You are on page 1of 35

1 2 3 4 5 6 7 8

MANUFACTURING : 1 Unit

A NAME OF PANEL CUBICEL NO FACTORY NO. A


All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

BUS SECTION =J01 FC101

B B

C C

01 29/04/2020 WD As Manufactured
D D
00 12/02/2020 FND First Issued

Rev N° Date Name Modification

Project Name

PENYEMPURNAAN SISTEM 20KV


Owner PT. PLN (PERSERO) UPT BANDA ACEH Order N° C2030-4029420
E E
Customer PT. ARAINS Switchboard 20kV MV SWITCHGEAR

EJIP PLOT 4B1-4B2 CIKARANG SELATAN Panel =PIX24


BEKASI 17550, JAWA BARAT, Title
Cover Sheet
INDONESIA
Tel : (+62-21) 897 02 03
PT SCHNEIDER INDONESIA Fax : (+62-21) 897 02 09
Date Name Sign Drawing Nr. X4029420-303
F Drawn 12/02/2020 FND Customer Doc. Nr. F

Checked 12/02/2020 BWP Document Type A Sheet 1

Approved 12/02/2020 DTA Format A3 Scale NTS 35 Sh.


1

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SHEET
INDEX MODIFICATION
DESCRIPTION OF TITLE
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

00 01 02 03 04 05 06 07 08 09
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

1 Cover Sheet 00 01
2 List of Contents 00 01
3 Legends 00 01
4 Power Circuit 00 01
5 Power & Measurement Circuit 00 01
6 Power Circuit 00 01
7 Power & Measurement Circuit 00 01
B 8 AC/DC Supplies 00 01 B

9 Control Circuit 00 01
10 Control Circuit 00 01
11 Control Circuit 00 01
12 Control Circuit 00 01
13 Control Circuit 00 01
14 Control Circuit 00 01
15 Control Circuit 00 01

C 16 Control Circuit 00 01 C
17 Control Circuit 00 01
18 Control Circuit 00 01
19 Terminal Plan 00 01
20 Terminal Plan 00 01
21 Terminal Plan 00 01
22 Terminal Plan 00 01
23 Terminal Plan 00 01
24 Terminal Plan 00 01
D D
25 Terminal Plan 00 01
26 Terminal Plan 00 01
27 Terminal Plan 00 01
28 Terminal Plan 00 01
29 Terminal Plan 00 01
30 Terminal Plan 00 01
31 Terminal Plan 00 01
32 LV Box Layout 00 01
E 33 LV Box Layout 00 01 E

34 Bill of Materials 00 01
35 Bill of Materials 00 01
.

F F

Date 12/02/2020 Project Name Title List of Contents Drawing Nr. =PIX24
01 As Manufactured 29/04/2020 WD Drawn FND
PENYEMPURNAAN SISTEM 20KV X4029420-303
00 First Issued 12/02/2020 FND Checked BWP PANEL BUS SECTION Customer Doc. Nr. Sheet 2
Rev N° Modification Date Name Approved DTA Order N° C2030-4029420 Switchboard 20kV MV SWITCHGEAR PT SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SWITCHES CONTACTS AND COIL PASSIVE COMPONENTS FUSE


All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A Description Symbol Description Symbol Description Symbol Description Symbol A


All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

NORMALLY OPEN
For POSITION SWITCH
1 2
THERMOSTAT RESISTOR FUSE
NORMALLY CLOSE
For POSITION SWITCH
IEC S00264 IEC S00259 & S00260 IEC S00555 IEC S00362

NORMALLY OPEN
For CONTACTOR
MV CIRCUIT BREAKER 1 2
In Rack Out Position RESISTOR FUSE ISOLATOR
NORMALLY CLOSE 3
Adjustable
For CONTACTOR

B IEC S00287 IEC S00284 & S00286 IEC S00557 IEC S00369 B
Make Contact
1 DELAYED CLOSING
MINIATURE CIRCUIT
BREAKER Break Contact
DIODE TRANSFORMER
2 DELAYED OPENING
IEC S00287 & S00191 IEC S00243 & S00245 IEC S00641 Description Symbol
REMOTE

P2
Make Contact
LOCAL

DELAYED CLOSING S2
LOCAL REMOTE LED CURRENT
Break Contact
SWITCH WITH KEY Light Emitting Diode TRANSFORMER
DELAYED OPENING S1
P1
IEC S00480 & S00179 IEC S00244 & S00246 IEC S00642 IEC S01344

C A C
CLOSE
OPEN

1 2 a
CB CONTROL SWITCH N
Spring Return to Center THERMAL SWITCH SPACE HEATER VOLTAGE
(Bimetal Break Contact) TRANSFORMER
n

IEC S00249 IEC S00265 IEC S00566 IEC S00842 N


OFF

2
3
4
5
1

MULTI STEP DISCONNECTOR SOCKET OUTLET TOROIDAL CT /


WITH OFF OFF Load Isolating Switch (Receptacle) CBCT / ZCT

IEC S00272 IEC S00288 IEC S00460 IEC S00889

D EMERGENCY DISCONNECTOR SURGE ARRESTER GROUNDING AND TERMINATION D


STOP ON Load Isolating Switch

IEC S00258 IEC S00290 IEC S00373 Description Symbol

PUSH BUTTON RELAY COIL LAMP AND INDICATION EARTH / GROUND TERMINAL WIRING CODE
NO & NC

IEC S00254 IEC S00305 Description Symbol IEC S00200 Terminal Designation
-X1 AC Supply For Internal Wiring
1 1 1
-X2 DC Supply For Internal Wiring
CONTACTS AND COIL TIMER OFF DELAY LAMP INDICATION OR OR TERMINAL BLOCK
RELAY COIL LED FL -X3 Current Circuit Wiring
E 2 2 2 -X4 Voltage Circuit Wiring E
Description Symbol IEC S00311 IEC S00965 IEC S00017
-X5 Spare Contact & To External
NORMALLY OPEN BUZZER
( NO ) CONTACT 1 1 -X6 Output Contact to SCADA/PLC
IEC S00973
NORMALLY CLOSE
TIMER ON DELAY OR CONNECTING LINK -X7 Aux. Contact For Internal Wiring
RELAY COIL HORN TERMINAL BLOCK
( NC ) CONTACT 2 2 -X11 Interconnection Wiring For AC Control Circuit
IEC S00227 & S00229 IEC S00312 IEC S00969 IEC S00044 -X21 Interconnection Wiring For DC Control Circuit
CAPACITIVE -X31 Interconnection Wiring For Current Circuit
CHANGE-OVER DIVIDER &
BREAK BEFORE -X41 Interconnection Wiring For Voltage Circuit
OR MECHANICALLY TEST BLOCK
MAKE CONTACT VOLTAGE INDICATION
LATCHED RELAY COIL -X51 Interconnection Wiring for Interpanel
VPIS
F IEC S00230 IEC S00318 -X61 Communication Wiring F

Date 12/02/2020 Project Name Title Legends Drawing Nr. =PIX24


01 As Manufactured 29/04/2020 WD Drawn FND
PENYEMPURNAAN SISTEM 20KV X4029420-303
00 First Issued 12/02/2020 FND Checked BWP PANEL BUS SECTION Customer Doc. Nr. Sheet 3
Rev N° Modification Date Name Approved DTA Order N° C2030-4029420 Switchboard 20kV MV SWITCHGEAR PT SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

CIRCUIT BREAKER TEST BLOCKS


Z-PLAN
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

L1
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

L2 /4.E5 TYPICAL APPLICATION


(DURING TEST)
L3 -XT01 OF TEST PLUG

GND ETB14P-V
TEST PLUG
ETB14
2 1
1 TEST BLOCK 2
4 3 !
3 4

FROM VT
CB AUX CONTACTS CAUTION!
6 5
A13-A12-A14 /13.B2 5 6 /6.C6 This terminals only
for Voltage Injection!
A16-A15-B1 /16.C2 8 7
7 8
B3-B2-B4 /11.B2
10 9
B5-B6 /16.C1 9 10
B B7-B8 /10.B2 12 11 B
11 12 /10.A4
C9-C10 /15.C1
14 13
C11-C12 /16.C1 13 14
Fit external links 13-14 &
END OF CHARGING SIGNAL FROM DC 16 15
-Q51 AUXILIARY 15 16 /10.C7 15-16 if station DC auxiliary
A8-A7-A9 /15.C2 is required during testing.
18 17
B15-B16 /15.C3 17 18
CB RELEASE COILS 20 19
19 20 /10.B8
CLOSING /9.D5
22 21

ALREADY CONNECT INSIDE


OPENING /10.D1 21 22
24 23
23 24

FROM CT
CAUTION!
26 25 This terminals only
25 26 /5.A4
for Current Injection!
28 27
C 27 28 C

Line Side Equipment Equipment Line Side


Socket (OR) Side Socket Side Sockets Sockets (OR)

REAR VIEW FRONT VIEW

/4.E5 TYPICAL APPLICATION


(DURING TEST)
-XT02 OF TEST PLUG

GND ETB14P-V
TEST PLUG
ETB14
2 1
1 TEST BLOCK 2
D 4 3 ! D
3 4

FROM VT
CAUTION!
6 5
5 6 /6.B6 This terminals only
for Voltage Injection!
8 7
7 8
10 9
9 10
12 11
11 12
14 13
13 14
Fit external links 13-14 &
FROM DC 16 15
15 16 15-16 if station DC auxiliary
AUXILIARY
is required during testing.
18 17
17 18

/10.D7

/4.D6
/9.E6

/4.A6
20 19
E 19 20 E
22 21

ALREADY CONNECT INSIDE


21 22
24 23
23 24

FROM CT
-XPE CAUTION!
26 25 This terminals only
1 2 3 4 5 6 7 8 25 26 /5.D4
for Current Injection!
28 27
-PE 2 27 28
/5.D3

/5.B3

/6.D5

/6.C5

/6.D5
Line Side Equipment Equipment Line Side
Socket (OR) Side Socket Side Sockets Sockets (OR)

REAR VIEW FRONT VIEW


To Next Sheet

F F

Date 12/02/2020 Project Name Title Power Circuit Drawing Nr. =PIX24
01 As Manufactured 29/04/2020 WD Drawn FND
PENYEMPURNAAN SISTEM 20KV X4029420-303
00 First Issued 12/02/2020 FND Checked BWP PANEL BUS SECTION Customer Doc. Nr. Sheet 4
Rev N° Modification Date Name Approved DTA Order N° C2030-4029420 Switchboard 20kV MV SWITCHGEAR PT SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
PROTECTION RELAY
CURRENT DIGITAL ENERGY METER DIGITAL POWER METER
TEST BLOCK EDMI MK6N PM5350
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

From Prev. Sheet

-F50
CT inputs
L1 L2 L3
-XT01
/4.C7
P1
1S1 -X3 21 22 C1 5A C2
1

1S2 -X3 23 24 C4 5A C5
2

1S3 -X3 25 26 C7 5A C8
3
B P2 B
-X3 27 28 C11 5A C10
+S4 P1 /4.F5
1S1 4
-T51L1-3
1st Winding -X3 CURRENT
1S2 -X3 5 TEST BLOCK
CT's Ratio and Burden
See Single Line 6

1S3 -X3
-X3 7
P2
8
P1
1S1 -X3
-X3 9

1S2 10

C 1S3 C
P2

-P50 -P51
CT inputs CT inputs

-XT02
/4.E7 Ia I1
P1
2S1 -X3 21 22 1 3 I1+ I1- -X3 L1
11 21
Ib I2
2S2 -X3 23 24 4 6 I2+ I2- -X3 L2
12 22 CT METERING CLASS
Ic I3 TO EXTERNAL
2S3 -X3 25 26 8 10 I3+ I3- -X3 L3
D 13 23 D
P2
-X3 27 28 -X3 N
+S4 P1 /4.F5
2S1 14 24
-T51L1-3
2nd Winding -X3 CURRENT
2S2 -X3 15 TEST BLOCK
CT's Ratio and Burden
See Single Line 16

2S3 -X3
-X3 17
P2
18
P1
2S1 -X3
-X3 19

2S2 20

E E
2S3

P2

To Next Sheet
F F

Date 12/02/2020 Project Name Title Power & Measurement Circuit Drawing Nr. =PIX24
01 As Manufactured 29/04/2020 WD Drawn FND
PENYEMPURNAAN SISTEM 20KV X4029420-303
00 First Issued 12/02/2020 FND Checked BWP PANEL BUS SECTION Customer Doc. Nr. Sheet 5
Rev N° Modification Date Name Approved DTA Order N° C2030-4029420 Switchboard 20kV MV SWITCHGEAR PT SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

VOLTAGE TRANSFORMERS VOLTAGE


STAR & STAR TEST BLOCK
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A From Prev. Sheet A


All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

L1 L2 L3

+S1.B -XT02
VT WITHDRAWABLE (AIN) -X021 -Q941 /4.D7
-F30L1 -X4 4P, 2A 1 2 UL11
-T61 L1 1F 1M 1 3 4
/7.C4
1a
1.4 A A -X4 3 4 UL12
B 2F 2M 2 5 6
/7.C4 B
15/24 kV 1n
-X4 5 6 UL13
3F 3M 3 7 8
/7.C4
2a
N -X4 7 8 UN1
4F 4M 4 1 2
/7.C4
PE 2n
-F30L2 -X4 VOLTAGE
-T61 L2 5F 5M 5 TEST BLOCK
1a
-Q941.1
ES AUX. CONTACTS
1.4 A A -X4
/4.F5 OF /13.B6
b 1-2 /11.C5 15/24 kV 1n 6F 6M 6
OF /15.C8
a 3-4 /16.C5
b 5-6 /17.C6 2a
a 7-8 /17.C6 N
+S1.B -XT01
C b 9-10 /17.C7 PE 2n -X022 -Q942 /4.B7 C
a 11-12 /17.C7 -F30L3 -X4 4P, 2A 1 2 UL21
-T61 L3 1F 1M 7 3 4
/7.D4
b 13-14 /17.C8 1a
a 15-16 /17.C8 1.4 A A -X4 3 4 UL22
2F 2M 8 5 6
/7.D4
15/24 kV 1n
-Q30 -X4 5 6 UL23
3F 3M 9 7 8
/7.D4
2a
N -X4 7 8 UN2
4F 4M 10 1 2
/7.D4
PE 2n
-X4 VOLTAGE
5F 5M 11 TEST BLOCK
-Q942.1
-X4
EARTHING SWITCH /4.F5 OF /13.B6
6F 6M 12
D OF /15.C8 D
-H101

-X022
/4.F5
7F 7M

VOLTAGE INDICATOR

E E

To Next Sheet

F F

Date 12/02/2020 Project Name Title Power Circuit Drawing Nr. =PIX24
01 As Manufactured 29/04/2020 WD Drawn FND
PENYEMPURNAAN SISTEM 20KV X4029420-303
00 First Issued 12/02/2020 FND Checked BWP PANEL BUS SECTION Customer Doc. Nr. Sheet 6
Rev N° Modification Date Name Approved DTA Order N° C2030-4029420 Switchboard 20kV MV SWITCHGEAR PT SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
PROTECTION RELAY
DIGITAL ENERGY METER DIGITAL POWER METER
EDMI MK6N PM5350
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A To Next Sheet A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

L1 L2 L3

-P51
-P50

VT inputs - 3PH/4W
VT inputs - 3PH/4W
V1 V2 V3
B Va Vb Vc B

V1 V2 V3 VN
2 5 9 13

UL11 -X4 L1
/6.B7 13

UL12 -X4 L2
/6.B7 14 3PH/4W
-X4 L3 VT METERING
UL13
/6.B7 15 CLASS
TO EXTERNAL
C UN1 -X4 N C
/6.B7 16

TO RISER

UL21 -X4 L1
/6.C7 17

UL22 -X4 L2
/6.C7 18 3PH/4W
-X4 L3 VT PROTECTION
UL23
/6.C7 19 CLASS
TO EXTERNAL
UN2 -X4 N
D /6.D7 20 D

-F50 C19 C20 C21 C22 -F50

VT inputs - 3PH/4W

V Check Synch
V1 V2 V3

C23 C24

E 1 3 E

OFF

ON
+S1.D
-S625

-S625 2 4 -X41 L1
1st /7.E6 -X41 9
2nd /7.E6 10
BUS VOLTAGE
-X41 L2
3rd
FOR PROTECTION
-X41 11
4th 12

F F

Date 12/02/2020 Project Name Title Power & Measurement Circuit Drawing Nr. =PIX24
01 As Manufactured 29/04/2020 WD Drawn FND
PENYEMPURNAAN SISTEM 20KV X4029420-303
00 First Issued 12/02/2020 FND Checked BWP PANEL BUS SECTION Customer Doc. Nr. Sheet 7
Rev N° Modification Date Name Approved DTA Order N° C2030-4029420 Switchboard 20kV MV SWITCHGEAR PT SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SPACE LIGHTING MOTOR DRIVE TRIPPING CIRCUIT CLOSE AND CONTROL FOR ANNUNCIATOR
HEATER CIRCUIT
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

-X11 -X11

FROM PREV. CUBICLE


disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

INTERCONNECTION

INTERCONNECTION
TO NEXT CUBICLE
A 1 2 A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

-X11 -X11
3 4
-X21 -X21
1 2
-X21 -X21
3 4

B B

1 3 1 3 1 3 1 3 1 3
+S1.B +S1.B +S1.B +S1.B +S1.B
-Q921 -Q922 -Q923 -Q924 -Q925
2P, 6A 2P, 10A 2P, 6A 2P, 6A 2P, 6A
2 4 2 4 2 4 2 4 2 4

-Q921.1 -Q922.1 -Q923.1 -Q924.1 -Q925.1


OF /12.B4 OF /12.B4 OF /12.B4 OF /12.B5 OF
C OF /16.C6 OF /16.C6 OF /16.C7 OF /16.C7 OF /16.C8 C

-X1 -X1
1 2

1 1

-S34 Contact will open


-B21 >ϑ
Heater

if door closed
c 2

-X1
D 3 D

1
+S4
-R11 L
-H34 -X2 -X2 -X2 -X2 -X2 -X2 -X2 -X2 -X2 -X2
2 9 8 10 11 14 13 12 15 16 17
LED
N

CS+

CS+

CS+
TR+

TR+

TR+

CS-

CS-

CS-
TR-

TR-

TR-
M+

L+
M-

L-
E -X1 -X1 E
5 6
/9.E1

/9.C1

/13.E1

/10.E1

/10.A1

/13.A1

/11.E1
/9.E1

/9.A1
/11.A1

/12.E1

/12.A1
/10.E7

/10.A7

/9.E7

/9.A7
F F

Date 12/02/2020 Project Name Title AC/DC Supplies Drawing Nr. =PIX24
01 As Manufactured 29/04/2020 WD Drawn FND
PENYEMPURNAAN SISTEM 20KV X4029420-303
00 First Issued 12/02/2020 FND Checked BWP PANEL BUS SECTION Customer Doc. Nr. Sheet 8
Rev N° Modification Date Name Approved DTA Order N° C2030-4029420 Switchboard 20kV MV SWITCHGEAR PT SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SPRING CHARGE CB CLOSING CIRCUIT BLOCKING CLOSING 25 - SYNCH DIGITAL ENERGY DIGITAL POWER
MOTOR LOCAL REMOTE CIRCUIT RELEASE CHECK METER METER
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

CS+ CS+
/8.E7 /8.E7
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

-X5 -X51 -X51

REMOTE
LOCAL
-S650 1 3 -F50 H7 H8 68 17 18
+S1.D
1st /9.A3 -S650 +S1.D -F50 G5
/9.A2 /9.A2
RL 4

INTERLOCK FROM

INTERLOCK FROM
2nd /9.A3 -S650

EXT. INCOMING

BUS COUPLER
3rd /10.B3 2 4 RL 10
/10.E4 - -
4th /10.B3
/10.E5
5th /13.B5
6th /13.B5 H9
7th /17.C5 G6
-X5 -X51 -X51
8th /17.C5
69 19 20
B -S601 -X5 -X5 32 34 -X5 B
1st /9.B2 1 2 -K86 5
2nd /10.B3 -F50 G1 /10.E8
31

PERMIT CLOSE FROM


BUS RISER / UTX
CLOSE FROM
CLOSE
OPEN 3 RL 8

REMOTE
+S1.D - -
-S601 /9.B2
/10.E5

4
G2
-X5 -X5 -X5
M+
/8.E5 3 4 6

C C

-X2 -X2
1 3

X01:A1 X01:A5

-P50 7 -P51 +
L/~ L/~

Vaux. Vaux.
U1 Supply Supply
C1
D M1 M F2 CC D
/4.C3 N/~ N/~
C2
U2 11 -
X01:A2 X01:A6 G

-X2
2
M-
/8.E4 /4.E5

CS- CS-
/8.E6 /8.E6

LEGEND OF HVX CB
Wiring Diagram Doc. No. : AGS553252-01 Rev. 03
E E
F2 : Closing Release Coil
F11 : Opening Release Coil
M1 : Motor for Spring Charging
S2 : Motor Mechanism Aux. Switch
S11/12 : CB Auxiliary Contact
S41/42 : Push button On/Off on CB
S61-63 : CB Truck Position Switches

F F

Date 12/02/2020 Project Name Title Control Circuit Drawing Nr. =PIX24
01 As Manufactured 29/04/2020 WD Drawn FND
PENYEMPURNAAN SISTEM 20KV X4029420-303
00 First Issued 12/02/2020 FND Checked BWP PANEL BUS SECTION Customer Doc. Nr. Sheet 9
Rev N° Modification Date Name Approved DTA Order N° C2030-4029420 Switchboard 20kV MV SWITCHGEAR PT SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

OPENING CB OPENING CIRCUIT 50/51, 50N/51N 50BF PROTECTION 50/51, 50N/51N EXTERNAL
RELEASE LOCAL REMOTE 67/67N RELAY TRIP & LOCKOUT TRIP
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

TR+ TR+
/8.E5 /8.E6
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

-F50 D6 9

REMOTE
17

LOCAL
5 7 -XT01
/4.B7 -XT01
L3 +S1.D +S1.D /4.C7
/9.A2 /9.B2
-S650 -S650
/10.E6 6 8
10 -X51 -X51
18
5 6
-F50 H5 -F50 H3 -F50 H16 H17
D5
-X5 -X5
7 8 RL 3 RL 2 RL 7

50BF FROM

50BF FROM
OUTGOING

OUTGOING
B -F50 G3 - -
B
/10.E4 /10.E4

OPEN FROM REMOTE


/10.F4
X01:B7

CLOSE
1

OPEN
RL 9
3 +S1.D -
/9.B2 H6 H4 H18
-Q51 S12 -S601 /10.E5
/4.B3 4
-X51 -X51
2 7 8
12
X01:B8 G4
-X5 -X5 -XT01
20
9 10
-XT01
-X2
7 11

19

C C

13
-X2 -X2 -XT01
6 4 /4.B7

X01:D11 D12 A3
14
-F50 J2
L/~
13 1
-Q51 S12 S11
/4.C3 14 Vaux.
2
Supply
GND
C1
N/~
D F11 OC D
J1
C2

A4
A1 A1
-K86 -K50BF

/4.E5
16
-X2 -XT01 RXM RXM
5 110VDC 110VDC
A2 A2

15
TR- TR-
/8.E5 /8.E5
ASSIGNMENT -F50 ASSIGNMENT -F50 ASSIGNMENT -F50 ASSIGNMENT -F50 -K86 -K50BF
WD a J14-J13 /17.C3 RL8 a G2-G1 /9.B3 L1 D2-D1 /13.D2 LED1 1st /12.C5 1st /14.C4
E WD b J12-J11 /15.C6 RL9 a G4-G3 /10.B3 L2 D4-D3 /13.D2 LED2 2nd /16.C8 2nd /14.C5 E
RL1 a H2-H1 /17.C4 RL10 a G6-G5 /9.B6 L3 D6-D5 /10.B2 LED3 3rd /9.B4 3rd
RL2 a H4-H3 /10.B8 a G9-G8 L4 D8-D7 /13.D3 LED4 4th /16.C3 4th
RL11 /15.C7
RL3 a H6-H5 /10.B4 b G9-G7 L5 D10-D9 /13.D3 LED5
a H9-H8 a G12-G11 L6 D12-D11 /13.D4 LED6
RL4 /9.B4 RL12 /15.C7
b H9-H7 b G12-G10 L7 D14-D13 /13.D4 LED7
a H12-H11 a G15-G14 L8 D16-D15 /13.D5 LED8
RL5 /17.C4 RL13 /12.B5
b H12-H10 b G15-G13
a H15-H14 a G18-G17 L9 F2-F1 /13.D5 L13 F10-F9
RL6 /17.C3 RL14
b H15-H13 b G18-G16 L10 F4-F3 /13.D6 L14 F12-F11
a H18-H17 DIGITAL OUTPUT L11 F6-F5 /13.D7 L15 F14-F13
RL7 /10.B8
b H18-H16 L12 F8-F7 /13.D7 L16 F16-F15
F DIGITAL OUTPUT DIGITAL INPUT DIGITAL INPUT F

Date 12/02/2020 Project Name Title Control Circuit Drawing Nr. =PIX24
01 As Manufactured 29/04/2020 WD Drawn FND
PENYEMPURNAAN SISTEM 20KV X4029420-303
00 First Issued 12/02/2020 FND Checked BWP PANEL BUS SECTION Customer Doc. Nr. Sheet 10
Rev N° Modification Date Name Approved DTA Order N° C2030-4029420 Switchboard 20kV MV SWITCHGEAR PT SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

CB OPEN CB CLOSE CB TEST CB OPEN CB CLOSE ES BLOCKING


POSITION CLOSE
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

CS+
/8.E7
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

-X5
-X2 -X5 28

18 32

INTERLOCK FROM
HV SIDE 150 kV
-
X01:B2
-X051 3F
3M

9 1 1 -X5
-Q51 S12 29
B /4.B3 10 -ST2 B
2 2
-X5
-X051 4M 26
4F
X01:B3 X01:B4
-X041
1F

-X2 -X2 -X5 1M


19 20 33 12 14 12 14

-K52 -K51
/11.E2 /11.E2
11 11 S1:1
+S4
-Q30
/6.C1
S1:2
C C

-X041
2M

2F
-X5
27
-X2
26
-X07 1F
1M

11
+S4
D -S8 14 D

+S4 A
X1 X1
-Y8
A1 A1 A1 -H52 -H51
-K52 -K51 -KST
B
RXM RXM RXM
LED LED
110VDC 110VDC 110VDC GREEN RED
A2 A2 A2 X2 X2 -X07 2M
CB OPEN CB CLOSE
2F
-X2
CS- 27
/8.E6
-K52 -K51 -KST
1st /11.C3 1st /11.C4 1st /17.C2
E 2nd /17.C1 2nd /17.C1 2nd /13.B3 E
3rd /16.C4 3rd /16.C5 3rd
4th 4th 4th

F F

Date 12/02/2020 Project Name Title Control Circuit Drawing Nr. =PIX24
01 As Manufactured 29/04/2020 WD Drawn FND
PENYEMPURNAAN SISTEM 20KV X4029420-303
00 First Issued 12/02/2020 FND Checked BWP PANEL BUS SECTION Customer Doc. Nr. Sheet 11
Rev N° Modification Date Name Approved DTA Order N° C2030-4029420 Switchboard 20kV MV SWITCHGEAR PT SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

AC/DC SUPPLY 50/51, 50BF [SPARE] [SPARE] [SPARE]


FAIL 50N/51N
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

L+
/8.E7
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

12 14 12 14 -X5 -X5 -X5


+S1.B +S1.B
-Q921.1 OF -Q923.1 OF 59 61 63
/8.C1 /8.C5 -F50 G13 G14
11 11

RL 13

B /10.F5 B
12 14 12 14
+S1.B +S1.B
-Q922.1 OF -Q924.1 OF
G15
/8.C4 /8.C6
11 11 -X5 -X5 -X5
60 62 64

12 14

-K86
/10.E8
11

C C

-X2
+S1.D 24
-U101
+VE C F1 F2 F3 F4 F5 F6
~/+
ANNUNCIATOR
6 WINDOWS PB +
2 BUZZER INPUTS
MBAS 08 Vaux.
Supply

D D
E ~/- -VE F1 F2 F3 F4 F5 F6

[SPARE]

[SPARE]

[SPARE]
AC/DC SUPPLY FAIL

OCR & EF FAIL

BREAKER FAIL
-X2
25

E E

L-
/8.E7

F F

Date 12/02/2020 Project Name Title Control Circuit Drawing Nr. =PIX24
01 As Manufactured 29/04/2020 WD Drawn FND
PENYEMPURNAAN SISTEM 20KV X4029420-303
00 First Issued 12/02/2020 FND Checked BWP PANEL BUS SECTION Customer Doc. Nr. Sheet 12
Rev N° Modification Date Name Approved DTA Order N° C2030-4029420 Switchboard 20kV MV SWITCHGEAR PT SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

CB OPEN CB CLOSE CB TEST CB SERVICE SWITCH POSITION VT SUPPLY DIGITAL INPUTS


POSITION POSITION LOCAL REMOTE FAIL [SPARE]
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

TR+
/8.E6
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

-X2 -X5 -X5 -X5


21 36 46 72

X01:A12 -X5 -X5


-X051 7F
7M 53 54

REMOTE
LOCAL
9 11
22 24 1 12 14 12 14
13 5 +S1.B +S1.B
+S1.D +S1.D
-Q51 S11 -KST /9.B2 /9.B2 -Q941.1 OF -Q942.1 OF
-SS2
B /4.B3 14 6 /11.E3 2
-S650 -S650 /6.C5 /6.D5 B
21 11 11
10 12

-X051 8M
8F
X01:A13 X01:A14
-X5 -X5
55 56

-X2 -X2 -X5


22 23 37 -X5 -X5
47 73

C C

-F50 D2 -F50 D4 -F50 D8 -F50 D10 -F50 D12 -F50 D14 -F50 D16 -F50 F2 -F50 F4 -F50 F6 -F50 F8

L1 L2 L4 L5 L6 L7 L8 L9 L 10 L 11 L 12

D /10.E6 /10.E6 /10.E6 /10.E6 /10.E6 /10.E6 /10.E6 /10.F6 /10.F6 /10.F6 /10.F6 D

D1 D3 D7 D9 D11 D13 D15 F1 F3 F5 F7

TR-
/8.E5

E E

F F

Date 12/02/2020 Project Name Title Control Circuit Drawing Nr. =PIX24
01 As Manufactured 29/04/2020 WD Drawn FND
PENYEMPURNAAN SISTEM 20KV X4029420-303
00 First Issued 12/02/2020 FND Checked BWP PANEL BUS SECTION Customer Doc. Nr. Sheet 13
Rev N° Modification Date Name Approved DTA Order N° C2030-4029420 Switchboard 20kV MV SWITCHGEAR PT SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
F
E
A

00
01
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

First Issued
Rev N° Modification
As Manufactured
INTERCONNECTION INTERCONNECTION

1
1

FROM PREV. CUBICLE FROM PREV. CUBICLE

-X51
-X51
-X51
-X51

23
27
25
21

Date
12/02/2020
29/04/2020
WD
FND
Name
Date
Drawn

2
2

Checked
Approved
DTA
FND
BWP
Order N°
12/02/2020 Project Name

3
3

C2030-4029420 Switchboard
PANEL BUS SECTION
PENYEMPURNAAN SISTEM 20KV

20kV MV SWITCHGEAR

4
4

/10.E8
-K50BF
11
12 14
50BF TRIP
TO INCOMING

/10.E8
-K50BF
21
22 24

PT SCHNEIDER INDONESIA
50BF TRIP

Title
TO EXT. INCOMING

5
5

Control Circuit

6
6

Drawing Nr.

Customer Doc. Nr.

7
7

X4029420-303
=PIX24
-X51
-X51
-X51
-X51

24
28
26
22

8
8

INTERCONNECTION INTERCONNECTION
TO NEXT CUBICLE TO NEXT CUBICLE
Sheet 14
35 Sh.
F
E
A

D
1 2 3 4 5 6 7 8

CB AUXILIARY CONTACT INSTANTANEOUS SPRING CHARGE CB PLUG CB POSITION CB POSITION WATCHDOG PROTECTION RELAY VT SUPPLY
(SPARE) AUX. CONTACTS IN/OUT TEST SERVICE RELAY FAILURE SPARE OUTPUT FAIL
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

B -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 B
15 17 19 22 24 76 78 80 82 57 48 74 70

-X052 -X052
-X052 1F 3F -X052 5F 7F
1M 5M
X01:C9 X01:A10 X01:A7 X01:B15 X01:D15 3M 7M
C C
-Q51 1
-F50 J11 -F50 G7 G8 -F50 G10 G11
S41
END OF CHARGING

END OF CHARGING

DISCONNECTED
5 2 5 11 13 1 1 1 1

CB PLUG
RL 11 RL 12 22 24 22 24
+S1.B +S1.B
-Q51 S12 -Q51 S2 -Q51 S2 -Q51 -SS3 -SS4 OF OF
/4.B3 /4.B3 /4.B3 14 -ST3 -ST4 WD -Q941.1 -Q942.1
6 9 6 12 2 2 2 2 /10.E4 /10.E5 /10.E5 /6.C5 /6.D5
S11 21 21
10
J12 G9 G12
X01:C10 X01:A11 X01:A8 X01:A9 X01:B16 X01:D16
-X052 -X052
4M 8M
-X052 2M -X052 6M
2F 4F 6F 8F

D D

-X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5 -X5
16 18 20 21 23 25 77 79 81 83 58 49 75 71

E E

SPARE TERMINALS
-X1 -X51
4 -X51 1
2
-X51
-X51 3
4

F F

Date 12/02/2020 Project Name Title Control Circuit Drawing Nr. =PIX24
01 As Manufactured 29/04/2020 WD Drawn FND
PENYEMPURNAAN SISTEM 20KV X4029420-303
00 First Issued 12/02/2020 FND Checked BWP PANEL BUS SECTION Customer Doc. Nr. Sheet 15
Rev N° Modification Date Name Approved DTA Order N° C2030-4029420 Switchboard 20kV MV SWITCHGEAR PT SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

CB INTERLOCKING OCR & EF FAIL CB STATUS EARTHING SW. AC/DC SUPPLY OCR & EF
TRIP INDICATION OPEN CLOSE CLOSE FAIL TRIP
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

INTERLOCK TO
EXT. INCOMING

INTERLOCK TO

INTERLOCK TO
BUS RISER + DS

RCP
BUS COUPLER

HV SIDE 150 kV
-X X -X X -X X -X X -X X -X X -X X -X X

B -X5 -X51 -X5 -X51 -X5 -X51 -X5 -X5 -X5 -X5 -X5 B
11 13 13 15 50 11 38 65 40 42 43

-X041 3F
3M
C X01:B5 X01:C11 X01:A15 C
S1:3
+S4
-Q30
/6.C1
11 15 15 7 42 44 32 34 32 34 S1:4 22 24 22 24 22 24 22 24 22 24 22 24
+S1.B +S1.B +S1.B +S1.B +S1.B
-Q51 S12 -Q51 S12 -Q51 S11
OF OF -Q923.1 OF -Q924.1 OF -Q925.1 OF
/4.B3 12 /4.B3 16 /4.B3 16 -K86 -K52 -K51 -Q921.1 -Q922.1 -K86
8
/10.E8 /11.E2 /11.E2 /8.C1 /8.C4 /8.C5 /8.C6 /8.C7 /10.E8
41 31 31 21 21 21 21 21 21
-X041 4M
4F
X01:B6 X01:C12 X01:A16 X01:B1

-X5
-X5 51 -X5
D 30 52 D
-X051 1F
1M

-ST1
2

-X051 2M
2F

-X5 -X51 -X5 -X51 -X5 -X51 -X5 -X5 -X5 -X5 -X5 -X5
12 14 14 16 31 12 39 66 67 41 44 45

E E
-X X -X X -X X -X X -X X -X X -X X -X X -X X
BUS RISER + DS
EXT. INCOMING

HV SIDE 150 kV
INTERLOCK TO

INTERLOCK TO

INTERLOCK TO
BUS COUPLER

RCP

F F

Date 12/02/2020 Project Name Title Control Circuit Drawing Nr. =PIX24
01 As Manufactured 29/04/2020 WD Drawn FND
PENYEMPURNAAN SISTEM 20KV X4029420-303
00 First Issued 12/02/2020 FND Checked BWP PANEL BUS SECTION Customer Doc. Nr. Sheet 16
Rev N° Modification Date Name Approved DTA Order N° C2030-4029420 Switchboard 20kV MV SWITCHGEAR PT SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
CB RACK POSITION
CB STATUS INDICATION TEST SERVICE OCR & EF PROTECTION UNDER TCS LOCAL REMOTE EARTHING SW.
OPEN CLOSE RACK-OUT RACK-IN TRIP HEALTHY VOLTAGE FAIL STATUS STATUS STATUS
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

SCADA

-X X -X X -X X -X X -X X -X X -X X -X X

B -X6 1 -X6 4 -X6 10 -X6 12 -X6 14 -X6 16 -X6 18 -X6 20 B

-X5 -X5 -X5 -X5 -X5 -X5


84 86 88 90 92 94

-X5
34 -X041 -X041 -X042 -X042 -X042
-X042
-X051 5F 5F 7F 1F 3F 5F 7F
5M
5M 7M 1M 3M 5M 7M
C C
-F50 H13 H14 -F50 J13 -F50 H10 H11 -F50 H1

REMOTE
LOCAL
13 15 S1:5 S1:7 S1:9
+S4 +S4 +S4 S1:11 S1:13 S1:15
1 RL 6 RL 5 RL 1 +S1.D +S1.D +S4 +S4 +S4
22 24 22 24 12 14 /9.B2 /9.B2 -Q30 -Q30 -Q30 -Q30 -Q30
WD -S650 -S650 /6.C1 /6.C1 /6.C1 -Q30
-SS1 /10.E4 S1:6 S1:8 S1:10 /6.C1 /6.C1 /6.C1
-K52 -K51 -KST 2
/10.F4 /10.E4 /10.F4 S1:12 S1:14 S1:16
/11.E2 /11.E2 /11.E3 14 16
21 21 11
H15 J14 H12 H2
-X041 -X041 -X042 -X042 -X042 -X042
6M 8M 2M 4M 6M 8M
-X051 6M
6F
6F 8F 2F 4F 6F 8F

-X5
D 35 D

-X5 -X5 -X5 -X5 -X5 -X5


-X6 2 -X6 3 -X6 5 -X6 6 -X6 11 -X6 13 -X6 15 -X6 17 -X6 19 -X6 21
85 87 89 91 93 95

16 18 20
E E
-X X -X X -X X -X X -X X -X X -X X -X X -X X -X X
SCADA

F F

Date 12/02/2020 Project Name Title Control Circuit Drawing Nr. =PIX24
01 As Manufactured 29/04/2020 WD Drawn FND
PENYEMPURNAAN SISTEM 20KV X4029420-303
00 First Issued 12/02/2020 FND Checked BWP PANEL BUS SECTION Customer Doc. Nr. Sheet 17
Rev N° Modification Date Name Approved DTA Order N° C2030-4029420 Switchboard 20kV MV SWITCHGEAR PT SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SERIAL LINK COMMUNICATION


PROTECTION RELAY DIGITAL POWER METER DIGITAL ENERGY METER

MiCOM P143
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

-P51
EDMI - Mk6N (Cls 0.5)
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A -F50 ETHERNET PM5350 A


All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

RS485 port -P50 RJ45 MODBUS RS 485 - RJ45 Conn. Ports


100Mbit/s Communication
NULL PL2 PL3
BL
BR
GR-WH
BL-WH
8 1 If use Ethernet 18 19 20 GR
BL-WH
BL
BR
GR-WH

RS485 is disable 8 1 8 1 8 1

B B
TO
ETHERNET MODBUS RS485 MODBUS RS485
SWITCH FROM PREV TO NEXT
PANEL PANEL

C C

TO NEXT CUBICLE
-X61 -X61
GROUP #2 FROM

+A2
PREV. CUBICLE
RS485 (2-WIRE)

RS485 (2-WIRE)
11 12
-X61 -B2 -X61
13 14
-X61 SH2 -X61
15 16

D D

E E

F F

Date 12/02/2020 Project Name Title Control Circuit Drawing Nr. =PIX24
01 As Manufactured 29/04/2020 WD Drawn FND
PENYEMPURNAAN SISTEM 20KV X4029420-303
00 First Issued 12/02/2020 FND Checked BWP PANEL BUS SECTION Customer Doc. Nr. Sheet 18
Rev N° Modification Date Name Approved DTA Order N° C2030-4029420 Switchboard 20kV MV SWITCHGEAR PT SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
F
E
A

00
01
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

First Issued
Rev N° Modification
As Manufactured
Terminal type

1
1

Terminal UT 4 [ 1 - 5 ]
TERMINAL PLAN
Terminal UT 4 [ 6 ]
Terminal
Terminal
Terminal
-X1

Date
12/02/2020
29/04/2020
Function Connection Target Signal Number Connection Target Reference
=PIX24 +S1.B -B21 :1 PH 1 =PIX24 +S1.B -Q921 :4 /8.C2

WD
FND
Name
=PIX24 +S1.B -S34 :1 PH 2 /8.C2

Date
=PIX24 +S1.B -B21 :c PH 3 =PIX24 +S4 -R11 :1 /8.D2

Drawn

2
2

Checked
Approved
4 /15.E5

DTA
FND
=PIX24 +S1.B -Q921 :2 N 5 =PIX24 +S4 -R11 :2 /8.E2

BWP
=PIX24 +S1.B -H34 :N N 6 /8.E2

Order N°
12/02/2020 Project Name

3
3

C2030-4029420 Switchboard
PANEL BUS SECTION
PENYEMPURNAAN SISTEM 20KV

20kV MV SWITCHGEAR

4
4

PT SCHNEIDER INDONESIA
Title

5
5

Terminal Plan

6
6

Drawing Nr.

Customer Doc. Nr.

7
7

X4029420-303
+S1.B
=PIX24

8
8

Sheet 19
35 Sh.
F
E
A

D
F
E
A

00
01
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

First Issued
Rev N° Modification
As Manufactured
Terminal type

1
1

Terminal UT 4 [ 1 - 24 ]
TERMINAL PLAN
Terminal UT 4 [ 25 - 27 ]
Terminal
Terminal
Terminal
-X2

Date
12/02/2020
29/04/2020
Function Connection Target Signal Number Connection Target Reference
=PIX24 +S1.B -Q922 :4 M+ 1 =PIX24 +S4 -Q51 M1:X01:A1 /9.C2

WD
FND
Name
=PIX24 +S1.B -Q922 :2 M- 2 =PIX24 +S4 -Q51 :X01:A2 /9.D2

Date
=PIX24 +S1.B -X5 :6 CS+ 3 =PIX24 +S4 -Q51 :X01:A5 /9.C5

Drawn

2
2

Checked
Approved
=PIX24 +S1.B -X51 :8 TR+ 4 =PIX24 +S4 -Q51 :X01:A3 /10.C2

DTA
FND
=PIX24 +S1.B -X2 :8 TR- 5 =PIX24 +S4 -Q51 :X01:A4 /10.D2

BWP
=PIX24 +S4 -Q51 :X01:D11 TR+ 6 =PIX24 +S4 -Q51 3:X01:B7 /10.C1
TR+ =PIX24 +S1.D -F50 :D5 /10.C1

Order N°
=PIX24 +S1.D -S601 :2 CS+ 7 =PIX24 +S4 -Q51 4:X01:B8 /10.C2

12/02/2020 Project Name


=PIX24 +S1.B -X2 :5 TR- 8 =PIX24 +S1.B -Q923 :2 /8.E5
=PIX24 +S1.B -K50BF RXM:A2 TR- 9 =PIX24 +S1.D -XT01 :15 /8.E5
TR- =PIX24 +S1.D -F50 :D1 /8.E5

3
3

=PIX24 +S1.B -X51 :6 TR+ 10 =PIX24 +S1.B -Q923 :4 /8.E5


=PIX24 +S1.B -X2 :21 TR+ 11 =PIX24 +S1.D -XT01 :13 /8.E6
=PIX24 +S1.B -X5 :36 TR+ /8.E6
=PIX24 +S1.B -Q924 :2 CS- 12 =PIX24 +S4 -Q51 :X01:A6 /8.E6

C2030-4029420 Switchboard
PANEL BUS SECTION
=PIX24 +S1.B -KST RXM:A2 CS- 13 =PIX24 +S1.D -H51 :X2 /8.E6
CS- 14 =PIX24 +S1.D -P50 :11 /8.E6

PENYEMPURNAAN SISTEM 20KV


=PIX24 +S1.B -Q924 :4 CS+ 15 =PIX24 +S1.D -S650 :3 /8.E7
=PIX24 +S1.B -X2 :18 CS+ 16 =PIX24 +S1.B -X5 :32 /8.E7

20kV MV SWITCHGEAR

4
4

CS+ 17 =PIX24 +S1.D -P50 :7 /8.E7


=PIX24 +S1.B -K52 :14 CS+ 18 =PIX24 +S4 -Q51 9:X01:B2 /11.A2
=PIX24 +S1.B -X2 :16 CS+ /11.A2
=PIX24 +S1.B -K52 110VDC:A1 CS+ 19 =PIX24 +S4 -Q51 10:X01:B3 /11.C2
=PIX24 +S1.B -K51 110VDC:A1 CS+ 20 =PIX24 +S4 -Q51 2:X01:B4 /11.C2
=PIX24 +S1.B -X2 :11 TR+ 21 =PIX24 +S1.D -S650 :9 /13.A2
=PIX24 +S1.B -KST :24 TR+ =PIX24 +S4 -Q51 13:X01:A12 /13.A2

PT SCHNEIDER INDONESIA
=PIX24 +S4 -Q51 14:X01:A13 TR+ 22 =PIX24 +S1.D -F50 L:D2 /13.C2

Title
=PIX24 +S4 -Q51 6:X01:A14 TR+ 23 =PIX24 +S1.D -F50 L:D4 /13.C2

5
5

=PIX24 +S1.B -Q925 :4 L+ 24 =PIX24 +S1.D -U101 :+VE /12.C3


=PIX24 +S1.B -Q925 :2 L- 25 =PIX24 +S1.D -U101 :-VE /12.D3
=PIX24 +S1.B -X5 :27 CS+ 26 =PIX24 +S4 -X07 :1F /11.D5
=PIX24 +S4 -X07 :2F CS- 27 =PIX24 +S1.D -H51 :X2 /11.E5

Terminal Plan

6
6

Drawing Nr.

Customer Doc. Nr.

7
7

X4029420-303
+S1.B
=PIX24

8
8

Sheet 20
35 Sh.
F
E
A

D
F
E
A

00
01
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

First Issued
Rev N° Modification
As Manufactured
Terminal type

1
1

Terminal URTK/S. [ 1 - 23 ]
TERMINAL PLAN
Terminal URTK/S. [ 24 ]
Terminal
Terminal
Terminal
-X3

Date
12/02/2020
29/04/2020
Function Connection Target Signal Number Connection Target Reference
=PIX24 +S1.D -XT01 :21 CL1 1 =PIX24 +S4 -T51 5:L1.1S1 /5.B3

WD
FND
Name
=PIX24 +S1.D -XT01 :23 CL2 2 =PIX24 +S4 -T51 :L2.1S1 /5.B3

Date
=PIX24 +S1.D -XT01 :25 CL3 3 =PIX24 +S4 -T51 :L3.1S1 /5.B3

Drawn

2
2

Checked
Approved
=PIX24 +S1.B -XPE :2 4 =PIX24 +S1.D -XT01 :27 /5.B3

DTA
FND
CL1 5 =PIX24 +S4 -T51 :L1.1S2 /5.B3

BWP
CL1 6 =PIX24 +S4 -T51 :L1.1S3 /5.B3
CL2 7 =PIX24 +S4 -T51 :L2.1S2 /5.B3

Order N°
CL2 8 =PIX24 +S4 -T51 :L2.1S3 /5.C3

12/02/2020 Project Name


CL3 9 =PIX24 +S4 -T51 :L3.1S2 /5.C3
CL3 10 =PIX24 +S4 -T51 :L3.1S3 /5.C3
=PIX24 +S1.D -XT02 :21 CL1 11 =PIX24 +S4 -T51 12:L1.2S1 /5.D3

3
3

=PIX24 +S1.D -XT02 :23 CL2 12 =PIX24 +S4 -T51 :L2.2S1 /5.D3
=PIX24 +S1.D -XT02 :25 CL3 13 =PIX24 +S4 -T51 :L3.2S1 /5.D3
=PIX24 +S1.B -XPE :1 14 =PIX24 +S1.D -XT02 :27 /5.D3
CL1 15 =PIX24 +S4 -T51 :L1.2S2 /5.D3

C2030-4029420 Switchboard
PANEL BUS SECTION
CL1 16 =PIX24 +S4 -T51 :L1.2S3 /5.D3
CL2 17 =PIX24 +S4 -T51 :L2.2S2 /5.E3

PENYEMPURNAAN SISTEM 20KV


CL2 18 =PIX24 +S4 -T51 :L2.2S3 /5.E3
CL3 19 =PIX24 +S4 -T51 :L3.2S2 /5.E3

20kV MV SWITCHGEAR

4
4

CL3 20 =PIX24 +S4 -T51 12:L3.2S3 /5.E3


CL1 21 =PIX24 +S1.D -P51 :I1- /5.D7
CL2 22 =PIX24 +S1.D -P51 :I2- /5.D7
CL3 23 =PIX24 +S1.D -P51 :I3- /5.D7
CLN 24 =PIX24 +S1.D -XT02 :28 /5.D7

PT SCHNEIDER INDONESIA
Title

5
5

Terminal Plan

6
6

Drawing Nr.

Customer Doc. Nr.

7
7

X4029420-303
+S1.B
=PIX24

8
8

Sheet 21
35 Sh.
F
E
A

D
F
E
A

00
01
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

First Issued
Rev N° Modification
As Manufactured
Terminal type

1
1

Terminal UT 4 [ 1 - 19 ]
TERMINAL PLAN
Terminal UT 4 [ 20 ]
Terminal
Terminal
Terminal
-X4

Date
12/02/2020
29/04/2020
Function Connection Target Signal Number Connection Target Reference
=PIX24 +S1.B -Q941 :3 UL1 1 =PIX24 +S4 -X021 :1M /6.B5

WD
FND
Name
=PIX24 +S1.B -Q941 :5 UL2 2 =PIX24 +S4 -X021 :2M /6.B5

Date
=PIX24 +S1.B -Q941 :7 UL3 3 =PIX24 +S4 -X021 :3M /6.B5

Drawn

2
2

Checked
Approved
=PIX24 +S1.B -Q941 4P, 2A:1 UN 4 =PIX24 +S4 -X021 :4M /6.B5

DTA
FND
UN 5 =PIX24 +S4 -X021 :5M /6.B5

BWP
=PIX24 +S1.B -XPE :5 6 =PIX24 +S4 -X021 :6M /6.C5
=PIX24 +S1.B -Q942 :3 UL1 7 =PIX24 +S4 -X022 :1M /6.C5

Order N°
=PIX24 +S1.B -Q942 :5 UL2 8 =PIX24 +S4 -X022 :2M /6.C5

12/02/2020 Project Name


=PIX24 +S1.B -Q942 :7 UL3 9 =PIX24 +S4 -X022 :3M /6.C5
=PIX24 +S1.B -Q942 4P, 2A:1 UN 10 =PIX24 +S4 -X022 :4M /6.D5
UN 11 =PIX24 +S4 -X022 :5M /6.D5

3
3

=PIX24 +S1.B -XPE :6 12 =PIX24 +S4 -X022 :6M /6.D5


UL11 13 =PIX24 +S1.D -P50 Va:2 /7.C7
UL12 14 =PIX24 +S1.D -P50 Vb:5 /7.C7
UL13 15 =PIX24 +S1.D -XT02 :6 /7.C7

C2030-4029420 Switchboard
PANEL BUS SECTION
UN1 16 =PIX24 +S1.D -XT02 :8 /7.C7
UL21 17 =PIX24 +S1.D -XT01 :2 /7.D7

PENYEMPURNAAN SISTEM 20KV


UL22 18 =PIX24 +S1.D -XT01 :4 /7.D7
UL23 19 =PIX24 +S1.D -XT01 :6 /7.D7

20kV MV SWITCHGEAR

4
4

UN2 20 =PIX24 +S1.D -XT01 :8 /7.D7

PT SCHNEIDER INDONESIA
Title

5
5

Terminal Plan

6
6

Drawing Nr.

Customer Doc. Nr.

7
7

X4029420-303
+S1.B
=PIX24

8
8

Sheet 22
35 Sh.
F
E
A

D
F
E
A

00
01
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

First Issued
Rev N° Modification
As Manufactured
Terminal type

1
1

Terminal UT 4 [ 1 - 56 ]
TERMINAL PLAN
Terminal
Terminal
Terminal
Terminal
-X5

Date
12/02/2020
29/04/2020
Function Connection Target Signal Number Connection Target Reference
CS+ 1 =PIX24 +S1.D -S650 :4 /9.B3

WD
FND
Name
CS+ 2 =PIX24 +S1.D -F50 RL:G1 /9.B3

Date
CS+ 3 =PIX24 +S1.D -S601 :4 /9.C3

Drawn

2
2

Checked
Approved
=PIX24 +S1.D -F50 :H7 CS+ 4 =PIX24 +S1.D -F50 :G2 /9.C3

DTA
FND
=PIX24 +S1.B -X5 :69 CS+ 5 =PIX24 +S1.B -X51 :19 /9.B5

BWP
=PIX24 +S1.B -X2 :3 CS+ 6 /9.C5
TR+ 7 =PIX24 +S1.D -S650 :8 /10.B3

Order N°
CS+ 8 =PIX24 +S1.D -F50 RL:G3 /10.B3

12/02/2020 Project Name


CS+ 9 =PIX24 +S1.D -S601 :2 /10.C3
=PIX24 +S1.D -XT01 :11 TR+ 10 =PIX24 +S1.D -F50 :G4 /10.C3
=PIX24 +S1.B -X51 :13 CS+ 11 =PIX24 +S4 -Q51 11:X01:B5 /16.B1

3
3

=PIX24 +S1.B -X51 :14 CS+ 12 =PIX24 +S4 -Q51 12:X01:B6 /16.E1
=PIX24 +S1.B -X51 :15 CS+ 13 =PIX24 +S4 -Q51 15:X01:C11 /16.B1
=PIX24 +S1.B -X51 :16 CS+ 14 =PIX24 +S4 -Q51 16:X01:C12 /16.E1
CS+ 15 =PIX24 +S4 -Q51 5:X01:C9 /15.B1

C2030-4029420 Switchboard
PANEL BUS SECTION
CS+ 16 =PIX24 +S4 -Q51 6:X01:C10 /15.E1
CS+ 17 =PIX24 +S4 -Q51 :X01:A10 /15.B2

PENYEMPURNAAN SISTEM 20KV


CS+ 18 =PIX24 +S4 -Q51 :X01:A11 /15.E2
CS+ 19 =PIX24 +S4 -Q51 5:X01:A7 /15.B2

20kV MV SWITCHGEAR

4
4

CS+ 20 =PIX24 +S4 -Q51 6:X01:A8 /15.E2


CS+ 21 =PIX24 +S4 -Q51 12:X01:A9 /15.E3
CS+ 22 =PIX24 +S4 -Q51 13:X01:B15 /15.B3
CS+ 23 =PIX24 +S4 -Q51 14:X01:B16 /15.E3
CS+ 24 =PIX24 +S4 -Q51 :X01:D15 /15.B3
CS+ 25 =PIX24 +S4 -Q51 :X01:D16 /15.E3
=PIX24 +S1.B -X5 :29 CS+ 26 =PIX24 +S4 -X041 :1F /11.B5

PT SCHNEIDER INDONESIA
=PIX24 +S1.B -X2 :26 CS+ 27 =PIX24 +S4 -X041 :2F /11.C5

Title
=PIX24 +S1.B -K51 :14 CS+ 28 /11.A5

5
5

=PIX24 +S1.B -X5 :26 CS+ 29 /11.B5


=PIX24 +S1.B -X5 :51 CS+ 30 =PIX24 +S4 -X051 :1F /16.D2
=PIX24 +S1.B -X51 :12 CS+ 31 =PIX24 +S4 -X051 :2F /16.E2
=PIX24 +S1.B -X2 :16 CS+ 32 =PIX24 +S4 -X051 :3F /11.A3
=PIX24 +S1.B -KST 110VDC:A1 CS+ 33 =PIX24 +S4 -X051 :4F /11.C3
=PIX24 +S1.B -X6 :4 CS+ 34 =PIX24 +S4 -X051 :5F /17.C2

Terminal Plan
=PIX24 +S1.B -X6 :6 CS+ 35 =PIX24 +S4 -X051 :6F /17.D2
=PIX24 +S1.B -X5 :46 TR+ 36 =PIX24 +S4 -X051 :7F /13.A3

6
6

=PIX24 +S1.B -X2 :11 TR+ /13.A3


=PIX24 +S4 -X051 :8F TR+ 37 =PIX24 +S1.D -F50 L:D10 /13.C3
=PIX24 +S1.B -K86 :44 CS+ 38 /16.B4
=PIX24 +S1.B -K86 :41 CS+ 39 /16.E4
Drawing Nr.

CS+ 40 =PIX24 +S4 -X041 :3F /16.B6


Customer Doc. Nr.

CS+ 41 =PIX24 +S4 -X041 :4F /16.E6


=PIX24 +S1.B -Q921.1 :22 CS+ 42 /16.B6
=PIX24 +S1.B -K86 :24 CS+ 43 /16.B8
7
7

=PIX24 +S1.B -Q921.1 :21 CS+ 44 /16.E6


=PIX24 +S1.B -K86 :21 CS+ 45 /16.E8
X4029420-303

=PIX24 +S1.B -X5 :53 TR+ 46 =PIX24 +S1.B -X5 :36 /13.A4
TR+ 47 =PIX24 +S1.D -F50 L:D12 /13.C4
CS+ 48 =PIX24 +S1.D -F50 RL:G8 /15.B7
CS+ 49 =PIX24 +S1.D -F50 :G9 /15.E7
=PIX24 +S1.B -X51 :11 CS+ 50 =PIX24 +S4 -Q51 15:X01:A15 /16.B2
+S1.B

=PIX24 +S1.B -X5 :30 CS+ 51 =PIX24 +S4 -Q51 16:X01:A16 /16.D2
=PIX24

CS+ 52 =PIX24 +S4 -Q51 8:X01:B1 /16.D2


8
8

=PIX24 +S1.B -X5 :72 TR+ 53 =PIX24 +S1.B -X5 :46 /13.B7
CS+ 54 /13.B7
TR+ 55 =PIX24 +S1.D -F50 L:F6 /13.B7
TR+ 56 =PIX24 +S1.D -F50 L:F8 /13.B7
Sheet 23
35 Sh.
F
E
A

D
F
E
A

00
01
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

First Issued
Rev N° Modification
As Manufactured
Terminal type

1
1

Terminal UT 4 [ 57 - 82 ]
TERMINAL PLAN
Terminal UT 4 [ 83 - 95 ]
Terminal
Terminal
Terminal
-X5

Date
12/02/2020
29/04/2020
Function Connection Target Signal Number Connection Target Reference
CS+ 57 =PIX24 +S1.D -F50 :J11 /15.B6

WD
FND
Name
CS+ 58 =PIX24 +S1.D -F50 :J12 /15.E6

Date
=PIX24 +S1.B -X5 :61 +24V 59 =PIX24 +S1.D -F50 RL:G14 /12.B6

Drawn

2
2

Checked
Approved
+24V 60 =PIX24 +S1.D -U101 :F4 /12.B6

DTA
FND
=PIX24 +S1.B -X5 :59 +24V 61 =PIX24 +S1.B -X5 :63 /12.B6

BWP
+24V 62 =PIX24 +S1.D -U101 :F5 /12.B6
=PIX24 +S1.B -X5 :61 +24V 63 =PIX24 +S1.B -Q921.1 :12 /12.B6

Order N°
+24V 64 =PIX24 +S1.D -U101 :F6 /12.B6

12/02/2020 Project Name


=PIX24 +S1.B -K51 :34 CS+ 65 /16.B5
=PIX24 +S1.B -K52 :31 CS+ 66 /16.E5
=PIX24 +S1.B -K51 :31 CS+ 67 /16.E5

3
3

=PIX24 +S1.B -K86 :31 CS+ 68 /9.A5


=PIX24 +S1.B -X5 :5 CS+ 69 /9.B5
=PIX24 +S1.B -Q942.1 :22 CS+ 70 /15.B8
=PIX24 +S1.B -Q942.1 :21 CS+ 71 /15.E8

C2030-4029420 Switchboard
PANEL BUS SECTION
=PIX24 +S1.B -X5 :53 TR+ 72 /13.A4
TR+ 73 =PIX24 +S1.D -F50 L:D14 /13.C4

PENYEMPURNAAN SISTEM 20KV


CS+ 74 =PIX24 +S1.D -F50 RL:G11 /15.B7
CS+ 75 =PIX24 +S1.D -F50 :G12 /15.E7

20kV MV SWITCHGEAR

4
4

CS+ 76 =PIX24 +S4 -X052 :1F /15.B4


CS+ 77 =PIX24 +S4 -X052 :2F /15.E4
CS+ 78 =PIX24 +S4 -X052 :3F /15.B5
CS+ 79 =PIX24 +S4 -X052 :4F /15.E5
CS+ 80 =PIX24 +S4 -X052 :5F /15.B5
CS+ 81 =PIX24 +S4 -X052 :6F /15.E5
CS+ 82 =PIX24 +S4 -X052 :7F /15.B6

PT SCHNEIDER INDONESIA
CS+ 83 =PIX24 +S4 -X052 :8F /15.E6

Title
TR+ 84 =PIX24 +S4 -X041 :5F /17.B6

5
5

TR+ 85 =PIX24 +S4 -X041 :6F /17.E6


TR+ 86 =PIX24 +S4 -X041 :7F /17.B6
TR+ 87 =PIX24 +S4 -X041 :8F /17.E6
CS+ 88 =PIX24 +S4 -X042 :1F /17.B7
CS+ 89 =PIX24 +S4 -X042 :2F /17.E7
CS+ 90 =PIX24 +S4 -X042 :3F /17.B7

Terminal Plan
CS+ 91 =PIX24 +S4 -X042 :4F /17.E7
92 =PIX24 +S4 -X042 :5F /17.B8

6
6

93 =PIX24 +S4 -X042 :6F /17.E8


94 =PIX24 +S4 -X042 :7F /17.B8
95 =PIX24 +S4 -X042 :8F /17.E8
Drawing Nr.

Customer Doc. Nr.

7
7

X4029420-303
+S1.B
=PIX24

8
8

Sheet 24
35 Sh.
F
E
A

D
F
E
A

00
01
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

First Issued
Rev N° Modification
As Manufactured
Terminal type

1
1

Terminal MTK-P/P [ 1 - 24 ]
TERMINAL PLAN
Terminal MTK-P/P [ 25 ]
Terminal
Terminal
Terminal
-X6

Date
12/02/2020
29/04/2020
Function Connection Target Signal Number Connection Target Reference
=PIX24 +S1.B -K51 :24 CS+ 1 /17.B1

WD
FND
Name
=PIX24 +S1.B -K52 :21 CS+ 2 /17.E1

Date
=PIX24 +S1.B -K51 :21 CS+ 3 /17.E2

Drawn

2
2

Checked
Approved
=PIX24 +S1.B -X5 :34 CS+ 4 =PIX24 +S1.B -KST :14 /17.B2

DTA
FND
=PIX24 +S1.B -KST :11 CS+ 5 /17.E2

BWP
=PIX24 +S1.B -X5 :35 CS+ 6 /17.E2
CS+ 7

Order N°
8

12/02/2020 Project Name


9
CS+ 10 =PIX24 +S1.D -F50 RL:H14 /17.B3
CS+ 11 =PIX24 +S1.D -F50 :H15 /17.E3

3
3

CS+ 12 =PIX24 +S1.D -F50 :J13 /17.B3


CS+ 13 =PIX24 +S1.D -F50 :J14 /17.E3
CS+ 14 =PIX24 +S1.D -F50 RL:H11 /17.B4
CS+ 15 =PIX24 +S1.D -F50 :H12 /17.E4

C2030-4029420 Switchboard
PANEL BUS SECTION
CS+ 16 =PIX24 +S1.D -F50 RL:H1 /17.B4
CS+ 17 =PIX24 +S1.D -F50 :H2 /17.E4

PENYEMPURNAAN SISTEM 20KV


CS+ 18 =PIX24 +S1.D -S650 :13 /17.B5
CS+ 19 =PIX24 +S1.D -S650 :14 /17.E5

20kV MV SWITCHGEAR

4
4

CS+ 20 =PIX24 +S1.D -S650 :15 /17.B5


CS+ 21 =PIX24 +S1.D -S650 :16 /17.E5
22
23
24
25

PT SCHNEIDER INDONESIA
Title

5
5

Terminal Plan

6
6

Drawing Nr.

Customer Doc. Nr.

7
7

X4029420-303
+S1.B
=PIX24

8
8

Sheet 25
35 Sh.
F
E
A

D
F
E
A

00
01
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

First Issued
Rev N° Modification
As Manufactured
Terminal type

1
1

Terminal UT 6. [ 1 - 3 ]
TERMINAL PLAN
Terminal UT 6. [ 4 ]
Terminal
Terminal
Terminal
-X11

Date
12/02/2020
29/04/2020
Function Connection Target Signal Number Connection Target Reference
220VAC (PH) =PIX24 +S1.B -Q921 :3 01P 1 /8.A1

WD
FND
Name
01P 2 /8.A8

Date
220VAC (N) =PIX24 +S1.B -Q921 2P, 6A:1 01N 3 /8.A1

Drawn

2
2

Checked
Approved
01N 4 /8.A8

DTA
FND
BWP
Order N°
12/02/2020 Project Name

3
3

C2030-4029420 Switchboard
PANEL BUS SECTION
PENYEMPURNAAN SISTEM 20KV

20kV MV SWITCHGEAR

4
4

PT SCHNEIDER INDONESIA
Title

5
5

Terminal Plan

6
6

Drawing Nr.

Customer Doc. Nr.

7
7

X4029420-303
+S1.B
=PIX24

8
8

Sheet 26
35 Sh.
F
E
A

D
F
E
A

00
01
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

First Issued
Rev N° Modification
As Manufactured
Terminal type

1
1

Terminal UT 6. [ 1 - 3 ]
TERMINAL PLAN
Terminal UT 6. [ 4 ]
Terminal
Terminal
Terminal
-X21

Date
12/02/2020
29/04/2020
Function Connection Target Signal Number Connection Target Reference
110VDC (+) =PIX24 +S1.B -Q922 :3 DC (+) 1 /8.A1

WD
FND
Name
DC (+) 2 /8.A8

Date
110VDC (-) =PIX24 +S1.B -Q922 2P, 10A:1 DC (-) 3 /8.B1

Drawn

2
2

Checked
Approved
DC (-) 4 /8.B8

DTA
FND
BWP
Order N°
12/02/2020 Project Name

3
3

C2030-4029420 Switchboard
PANEL BUS SECTION
PENYEMPURNAAN SISTEM 20KV

20kV MV SWITCHGEAR

4
4

PT SCHNEIDER INDONESIA
Title

5
5

Terminal Plan

6
6

Drawing Nr.

Customer Doc. Nr.

7
7

X4029420-303
+S1.B
=PIX24

8
8

Sheet 27
35 Sh.
F
E
A

D
F
E
A

00
01
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

First Issued
Rev N° Modification
As Manufactured
Terminal type

1
1

Terminal UT 4 [ 1 - 11 ]
TERMINAL PLAN
Terminal UT 4 [ 12 ]
Terminal
Terminal
Terminal
-X41

Date
12/02/2020
29/04/2020
Function Connection Target Signal Number Connection Target Reference
1

WD
FND
Name
2

Date
3

Drawn

2
2

Checked
Approved
4

DTA
FND
5

BWP
6
7

Order N°
8

12/02/2020 Project Name


UL21 9 =PIX24 +S1.D -S625 :2 /7.E7
10 /7.E7
UL22 11 =PIX24 +S1.D -S625 :4 /7.F7

3
3

12 /7.F7

C2030-4029420 Switchboard
PANEL BUS SECTION
PENYEMPURNAAN SISTEM 20KV

20kV MV SWITCHGEAR

4
4

PT SCHNEIDER INDONESIA
Title

5
5

Terminal Plan

6
6

Drawing Nr.

Customer Doc. Nr.

7
7

X4029420-303
+S1.B
=PIX24

8
8

Sheet 28
35 Sh.
F
E
A

D
F
E
A

00
01
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

First Issued
Rev N° Modification
As Manufactured
Terminal type

1
1

Terminal UT 4 [ 1 - 20 ]
TERMINAL PLAN
Terminal UT 4. [ 21 - 27 ]
Terminal UT 4. [ 28 ]
Terminal
Terminal
-X51

Date
12/02/2020
29/04/2020
Function Connection Target Signal Number Connection Target Reference
1 /15.E5

WD
FND
Name
2 /15.E5

Date
3 /15.F5

Drawn

2
2

Checked
Approved
4 /15.F5

DTA
FND
TR+ 5 =PIX24 +S1.D -XT01 :9 /10.B5

BWP
=PIX24 +S1.B -X2 :10 TR+ 6 /10.B5
TR+ 7 =PIX24 +S1.D -XT01 :11 /10.B5

Order N°
=PIX24 +S1.B -X2 :4 TR+ 8 /10.B5

12/02/2020 Project Name


9
10
=PIX24 +S1.B -X5 :50 CS+ 11 /16.B2

3
3

=PIX24 +S1.B -X5 :31 CS+ 12 /16.E2


=PIX24 +S1.B -X5 :11 CS+ 13 /16.B1
=PIX24 +S1.B -X5 :12 CS+ 14 /16.E1
=PIX24 +S1.B -X5 :13 CS+ 15 /16.B2

C2030-4029420 Switchboard
PANEL BUS SECTION
=PIX24 +S1.B -X5 :14 CS+ 16 /16.E2
=PIX24 +S1.B -K86 :31 CS+ 17 /9.A6

PENYEMPURNAAN SISTEM 20KV


CS+ 18 =PIX24 +S1.D -F50 RL:G5 /9.A6
=PIX24 +S1.B -X5 :5 CS+ 19 /9.B6

20kV MV SWITCHGEAR

4
4

CS+ 20 =PIX24 +S1.D -F50 :G6 /9.B6


TR+ 21 /14.A1
=PIX24 +S1.B -K50BF :14 TR+ 22 /14.A8
TR+ 23 /14.E1
=PIX24 +S1.B -K50BF :11 TR+ 24 /14.E8
TR+ 25 /14.B1
=PIX24 +S1.B -K50BF :24 TR+ 26 /14.B8

PT SCHNEIDER INDONESIA
TR+ 27 /14.E1

Title
=PIX24 +S1.B -K50BF :21 TR+ 28 /14.E8

5
5

Terminal Plan

6
6

Drawing Nr.

Customer Doc. Nr.

7
7

X4029420-303
+S1.B
=PIX24

8
8

Sheet 29
35 Sh.
F
E
A

D
F
E
A

00
01
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

First Issued
Rev N° Modification
As Manufactured
Terminal type

1
1

Terminal UT 4 [ 1 - 15 ]
TERMINAL PLAN
Terminal UT 4 [ 16 ]
Terminal
Terminal
Terminal
-X61

Date
12/02/2020
29/04/2020
Function Connection Target Signal Number Connection Target Reference
1

WD
FND
Name
2

Date
3

Drawn

2
2

Checked
Approved
4

DTA
FND
5

BWP
6
7

Order N°
8

12/02/2020 Project Name


9
10
+A2 11 =PIX24 +S1.D -P51 :20 /18.D2

3
3

+A2 12 =PIX24 +S1.D -P51 :20 /18.D7


-B2 13 =PIX24 +S1.D -P51 :19 /18.D2
-B2 14 =PIX24 +S1.D -P51 :19 /18.D7
SH2 15 =PIX24 +S1.D -P51 PM5350:18 /18.D2

C2030-4029420 Switchboard
PANEL BUS SECTION
SH2 16 =PIX24 +S1.D -P51 PM5350:18 /18.D7

PENYEMPURNAAN SISTEM 20KV

20kV MV SWITCHGEAR

4
4

PT SCHNEIDER INDONESIA
Title

5
5

Terminal Plan

6
6

Drawing Nr.

Customer Doc. Nr.

7
7

X4029420-303
+S1.B
=PIX24

8
8

Sheet 30
35 Sh.
F
E
A

D
F
E
A

00
01
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

First Issued
Rev N° Modification
As Manufactured
Terminal type

1
1

Terminal UT 4-PE [ 1 - 7 ]
TERMINAL PLAN
Terminal UT 4-PE [ 8 ]
Terminal
Terminal
Terminal
-XPE

Date
12/02/2020
29/04/2020
Function Connection Target Signal Number Connection Target Reference
=PIX24 +S1.B -X3 :14 PE 1 =PIX24 +S4 -Q51 :X01:G /4.E5

WD
FND
Name
=PIX24 +S1.B -X3 :4 PE 2 /4.E5

Date
PE 3 =PIX24 +S1.D -F50 P143:GND /4.E5

Drawn

2
2

Checked
Approved
PE 4 =PIX24 +S4 -X022 :7M /4.E5

DTA
FND
=PIX24 +S1.B -X4 :6 PE 5 /4.E5

BWP
=PIX24 +S1.B -X4 :12 PE 6 =PIX24 +S1.D -XT02 ETB14:GND /4.E5
PE 7 =PIX24 +S1.D -XT01 ETB14:GND /4.E5

Order N°
PE 8 =PIX24 +S4 -PE :2 /4.E6

12/02/2020 Project Name

3
3

C2030-4029420 Switchboard
PANEL BUS SECTION
PENYEMPURNAAN SISTEM 20KV

20kV MV SWITCHGEAR

4
4

PT SCHNEIDER INDONESIA
Title

5
5

Terminal Plan

6
6

Drawing Nr.

Customer Doc. Nr.

7
7

X4029420-303
+S1.B
=PIX24

8
8

Sheet 31
35 Sh.
F
E
A

D
1 2 3 4 5 6 7 8

LV DOOR
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

PIX W1000 H730

NOTE :
DEVICE CODE
ENGRAVING / ( NO ENGRAVING ) REMARKS
ENGRAVING
-F50 PROTECTION RELAY MiCOM P143
-P50 DIGITAL ENERGY METER EDMI Mk6N
B B
-U101 -P51
-P50
-P51 DIGITAL POWER METER PM5350MG
minilec ® Mk6N GENIUS
PowerLogic PM5350

BILLING
RESET

-H51 CB CLOSE PILOT LIGHT, RED


SELECT

BUZZER
PULSE 1

WHrs X 1.0
Default Setting
PULSE 2

VarHrs X 1.0
Default Setting
-H52 CB OPEN PILOT LIGHT, GREEN
TEST MUTE ACK RST

MBAS 08 ALARM ANNUNCIATOR

-U101 ANNUNCIATOR MBAS 08


-S601 (CIRCUIT BREAKER CONTROL, OPEN-CLOSE) SELECTOR SWITCH

-XT01 -XT02
-S650 (CIRCUIT BREAKER MODE, LOCAL-REMOTE) SELECTOR SWITCH
-F50

C MiCOM P143 -S625 (SYNCHRO, OFF-ON) SELECTOR SWITCH C


TRIP

ALARM
-XT01 VTB-CTB FOR PROTECTION ETB14
OUT OF SERVICE
O I

-XT02 VTB-CTB FOR METERING ETB14


HEALTHY

C = CLEAR
-H52 -H51
= READ
= ENTER

-S650 -S601 -S625


LOCAL REMOTE OPEN CLOSE OFF ON

D D
-F50 -U101
DISPLAY RELAY FUNCTION DISPLAY ANNUNCIATOR FUNCTION

50/51 TRIP

PIX LV DOOR 50N/51N TRIP AC / DC SUPPLY [ SPARE ]


HEIGHT : 730 (710) mm FAIL
WIDTH : 1000 (960) mm 67/67N TRIP

74 / TCS FAULT OCR & EF FAIL [ SPARE ]


E E
50BF TRIP

25 / SYNCH BREAKER FAIL [ SPARE ]

F F

Date 12/02/2020 Subject Title LV-Box Layout Drawing Nr. =PIX24


01 As Manufactured 29/04/2020 WD Drawn FND
PENYEMPURNAAN SISTEM 20KV X4029420-303 +Layout
00 First Issued 12/02/2020 FND Checked BWP PANEL BUS SECTION Customer Doc. Nr. Sheet 32
Rev N° Modification Date Name Approved DTA Order N° C2030-4029420 Switchboard 20kV MV SWITCHGEAR PT SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

LV BOX
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A PIX W1000 H730 A


All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

-H34
CD W65xH65
-S34

-X11 -X21 -X41 -X51 -X61

21
11

11

11
22
20

23
24
25
26
27
28
12

12

12
10

10

13
14
15
16
17
18
19

10

13
14
15
16
1

1
2

4
3

1
2

4
3

5
6
7
8
9

5
6
7
8
9

5
6
7
8
9
4 4 12 28 16
B B

CD W45xH65

-Q941.1

-Q942.1
-KST -K52 -K51 -K50BF -K86 -Q941 -Q942
14 14
1 3 5 7 1 3 5 7

-X2
14 14
12 12
12 12
11 11
11 11

OF +OF iC60N OF +OF iC60N

reset reset
110 VDC 110 VDC 110 VDC 110 VDC 110 VDC

O . OFF O . OFF O . OFF O . OFF O . OFF O . OFF O . OFF O . OFF

T T

21
11

22
20

23
24
25
26
27
12
10

13
14
15
16
17
18
19
1
2

4
3

5
6
7
8
9
21 21
21 91 21 91

27 22

24
22
24
94

92
2 4 6 8
22

24
22
24
94

92
2 4 6 8

C C

CD W65xH65

-X1
-Q921.1

-Q922.1

-Q923.1

-Q924.1

-Q925.1
1
2
3
-Q921 -Q922 -Q923 -Q924 -Q925 4

-X3 5

6
14
1 3
14
1 3
14
1 3
14
1 3
14
1 3 6
-XPE -X4
14 14 14 14 14
12 12 12 12 12
12 12 12 12 12
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 11 11 11 11 11
11 11 11 11 11

OF +OF iC60N OF +OF iC60N OF +OF iC60N OF +OF iC60N OF +OF iC60N

Cymax ®
-B21
reset reset reset reset reset 60 5
70 0

40
80

1
O . OFF O . OFF O . OFF O . OFF O . OFF O . OFF O . OFF O . OFF O . OFF O . OFF

30
T T T T T

90
THERMOSTAT

20
11

20
12
10

13
14
15
16
17
18
19
1

1
2

4
3

5
6
7
8

5
6
7
8
9
0 10

21 21 21 21 21
21 91 21 91 21 91 21 91 21 91
CD W65xH65

CD W65xH65
8 20 22

24
22
24
94

92
2 4
22

24
22
24
94

92
2 4
22

24
22
24
94

92
2 4
22

24
22
24
94

92
2 4
22

24
22
24
94

92
2 4

24

D D
CD W65xH65

PIX LV BOX
HEIGHT : 730 mm
WIDTH : 1000 mm

E E

-X5 -X6
A A A A A A A A A A A A A A A A A A A A A A A A A
41
21

31

51

61

71

81

91
11

42
22

40

43
44
45
46
47
48
49
20

23
24
25
26
27
28
29

32

52

62

72

82

92
30

33
34
35
36
37
38
39

50

53
54
55
56
57
58
59
60

63
64
65
66
67
68
69
70

73
74
75
76
77
78
79
80

83
84
85
86
87
88
89
90

93
94
95
12
10

13
14
15
16
17
18
19
1
2

4
3

5
6
7
8
9

21
11

20

22
23
24
25
10

12
13
14

16
17
15

18
19
1

4
2
3

6
7
5

8
9
B B B B B B B B B B B B B B B B B B B B B B B B B

95 25

F F

Date 12/02/2020 Subject Title LV-Box Layout Drawing Nr. =PIX24


01 As Manufactured 29/04/2020 WD Drawn FND
PENYEMPURNAAN SISTEM 20KV X4029420-303 +Layout
00 First Issued 12/02/2020 FND Checked BWP PANEL BUS SECTION Customer Doc. Nr. Sheet 33
Rev N° Modification Date Name Approved DTA Order N° C2030-4029420 Switchboard 20kV MV SWITCHGEAR PT SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Device Designation Description Technical Data Reff/Part Number Manufacturer Panel Location Remarks
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

-B21 Thermostat 0 to 90 C Deg. Max 250VAC Cymax CYIT-90 Gumsung Controls =PIX24 +S1.B -
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

-H34 Panel Lighting LED 5W, 85-260VAC, 50/60Hz YS T8-30-5 YongSung Electrcic =PIX24 +S1.B -

-K50BF Aux Relay + Socket 4COS, Vaux 110VDC with LED RXM4AB2FD+RXZE2M114M Schneider Electric =PIX24 +S1.B -

-K51 Aux Relay + Socket 4COS, Vaux 110VDC with LED RXM4AB2FD+RXZE2M114M Schneider Electric =PIX24 +S1.B -

-K52 Aux Relay + Socket 4COS, Vaux 110VDC with LED RXM4AB2FD+RXZE2M114M Schneider Electric =PIX24 +S1.B -

-K86 Aux Relay + Socket 4COS, Vaux 110VDC with LED RXM4AB2FD+RXZE2M114M Schneider Electric =PIX24 +S1.B -

-KST Aux Relay + Socket 4COS, Vaux 110VDC with LED RXM4AB2FD+RXZE2M114M Schneider Electric =PIX24 +S1.B -

B -Q921 MCB 2P, C 6A, 10kA at 415VAC, 50/60Hz; 6kA at 133VDC iC60N / A9F74206 Schneider Electric =PIX24 +S1.B - B

-Q921.1 Aux Contact of MCB for iC60, 2 OF iOF/SD+OF / A9A26929 Schneider Electric =PIX24 +S1.B -

-Q922 MCB 2P, C 10A, 10kA at 415VAC, 50/60Hz; 6kA at 133VDC iC60N / A9F74210 Schneider Electric =PIX24 +S1.B -

-Q922.1 Aux Contact of MCB for iC60, 2 OF iOF/SD+OF / A9A26929 Schneider Electric =PIX24 +S1.B -

-Q923 MCB 2P, C 6A, 10kA at 415VAC, 50/60Hz; 6kA at 133VDC iC60N / A9F74206 Schneider Electric =PIX24 +S1.B -

-Q923.1 Aux Contact of MCB for iC60, 2 OF iOF/SD+OF / A9A26929 Schneider Electric =PIX24 +S1.B -

-Q924 MCB 2P, C 6A, 10kA at 415VAC, 50/60Hz; 6kA at 133VDC iC60N / A9F74206 Schneider Electric =PIX24 +S1.B -

C -Q924.1 Aux Contact of MCB for iC60, 2 OF iOF/SD+OF / A9A26929 Schneider Electric =PIX24 +S1.B - C

-Q925 MCB 2P, C 6A, 10kA at 415VAC, 50/60Hz; 6kA at 133VDC iC60N / A9F74206 Schneider Electric =PIX24 +S1.B -

-Q925.1 Aux Contact of MCB for iC60, 2 OF iOF/SD+OF / A9A26929 Schneider Electric =PIX24 +S1.B -

-Q941 MCB 4P, C 2A, 50kA at 415VAC, 50/60Hz iC60N / A9F74402 Schneider Electric =PIX24 +S1.B -

-Q941.1 Aux Contact of MCB for iC60, 2 OF iOF/SD+OF / A9A26929 Schneider Electric =PIX24 +S1.B -

-Q942 MCB 4P, C 2A, 50kA at 415VAC, 50/60Hz iC60N / A9F74402 Schneider Electric =PIX24 +S1.B -

-Q942.1 Aux Contact of MCB for iC60, 2 OF iOF/SD+OF / A9A26929 Schneider Electric =PIX24 +S1.B -

D -S34 Door Switch 1 N/C, Imax. 16A, 400VAC XP42-Z11 Saia-Burgess =PIX24 +S1.B - D
-H51 Pilot Light with Integral LED Red, Vaux 24-120 VDC/AC, 50/60Hz ZB5AVBG4+ZB5AV043 Schneider Electric =PIX24 +S1.D -

-H52 Pilot Light with Integral LED Green, Vaux 24-120 VDC/AC, 50/60Hz ZB5AVBG3+ZB5AV033 Schneider Electric =PIX24 +S1.D -

-P50 Energy Meter Multi Tariff Cls 0.5, RS485 ports Vaux. 110VDC Mk6N EDMI =PIX24 +S1.D -

-P51 Digital Power Meter Vaux 100-300VDC/85-265VAC, 45-65Hz. RS485 (2-wire) PM5350MG Schneider Electric =PIX24 +S1.D -

-S601 Control Switch, Spring Return to Center 1 pole, V/Imax 690VAC/20A, 110VDC/1A CA10-A714-600 K&N =PIX24 +S1.D -

-S625 Selector Switch OFF-ON Stay put, 4 NO, V/Imax 690VAC/20A, 110VDC/1A CA10-A203 K&N =PIX24 +S1.D -

-S650 Control Switch, Multi-Step 2 Pos, 4 Poles, V/Imax 690VAC/20A, 110VDC/1A CA10-A723-600 K&N =PIX24 +S1.D -
E E
-U101 Alarm Annunciator 6 Windows PB + 2 Buzzer, Vaux. 90~270VAC/DC MBAS 08 Minilec =PIX24 +S1.D -

-XT01 Easergy Test Block for VT-CT Imax 20A, Umax 300V AC/DC ETB14 Schneider Electric =PIX24 +S1.D -

-XT02 Easergy Test Block for VT-CT Imax 20A, Umax 300V AC/DC ETB14 Schneider Electric =PIX24 +S1.D -

-H101 Voltage Presence Indicating System LED VPIS-V2 Schneider Electric =PIX24 +S4 -

-Q30 Earthing Switch + Aux contacts 3P + Aux. Contacts (4 N/C + 4 N/O) - Schneider Electric =PIX24 +S4 -

F F

Date 12/02/2020 Project Name Title Bill of Materials Drawing Nr. =PIX24
01 As Manufactured 29/04/2020 WD Drawn FND
PENYEMPURNAAN SISTEM 20KV X4029420-303 +Layout
00 First Issued 12/02/2020 FND Checked BWP PANEL BUS SECTION Customer Doc. Nr. Sheet 34
Rev N° Modification Date Name Approved DTA Order N° C2030-4029420 Switchboard 20kV MV SWITCHGEAR PT SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Device Designation Description Technical Data Reff/Part Number Manufacturer Panel Location Remarks
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

-Q51 Vacuum Circuit Breaker 3P, c/w F2 (CC), F11 (OC) HVX Schneider Electric =PIX24 +S4 -
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

-R11 Heating Resistor 40W, 100-240VAC Blizzard 50H 40W DBK =PIX24 +S4 -

-S8 Micro Switch V-156-1A5, 1COS V-156-1A5 OMRON =PIX24 +S4 -

-SS1 Service Position Micro Switch EX1.20YR2 (Yellow), 1NO EX1.20YR2 ELMEX =PIX24 +S4 -

-SS2 Service Position Micro Switch EX1.20YR2 (Yellow), 1NO EX1.20YR2 ELMEX =PIX24 +S4 -

-SS3 Service Position Micro Switch EX1.20YR2 (Yellow), 1NO EX1.20YR2 ELMEX =PIX24 +S4 -

-SS4 Service Position Micro Switch EX1.20YR2 (Yellow), 1NO EX1.20YR2 ELMEX =PIX24 +S4 -

B -ST1 Test Position Micro Switch EX1.20BR2 (Blue), 1NC EX1.20BR2 ELMEX =PIX24 +S4 - B

-ST2 Test Position Micro Switch EX1.20BR2 (Blue), 1NC EX1.20BR2 ELMEX =PIX24 +S4 -

-ST3 Test Position Micro Switch EX1.20BR2 (Blue), 1NC EX1.20BR2 ELMEX =PIX24 +S4 -

-ST4 Test Position Micro Switch EX1.20BR2 (Blue), 1NC EX1.20BR2 ELMEX =PIX24 +S4 -

-X07 Mate n Lock Terminal SP SC 2.5/2, 2 Pole - PHOENIX =PIX24 +S4 -

-Y8 E/S Blocking Magnet 24V DC - - =PIX24 +S4 -

-Q51 Circuit Breaker 3P, Vacuum HVX - Schneider Electric =PIX24 +S4 - -

C -M1 - Spring Charging Motor Ur min -15% max +10 %, 100 W/VA Ua 110 VDC Schneider Electric =PIX24 +S4 - - C

-F2 - Closing Release Coil Ur 60-140 V DC/AC, 50/60Hz, ≤ 250 W/VA Ua 110 VDC Schneider Electric =PIX24 +S4 - -

-K01 - Anti-pumping Relay for Closing circuit Ua 110 VDC Schneider Electric =PIX24 +S4 - -

-F11 - Opening Release Coil Ur 60-140 V DC/AC, 50/60Hz, ≤ 250 W/VA Ua 110 VDC Schneider Electric =PIX24 +S4 - -

-T51 L1 Current Transformer 3 Windings (See SLD) Trafindo / Schneider Electric


=PIX24 +S4 - -

-T51 L2 Current Transformer 3 Windings (See SLD) Trafindo / Schneider Electric


=PIX24 +S4 - -

-T51 L3 Current Transformer 3 Windings (See SLD) Trafindo / Schneider Electric


=PIX24 +S4 - -

D -T61 L1 Voltage Transformer VT 2 Windings - Trafindo =PIX24 +S4 - - D


-T61 L2 Voltage Transformer VT 2 Windings - Trafindo =PIX24 +S4 - -

-T61 L3 Voltage Transformer VT 2 Windings - Trafindo =PIX24 +S4 - -

VT Withdrawable - AIN for PIX 24 - Schneider Electric =PIX24 +S4 - -

-F30 L1 VT Fuse with Indicator Ir 1.4 A Ur 15/24 kV dia. 22, L=280 mm HSW 67037.0004 / F3007500002 Efen =PIX24 +S4 - -

-F30 L2 VT Fuse with Indicator Ir 1.4 A Ur 15/24 kV dia. 22, L=280 mm HSW 67037.0004 / F3007500002 Efen =PIX24 +S4 - -

-F30 L3 VT Fuse with Indicator Ir 1.4 A Ur 15/24 kV dia. 22, L=280 mm HSW 67037.0004 / F3007500002 Efen =PIX24 +S4 - -

-X021 VT Plug-in Connector, Male-Female 8 pos, 2.5 sqmm, max 24A 500V ST Combi 8 pos Phoenix =PIX24 +S4 - -
E E
-X022 VT Plug-in Connector, Male-Female 8 pos, 2.5 sqmm, max 24A 500V ST Combi 8 pos Phoenix =PIX24 +S4 - -

-F50 PROTECTION RELAY Rated Current Input : 1/5A MiCOM P143 Schneider Electric =PIX24 +S1.D - -
Auxiliary Voltage Rating : 110-250Vdc (100-240Vac)
Rated Voltage Input : Vn = 100-120Vac
Hardware option: Ethernet (100Mbit/s) plus IRIG-B (Modulated)
Product Specific Options : 24 inputs & 22 outputs
Protocol Communication : IEC 61850 over Ethernet and
Courier via rear K-Bus/RS485
Language : English, French, German, Spanish
Flush Panel
F F

Date 12/02/2020 Project Name Title Bill of Materials Drawing Nr. =PIX24
01 As Manufactured 29/04/2020 WD Drawn FND
PENYEMPURNAAN SISTEM 20KV X4029420-303 +Layout
00 First Issued 12/02/2020 FND Checked BWP PANEL BUS SECTION Customer Doc. Nr. Sheet 35
Rev N° Modification Date Name Approved DTA Order N° C2030-4029420 Switchboard 20kV MV SWITCHGEAR PT SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8

You might also like