATURE CIRCUIT BREAKER (MCB) TRANSFORMER
B Description Symbol Description Symbol B
IEC S00287 IEC S00230

MANUAL
1

AUTO
CURRENT P1 P2
LOCAL REMOTE ON
SWITCH DELAY CONTACT TRANSFORMER
2
S1 S2
MINIATURE CIRCUIT
IEC S00480 IEC S00243 BREAKER IEC S00842

ACCESSORIES
OF SD/OF
CLOSE

MINIATURE CIRCUIT
OPEN

A N
OFF BREAKER VOLTAGE
CB CONTROL

92
94
12
14
DELAY CONTACT TRANSFORMER PE
SWITCH
a1 n1 a2 n2

11

91
C IEC S00272 IEC S00244 IEC S00265 IEC S00842 C
OFF

2
3
4
5
1

RELAY COIL
MULTI STEP OFF
GROUNDING FUSE

IEC S00272 IEC S00305


Description Symbol Description Symbol

EMERGENCY FUSE
TIMER
STOP DISCONNECTOR
RELAY COIL

IEC S00258 IEC S00312 IEC S00369


D EARTHING D
EARTHING SWITCH

S1:1

S1:3

S1:5

S1:7
POSITION
PUSH BUTTON SWITCH
DISCONNECTOR
SEMICONDUCTOR

S1:2

S1:4

S1:6

S1:8
IEC S00254 Description Symbol IEC S00200 IEC S00370

FUSE
RESISTOR
CONTACT AND CONTACTORS LAMP AND INDICATION
Description Symbol IEC S00555
Description Symbol IEC S00362
E E
1
NORMALLY OPEN LAMP INDICATION
FOR Position switch RESISTOR
ADJUSTABLE ARRESTER
2
IEC S00259 IEC S00555 IEC S00965 Description Symbol

NORMALLY OPEN CAPACITIVE 1


HORN SURGE
( NO ) CONTACT DIVIDER ARRESTER
C 2
11/08/2018

IEC S00227 IEC S00567 IEC S00969 IEC S00371


F F

Date 11/08/2018 Project Name Title Legend Drawing Nr. =Outgoing Trafo B
01 As Manufactured 14/03/2019 WD Drawn AF
PAPUA DFE PROJECT Schematic Diagram
X4024122-302 C01
00 First Issued 11/08/2018 AF Checked AYH 11kV Outgoing Trafo Customer Doc. Nr. Sheet 4
Rev N° Modification Date Name Approved DTA Order N° C2030-4024122 Switchboard 17kV Switchgear PT. SCHNEIDER INDONESIA 33 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

HEATER SPACE LV BOX MOTOR DRIVE TRIPPING CIRCUIT CONTROL CIRCUIT


ON HEATER LIGHTING
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

+S1.B +S1.B
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A -X11 1 220V AC SUPPLY (P) -X11 2 A


All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

P
+S1.B +S1.B
-X11 3 N 220V AC SUPPLY (N) -X11 4
PREVIOUS +S1.B +S1.B NEXT
CUBICLE -X21 1 L+ 110V DC SUPPLY (L+) -X21 2 CUBICLE
+S1.B +S1.B
-X21 3 L- 110V DC SUPPLY (L-) -X21 4

B B

1 3 1 3 1 3 1 3
+S1.B +S1.B +S1.B +S1.B
-Q921 -Q922 -Q923 -Q924
2P, 6A 2P, 6A 2P, 6A 2P, 6A
2 4 2 4 2 4 2 4
-Q921.1 -Q922.1 -Q923.1 -Q924.1
OF /Q04.C1 OF /Q04.C2 OF /Q04.C2 OF /Q04.C3
SD /Q04.C3 SD /Q04.C4 SD /Q04.C4 SD /Q04.C4
C C

1 1

-B21 >ϑ +S1.B


-S34 2
c

D D

+S1.B
-X1 3

CS+
TR+

CS-
TR-
M+
M-

1 1
X1 +S4
-H18 +S1.B
-R11 -H17
LED
/M01.E1

/M01.C1

/G01.E1

/G01.A1

/M01.E1

/M01.A1
E GREEN 2 FL 2 E
X2
HEATER ON

+S1.B
-X1 -X1 6
5
11/08/2018

F F

Date 11/08/2018 Project Name Title AC/DC Supply Drawing Nr. =Outgoing Trafo S
01 As Manufactured 14/03/2019 WD Drawn AF
PAPUA DFE PROJECT Schematic Diagram
X4024122-302 D01
00 First Issued 11/08/2018 AF Checked AYH 11kV Outgoing Trafo Customer Doc. Nr. Sheet 5
Rev N° Modification Date Name Approved DTA Order N° C2030-4024122 Switchboard 17kV Switchgear PT. SCHNEIDER INDONESIA 33 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

CB STATUS ES POSITION SPARE


OPEN CLOSE CLOSE
CB TEST POSITION
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

+S1.B
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A -X2 9 A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

TR+ TR+
/D01.E5 /M02.A1

-X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5
B 5 130 131 30 52 114 115 118 119 120 124 125 126 B

+S4 3F +S4 1F
-X041 -X052
X01:A12 3M 1M

13 5 S1:3 1
+S4
-Q51 S11 +S4
C /S01.B1 14 6
-Q30 -ST3 C
/S02.C8 S1:4 2

X01:A13 X01:A14 +S4 +S4


-X041 4M -X052 2M

4F 2F

-X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5
D 6 7 134 135 31 53 116 117 121 122 123 127 128 129 D

-F50 X4:7 -F50 X4:9 -F50 X4:11 -F50 X4:13 -F50 -F50 -F50 X5:2 X5:3 X5:4 -F50 X5:6 X5:7 X5:8

X4:16 X4:17 X4:19 X4:20


DI3 DI4 DI5 DI6 DI7 DI8 DI9 DI10 DI11 DI12 DI13 DI14 14 DI15 DI16
/M02.F3 /M02.F3
/M02.E3 /M02.E3 /M02.E3 /M02.E3 /M02.E3 /M02.E3
X4:15 X4:18

E X4:8 X4:10 X4:12 X4:14 X5:1 X5:5 E

TR-
/D01.E5 /M02.E1
11/08/2018

F F

Date 11/08/2018 Project Name Title Digital Inputs Drawing Nr. =Outgoing Trafo S
01 As Manufactured 14/03/2019 WD Drawn AF
PAPUA DFE PROJECT Schematic Diagram
X4024122-302 G01
00 First Issued 11/08/2018 AF Checked AYH 11kV Outgoing Trafo Customer Doc. Nr. Sheet 6
Rev N° Modification Date Name Approved DTA Order N° C2030-4024122 Switchboard 17kV Switchgear PT. SCHNEIDER INDONESIA 33 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SPRING CHARGE CB CLOSE MEASUREMENT


MOTOR LOCAL REMOTE PERMISSIVE CLOSE POWER SUPPLY
+S1.B
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

CS+ -X2 15 CS+


/D01.E6 /Q01.A1
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

1 3
+S1.D

R
L
-S650 +S1.D -F50 X5:12
/M01.B2 /M01.B2
-S650 -S650
1st /M01.B3 2 4 T6
2nd /M01.B4
/M02.E2
3rd /M02.B2
4th /M02.B3 -X5
5th 1 X5:11
B 6th -F50 X3:17 B
3
+S1.D

Close From
N
C
T
T1

Remote
-S601 /M01.B2 .
/M02.E2
-S601 4
1st /M01.B3 74
2nd /M02.B2 -X5 X3:16 1 5

2 -K86
/M02.E7
9

-X5
C M+ 79 C
/D01.E4
SPARE
+S1.B
-X2 1
FOR INTERLOCK
-X5
80

X01:A1

U1
D -X2 D
M1 M
11
U2
+S1.D
-P50 L1
X01:A2 X01:A5
Vaux.
Supply

L2
+S1.B
-X2 2

C1
F2 CC
M- /S01.C1 C2
/D01.E4
X01:A6 G
E E

/S02.E7
CS- -X2 CS-
/D01.E6 /Q01.E1
12

LEGEND OF HVX CB
Wiring Diagram Doc. No. : AGS553252-01 Rev. 03
F2 : Closing Release Coil
F11 : Opening Release Coil
M1 : Motor for Spring Charging
S2 : Motor Mechanism Aux. Switch
S11/12 : CB Auxiliary Contact
11/08/2018

S41/42 : Push button On/Off on CB


F F

Date 11/08/2018 Project Name Title Closing Circuit Drawing Nr. =Outgoing Trafo S
01 As Manufactured 14/03/2019 WD Drawn AF
PAPUA DFE PROJECT Schematic Diagram
X4024122-302 M01
00 First Issued 11/08/2018 AF Checked AYH 11kV Outgoing Trafo Customer Doc. Nr. Sheet 7
Rev N° Modification Date Name Approved DTA Order N° C2030-4024122 Switchboard 17kV Switchgear PT. SCHNEIDER INDONESIA 33 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

PROTECTION RELAY CB OPEN OPEN COMMAND 50, 51 50, 51 50N, 51N 74 - TRIP CIRCUIT 50, 51 50BF
SUPPLY VAMP 57 LOCAL REMOTE FROM EXT TRIP LOCKOUT TRIP TRIP SUPERVISION TRIP LOCKOUT TRIP
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A -X2 A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

TR+
/G01.A8
10

5 7

R
L
+S1.D +S1.D
/M01.B2 /M01.B2
-S650 -S650
6 8

1 -X5 -X5 -X5 -X5 -X5


B B

N
C
T
+S1.D 3 77 108 110 112
/M01.C2
-S601 -F50 X3:15 -F50 X3:13 -F50 X3:4 -F50 X3:6 -F50 X5:14 -F50 X3:11

TRIP FROM EXTERNAL

TRIP FROM EXTERNAL

TRIP FROM EXTERNAL


2
2 6 DI1 1 DI2 2

OPEN FROM
T2 T3 T5 T4

EXTERNAL
REMOTE
. . . . . -K86 /M02.E2 /M02.E2 /M02.E2 /M02.E2
/M02.E7 /M02.E3 /M02.E3
10

X3:14 X3:12 X3:3 X3:5 X5:13 X3:10


-X5 -X5 -X5 -X5 -X5
4 78 109 111 113

C C

-X2 -X2
4 6
-F50 X2:1
L/~
X01:D11 D12 A3

Vaux.
Supply 13 1
D GND -Q51 S12 S11 D
/S01.C1 14 2
N/~
X2:2 2
C1 13
-K86 +S1.B
F11 OC
/S02.E7

RXM -K50BF
C2
110VDC
14
A4 1

TR- -X2
/G01.E8
5
ASSIGNMENT -F50 ASSIGNMENT -F50 -K86 -K50BF
A1 /Q03.C1 DI 1 /M02.B6 1st /M01.C5 a 3-7
/Q03.C4
E SF /Q03.C2 DI 2 /M02.B7 2nd /M02.B5 b 3-11 E
T1 /M01.B5 DI 3 /G01.E2 3rd /Q03.C3 a 4-8
/Q03.C5
T2 /M02.B5 DI 4 /G01.E2 4th /Q03.C3 b 4-12
T3 /M02.B6 DI 5 /G01.E3 a 5-9
/Q03.C5
T4 /M02.B8 DI 6 /G01.E3 b 5-13
T5 /M02.B7 DI 7~8 /G01.E3 a 6-10
/Q03.C5
T6 /M01.B5 DI 9~10 /G01.E5 b 6-14
T7 /Q03.C2 DI 11~13 /G01.E6 AUX. CONTACT
DIGITAL OUTPUT DI 14~16 /G01.E7
DIGITAL INPUT
11/08/2018

F F

Date 11/08/2018 Project Name Title Tripping Circuit Drawing Nr. =Outgoing Trafo S
01 As Manufactured 14/03/2019 WD Drawn AF
PAPUA DFE PROJECT Schematic Diagram
X4024122-302 M02
00 First Issued 11/08/2018 AF Checked AYH 11kV Outgoing Trafo Customer Doc. Nr. Sheet 8
Rev N° Modification Date Name Approved DTA Order N° C2030-4024122 Switchboard 17kV Switchgear PT. SCHNEIDER INDONESIA 33 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

CB OPEN CB CLOSE ES CLOSE CB TEST CB SERVICE

+S1.B
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

CS+ -X2 16
/M01.A8
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

B B

-X5 -X5 -X5


34 38 56

+S4 7F +S4 3F +S4 5F


-X041 -X051 -X052
X01:B2 7M 3M 5M

9 1
S1:7 1 1
-Q51 S12 +S4
+S4 +S4
C /S01.B1 10 2 -Q30 -ST2 -SS3 C
/S02.C8 S1:8 2 2

X01:B3 X01:B4 +S4 +S4 +S4


-X041 8M -X051 4M -X052 6M

8F 4F 6F

+S1.B +S1.B
-X2 19 -X2 20
-X5 -X5 -X5
35 39 57

D D

X1 X1 X1 X1 X1
-H52 -H51 -H30 -HST -HSS
LED LED LED LED LED
RED GREEN AMBER RED GREEN
X2 X2 X2 X2 X2
CB OPEN CB CLOSE ES CLOSE CB TEST CB SERVICE
E E
CS- -X2
/M01.E8
13
11/08/2018

F F

Date 11/08/2018 Project Name Title Local Control Indication Drawing Nr. =Outgoing Trafo S
01 As Manufactured 14/03/2019 WD Drawn AF
PAPUA DFE PROJECT Schematic Diagram
X4024122-302 Q01
00 First Issued 11/08/2018 AF Checked AYH 11kV Outgoing Trafo Customer Doc. Nr. Sheet 9
Rev N° Modification Date Name Approved DTA Order N° C2030-4024122 Switchboard 17kV Switchgear PT. SCHNEIDER INDONESIA 33 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

CIRCUIT BREAKER INSTANTANEOUS SPRING CHARGE CB PLUG IN/OUT CB CHARGE EARTHING SWITCH
AUX. CONTACTS AUX. CONTACT AUX. CONTACTS CB DISCONNECTED AUX. CONTACT
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

-X2 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5
8 8 13 15 17 19 24 26 21 44 32 28 46 48 50
B B

+S4 1F +S4 5F +S4 1F +S4 3F +S4 7F +S4 5F


C -X042 -X041 -X041 -X042 -X042 -X042 C
X01:B7 X01:A15 X01:B5 X01:C9 X01:C11 X01:A10 X01:B15 X01:D15 X01:A7 1M 5M 1M 3M 7M 5M

-Q51 1
S41

END OF CHARGING

END OF CHARGING
DISCONNECTED
3 15 7 11 5 15 2 13 5 11

CB PLUG
S1:9 +S4 S1:5 S1:1 S1:11 S1:13 S1:15
-Q51 S12 -Q51 S11 -Q51 S12 -Q51 S12 -Q51 S12 -Q51 S2 -Q51 -Q51 S2 +S4 +S4 +S4
/S01.B1 4 /S01.B1 16 /S01.B1 12 /S01.B1 6 /S01.C1 16 /S01.C1 14 /S01.C1 6 -Q30 -Q30 -Q30 -Q30 +S4 +S4
8 9 12 /S02.C8
/S02.C8 S1:10 S1:6 /S02.C8 S1:2 /S02.C8 S1:12 -Q30 S1:14 -Q30 S1:16
S11 /S02.C8 /S02.C8
10

X01:B8 X01:A16 X01:B1 X01:B6 X01:C10 X01:C12 X01:A11 X01:B16 X01:D16 X01:A8 X01:A9 +S4 +S4 +S4 +S4 +S4 +S4
-X042 2M -X041 6M -X041 2M -X042 4M -X042 8M -X042 6M

2F 6F 2F 4F 8F 6F
D D

-X2 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5
E 7 9 10 14 16 18 20 25 27 22 23 45 33 29 47 49 51 E

Terminal Block Spare


+S1.B
-X1 -X2 -X5 -X51
-X1 1 -X2 3 -X5 11 -X51 1
-X1 2 14 -X5 12 -X51 2
4 -X5 94 -X51 3
95 4
11/08/2018

F F

Date 11/08/2018 Project Name Title Spare Contacts Drawing Nr. =Outgoing Trafo S
01 As Manufactured 14/03/2019 WD Drawn AF
PAPUA DFE PROJECT Schematic Diagram
X4024122-302 Q02
00 First Issued 11/08/2018 AF Checked AYH 11kV Outgoing Trafo Customer Doc. Nr. Sheet 10
Rev N° Modification Date Name Approved DTA Order N° C2030-4024122 Switchboard 17kV Switchgear PT. SCHNEIDER INDONESIA 33 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
50, 51 50BF
AUX. CONTACT PROTECTION TRIP LOCKOUT TRIP CB TEST POSITION CB SERVICE POSITION
VAMP 57 AUX. CONTACT AUX. CONTACT AUX. CONTACT AUX. CONTACT
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

-X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5
132 85 87 89 90 92 73 75 81 83 36 54 40 58 42

B B

+S4 5F
+S4 +S4 -X051 +S4 +S4
1F 3F 7F 7F
-X051 -X052 5M -X052 -X051
1M 3M 7M 7M

C C
-F50 X3:9 X3:8 -F50 X5:10 -F50 X3:20X3:19
1 1 1 1 1
3 7 4 8 11 7 12 8 13 9 14 10 +S4 +S4 +S4 +S4
A1 T7 SF -SS4 -SS2
-ST1 -ST4 +S4
/M02.F2
-K86 -K86 -K50BF -K50BF -K50BF -K50BF 2 2 -SS1 2 2 2
/M02.E2 /M02.E2 /M02.E7 /M02.E7 /M02.E8 /M02.E8 /M02.E8 /M02.E8
11 12 3 4 5 6

X3:7 X5:9 X3:18 +S4 +S4 +S4 +S4 +S4


-X051 2M -X052 4M -X051 6M -X052 8M -X051 8M

2F 4F 6F 8F 8F

D D

-X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5
E 133 86 88 91 93 74 76 82 84 37 55 41 59 43 E
11/08/2018

F F

Date 11/08/2018 Project Name Title Aux. Contacts Spare Drawing Nr. =Outgoing Trafo S
01 As Manufactured 14/03/2019 WD Drawn AF
PAPUA DFE PROJECT Schematic Diagram
X4024122-302 Q03
00 First Issued 11/08/2018 AF Checked AYH 11kV Outgoing Trafo Customer Doc. Nr. Sheet 11
Rev N° Modification Date Name Approved DTA Order N° C2030-4024122 Switchboard 17kV Switchgear PT. SCHNEIDER INDONESIA 33 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

AC/DC MCB AC/DC MCB VT MCB VT MCB


SIGNAL FAULT TRIP SIGNAL FAULT TRIP
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

SYNCHRO Panel
-X5 -X5 -X5 -X5 -X5 -X5
60 62 64 66 68 70
B B

C C

12 14 12 14 12 14 12 14 92 94 92 94 92 94 92 94 92 94 92 94 12 14 12 14
+S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B
-Q921.1 OF -Q922.1 OF -Q923.1 OF -Q924.1 OF -Q921.1 SD -Q922.1 SD -Q923.1 SD -Q924.1 SD -Q941.1 SD -Q942.1 SD -Q941.1 OF -Q942.1 OF
/D01.C2 /D01.C4 /D01.C5 /D01.C6 /D01.C2 /D01.C4 /D01.C5 /D01.C6 /T01.D3 /T01.D6 /T01.D3 /T01.D6
11 11 11 11 91 91 91 91 91 91 11 11

D D

-X5 -X5 -X5 -X5


-X5 -X5 65 67 69 71
E 61 63 E

SYNCHRO Panel
11/08/2018

F F

Date 11/08/2018 Project Name Title Aux. Contacts Spare Drawing Nr. =Outgoing Trafo S
01 As Manufactured 14/03/2019 WD Drawn AF
PAPUA DFE PROJECT Schematic Diagram
X4024122-302 Q04
00 First Issued 11/08/2018 AF Checked AYH 11kV Outgoing Trafo Customer Doc. Nr. Sheet 12
Rev N° Modification Date Name Approved DTA Order N° C2030-4024122 Switchboard 17kV Switchgear PT. SCHNEIDER INDONESIA 33 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SERIAL LINK COMMUNICATION


All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

-F50
Ethernet Ports
+S1.D RS485
ETH1 ETH2 -P50

C + -

B B

NOTE :
RJ-45 CONNECTORS
SUPPLIED BY OTHER

FROM ETHERNET FROM ETHERNET


-X6L-1 SWITCH / OTHER SWITCH / OTHER -X6R-1
1F 1M 1M 1F
FROM PREVIOUS CUBICLE

Sh Sh

2F 2M 2M 2F
RS485 2-WIRE

Gr Gr

TO NEXT
CUBICLE
3F 3M 3M 3F
Wh Wh

C 4F 4M 4M 4F C
Rd Rd

5F 5M 5M 5F
Bk Bk

MSTB 5x2.5 UMSTBVK 5x2.5 UMSTBVK 5x2.5 MSTB 5x2.5


(Female) (Male) mounted (Male) mounted (Female)
on DIN Rail on DIN Rail

D D

E E
11/08/2018

F F

Date 11/08/2018 Project Name Title Communication Drawing Nr. =Outgoing Trafo S
01 As Manufactured 14/03/2019 WD Drawn AF
PAPUA DFE PROJECT Schematic Diagram
X4024122-302 Q05
00 First Issued 11/08/2018 AF Checked AYH 11kV Outgoing Trafo Customer Doc. Nr. Sheet 13
Rev N° Modification Date Name Approved DTA Order N° C2030-4024122 Switchboard 17kV Switchgear PT. SCHNEIDER INDONESIA 33 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
CURRENT TRANSFORMER
PROTECTION PROTECTION
DIFFERENTIAL TRANSFORMER
+S4 +S4 +S4 +S4 +S4 +S4
L1 L2 L3
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

-T51L1 -T51L2 -T51L3 -T51L1 -T51L2 -T51L3


disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

P1

P1 TO VOLTAGE
CIRCUIT
P1

1S1

1S1

1S1

2S1

2S1

2S1
1S2

1S2

1S2

2S2

2S2

2S2
-Q51
CB AUX CONTACTS
B A13-A12-A14 /G01.C2 B
A16-A15-B1 /Q02.D1
B3-B2-B4 /Q01.C1

/S02.E7

/S02.E7
B5-B6 /Q02.D2
B7-B8 /Q02.D1
C9-C10 /Q02.D2
C11-C12 /Q02.D3
END OF CHARGING SIGNAL -X3 -X3 -X3 -X3 -X3 -X3 -X3 -X3
A8-A7-A9 /Q02.D5
B15-B16 /Q02.D4
CB RELEASE COILS 1 2 3 4 5 6 7 8 9 10 11 12 13 14
CLOSING /M01.E3 (*) (*) (*) (*) (*) (*)
C OPENING /M02.D2 C

(*) NOTE:
REMOVE JUMPER LINKS
WHEN USED -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5
96 97 98 99 100 101 102 103

TO EXTERNAL
-X5 -X5 -X5 -X5
168 169 170 171
D D

24kV Switchgear

E E
11/08/2018

F F

Date 11/08/2018 Project Name Title Current Circuit Drawing Nr. =Outgoing Trafo S
01 As Manufactured 14/03/2019 WD Drawn AF
PAPUA DFE PROJECT Schematic Diagram
X4024122-302 S01
00 First Issued 11/08/2018 AF Checked AYH 11kV Outgoing Trafo Customer Doc. Nr. Sheet 14
Rev N° Modification Date Name Approved DTA Order N° C2030-4024122 Switchboard 17kV Switchgear PT. SCHNEIDER INDONESIA 33 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
CURRENT TRANSFORMER
PROTECTION MEASUREMENT EARTHING SWITCH

+S4 +S4 +S4 +S4 +S4 +S4


All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

-T51L1 -T51L2 -T51L3 -T51L1 -T51L2 -T51L3


disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

P2

FROM PREV. P2 TO NEXT


PAGE PAGE
P2

3S1

3S1

3S1

4S1

4S1

4S1
3S2

3S2

3S2

4S2

4S2

4S2
+S4
-Q30

B B

/S02.E7

/S02.E7
-Q30
b 1-2 /Q02.D7

-X3 -X3 -X3 -X3 -X3 -X3 -X3 -X3 a 3-4 /G01.C3
b 5-6 /Q02.D6
a 7-8 /Q01.C2
15 16 17 18 19 20 21 22 23 24 25 26 27 28 b 9-10 /Q02.D6
a 11-12 /Q02.D7
b 13-14 /Q02.D8
C C
a 15-16 /Q02.D8
+S1.D +S1.D
-XA1 -XA2 AUX. CONTACT
2 4 6 8 2 4 6 8

CTT CTT

1 3 5 7 1 3 5 7

-F50.
X1:1 X1:3 X1:5 I1+ I2+ I3+
D D
Current Inputs

+S1.D
IL1 IL2 IL3 -P50

X1:2 X1:4 X1:6 I1- I2- I3-

/M02.D2

/S01.C4

/S01.C6

/T01.C5

/T01.C8
+S1.B
-XPE 1 2 3 4 5 6
7

+S4 1
E -PE1 E

/M01.E3

/S02.C4

/S02.C6

/T01.B6
11/08/2018

F F

Date 11/08/2018 Project Name Title Current Circuit Drawing Nr. =Outgoing Trafo S
01 As Manufactured 14/03/2019 WD Drawn AF
PAPUA DFE PROJECT Schematic Diagram
X4024122-302 S02
00 First Issued 11/08/2018 AF Checked AYH 11kV Outgoing Trafo Customer Doc. Nr. Sheet 15
Rev N° Modification Date Name Approved DTA Order N° C2030-4024122 Switchboard 17kV Switchgear PT. SCHNEIDER INDONESIA 33 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
VOLTAGE INDICATOR
VOLTAGE TRANSFORMER
MEASUREMENT PROTECTION
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

FROM CURRENT
CIRCUIT

-F30L1 -F30L2 -F30L3

-H101

+S4 +S4 +S4


B A -T61L1 N A -T61L2 N A -T61L3 N 7F B
-X021
PE PE PE 7M

a1 n1 a2 n2 a1 n1 a2 n2 a1 n1 a2 n2

/S02.E8
1F 4F 2F 3F 6F
-X021 -X021 5F -X021
1M 4M 2M 5M 3M 6M
1F 4F 2F 5F 3F 6F
-X022 -X022 -X022
1M 4M 2M 5M 3M 6M

C C

-X4 -X4 -X4 -X4 -X4 -X4 -X4 -X4 -X4 -X4
1 2 3 4 5 6 7 8 9 10 11 12
-Q941.1 1 3 5 7 -Q942.1 1 3 5 7
+S1.B +S1.B
OF /Q04.C6 -Q941 OF /Q04.C7 -Q942

/S02.E8

/S02.E8
SD /Q04.C5 4P, 2A SD /Q04.C6 4P, 2A
2 4 6 8 2 4 6 8

-X41 -X41 -X41 -X41


1 2 13 14
-X41 -X41 -X41 -X41
D -X41 -X41 3 4 15 16 D
PREVIOUS 9 10 NEXT -X41 -X41 -X41 -X41
CUBICLE -X41 -X41 CUBICLE 5 6 17 18
11 12 -X41 -X41 -X41 -X41
7 8 19 20

3 1
OFF

ON

+S1.D -XV1 -XV2


-S625 +S1.D
2 4 6 8 2 4 6 8
-S625
4 2 PTT PTT

1 3 5 7 1 3 5 7
/T01.E6
E /T01.E6 E
/T01.E6 /T01.E3
+S1.D +S1.D /T01.E6 /T01.E3
-F50 X5:20 X5:18 X5:16 -F50 X1:10 X1:11 /T01.E3
V1 V2 V3 VN
/T01.E3
Voltage Inputs

VT Input

+S1.D
U1 U2 U3 U4 -P50

X5:19 X5:17 X5:15


11/08/2018

F F

Date 11/08/2018 Project Name Title Voltage Circuit Drawing Nr. =Outgoing Trafo S
01 As Manufactured 14/03/2019 WD Drawn AF
PAPUA DFE PROJECT Schematic Diagram
X4024122-302 T01
00 First Issued 11/08/2018 AF Checked AYH 11kV Outgoing Trafo Customer Doc. Nr. Sheet 16
Rev N° Modification Date Name Approved DTA Order N° C2030-4024122 Switchboard 17kV Switchgear PT. SCHNEIDER INDONESIA 33 Sh.

1 2 3 4 5 6 7 8
F
E
A

00
01
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.
11/08/2018 All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

First Issued
Rev N° Modification
As Manufactured
Terminal type

1
1

Terminal UT 4. [ 1 - 5 ]
TERMINAL PLAN
Terminal UT 4. [ 6 ]
Terminal
Terminal
Terminal
-X1

Date
11/08/2018
14/03/2019
Function Connection Target Signal Number Connection Target Reference

AF
1 /Q02.E4

WD

Name
2 /Q02.E4

Date
HEATER =Outgoing Trafo +S1.D -H18 GREEN:X1 01P 3 =Outgoing Trafo +S1.B -B21 :c /D01.D3

Drawn

2
2

Checked
Approved
HEATER =Outgoing Trafo +S4 -R11 :1 01P /D01.D3

AF

DTA
AYH
SPARE 4 /Q02.F4
HEATER =Outgoing Trafo +S4 -R11 :2 01N 5 =Outgoing Trafo +S1.D -H18 :X2 /D01.E3
LIGHTING =Outgoing Trafo +S1.B -Q921 :4 01N 6 =Outgoing Trafo +S1.B -H17 :2 /D01.E3

Order N°
11/08/2018 Project Name

3
3

11kV
C2030-4024122 Switchboard
PAPUA DFE PROJECT

17kV Switchgear

4
4

PT. SCHNEIDER INDONESIA


Title

5
5

Outgoing Trafo
TERMINAL PLAN
Schematic Diagram

6
6

Drawing Nr.

Customer Doc. Nr.

7
7

X4024122-302
+S1.B
=Outgoing Trafo

8
8

Sheet 17
V

33 Sh.
V01
F
E
A

D
F
E
A

00
01
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.
11/08/2018 All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

First Issued
Rev N° Modification
As Manufactured
Terminal type

1
1

Terminal UT 4. [ 1 - 19 ]
TERMINAL PLAN
Terminal UT 4. [ 20 ]
Terminal
Terminal
Terminal
-X2

Date
11/08/2018
14/03/2019
Function Connection Target Signal Number Connection Target Reference

AF
=Outgoing Trafo +S4 -Q51 M1:X01:A1 M+ 1 =Outgoing Trafo +S1.B -Q922 :4 /M01.C2

WD

Name
=Outgoing Trafo +S4 -Q51 :X01:A2 M- 2 =Outgoing Trafo +S1.B -Q922 :2 /M01.E2

Date
CS- 3 /Q02.E5

Drawn

2
2

Checked
Approved
=Outgoing Trafo +S1.D -F50 DI2:X3:6 TR+ 4 =Outgoing Trafo +S4 -Q51 :X01:D11 /M02.D2

AF

DTA
AYH
=Outgoing Trafo +S4 -Q51 :X01:A4 TR- 5 =Outgoing Trafo +S1.B -K50BF :1 /M02.E3
=Outgoing Trafo +S1.D -F50 :X2:2 TR- =Outgoing Trafo +S1.B -Q923 :2 /M02.E3
=Outgoing Trafo +S1.D -S601 :2 TR+ 6 =Outgoing Trafo +S4 -Q51 :X01:A3 /M02.D3

Order N°
=Outgoing Trafo +S4 -Q51 4:X01:B8 CS+ 7 /Q02.E1

11/08/2018 Project Name


=Outgoing Trafo +S4 -Q51 3:X01:B7 CS+ 8 /Q02.B1
=Outgoing Trafo +S1.D -F50 :X2:1 TR+ 9 =Outgoing Trafo +S1.B -X5 :5 /G01.A2
=Outgoing Trafo +S1.B -Q923 :4 TR+ =Outgoing Trafo +S1.B -X5 :30 /G01.A2

3
3

=Outgoing Trafo +S1.D -S650 :5 TR+ 10 Connection is not unique. /M02.A2


=Outgoing Trafo +S1.D -F50 T5:X5:14 TR+ /M02.A2

11kV
=Outgoing Trafo +S4 -Q51 :X01:A5 CS+ 11 =Outgoing Trafo +S1.B -X5 :80 /M01.D3
=Outgoing Trafo +S4 -Q51 :X01:A6 CS- 12 =Outgoing Trafo +S1.B -Q924 :2 /M01.E3

C2030-4024122 Switchboard
PAPUA DFE PROJECT
=Outgoing Trafo +S1.D -H52 :X2 CS- 13 =Outgoing Trafo +S1.D -P50 :L2 /Q01.E1
=Outgoing Trafo +S1.D -HST :X2 CS- /Q01.E1
CS- 14 /Q02.E5
=Outgoing Trafo +S1.D -S650 :3 CS+ 15 =Outgoing Trafo +S1.B -Q924 :4 /M01.A3

17kV Switchgear

4
4

=Outgoing Trafo +S4 -Q51 9:X01:B2 CS+ 16 =Outgoing Trafo +S1.B -X5 :34 /Q01.A1
=Outgoing Trafo +S1.D -P50 :L1 CS+ /Q01.A1
=Outgoing Trafo +S4 -Q51 10:X01:B3 CS+ 19 =Outgoing Trafo +S1.D -H52 RED:X1 /Q01.D1
=Outgoing Trafo +S4 -Q51 2:X01:B4 CS+ 20 =Outgoing Trafo +S1.D -H51 GREEN:X1 /Q01.D2

PT. SCHNEIDER INDONESIA


Title

5
5

Outgoing Trafo
TERMINAL PLAN
Schematic Diagram

6
6

Drawing Nr.

Customer Doc. Nr.

7
7

X4024122-302
+S1.B
=Outgoing Trafo

8
8

Sheet 18
V
V02

33 Sh.
F
E
A

D
F
E
A

00
01
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.
11/08/2018 All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

First Issued
Rev N° Modification
As Manufactured
Terminal type

1
1

Terminal URTK/S [ 1 - 27 ]
TERMINAL PLAN
Terminal URTK/S [ 28 ]
Terminal
Terminal
Terminal
-X3

Date
11/08/2018
14/03/2019
Function Connection Target Signal Number Connection Target Reference

AF
=Outgoing Trafo +S4 -T51L1 :1S1 CL1 1 =Outgoing Trafo +S1.B -X5 :96 /S01.C2

WD

Name
=Outgoing Trafo +S4 -T51L2 :1S1 CL2 2 =Outgoing Trafo +S1.B -X5 :97 /S01.C3

Date
=Outgoing Trafo +S4 -T51L3 :1S1 CL3 3 =Outgoing Trafo +S1.B -X5 :98 /S01.C3

Drawn

2
2

Checked
Approved
=Outgoing Trafo +S1.B -X5 :99 4 =Outgoing Trafo +S1.B -XPE :2 /S01.C4

AF

DTA
AYH
=Outgoing Trafo +S4 -T51L1 :1S2 CN 5 /S01.C4
=Outgoing Trafo +S4 -T51L2 :1S2 CN 6 /S01.C4
=Outgoing Trafo +S4 -T51L3 :1S2 CN 7 /S01.C4

Order N°
=Outgoing Trafo +S4 -T51L1 :2S1 CL1 8 =Outgoing Trafo +S1.B -X5 :100 /S01.C5

11/08/2018 Project Name


=Outgoing Trafo +S4 -T51L2 :2S1 CL2 9 =Outgoing Trafo +S1.B -X5 :101 /S01.C5
=Outgoing Trafo +S4 -T51L3 :2S1 CL3 10 =Outgoing Trafo +S1.B -X5 :102 /S01.C6
=Outgoing Trafo +S1.B -X5 :103 11 =Outgoing Trafo +S1.B -XPE :3 /S01.C6

3
3

=Outgoing Trafo +S4 -T51L1 :2S2 CN 12 /S01.C6


=Outgoing Trafo +S4 -T51L2 :2S2 CN 13 /S01.C6

11kV
=Outgoing Trafo +S4 -T51L3 :2S2 CN 14 /S01.C7
=Outgoing Trafo +S1.D -XA1 :2 CL1 15 =Outgoing Trafo +S4 -T51L1 :3S1 /S02.C2

C2030-4024122 Switchboard
PAPUA DFE PROJECT
=Outgoing Trafo +S1.D -XA1 :4 CL2 16 =Outgoing Trafo +S4 -T51L2 :3S1 /S02.C3
=Outgoing Trafo +S1.D -XA1 :6 CL3 17 =Outgoing Trafo +S4 -T51L3 :3S1 /S02.C3
=Outgoing Trafo +S1.D -XA1 :8 18 =Outgoing Trafo +S1.B -XPE :2 /S02.C4
=Outgoing Trafo +S4 -T51L1 :3S2 CN 19 /S02.C4

17kV Switchgear

4
4

=Outgoing Trafo +S4 -T51L2 :3S2 CN 20 /S02.C4


=Outgoing Trafo +S4 -T51L3 :3S2 CN 21 /S02.C4
=Outgoing Trafo +S4 -T51L1 :4S1 CL1 22 =Outgoing Trafo +S1.D -XA2 :2 /S02.C5
=Outgoing Trafo +S4 -T51L2 :4S1 CL2 23 =Outgoing Trafo +S1.D -XA2 :4 /S02.C5
=Outgoing Trafo +S4 -T51L3 :4S1 CL3 24 =Outgoing Trafo +S1.D -XA2 :6 /S02.C6
=Outgoing Trafo +S1.D -XA2 :8 25 =Outgoing Trafo +S1.B -XPE :3 /S02.C6
=Outgoing Trafo +S4 -T51L1 :4S2 CN 26 /S02.C6

PT. SCHNEIDER INDONESIA


=Outgoing Trafo +S4 -T51L2 :4S2 CN 27 /S02.C6

Title
=Outgoing Trafo +S4 -T51L3 :4S2 CN 28 /S02.C7

5
5

Outgoing Trafo
TERMINAL PLAN
Schematic Diagram

6
6

Drawing Nr.

Customer Doc. Nr.

7
7

X4024122-302
+S1.B
=Outgoing Trafo

8
8

Sheet 19
V
V03

33 Sh.
F
E
A

D
F
E
A

00
01
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.
11/08/2018 All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

First Issued
Rev N° Modification
As Manufactured
Terminal type

1
1

Terminal UT 4. [ 1 - 11 ]
TERMINAL PLAN
Terminal UT 4. [ 12 - 12 ]
Terminal
Terminal
Terminal
-X4

Date
11/08/2018
14/03/2019
Function Connection Target Signal Number Connection Target Reference

AF
=Outgoing Trafo +S4 -X022 :1M UR 1 =Outgoing Trafo +S1.B -Q941 4P, 2A:1 /T01.C4

WD

Name
=Outgoing Trafo +S4 -X022 :2F US 2 =Outgoing Trafo +S1.B -Q941 :3 /T01.C4

Date
=Outgoing Trafo +S4 -X022 :3M UT 3 =Outgoing Trafo +S1.B -Q941 :5 /T01.C5

Drawn

2
2

Checked
Approved
=Outgoing Trafo +S4 -X022 :4F UN 4 =Outgoing Trafo +S1.B -Q941 :7 /T01.C5

AF

DTA
AYH
=Outgoing Trafo +S4 -X022 :5M UN 5 /T01.C5
=Outgoing Trafo +S4 -X022 :6F UN 6 =Outgoing Trafo +S1.B -XPE :4 /T01.C5
=Outgoing Trafo +S4 -X021 :1M UR 7 =Outgoing Trafo +S1.B -Q942 4P, 2A:1 /T01.C7

Order N°
=Outgoing Trafo +S4 -X021 :2F US 8 =Outgoing Trafo +S1.B -Q942 :3 /T01.C7

11/08/2018 Project Name


=Outgoing Trafo +S4 -X021 :3M UT 9 =Outgoing Trafo +S1.B -Q942 :5 /T01.C8
=Outgoing Trafo +S4 -X021 :4F UN 10 =Outgoing Trafo +S1.B -Q942 :7 /T01.C8
UN =Outgoing Trafo +S1.B -X4 :11 /T01.C8

3
3

=Outgoing Trafo +S4 -X021 :5M UN 11 =Outgoing Trafo +S1.B -X4 :12 /T01.C8
UN =Outgoing Trafo +S1.B -X4 :10 /T01.C8

11kV
=Outgoing Trafo +S4 -X021 :6F PE 12 =Outgoing Trafo +S1.B -XPE :6 /T01.C8
UN =Outgoing Trafo +S1.B -X4 :11 /T01.C8

C2030-4024122 Switchboard
PAPUA DFE PROJECT

17kV Switchgear

4
4

PT. SCHNEIDER INDONESIA


Title

5
5

Outgoing Trafo
TERMINAL PLAN
Schematic Diagram

6
6

Drawing Nr.

Customer Doc. Nr.

7
7

X4024122-302
+S1.B
=Outgoing Trafo

8
8

Sheet 20
V
V04

33 Sh.
F
E
A

D
F
E
A

00
01
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.
11/08/2018 All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

First Issued
Rev N° Modification
As Manufactured
Terminal type

1
1

Terminal UT 4. [ 1 - 53 ]
TERMINAL PLAN
Terminal
Terminal
Terminal
Terminal
-X5

Date
11/08/2018
14/03/2019
Function Connection Target Signal Number Connection Target Reference

AF
=Outgoing Trafo +S1.D -S650 :4 CS+ 1 /M01.B4

WD

Name
=Outgoing Trafo +S1.D -S601 :4 CS+ 2 /M01.C4

Date
=Outgoing Trafo +S1.D -S650 :8 TR+ 3 /M02.B3

Drawn

2
2

Checked
Approved
=Outgoing Trafo +S1.D -S601 :2 TR+ 4 =Outgoing Trafo +S1.B -X5 :78 /M02.C3

AF

DTA
AYH
=Outgoing Trafo +S4 -Q51 13:X01:A12 TR+ 5 =Outgoing Trafo +S1.B -X2 :9 /G01.B2
=Outgoing Trafo +S4 -Q51 14:X01:A13 TR+ 6 =Outgoing Trafo +S1.D -F50 DI3:X4:7 /G01.D2
=Outgoing Trafo +S4 -Q51 6:X01:A14 TR+ 7 =Outgoing Trafo +S1.D -F50 DI4:X4:9 /G01.D2

Order N°
=Outgoing Trafo +S4 -Q51 15:X01:A15 CS+ 8 /Q02.B1

11/08/2018 Project Name


=Outgoing Trafo +S4 -Q51 16:X01:A16 CS+ 9 /Q02.E1
=Outgoing Trafo +S4 -Q51 8:X01:B1 CS+ 10 /Q02.E2
11 /Q02.E5

3
3

CS+ 12 /Q02.E5
=Outgoing Trafo +S4 -Q51 11:X01:B5 CS+ 13 /Q02.B2

11kV
=Outgoing Trafo +S4 -Q51 12:X01:B6 CS+ 14 /Q02.E2
=Outgoing Trafo +S4 -Q51 5:X01:C9 CS+ 15 /Q02.B2

C2030-4024122 Switchboard
PAPUA DFE PROJECT
=Outgoing Trafo +S4 -Q51 6:X01:C10 CS+ 16 /Q02.E2
=Outgoing Trafo +S4 -Q51 15:X01:C11 CS+ 17 /Q02.B3
=Outgoing Trafo +S4 -Q51 16:X01:C12 CS+ 18 /Q02.E3
=Outgoing Trafo +S4 -Q51 :X01:A10 CS+ 19 /Q02.B3

17kV Switchgear

4
4

=Outgoing Trafo +S4 -Q51 :X01:A11 CS+ 20 /Q02.E3


=Outgoing Trafo +S4 -Q51 5:X01:A7 CS+ 21 /Q02.B5
=Outgoing Trafo +S4 -Q51 6:X01:A8 CS+ 22 /Q02.E5
=Outgoing Trafo +S4 -Q51 12:X01:A9 CS+ 23 /Q02.E5
=Outgoing Trafo +S4 -Q51 13:X01:B15 CS+ 24 /Q02.B4
=Outgoing Trafo +S4 -Q51 14:X01:B16 CS+ 25 /Q02.E4
=Outgoing Trafo +S4 -Q51 :X01:D15 CS+ 26 /Q02.B4

PT. SCHNEIDER INDONESIA


=Outgoing Trafo +S4 -Q51 :X01:D16 CS+ 27 /Q02.E4

Title
=Outgoing Trafo +S4 -X041 :1F CS+ 28 /Q02.B7

5
5

=Outgoing Trafo +S4 -X041 :2F CS+ 29 /Q02.E7


=Outgoing Trafo +S4 -X041 :3F TR+ 30 =Outgoing Trafo +S1.B -X2 :9 /G01.B3
TR+ =Outgoing Trafo +S1.B -X5 :52 /G01.B3
=Outgoing Trafo +S4 -X041 :4F TR+ 31 =Outgoing Trafo +S1.D -F50 DI7:X4:16 /G01.D3
=Outgoing Trafo +S4 -X041 :5F CS+ 32 /Q02.B6
=Outgoing Trafo +S4 -X041 :6F CS+ 33 /Q02.E6

Outgoing Trafo
TERMINAL PLAN
Schematic Diagram
=Outgoing Trafo +S4 -X041 :7F CS+ 34 =Outgoing Trafo +S1.B -X2 :16 /Q01.B2
CS+ =Outgoing Trafo +S1.B -X5 :38 /Q01.B2

6
6

=Outgoing Trafo +S4 -X041 :8F CS+ 35 =Outgoing Trafo +S1.D -H30 AMBER:X1 /Q01.D2
=Outgoing Trafo +S4 -X051 :1F CS+ 36 /Q03.B6
=Outgoing Trafo +S4 -X051 :2F CS+ 37 /Q03.E6
=Outgoing Trafo +S4 -X051 :3F CS+ 38 =Outgoing Trafo +S1.B -X5 :34 /Q01.B3
Drawing Nr.

CS+ =Outgoing Trafo +S1.B -X5 :56 /Q01.B3


Customer Doc. Nr.

=Outgoing Trafo +S4 -X051 :4F CS+ 39 =Outgoing Trafo +S1.D -HST RED:X1 /Q01.D3
=Outgoing Trafo +S4 -X051 :5F CS+ 40 /Q03.B7
=Outgoing Trafo +S4 -X051 :6F CS+ 41 /Q03.E7
7
7

=Outgoing Trafo +S4 -X051 :7F CS+ 42 /Q03.B8


=Outgoing Trafo +S4 -X051 :8F CS+ 43 /Q03.E8
X4024122-302

=Outgoing Trafo +S4 -X042 :1F CS+ 44 /Q02.B6


=Outgoing Trafo +S4 -X042 :2F CS+ 45 /Q02.E6
=Outgoing Trafo +S4 -X042 :3F CS+ 46 /Q02.B7
=Outgoing Trafo +S4 -X042 :4F CS+ 47 /Q02.E7
=Outgoing Trafo +S4 -X042 :7F CS+ 48 /Q02.B8
+S1.B

=Outgoing Trafo +S4 -X042 :8F CS+ 49 /Q02.E8


=Outgoing Trafo +S4 -X042 :5F CS+ 50 /Q02.B8
=Outgoing Trafo

8
8

=Outgoing Trafo +S4 -X042 :6F CS+ 51 /Q02.E8


=Outgoing Trafo +S4 -X052 :1F TR+ 52 =Outgoing Trafo +S1.B -X5 :30 /G01.B4
TR+ =Outgoing Trafo +S1.B -X5 :114 /G01.B4
=Outgoing Trafo +S4 -X052 :2F TR+ 53 =Outgoing Trafo +S1.D -F50 DI8:X4:17 /G01.D4
Sheet 21
V
V05

33 Sh.
F
E
A

D
F
E
A

00
01
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.
11/08/2018 All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

First Issued
Rev N° Modification
As Manufactured
Terminal type

1
1

Terminal UT 4. [ 54 - 110 ]
TERMINAL PLAN
Terminal
Terminal
Terminal
Terminal
-X5

Date
11/08/2018
14/03/2019
Function Connection Target Signal Number Connection Target Reference

AF
=Outgoing Trafo +S4 -X052 :3F CS+ 54 /Q03.B7

WD

Name
=Outgoing Trafo +S4 -X052 :4F CS+ 55 /Q03.E7

Date
=Outgoing Trafo +S4 -X052 :5F CS+ 56 =Outgoing Trafo +S1.B -X5 :38 /Q01.B4

Drawn

2
2

Checked
Approved
=Outgoing Trafo +S4 -X052 :6F CS+ 57 =Outgoing Trafo +S1.D -HSS GREEN:X1 /Q01.D4

AF

DTA
AYH
=Outgoing Trafo +S4 -X052 :7F CS+ 58 /Q03.B8
=Outgoing Trafo +S4 -X052 :8F CS+ 59 /Q03.E8
CS+ 60 =Outgoing Trafo +S1.B -Q924.1 :12 /Q04.B1

Order N°
CS+ 61 =Outgoing Trafo +S1.B -Q924.1 :11 /Q04.E1

11/08/2018 Project Name


CS+ 62 =Outgoing Trafo +S1.B -Q921.1 SD:94 /Q04.B3
CS+ 63 =Outgoing Trafo +S1.B -Q921.1 :91 /Q04.E3
CS+ 64 =Outgoing Trafo +S1.B -Q941.1 SD:94 /Q04.B5

3
3

CS+ 65 =Outgoing Trafo +S1.B -Q941.1 :91 /Q04.E5


CS+ 66 =Outgoing Trafo +S1.B -Q942.1 SD:94 /Q04.B6

11kV
CS+ 67 =Outgoing Trafo +S1.B -Q942.1 :91 /Q04.E6
CS+ 68 =Outgoing Trafo +S1.B -Q941.1 OF:14 /Q04.B6

C2030-4024122 Switchboard
PAPUA DFE PROJECT
CS+ 69 =Outgoing Trafo +S1.B -Q941.1 :11 /Q04.E6
CS+ 70 =Outgoing Trafo +S1.B -Q942.1 :12 /Q04.B7
CS+ 71 =Outgoing Trafo +S1.B -Q942.1 :11 /Q04.E7
CS+ 72

17kV Switchgear

4
4

CS+ 73 =Outgoing Trafo +S1.B -K50BF :7 /Q03.B4


CS+ 74 =Outgoing Trafo +S1.B -K50BF :3 /Q03.E4
CS+ 75 =Outgoing Trafo +S1.B -K50BF :8 /Q03.B5
CS+ 76 =Outgoing Trafo +S1.B -K50BF :4 /Q03.E5
=Outgoing Trafo +S1.D -S650 :7 TR+ 77 =Outgoing Trafo +S1.B -X5 :108 /M02.B3
=Outgoing Trafo +S1.B -X5 :109 TR+ 78 =Outgoing Trafo +S1.B -X5 :4 /M02.C3
=Outgoing Trafo +S1.B -X5 :80 CS+ 79 =Outgoing Trafo +S1.B -K86 :9 /M01.C5

PT. SCHNEIDER INDONESIA


=Outgoing Trafo +S1.B -X2 :11 CS+ 80 =Outgoing Trafo +S1.B -X5 :79 /M01.C5

Title
CS+ 81 =Outgoing Trafo +S1.B -K50BF :9 /Q03.B5

5
5

CS+ 82 =Outgoing Trafo +S1.B -K50BF :5 /Q03.E5


CS+ 83 =Outgoing Trafo +S1.B -K50BF :10 /Q03.B5
CS+ 84 =Outgoing Trafo +S1.B -K50BF :6 /Q03.E5
=Outgoing Trafo +S1.D -F50 T7:X5:10 CS+ 85 /Q03.B2
=Outgoing Trafo +S1.D -F50 T7:X5:9 CS+ 86 /Q03.E2
=Outgoing Trafo +S1.D -F50 :X3:20 CS+ 87 /Q03.B2

Outgoing Trafo
TERMINAL PLAN
Schematic Diagram
=Outgoing Trafo +S1.D -F50 SF:X3:18 CS+ 88 /Q03.E2
=Outgoing Trafo +S1.D -F50 SF:X3:19 CS+ 89 /Q03.B2

6
6

CS+ 90 =Outgoing Trafo +S1.B -K86 :7 /Q03.B3


CS+ 91 =Outgoing Trafo +S1.B -K86 :11 /Q03.E3
CS+ 92 =Outgoing Trafo +S1.B -K86 :8 /Q03.B3
CS+ 93 =Outgoing Trafo +S1.B -K86 :12 /Q03.E3
Drawing Nr.

94 /Q02.F5
Customer Doc. Nr.

95 /Q02.F5
CL1 96 =Outgoing Trafo +S1.B -X3 :1 /S01.D2
CL2 97 =Outgoing Trafo +S1.B -X3 :2 /S01.D3
7
7

CL3 98 =Outgoing Trafo +S1.B -X3 :3 /S01.D3


CN 99 =Outgoing Trafo +S1.B -X3 :4 /S01.D4
X4024122-302

CL1 100 =Outgoing Trafo +S1.B -X3 :8 /S01.D5


CL2 101 =Outgoing Trafo +S1.B -X3 :9 /S01.D5
CL3 102 =Outgoing Trafo +S1.B -X3 :10 /S01.D6
CN 103 =Outgoing Trafo +S1.B -X3 :11 /S01.D6
UR 104
+S1.B

US 105
UT 106
=Outgoing Trafo

8
8

UN 107
=Outgoing Trafo +S1.B -X5 :110 TR+ 108 =Outgoing Trafo +S1.B -X5 :77 /M02.B4
=Outgoing Trafo +S1.B -X5 :111 TR+ 109 =Outgoing Trafo +S1.B -X5 :78 /M02.C4
=Outgoing Trafo +S1.B -X5 :112 TR+ 110 =Outgoing Trafo +S1.B -X5 :108 /M02.B4
Sheet 22
V

33 Sh.
V05.1
F
E
A

D
F
E
A

00
01
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.
11/08/2018 All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

First Issued
Rev N° Modification
As Manufactured
Terminal type

1
1

Terminal UT 4. [ 111 - 124 , 127 - 134 ]


TERMINAL PLAN
Terminal UT 4. [ 125 - 126 , 135 ]
Terminal
Terminal
Terminal
-X5

Date
11/08/2018
14/03/2019
Function Connection Target Signal Number Connection Target Reference

AF
=Outgoing Trafo +S1.B -X5 :113 TR+ 111 =Outgoing Trafo +S1.B -X5 :109 /M02.C4

WD

Name
=Outgoing Trafo +S1.B -X5 :110 TR+ 112 =Outgoing Trafo +S1.B -K86 :6 /M02.B5

Date
=Outgoing Trafo +S1.B -K86 :10 TR+ 113 =Outgoing Trafo +S1.B -X5 :111 /M02.C5

Drawn

2
2

Checked
Approved
=Outgoing Trafo +S1.B -X5 :118 TR+ 114 =Outgoing Trafo +S1.B -X5 :52 /G01.B5

AF

DTA
AYH
TR+ 115 /G01.B5
=Outgoing Trafo +S1.D -F50 DI9:X4:19 #18920 116 /G01.D5
=Outgoing Trafo +S1.D -F50 DI10:X4:20 #18921 117 /G01.D5

Order N°
=Outgoing Trafo +S1.B -X5 :124 TR+ 118 =Outgoing Trafo +S1.B -X5 :114 /G01.B6

11/08/2018 Project Name


TR+ 119 /G01.B6
TR+ 120 /G01.B6
=Outgoing Trafo +S1.D -F50 DI11:X5:2 TR- 121 /G01.D6

3
3

=Outgoing Trafo +S1.D -F50 DI12:X5:3 #18923 122 /G01.D6


=Outgoing Trafo +S1.D -F50 DI13:X5:4 #18924 123 /G01.D6

11kV
=Outgoing Trafo +S1.B -X5 :118 TR+ 124 =Outgoing Trafo +S1.B -X5 :130 /G01.B7
TR+ 125 /G01.B7

C2030-4024122 Switchboard
PAPUA DFE PROJECT
TR+ 126 /G01.B7
=Outgoing Trafo +S1.D -F50 DI14:X5:6 TR- 127 /G01.D7
=Outgoing Trafo +S1.D -F50 DI15:X5:7 #18926 128 /G01.D7
=Outgoing Trafo +S1.D -F50 DI16:X5:8 #18927 129 /G01.D7

17kV Switchgear

4
4

Connection is not unique. TR+ 130 =Outgoing Trafo +S1.B -X5 :124 /G01.B3
TR+ 131 /G01.B3
=Outgoing Trafo +S1.D -F50 A1:X3:8 CS+ 132 /Q03.B1
=Outgoing Trafo +S1.D -F50 A1:X3:7 CS+ 133 /Q03.E1
=Outgoing Trafo +S1.D -F50 DI5:X4:11 TR- 134 /G01.D3
=Outgoing Trafo +S1.D -F50 DI6:X4:13 TR- 135 /G01.D3

PT. SCHNEIDER INDONESIA


Title

5
5

Outgoing Trafo
TERMINAL PLAN
Schematic Diagram

6
6

Drawing Nr.

Customer Doc. Nr.

7
7

X4024122-302
+S1.B
=Outgoing Trafo

8
8

Sheet 23
V
V05.2

33 Sh.
F
E
A

D
F
E
A

00
01
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.
11/08/2018 All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

First Issued
Rev N° Modification
As Manufactured
Terminal type

1
1

Terminal UT 4. [ 1 - 3 ]
TERMINAL PLAN
Terminal UT 4. [ 4 ]
Terminal
Terminal
Terminal
-X11

Date
11/08/2018
14/03/2019
Function Connection Target Signal Number Connection Target Reference

AF
220V AC SUPPLY (P) P 1 =Outgoing Trafo +S1.B -Q921 2P, 6A:1 /D01.A2

WD

Name
230V AC SUPPLY (P) P 2 /D01.A8

Date
220V AC SUPPLY (N) N 3 =Outgoing Trafo +S1.B -Q921 :3 /D01.A2

Drawn

2
2

Checked
Approved
230V AC SUPPLY (N) N 4 /D01.A8

AF

DTA
AYH
Order N°
11/08/2018 Project Name

3
3

11kV
C2030-4024122 Switchboard
PAPUA DFE PROJECT

17kV Switchgear

4
4

PT. SCHNEIDER INDONESIA


Title

5
5

Outgoing Trafo
TERMINAL PLAN
Schematic Diagram

6
6

Drawing Nr.

Customer Doc. Nr.

7
7

X4024122-302
+S1.B
=Outgoing Trafo

8
8

Sheet 24
V
V06

33 Sh.
F
E
A

D
F
E
A

00
01
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.
11/08/2018 All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

First Issued
Rev N° Modification
As Manufactured
Terminal type

1
1

Terminal UT 4. [ 1 - 3 ]
TERMINAL PLAN
Terminal UT 4. [ 4 ]
Terminal
Terminal
Terminal
-X21

Date
11/08/2018
14/03/2019
Function Connection Target Signal Number Connection Target Reference

AF
110V DC SUPPLY (L+) L+ 1 =Outgoing Trafo +S1.B -Q922 :3 /D01.A2

WD

Name
110V DC SUPPLY (L+) L+ 2 /D01.A8

Date
110V DC SUPPLY (L-) L- 3 =Outgoing Trafo +S1.B -Q922 2P, 6A:1 /D01.B2

Drawn

2
2

Checked
Approved
110V DC SUPPLY (L-) L- 4 /D01.B8

AF

DTA
AYH
Order N°
11/08/2018 Project Name

3
3

11kV
C2030-4024122 Switchboard
PAPUA DFE PROJECT

17kV Switchgear

4
4

PT. SCHNEIDER INDONESIA


Title

5
5

Outgoing Trafo
TERMINAL PLAN
Schematic Diagram

6
6

Drawing Nr.

Customer Doc. Nr.

7
7

X4024122-302
+S1.B
=Outgoing Trafo

8
8

Sheet 25
V
V07

33 Sh.
F
E
A

D
F
E
A

00
01
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.
11/08/2018 All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

First Issued
Rev N° Modification
As Manufactured
Terminal type

1
1

Terminal UT 4. [ 1 - 11 , 13 - 19 ]
TERMINAL PLAN
Terminal UT 4. [ 12 , 20 ]
Terminal
Terminal
Terminal
-X41

Date
11/08/2018
14/03/2019
Function Connection Target Signal Number Connection Target Reference

AF
=Outgoing Trafo +S1.D -XV1 :2 UR 1 =Outgoing Trafo +S1.B -Q941 :2 /T01.D3

WD

Name
UR 2 /T01.D5

Date
=Outgoing Trafo +S1.D -XV1 :4 US 3 =Outgoing Trafo +S1.B -Q941 :4 /T01.D3

Drawn

2
2

Checked
Approved
US 4 /T01.D5

AF

DTA
AYH
=Outgoing Trafo +S1.D -XV1 :6 UT 5 /T01.D3
UT 6 =Outgoing Trafo +S1.B -Q941 :6 /T01.D5
=Outgoing Trafo +S1.D -XV1 :8 UN 7 /T01.D3

Order N°
UN 8 =Outgoing Trafo +S1.B -Q941 :8 /T01.D5

11/08/2018 Project Name


=Outgoing Trafo +S1.D -S625 :3 P 9 /T01.D2
P 10 /T01.D3
=Outgoing Trafo +S1.D -S625 :1 N 11 /T01.D2

3
3

N 12 /T01.D3
=Outgoing Trafo +S1.D -XV2 :2 UR 13 /T01.D6

11kV
UR 14 =Outgoing Trafo +S1.B -Q942 :2 /T01.D8
=Outgoing Trafo +S1.D -XV2 :4 US 15 /T01.D6

C2030-4024122 Switchboard
PAPUA DFE PROJECT
US 16 =Outgoing Trafo +S1.B -Q942 :4 /T01.D8
=Outgoing Trafo +S1.D -XV2 :6 UT 17 /T01.D6
UT 18 =Outgoing Trafo +S1.B -Q942 :6 /T01.D8
=Outgoing Trafo +S1.D -XV2 :8 UN 19 /T01.D6

17kV Switchgear

4
4

UN 20 =Outgoing Trafo +S1.B -Q942 :8 /T01.D8

PT. SCHNEIDER INDONESIA


Title

5
5

Outgoing Trafo
TERMINAL PLAN
Schematic Diagram

6
6

Drawing Nr.

Customer Doc. Nr.

7
7

X4024122-302
+S1.B
=Outgoing Trafo

8
8

Sheet 26
V
V08

33 Sh.
F
E
A

D
F
E
A

00
01
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.
11/08/2018 All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

First Issued
Rev N° Modification
As Manufactured
Terminal type

1
1

Terminal USLKG5 [ 1 - 7 ]
TERMINAL PLAN
Terminal
Terminal
Terminal
Terminal
-XPE

Date
11/08/2018
14/03/2019
Function Connection Target Signal Number Connection Target Reference

AF
=Outgoing Trafo +S1.D -F50 :GND CN 1 =Outgoing Trafo +S4 -Q51 :X01:G /S02.E7

WD

Name
=Outgoing Trafo +S1.B -X3 :18 PE 2 =Outgoing Trafo +S1.B -X3 :4 /S02.E7

Date
=Outgoing Trafo +S1.B -X3 :25 PE 3 =Outgoing Trafo +S1.B -X3 :11 /S02.E7

Drawn

2
2

Checked
Approved
UN 4 =Outgoing Trafo +S1.B -X4 :6 /S02.E8

AF

DTA
AYH
=Outgoing Trafo +S4 -X021 :7M PE 5 /S02.E8
PE 6 =Outgoing Trafo +S1.B -X4 :12 /S02.E8
=Outgoing Trafo +S4 -PE1 :1 PE 7 /S02.E8

Order N°
11/08/2018 Project Name

3
3

11kV
C2030-4024122 Switchboard
PAPUA DFE PROJECT

17kV Switchgear

4
4

PT. SCHNEIDER INDONESIA


Title

5
5

Outgoing Trafo
TERMINAL PLAN
Schematic Diagram

6
6

Drawing Nr.

Customer Doc. Nr.

7
7

X4024122-302
+S1.B
=Outgoing Trafo

8
8

Sheet 27
V
V09

33 Sh.
F
E
A

D
1 2 3 4 5 6 7 8
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

LV DOOR
PIX W1000 H800

B NOTE : B
DEVICE CODE
ENGRAVING / ( NO ENGRAVING ) REMARKS
ENGRAVING

-F50 PROTECTION RELAY VAMP 57


-H18 HEATER ON PILOT LIGHT, GREEN
-H30 ES CLOSE PILOT LIGHT, AMBER
-H51 CB CLOSE PILOT LIGHT, GREEN
C -F50 C
-H52 CB OPEN PILOT LIGHT, RED
-HSS CB SERVICE PILOT LIGHT, GREEN
Vamp57

i
-P50
OK -HST CB TEST PILOT LIGHT, RED
F1 F2
VAMP

O -S601 OPEN/CLOSE SWITCH K&N


I

-S650 LOCAL-REMOTE K&N


-H18 -H52 -H51 -H30 -HSS -HST -XA1 CTB FOR PROTECTION YONGSUNG
D -XA2 CTB FOR MEASUREMENT YONGSUNG D

-XA1 -XA2 -S650 -S601 -S625 -XV1 -XV2 -XV1 VTB FOR MEASUREMENT YONGSUNG
L R N OFF ON
T C

CTT CTT PTT PTT


-XV2 VTB FOR PROTECTION YONGSUNG
-P50 DIGITAL POWER METER PM 8240
-S625 SHYNCRO SELECTOR SELECTOR SWITCH

E E

PIX LV DOOR
HEIGHT : 800 (780) mm
WIDTH : 1000 (960) mm
11/08/2018

F F

Date 11/08/2018 Project Name Title LV Door Layout Drawing Nr. =Outgoing Trafo Y
01 As Manufactured 14/03/2019 WD Drawn AF
PAPUA DFE PROJECT Schematic Diagram
X4024122-302 +S1.B X01
00 First Issued 11/08/2018 AF Checked AYH 11kV Outgoing Trafo Customer Doc. Nr. Sheet 28
Rev N° Modification Date Name Approved DTA Order N° C2030-4024122 Switchboard 17kV Switchgear PT. SCHNEIDER INDONESIA 33 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

LV BOX
PIX W1000 H800
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

-H17
CD W65xH65 1

-S34
2

-X11 -X21 -X41 -X51 -X6L-1 -X6R-1

1 2 3 4 1 2 3 4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 1 2 3 4

4 4 20 4

B B

CD W65xH65

-K86
-X1 -X2 -K50BF
13 8 7 B1
6 12 3 1

110 VDC

14 5 4 2
1 2 3 4 5 6 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 19 20 9
10 11

6 20

C C

CD W65xH65

-X5
-XPE -Q921 -Q922 -Q923 -Q924 -Q941 -Q942

135
-X3

9
8
-X4
14 14 14 14 14 14
-XPE 14 1 3 14 1 3 14 1 3 14 1 3 14 14 1 3 5 7 1 3 5 7

-XPE
-XPE
-XPE
-XPE
-XPE

7
12 12 12 12 12 12
12 12 12 12 12 12

6
11 11 11 11 11 11
11 11 11 11 11 11

5
4
SD +OF iC60N SD OF SD OF SD OF SD +OF SD +OF

3
reset

reset

reset

2
reset reset reset

1
1 2 3 4 5 6 7

126
O . OFF O . OFF O . OFF O . OFF O . OFF O . OFF O . OFF O . OFF O . OFF O . OFF O . OFF O . OFF O . OFF O . OFF O . OFF O . OFF

T T T T T T
1 2 3 4 5 6 7 8 9 10 11 12
26929 26929 26929

91 91 91 91 91 91
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
12
CD W65xH65

CD W65xH65
21 91 21 91 21 91 21 91 21 91 21 91
94 94 94 94 94 94
22 94 22 94 22 94 22 94 22 94 22 94
92 2 4 92 2 4 92 2 4 92 2 4 92 92 2 4 6 8 2 4 6 8
24 92 24 92 24 92 24 92 24 92 24 92

28

Cymax ®
-B21
60 5
70 0

40
80

1
30
90
THERMOSTAT

20
0 10

D D
CD W65xH65

PIX LV BOX
HEIGHT : 800 mm
WIDTH : 1000 mm

E E

-X5

10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135

125
11/08/2018

F F

Date 11/08/2018 Project Name Title LV Box Layout Drawing Nr. =Outgoing Trafo Y
01 As Manufactured 14/03/2019 WD Drawn AF
PAPUA DFE PROJECT Schematic Diagram
X4024122-302 +S1.B X02
00 First Issued 11/08/2018 AF Checked AYH 11kV Outgoing Trafo Customer Doc. Nr. Sheet 29
Rev N° Modification Date Name Approved DTA Order N° C2030-4024122 Switchboard 17kV Switchgear PT. SCHNEIDER INDONESIA 33 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

LV DOOR
PIX W750 H800
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

NOTE :
DEVICE CODE
ENGRAVING / ( NO ENGRAVING ) REMARKS
ENGRAVING

-F50 PROTECTION RELAY VAMP 57


B -H18 HEATER ON PILOT LIGHT, GREEN B

-H30 ES CLOSE PILOT LIGHT, AMBER


-H51 CB CLOSE PILOT LIGHT, GREEN
-F50

-P50 -H52 CB OPEN PILOT LIGHT, RED


Vamp57

-HSS CB SERVICE PILOT LIGHT, GREEN


i
OK
-HST CB TEST PILOT LIGHT, RED
F1 F2
VAMP

O
-S601 OPEN/CLOSE SWITCH K&N
C I -H30 -HSS -HST C
-S650 LOCAL-REMOTE K&N
-H18 -H52 -H51 -XA1 CTB FOR PROTECTION YONGSUNG
-XA1 -XA2

-XA2 CTB FOR MEASUREMENT YONGSUNG


CTT CTT

-S650 -S601 -S625 -XV1 VTB FOR MEASUREMENT YONGSUNG


-XV1 -XV2 L R N OFF ON
T C

-XV2 VTB FOR PROTECTION YONGSUNG


PTT PTT

-P50 DIGITAL POWER METER PM 8240


D D
-S652 SHYNCRO SELECTOR SELECTOR SWITCH

PIX LV DOOR
HEIGHT : 800 (780) mm
WIDTH : 750 (710) mm

E E

F F

Date 11/08/2018 Project Name Title LV Door Layout Drawing Nr. =Outgoing Trafo Y
01 As Manufactured 14/03/2019 WD Drawn AF
PAPUA DFE PROJECT Schematic Diagram
X4024122-302 +S1.B X03
00 First Issued 11/08/2018 AF Checked AYH 11kV Outgoing Trafo Customer Doc. Nr. Sheet 30
Rev N° Modification Date Name Approved DTA Order N° C2030-4024122 Switchboard 17kV Switchgear PT. SCHNEIDER INDONESIA 33 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

LV BOX
PIX W750 H800
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

-H17
CD W65xH65 1

-S34
2

-X11 -X21 -X51 -X6L-2 -X6R-2 -X6L-1 -X6R-1

1 2 3 4 1 2 3 4 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4

4 4 12 4

B B

CD W65xH65

-K87 -Q925 -Q941


-X1 -X2
14 14

-K50BF 14 1 3 14 1 3 5 7
12 12
12 12
11 11
11 11

13 8 7 B1
SD +OF SD +OF
6 12 3 1

reset reset
110 VDC

O . OFF O . OFF O . OFF O . OFF O . OFF O . OFF

T T
14 5 4 2
1 2 3 4 5 6 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 19 20 9
10 11

91 91

6 20 94
92
21

22

24
91

94

92
2 4
21

22

24
94
92
91

94

92
2 4 6 8

C C

CD W65xH65

-XPE

Cymax ®
-Q921 -Q922 -Q923 -Q924

-B21
60 5
70 0

-X3

40
80

1
-X4

30
90
14
1 3
14
1 3
14
1 3
14
1 3
THERMOSTAT
14 14 14 14

-XPE
-XPE
-XPE
-XPE
-XPE
-XPE
12 12 12 12

20
12 12 12 12
11 11 11 11
11 11 11 11 0 10

SD +OF iC60N SD OF SD OF SD OF

reset

reset

reset
reset

1 2 3 4 5 6 7 O . OFF O . OFF O . OFF O . OFF O . OFF O . OFF O . OFF O . OFF

T T T T
1 2 3 4 5 6 7 8 9 10 11
26929 26929 26929

91 91 91 91

CD W65xH65
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
11

CD W65xH65
21 91 21 91 21 91 21 91
94 94 94 94
22 94 22 94 22 94 22 94
92 2 4 92 2 4 92 2 4 92 2 4
24 92 24 92 24 92 24 92

28

D D
CD W65xH65

PIX LV BOX
HEIGHT : 800 mm
WIDTH : 750 mm

E E

-X5

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89

89

F F

Date 11/08/2018 Project Name Title LV Box Layout Drawing Nr. =Outgoing Trafo Y
01 As Manufactured 14/03/2019 WD Drawn AF
PAPUA DFE PROJECT Schematic Diagram
X4024122-302 +S1.B X04
00 First Issued 11/08/2018 AF Checked AYH 11kV Outgoing Trafo Customer Doc. Nr. Sheet 31
Rev N° Modification Date Name Approved DTA Order N° C2030-4024122 Switchboard 17kV Switchgear PT. SCHNEIDER INDONESIA 33 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
BILL OF MATERIALS

Device Designation Description Technical Data Type / Ref. Number Manufacturer Panel Location
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

-B21 Thermostat 0 to 90 C Deg. Max 250VAC Cymax CYIT-90 Gumsung Controls =Outgoing +S1.B - -
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

-H17 Panel Lighting 220V AC, 9 Watt E27 GE =Outgoing +S1.B - -

-K50BF Instantaneous Fast Trip Relay + Socket 4COS, Vaux 110VDC REL91223+REL91350 Schneider Electric =Outgoing +S1.B - -

-K86 Aux Relay + Socket 4COS, Vaux 110VDC with LED RXM4AB2FD+RXZE2M114M Schneider Electric =Outgoing +S1.B - -

-Q921 MCB 2P, C 6A, 10kA at 415VAC, 50/60Hz; 6kA at 133VDC iC60N / A9F74206 Schneider Electric =Outgoing +S1.B - -

-Q921.1 Aux Contact of MCB for iC60, 1 SD + 1 OF iOF/SD+OF / A9A26929 Schneider Electric =Outgoing +S1.B - -

-Q922 MCB 2P, C 6A, 10kA at 415VAC, 50/60Hz; 6kA at 133VDC iC60N / A9F74206 Schneider Electric =Outgoing +S1.B - -

B -Q922.1 Aux Contact of MCB for iC60, 1 SD + 1 OF iOF/SD+OF / A9A26929 Schneider Electric =Outgoing +S1.B - - B

-Q923 MCB 2P, C 6A, 10kA at 415VAC, 50/60Hz; 6kA at 133VDC iC60N / A9F74206 Schneider Electric =Outgoing +S1.B - -

-Q923.1 Aux Contact of MCB for iC60, 1 SD + 1 OF iOF/SD+OF / A9A26929 Schneider Electric =Outgoing +S1.B - -

-Q924 MCB 2P, C 6A, 10kA at 415VAC, 50/60Hz; 6kA at 133VDC iC60N / A9F74206 Schneider Electric =Outgoing +S1.B - -

-Q924.1 Aux Contact of MCB for iC60, 1 SD + 1 OF iOF/SD+OF / A9A26929 Schneider Electric =Outgoing +S1.B - -

-Q941 MCB 4P, C 2A, 50kA at 415VAC, 50/60Hz iOF/SD+OF / A9A26929 Schneider Electric =Outgoing +S1.B - -

-Q941.1 Aux Contact of MCB for iC60, 1 SD + 1 OF iOF/SD+OF / A9A26929 Schneider Electric =Outgoing +S1.B - -

C -Q942 MCB 4P, C 2A, 50kA at 415VAC, 50/60Hz iOF/SD+OF / A9A26929 Schneider Electric =Outgoing +S1.B - - C

-Q942.1 Aux Contact of MCB for iC60, 1 SD + 1 OF iOF/SD+OF / A9A26929 Schneider Electric =Outgoing +S1.B - -

-S34 Microswitch XP42-Z11, 1NC, 16A, 400VAC - Saia-Burgess =Outgoing +S1.B - -

-F50 Protection Relay VAMP 57 VAMP 57 Schneider =Outgoing +S1.D - -

-H18 Pilot Light with Integral LED Green, Vaux 220 AC, 50/60Hz ZB5AVM3+ZB5AV033 Schneider Electric =Outgoing +S1.D - -

-H30 Pilot Light with Integral LED Yellow, Vaux 24-132 VDC/AC, 50/60Hz ZB5AVBG5+ZB5AV053 Schneider Electric =Outgoing +S1.D - -

-H51 Pilot Light with Integral LED Green, Vaux 24-132 VDC/AC, 50/60Hz ZB5AVBG3+ZB5AV033 Schneider Electric =Outgoing +S1.D - -

D -H52 Pilot Light with Integral LED Red, Vaux 24-132 VDC/AC, 50/60Hz ZB5AVBG4+ZB5AV043 Schneider Electric =Outgoing +S1.D - - D
-HSS Pilot Light with Integral LED Green, Vaux 24-132 VDC/AC, 50/60Hz ZB5AVBG3+ZB5AV033 Schneider Electric =Outgoing +S1.D - -

-HST Pilot Light with Integral LED Red, Vaux 24-132 VDC/AC, 50/60Hz ZB5AVBG4+ZB5AV043 Schneider Electric =Outgoing +S1.D - -

-P50 Digital Power Meter PM8240, 3P4W MEISEPM8240 Schneider =Outgoing +S1.D - -

-S601 Control Switch, Spring Return to Center 1 poles, V/Imax 690VAC/20A, 110VDC/1A S0-CA10-A714-600 K&N =Outgoing +S1.D - -

-S625 Synchro Check Switch 2 Poles, 2 Position with 60 degree Switching Angle S0-CA10-A201-620 FT2 K&N =Outgoing +S1.D - -

-S611 Ammeter Switch, Single Pole 3 Current 4 Pos, 90 degree, V/Imax 690VAC/20A, 110VDC/1A S0-CA10-A058-621 K&N =Outgoing +S1.D - -

-S650 Control Switch, Multi-Step 2 Pos, 3 Poles, V/Imax 690VAC/20A, 110VDC/1A CA10-A722-600 K&N =Outgoing +S1.D - -
E E
-XA1 Current Test Block 4P, 10A, 250VAC YS CTT-04C / X0140500004 YongSung Electric =Outgoing +S1.D - -

-XA2 Current Test Block 4P, 10A, 250VAC YS CTT-04C / X0140500004 YongSung Electric =Outgoing +S1.D - -

-XV1 Voltage Test Block 4P, 10A, 250VAC YS PTT-04C / X0140500002 YongSung Electric =Outgoing +S1.D - -

-XV2 Voltage Test Block 4P, 10A, 250VAC YS PTT-04C / X0140500002 YongSung Electric =Outgoing +S1.D - -

-H101 Voltage Presence Indicating System LED VPIS-V2 Schneider Electric =Outgoing +S4 - -

-Q30 Earthing Switch Auxiliary Contact EX-7.11M, 4NO + 4NC ES-PIX-12 SCHNEIDER =Outgoing +S4 - -
11/08/2018

F F

Date 11/08/2018 Project Name Title BILL OF MATERIALS Drawing Nr. =Outgoing Trafo V
01 As Manufactured 14/03/2019 WD Drawn AF
PAPUA DFE PROJECT Schematic Diagram
X4024122-302 +S1.B Y01
00 First Issued 11/08/2018 AF Checked AYH 11kV Outgoing Trafo Customer Doc. Nr. Sheet 32
Rev N° Modification Date Name Approved DTA Order N° C2030-4024122 Switchboard 17kV Switchgear PT. SCHNEIDER INDONESIA 33 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
BILL OF MATERIALS

Device Designation Description Technical Data Type / Ref. Number Manufacturer Panel Location
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

-Q51 Vacuum Circuit Breaker 3P, c/w F2 (CC), F11 (OC) HVX Schneider Electric =Outgoing +S4 - -
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

-R11 Heating Resistor 150W, 220/240VAC - Local =Outgoing +S4 - -

-SS1 Service Position Micro Switch EX1.20YR2 (Yellow), 1NO - ELMEX =Outgoing +S4 - -

-SS2 Service Position Micro Switch EX1.20YR2 (Yellow), 1NO - ELMEX =Outgoing +S4 - -

-SS3 Service Position Micro Switch EX1.20YR2 (Yellow), 1NO - ELMEX =Outgoing +S4 - -

-SS4 Service Position Micro Switch EX1.20YR2 (Yellow), 1NO - ELMEX =Outgoing +S4 - -

-ST1 Test Position Micro Switch EX1.20BR2 (Blue), 1NC - ELMEX =Outgoing +S4 - -

B -ST2 Test Position Micro Switch EX1.20BR2 (Blue), 1NC - ELMEX =Outgoing +S4 - - B

-ST3 Test Position Micro Switch EX1.20BR2 (Blue), 1NC - ELMEX =Outgoing +S4 - -

-ST4 Test Position Micro Switch EX1.20BR2 (Blue), 1NC - ELMEX =Outgoing +S4 - -

-T51L1 4 Cores Current Transformer Refer to sheet A02 CT Refer to sheet A02 =Outgoing +S4 - -

-T51L2 4 Cores Current Transformer Refer to sheet A02 CT Refer to sheet A02 =Outgoing +S4 - -

-T51L3 4 Cores Current Transformer Refer to sheet A02 CT Refer to sheet A02 =Outgoing +S4 - -

-T61L1 2 Winding Voltage Transformer Refer to sheet A02 - Refer to sheet A02 =Outgoing +S4 - -

C -T61L2 2 Winding Voltage Transformer Refer to sheet A02 - Refer to sheet A02 =Outgoing +S4 - - C

-T61L3 2 Winding Voltage Transformer Refer to sheet A02 - Refer to sheet A02 =Outgoing +S4 - -

-X021 Mate n Lock Terminal SP SC 2.5/8, 8 Pole - PHOENIX =Outgoing +S4 - -

-X022 Mate n Lock Terminal SP SC 2.5/8, 8 Pole - PHOENIX =Outgoing +S4 - -

-X041 Mate n Lock Terminal SP SC 2.5/8, 8 Pole - PHOENIX =Outgoing +S4 - -

-X042 Mate n Lock Terminal SP SC 2.5/8, 8 Pole - PHOENIX =Outgoing +S4 - -

-X051 Mate n Lock Terminal SP SC 2.5/8, 8 Pole - PHOENIX =Outgoing +S4 - -

D -X052 Mate n Lock Terminal SP SC 2.5/8, 8 Pole - PHOENIX =Outgoing +S4 - - D

E E
11/08/2018

F F

Date 11/08/2018 Project Name Title BILL OF MATERIALS Drawing Nr. =Outgoing Trafo V
01 As Manufactured 14/03/2019 WD Drawn AF
PAPUA DFE PROJECT Schematic Diagram
X4024122-302 +S1.B Y02
00 First Issued 11/08/2018 AF Checked AYH 11kV Outgoing Trafo Customer Doc. Nr. Sheet 33
Rev N° Modification Date Name Approved DTA Order N° C2030-4024122 Switchboard 17kV Switchgear PT. SCHNEIDER INDONESIA 33 Sh.

1 2 3 4 5 6 7 8

You might also like