Main Cover Sheet
B B
C C
Last Used by: z004mx4y
Time: 9:54:14 AM
Date: 11/26/2022
End Customer
Torrent Power Ltd, Ahmedabad
Consultant
D EPC/Contractor D
Siemens Ltd.
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) 206 01
Drawing No.
(3)G719EA-MG9256-02-206
F F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad Main Cover Sheet System for Various Substations 20601
3007687802(T),30071 Sh. 01 of 2
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Main Cover Sheet
G) <- 02>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1. The revision no. of the drawing is changed whenever changes are asked by client.
A A
The revision no. is continuous from 0, A, B, C….. & so on.
2. The version no. of the drawing is changed whenever the drawing is revised whether due to client’s comments, engineering changes,
factory changes, site comments etc. The version no. is continuous from 0, 1, 2, 3….. & so on.
3. The sheets which are changed can be tracked from the sheet “Summary of Amendments”.
The revision no., version no. and the corresponding reason for amendment is reflected on the “Summary of Amendments” sheet.
B B
C C
Last Used by: z004mx4y
Time: 9:54:39 AM
Date: 11/25/2022
SUMMARY OF AMENDMENTS
D 03 - - - - - - D
04 -- -- -- -- -- --
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) 206 02
05 -- -- -- -- -- --
06 -- -- -- -- -- --
07 -- -- -- -- -- --
CopyRight (C) Siemens Limited, India All Rights Reserved.
08 -- -- -- -- -- --
09 -- -- - -- -- --
E E
10 -- -- -- -- -- --
11 -- -- - -- -- --
12 -- -- -- -- -- --
13 -- -- -- -- -- --
14 -- -- -- -- -- --
15 -- -- - -- -- --
F F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad Summary of Amendments System for Various Substations 20602
3007687802(T),30071 Sh. 02 of 2
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Main Cover Sheet
G) <01 ->
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
A A
SI DG EA
Equipment List
B B
C C
Last Used by: z004mx4y
Time: 9:55:00 AM
Date: 11/28/2022
D D
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) E206 01
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
F F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated E 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad Cover Sheet System for Various Substations E20601
3007687802(T),30071 Sh. 01 of 8
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-E206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Equipment List
G) <- 02>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Case Size: 1/1 19", 12xI, 8xV, 119 BI, 12 BO, 1 Live Status, 32 LED, Flush Mounting
Numerical Relay 7UT86
87T1 (7UT86) Siemens CT Sec: 1A, PT Sec: 110V AC, Aux Supply: 60-250V DC, 100-230V AC, AI: 4(4-20mA) Boughtout Front Mount 1
Transf. Prot P1F675604
2 x Optical Ethernet, LC Duplex Connector, 100 Mbit/s
RET670 Case Size: 3/4 19", 9xI, 3xV, 32 BI, 24 BO, 1 Watchdog Contact, 15 LED, Flush Mounting
Numerical Relay
87T2(RET670) ABB, India RET670 2.2-1MRK002816-AG CT Sec: 1A, PT Sec: 110V AC, Aux Supply: 90-250V DC, mA Input Module (MIM) Boughtout Front Mount 1
Main-2Transf. Prot
(15I,9V,32BI,24BO,6mA MIM) IEC 61850, Optical, Single, LC Connector
Case Size: 1/1 19", 4xI, 4xV, 143 BI, 48 BO, 1 Live Status, 32 LED, Flush Mounting
Numerical Relay 6MD86
BCPU(6MD86) Siemens CT Sec: 1A, PT Sec: 110V AC, Aux Supply: 60-250V DC, 100-230V AC Boughtout Front Mount 1
Bay Control Unit P1G514231
B 2 x Optical Ethernet, LC Duplex Connector, 100 Mbit/s B
1U, 19” Rack Mount, Ethernet: Rear, LED: Front, Power: Rear, Screw-Type Terminals
Ethernet Switch Siemens-Ruggedcom, RSG2100
2ES-1 Dual Aux Supply: 88-300V DC, 85-264V AC, Ports: 2 RJ45, 12 LC FO Multimode: 1300nm Boughtout Front Mount 1
RUGGEDCOM RSG2100 Canada RSG2100
Model: 6GK6021-0AS23-3DB1-Z A05+B05+C05+D05+E00+F00+G00+H05+J05+K01
Relay Case With Base, Type: RHGX20
Accessory- Relay, Contactor RHGX
ABB-Case-1 ABB, India Case Size: 4U 60C Boughtout Front Mount 1
RHGX20-With Case (Flush) 1MYN 560 004-D
With EPDM Gasket
Relay Case With Base, Type: RHGX20
Accessory- Relay, Contactor RHGX
ABB-Case-2 ABB, India Case Size: 4U 60C Boughtout Front Mount 1
RHGX20-With Case (Flush) 1MYN 560 004-D
With EPDM Gasket
Relay Case With Base, Type: RHGX20
Accessory- Relay, Contactor RHGX
ABB-Case-3 ABB, India Case Size: 4U 60C Boughtout Front Mount 1
RHGX20-With Case (Flush) 1MYN 560 004-D
With EPDM Gasket
C C
Last Used by: z004mx4y
Aux Voltage: 110/220V DC, Contacts: 1NO+2NC, S/R, Flag: Yes (LED)
Relay, Contactor TSR-B
195-B ABB, India Case Size: 2U 6C, Dropout Delay ≥ 300ms Boughtout Front Mount 1
Time: 9:55:27 AM
Date: 11/26/2022
Aux Voltage: 110/220V DC, Contacts: 1NO+2NC, S/R, Flag: Yes (LED)
Relay, Contactor TSR-B
195-R ABB, India Case Size: 2U 6C, Dropout Delay ≥ 300ms Boughtout Front Mount 1
Supervision Relay 1MYN 569 339-A
Aux Voltage: 110/220V DC, Contacts: 1NO+2NC, S/R, Flag: Yes (LED)
Relay, Contactor TSR-B
195-Y ABB, India Case Size: 2U 6C, Dropout Delay ≥ 300ms Boughtout Front Mount 1
Supervision Relay 1MYN 569 339-A
Aux Voltage: 110/220V DC, Contacts: 1NO+2NC, S/R, Flag: Yes (LED)
Relay, Contactor TSR-B
295-B ABB, India Case Size: 2U 6C, Dropout Delay ≥ 300ms Boughtout Front Mount 1
Supervision Relay 1MYN 569 339-A
D D
Aux Voltage: 110/220V DC, Contacts: 1NO+2NC, S/R, Flag: Yes (LED)
Relay, Contactor TSR-B
295-R ABB, India Case Size: 2U 6C, Dropout Delay ≥ 300ms Boughtout Front Mount 1
Supervision Relay 1MYN 569 339-A
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) E206 02
Aux Voltage: 110/220V DC, Contacts: 1NO+2NC, S/R, Flag: Yes (LED)
Relay, Contactor TSR-B
295-Y ABB, India Case Size: 2U 6C, Dropout Delay ≥ 300ms Boughtout Front Mount 1
Supervision Relay 1MYN 569 339-A
Aux Voltage: 110/220V DC, Contacts: 1NO+2NC, S/R, Flag: Yes (LED)
Relay, Contactor TSR-B
80A ABB, India Case Size: 2U 6C, Dropout Delay ≥ 300ms Boughtout Front Mount 1
DC-1 Supervision Relay 1MYN 569 339-A
CopyRight (C) Siemens Limited, India All Rights Reserved.
Aux Voltage: 110/220V DC, Contacts: 1NO+2NC, S/R, Flag: Yes (LED)
Relay, Contactor TSR-B
80B ABB, India Case Size: 2U 6C, Dropout Delay ≥ 300ms Boughtout Front Mount 1
DC-2 Supervision Relay 1MYN 569 339-A
E Aux Voltage: 110/220V DC, Contacts: 1NO+2NC, S/R, Flag: Yes (LED) E
Relay, Contactor TSR-B
95.1 ABB, India Case Size: 2U 6C, Dropout Delay ≥ 300ms Boughtout Front Mount 1
86.1 Supvn relay 1MYN 569 339-A
Aux Voltage: 110/220V DC, Contacts: 1NO+2NC, S/R, Flag: Yes (LED)
Relay, Contactor TSR-B
95.2 ABB, India Case Size: 2U 6C, Dropout Delay ≥ 300ms Boughtout Front Mount 1
86.2 Supvn relay 1MYN 569 339-A
Aux Voltage: 110V DC, Contacts: 7NO+7NC, E/R, Flag: Yes (Mechanical)
Relay, Contactor RXPSU14n
75.1 ABB, India Case Size: 2U 12C Boughtout Front Mount 1
Voltage Selection Relay 1MYN563646-DBA
Aux Voltage: 110V DC, Contacts: 7NO+7NC, E/R, Flag: Yes (Mechanical)
Relay, Contactor RXPSU14n
75.2 ABB, India Case Size: 2U 12C Boughtout Front Mount 1
Voltage Selection Relay 1MYN563646-DBA
F F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated E 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad Bill of Materials System for Various Substations E20602
3007687802(T),30071 Sh. 02 of 8
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-E206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Equipment List
G) <01 03>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Aux Voltage: 110-125V DC, Contacts: 6NO (3NO Per Coil), Flag: No
Relay, Contactor RXMM1
52A ABB, India Case Size: 2U 6C Boughtout Front Mount 1
CB OPEN MUL.RELAY RK 214 003-AN
Aux Voltage: 110-125V DC, Contacts: 6NO (3NO Per Coil), Flag: No
Relay, Contactor RXMM1
52B ABB, India Case Size: 2U 6C Boughtout Front Mount 1
CB CLOSE MUL.RELAY RK 214 003-AN
Aux Voltage: 24V DC, Contacts: 11NO+3NC, H/R or E/R, Flag: Yes
Relay, Contactor RXMVB4
86.1 ABB, India Case Size: 4U 12C Boughtout Front Mount 1
Trip Relay RK 251 900-XR (403-AD)
Use With RXTMA Series Resistor
Aux Voltage: 24V DC, Contacts: 11NO+3NC, H/R or E/R, Flag: Yes
Relay, Contactor RXMVB4
86.2 ABB, India Case Size: 4U 12C Boughtout Front Mount 1
Trip Relay RK 251 900-XR (403-AD)
Use With RXTMA Series Resistor
Aux Voltage: 110-125V DC, Contacts: 6NO (3NO Per Coil), S/R, Flag: Yes
Relay, Contactor RXSF1
GC00 ABB, India Case Size: 2U 6C Boughtout Front Mount 1
Auxiliary Relay RK 271 018-AN
D D
Aux Voltage: 110-125V DC, Contacts: 6NO (3NO Per Coil), S/R, Flag: Yes
Relay, Contactor RXSF1
GC01 ABB, India Case Size: 2U 6C Boughtout Front Mount 1
Auxiliary Relay RK 271 018-AN
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) E206 03
Aux Voltage: 110-125V DC, Contacts: 6NO (3NO Per Coil), S/R, Flag: Yes
Relay, Contactor RXSF1
GC02 ABB, India Case Size: 2U 6C Boughtout Front Mount 1
Auxiliary Relay RK 271 018-AN
Aux Voltage: 110-125V DC, Contacts: 6NO (3NO Per Coil), S/R, Flag: Yes
Relay, Contactor RXSF1
GC03 ABB, India Case Size: 2U 6C Boughtout Front Mount 1
Auxiliary Relay RK 271 018-AN
CopyRight (C) Siemens Limited, India All Rights Reserved.
Aux Voltage: 110-125V DC, Contacts: 6NO (3NO Per Coil), S/R, Flag: Yes
Relay, Contactor RXSF1
GC04 ABB, India Case Size: 2U 6C Boughtout Front Mount 1
Auxiliary Relay RK 271 018-AN
E Aux Voltage: 110-125V DC, Contacts: 6NO (3NO Per Coil), S/R, Flag: Yes E
Relay, Contactor RXSF1
GC05 ABB, India Case Size: 2U 6C Boughtout Front Mount 1
Auxiliary Relay RK 271 018-AN
Aux Voltage: 110-125V DC, Contacts: 6NO (3NO Per Coil), S/R, Flag: Yes
Relay, Contactor RXSF1
GC06 ABB, India Case Size: 2U 6C Boughtout Front Mount 1
Auxiliary Relay RK 271 018-AN
Aux Voltage: 110-125V DC, Contacts: 6NO (3NO Per Coil), S/R, Flag: Yes
Relay, Contactor RXSF1
GC07 ABB, India Case Size: 2U 6C Boughtout Front Mount 1
Auxiliary Relay RK 271 018-AN
Aux Voltage: 110-125V DC, Contacts: 6NO (3NO Per Coil), S/R, Flag: Yes
Relay, Contactor RXSF1
GC08 ABB, India Case Size: 2U 6C Boughtout Front Mount 1
Auxiliary Relay RK 271 018-AN
F F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated E 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad Bill of Materials System for Various Substations E20603
3007687802(T),30071 Sh. 03 of 8
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-E206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Equipment List
G) <02 04>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Aux Voltage: 110-125V DC, Contacts: 6NO (3NO Per Coil), S/R, Flag: Yes
Relay, Contactor RXSF1
GC10 ABB, India Case Size: 2U 6C Boughtout Front Mount 1
Auxiliary Relay RK 271 018-AN
Aux Voltage: 110-125V DC, Contacts: 6NO (3NO Per Coil), S/R, Flag: Yes
Relay, Contactor RXSF1
GC11 ABB, India Case Size: 2U 6C Boughtout Front Mount 1
Auxiliary Relay RK 271 018-AN
Aux Voltage: 110-125V DC, Contacts: 6NO (3NO Per Coil), S/R, Flag: Yes
Relay, Contactor RXSF1
GC12 ABB, India Case Size: 2U 6C Boughtout Front Mount 1
Auxiliary Relay RK 271 018-AN
B B
Aux Voltage: 110-125V DC, Contacts: 6NO (3NO Per Coil), S/R, Flag: Yes
Relay, Contactor RXSF1
GC13 ABB, India Case Size: 2U 6C Boughtout Front Mount 1
Auxiliary Relay RK 271 018-AN
Aux Voltage: 110-125V DC, Contacts: 6NO (3NO Per Coil), S/R, Flag: Yes
Relay, Contactor RXSF1
GC14 ABB, India Case Size: 2U 6C Boughtout Front Mount 1
Auxiliary Relay RK 271 018-AN
Aux Voltage: 110-125V DC, Contacts: 6NO (3NO Per Coil), S/R, Flag: Yes
Relay, Contactor RXSF1
GC15 ABB, India Case Size: 2U 6C Boughtout Front Mount 1
Auxiliary Relay RK 271 018-AN
Aux Voltage: 110-125V DC, Contacts: 6NO (3NO Per Coil), S/R, Flag: Yes
Relay, Contactor RXSF1
GC16 ABB, India Case Size: 2U 6C Boughtout Front Mount 1
Auxiliary Relay RK 271 018-AN
C C
Last Used by: z004mx4y
Contacts: 2NO+2NC
Push Button IN5396
PB86.1 ABB, India Aux. Voltage: 48-220V DC Boughtout Front Mount 1
Time: 9:56:08 AM
Date: 11/28/2022
F F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated E 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad Bill of Materials System for Various Substations E20604
3007687802(T),30071 Sh. 04 of 8
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-E206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Equipment List
G) <03 05>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
F F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated E 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad Bill of Materials System for Various Substations E20605
3007687802(T),30071 Sh. 05 of 8
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-E206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Equipment List
G) <04 06>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Rating: 4A
Fuse Holder+Fuse 3NW
FSB1BC3 Siemens, India Aux Voltage: 110V AC Boughtout Internal Mount 1
VT Fuse 3NW32NNSF+3NWNS4
C C
Last Used by: z004mx4y
Rating: 4A
Fuse Holder+Fuse 3NW
FSB1BC4 Siemens, India Aux Voltage: 110V AC Boughtout Internal Mount 1
Time: 9:56:56 AM
Date: 11/28/2022
VT Fuse 3NW32NNSF+3NWNS4
Rating: 4A
Fuse Holder+Fuse 3NW
FSB1BM Siemens, India Aux Voltage: 110V AC Boughtout Internal Mount 1
VT Fuse 3NW32NNSF+3NWNS4
Rating: 4A
Fuse Holder+Fuse 3NW
FSB1RC3 Siemens, India Aux Voltage: 110V AC Boughtout Internal Mount 1
VT Fuse 3NW32NNSF+3NWNS4
Rating: 4A
Fuse Holder+Fuse 3NW
FSB1RC4 Siemens, India Aux Voltage: 110V AC Boughtout Internal Mount 1
VT Fuse 3NW32NNSF+3NWNS4
D D
Rating: 4A
Fuse Holder+Fuse 3NW
FSB1RM Siemens, India Aux Voltage: 110V AC Boughtout Internal Mount 1
VT Fuse 3NW32NNSF+3NWNS4
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) E206 06
Rating: 4A
Fuse Holder+Fuse 3NW
FSB1YC3 Siemens, India Aux Voltage: 110V AC Boughtout Internal Mount 1
VT Fuse 3NW32NNSF+3NWNS4
Rating: 4A
Fuse Holder+Fuse 3NW
FSB1YC4 Siemens, India Aux Voltage: 110V AC Boughtout Internal Mount 1
VT Fuse 3NW32NNSF+3NWNS4
CopyRight (C) Siemens Limited, India All Rights Reserved.
Rating: 4A
Fuse Holder+Fuse 3NW
FSB1YM Siemens, India Aux Voltage: 110V AC Boughtout Internal Mount 1
VT Fuse 3NW32NNSF+3NWNS4
E Rating: 4A E
Fuse Holder+Fuse 3NW
FSB2BC3 Siemens, India Aux Voltage: 110V AC Boughtout Internal Mount 1
VT Fuse 3NW32NNSF+3NWNS4
Rating: 4A
Fuse Holder+Fuse 3NW
FSB2BC4 Siemens, India Aux Voltage: 110V AC Boughtout Internal Mount 1
VT Fuse 3NW32NNSF+3NWNS4
Rating: 4A
Fuse Holder+Fuse 3NW
FSB2BM Siemens, India Aux Voltage: 110V AC Boughtout Internal Mount 1
VT Fuse 3NW32NNSF+3NWNS4
Rating: 4A
Fuse Holder+Fuse 3NW
FSB2RC3 Siemens, India Aux Voltage: 110V AC Boughtout Internal Mount 1
VT Fuse 3NW32NNSF+3NWNS4
F F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated E 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad Bill of Materials System for Various Substations E20606
3007687802(T),30071 Sh. 06 of 8
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-E206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Equipment List
G) <05 07>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Rating: 4A
Fuse Holder+Fuse 3NW
FSB2RM Siemens, India Aux Voltage: 110V AC Boughtout Internal Mount 1
VT Fuse 3NW32NNSF+3NWNS4
Rating: 4A
Fuse Holder+Fuse 3NW
FSB2YC3 Siemens, India Aux Voltage: 110V AC Boughtout Internal Mount 1
VT Fuse 3NW32NNSF+3NWNS4
Rating: 4A
Fuse Holder+Fuse 3NW
FSB2YC4 Siemens, India Aux Voltage: 110V AC Boughtout Internal Mount 1
VT Fuse 3NW32NNSF+3NWNS4
B B
Rating: 4A
Fuse Holder+Fuse 3NW
FSB2YM Siemens, India Aux Voltage: 110V AC Boughtout Internal Mount 1
VT Fuse 3NW32NNSF+3NWNS4
Rating: 4A
Fuse Holder+Fuse 3NW
FSLB Siemens, India Aux Voltage: 110V AC Boughtout Internal Mount 1
VT Fuse 3NW32NNSF+3NWNS4
Rating: 4A
Fuse Holder+Fuse 3NW
FSLR Siemens, India Aux Voltage: 110V AC Boughtout Internal Mount 1
VT Fuse 3NW32NNSF+3NWNS4
Rating: 4A
Fuse Holder+Fuse 3NW
FSLV Siemens, India Aux Voltage: 110V AC Boughtout Internal Mount 1
VT Fuse 3NW32NNSF+3NWNS4
C C
Last Used by: z004mx4y
Rating: 4A
Fuse Holder+Fuse 3NW
FSLVB Siemens, India Aux Voltage: 110V AC Boughtout Internal Mount 1
Time: 9:57:19 AM
Date: 11/28/2022
VT Fuse 3NW32NNSF+3NWNS4
Rating: 4A
Fuse Holder+Fuse 3NW
FSLVR Siemens, India Aux Voltage: 110V AC Boughtout Internal Mount 1
VT Fuse 3NW32NNSF+3NWNS4
Rating: 4A
Fuse Holder+Fuse 3NW
FSLVY Siemens, India Aux Voltage: 110V AC Boughtout Internal Mount 1
VT Fuse 3NW32NNSF+3NWNS4
Rating: 4A
Fuse Holder+Fuse 3NW
FSLY Siemens, India Aux Voltage: 110V AC Boughtout Internal Mount 1
VT Fuse 3NW32NNSF+3NWNS4
D D
Rating: 4A
Fuse Holder+Fuse 3NW
FSSBC3 Siemens, India Aux Voltage: 110V AC Boughtout Internal Mount 1
VT Fuse 3NW32NNSF+3NWNS4
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) E206 07
Rating: 4A
Fuse Holder+Fuse 3NW
FSSBC3-1 Siemens, India Aux Voltage: 110V AC Boughtout Internal Mount 1
VT Fuse 3NW32NNSF+3NWNS4
Rating: 4A
Fuse Holder+Fuse 3NW
FSSBC4 Siemens, India Aux Voltage: 110V AC Boughtout Internal Mount 1
VT Fuse 3NW32NNSF+3NWNS4
CopyRight (C) Siemens Limited, India All Rights Reserved.
Rating: 4A
Fuse Holder+Fuse 3NW
FSSRC3 Siemens, India Aux Voltage: 110V AC Boughtout Internal Mount 1
VT Fuse 3NW32NNSF+3NWNS4
E Rating: 4A E
Fuse Holder+Fuse 3NW
FSSRC3-1 Siemens, India Aux Voltage: 110V AC Boughtout Internal Mount 1
VT Fuse 3NW32NNSF+3NWNS4
Rating: 4A
Fuse Holder+Fuse 3NW
FSSRC4 Siemens, India Aux Voltage: 110V AC Boughtout Internal Mount 1
VT Fuse 3NW32NNSF+3NWNS4
Rating: 4A
Fuse Holder+Fuse 3NW
FSSYC3 Siemens, India Aux Voltage: 110V AC Boughtout Internal Mount 1
VT Fuse 3NW32NNSF+3NWNS4
Rating: 4A
Fuse Holder+Fuse 3NW
FSSYC3-1 Siemens, India Aux Voltage: 110V AC Boughtout Internal Mount 1
VT Fuse 3NW32NNSF+3NWNS4
F F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated E 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad Bill of Materials System for Various Substations E20607
3007687802(T),30071 Sh. 07 of 8
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-E206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Equipment List
G) <06 08>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
D D
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) E206 08
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
F F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated E 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad Bill of Materials System for Various Substations E20608
3007687802(T),30071 Sh. 08 of 8
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-E206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Equipment List
G) <07 ->
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
A A
SI DG EA
General Arrangement
B B
C C
Last Used by: z004mx4y
Time: 9:58:07 AM
Date: 11/28/2022
D D
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) F206 01
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
F F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated F 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad Cover Sheet System for Various Substations F20601
3007687802(T),30071 Sh. 01 of 5
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-F206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: General Arrangement
G) <- 02>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
(Board)
REAR VIEW WITH SWING FRAME B-TYPE NAME PLATE -1 NO.
1 CONTROL & RELAY PANEL
A
A A
PANEL REF:206R
S. NO. ▲2 DESIGN. DESCRIPTION TYPE MANUFACTURER
PB86.1 RU.86.1
PB86.2 RU.86.2
2U
95.1
95.2
2ES-6
86.2
5 BCPU(6MD86) Bay Control Unit 6MD86 Siemens
86.1
ABB-Case-1
52A
80A
52B
80B
7 87T2(RET670) Main-2Transf. Prot RET670 ABB
5U
DCC02 DCC01
11 75.2 Voltage Selection Relay RXPSU14n ABB
195-B
195-R
195-Y
75.1
K1
12 75.3 Voltage Selection Relay RXPSU14n ABB
BCPU(6MD86)
BCPU(6MD86)
BCPU(6MD86)
BCPU(6MD86)
BCPU(6MD86)
ABB-Case-2
295-R
295-Y
295-B
75.2
75.3
7U
K2
14 80B DC-2 Supervision Relay TSR-B ABB
15 86.1 Trip Relay RXMVB4 ABB
16 86.2 Trip Relay RXMVB4 ABB
17 95.1 86.1 Supvn relay TSR-B ABB
1U
87T1 (7UT86)
87T1 (7UT86)
87T1 (7UT86)
CS52
Time: 9:58:44 AM
Date: 11/26/2022
GC04
GC00
GC02
GC06
GC12
GC08
GC10
GC14
GC16
K3
24 295-Y Supervision Relay TSR-B ABB
ABB-Case-3
25 DCC01 Dc-1 CHANGE OVER RXMH2 ABB
GC01
GC03
GC05
GC07
GC09
GC11
1U
GC13
GC15
K4
26 DCC02 Dc-2 CHANGE OVER RXMH2 ABB
1780
1U
**PS2
43 GC16 Auxiliary Relay RXSF1 ABB
100
44 K1 SF6 ZONE TRIP 86-A/B RXMS1 ABB
45 K2 TO ZONE INTER-TRIP RXMS1 ABB
46 K3 BUSBAR ZONE-1 TRIP RXMS1 ABB
0 0
A A
275
400
80
BACK DOORS
FRONT
129
2195
Time: 9:59:15 AM
Date: 11/03/2022
25
2312
328
1000
63
D D
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) F206 03
328
15mm Anti Vibration Pad
CopyRight (C) Siemens Limited, India All Rights Reserved.
25
152
100 100
148
E 12 E
EARTH BUSBAR SLOT 120 299 299 120
62
54
900
65
0
102
1027
FRONT
F Dimension Unit: mm, All Dimension Tolerance= ±5mm F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated F 206R 1 mm. : 10 mm.
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad Side View & Panel Fixing-Top View System for Various Substations F20603
3007687802(T),30071 Sh. 03 of 5
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd. 1 Cubicle per Bay
48372(L),3007688671( (3)G719EA-MG9256-02-F206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: General Arrangement
G) <02 04>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
A A
B B
220kV BUSBAR 220/132/33kV,250MVA ICT-1 220kV LINE-1 220/132/33kV,250MVA ICT-2 220kV BUSCOUPLER 220K LINE-2 220/132/33kV ,250MVA ICT-3
PROTECTION PANEL CONTROL & RELAY PANEL CONTROL & RELAY PANEL CONTROL & RELAY PANEL PROTN. PANEL CONTROL & RELAY PANEL CONTROL & RELAY PANEL
PANEL REF:200R PANEL REF:201R PANEL REF:202R PANEL REF:203R PANEL REF:204R PANEL REF:205R PANEL REF:206R
200R 201R 202R 203R 204R 205R 206R
C C
Last Used by: z004mx4y
Time: 9:59:38 AM
Date: 11/28/2022
2200
2315
D D
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) F206 04
100
E E
A. PANEL CONSTRUCTION
A A
Panel Type and Dimensions
a. Type of Panel Simplex 1.Panel Width in mm 900
b. Type of Construction Swing Frame with Non Std Rack type 2.Total Height (incl Ant Pad and Base frame) in mm 2312
1) c. Front Door Full Glass Door g. Panel Dimensions 3.Panel Depth in mm 1000 i. Degree of Protection IP54
d. Rear Door Single Leaf Door 4.Anti-vibration Pad thickness in mm 15
e. Type of sheet steel CRCA Sheets 5.Base frame height in mm 102
f Sheet steel thickness Load bearing - 3 mm h. Sheet steel thickness Non-Load bearing - 2 mm j. Cable entry Bottom
Powder coating
2) a. External Colour Shade RAL 7032-Siemens Grey b Internal Colour Shade RAL 7032-Siemens Grey c Base Frame External Colour Black
shade
B B
Mimic Details
a. Type Not Applicable d. Colour for Earth Symbol Not Applicable g. Colour for 400 kV Not Applicable
3) b. Bus Width in mm Not Applicable e. Colour for 220kV Not Applicable h. Colour for 66kV Not Applicable
c. Branch Width in mm Not Applicable f. Colour for 132kV / 110kV Not Applicable i. Colour for 33kV / 22kV Not Applicable
Time: 10:00:12 AM
Date: 11/28/2022
5) a. Special instructions (if any) All Equipments are to be connected to earth bus with individual wires. No looping of earthing wires is allowed. Door and gland plate earthing to be done with 4 sqmm braded Cu wire.
B. PANEL WIRING
Terminal Blocks
a. Type of Material Polyamide type
b. Application Terminal Blocks Type Terminal Blocks Size Application Terminal Blocks Type Terminal Blocks Size
8)
Incoming CT/ PT circuits Disconnecting Stud Type Suitable for 2*4 sqmm Incoming AC & DC Circuits Non Disconnecting Stud Type Suitable for 2*16 sqmm
DC & AC Auxiliary/Control Non Disconnecting Stud Type Suitable for 2*2.5 sqmm Automation : Digital / Analog signals Non Disconnecting Stud Type Suitable for 2*1.5 sqmm
9) a. Special instructions (if any) All wires associated with tripping ckts. to be provided with red coloured 'T' ferrules. Transparent Covers shall be provided for TBs.
A A
SI DG EA
Internal Layout
B B
C C
Last Used by: z004mx4y
Time: 10:01:15 AM
Date: 11/28/2022
D D
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) V206 01
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
F F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated V 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad Cover Sheet System for Various Substations V20601
3007687802(T),30071 Sh. 01 of 3
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-V206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Internal Layout
G) <- 02>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
A A
SD1 SR1
RU.86.1 PB86.1
RU.86.2 PB86.2
95.1
95.2
86.2
86.1
ABB-Case-1
52A
80A
52B
80B
B B
FH3 (D60.00 mmxW60.00 mm)
FH3
DCC01 DCC02
195-B
195-R
195-Y
75.1
K1
ABB-Case-2
295-R
295-B
295-Y
75.2
75.3
K2
FH4 FH4 (D60.00 mmxW40.00 mm)
Time: 10:01:47 AM
CS52
Date: 11/26/2022
2195
FH5 FH5 (D60.00 mmxW40.00 mm)
GC04
GC12
GC06
GC02
GC00
GC16
GC14
GC10
GC08
K3
ABB-Case-3
GC05
GC03
GC01
GC09
GC07
GC11
GC15
GC13
K4
FH6 FH6 (D60.00 mmxW40.00 mm)
D D
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) V206 02
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
FV2
FV1
900
A A
CFLS
LED
RH1 RH1 (D60.00 mmxW40.00 mm)
LH1 LH1 (D60.00 mmxW40.00 mm)
MH1 (D60.00 mmxW60.00 mm)
MH1 XB:BB6(1-25) XB:BC6(1-7)
XB:AC(1-3) XB:ZZ(1-4) 2088 2088 2088
RU
XB:BC6
XB:BB6
RHMR1
XB:BC6
XB:BC6
XB:BC6
XB:BC6
XB:BC6
XB:BC6
XB:BC6
XB:BB6
XB:BB6
XB:BB6
XB:BB6
XB:BB6
XB:BB6
XB:BB6
XB:BB6
XB:BB6
XB:BB6
XB:BB6
XB:BB6
XB:BB6
XB:BB6
XB:BB6
XB:BB6
XB:BB6
XB:BB6
XB:BB6
XB:BB6
XB:BB6
XB:BB6
XB:BB6
XB:BB6
XB:BB6
XB:PT1
XB:PT2
XB:DC
XB:AC
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
XB:ZZ
7
1
9
LHMR1
XB:PT1
XB:PT1
XB:PT1
XB:PT1
XB:PT1
XB:PT1
XB:PT1
XB:PT1
XB:PT1
XB:PT1
XB:PT1
XB:PT1
XB:PT1
XB:PT1
XB:PT2
XB:PT2
XB:PT2
XB:PT2
XB:PT2
XB:PT2
XB:PT2
XB:PT2
XB:PT2
XB:PT2
XB:PT2
XB:PT2
XB:PT2
XB:PT2
XB:AC
XB:AC
XB:AC
XB:DC
XB:DC
XB:DC
XB:DC
XB:DC
XB:Z Z
XB:Z Z
XB:Z Z
XB:Z Z
10
11
12
13
14
10
11
12
13
14
1
9
1
4
2038 2038 2038
XB:DC(1-5) XB:PT1(1-14) XB:PT2(1-14) LM-2 LM-1 RH2 (D60.00 mmxW40.00 mm)
1988 1988 RH2 1988
LH2 LH2 (D60.00 mmxW40.00 mm)
1938 1938 1938
MCB-SP2
MCB-SP3
MCB-86.2
MCB-SP1
B B
MWT
LHMR2 1738 1738 HTS PS1 TH
RHMR2 1738
FSB1RC3
FSB1YC3
FSB1BC3
LKB1NC3
FSB2RC2
FSB2RC3
FSB1RC4
FSB2RC4
LKB1NC2
FSB2YC2
FSB2BC2
LKB2NC2
FSB2YC3
FSB2BC3
LKB2NC3
FSB1YC4
FSB1BC4
LKB1NC4
FSB2YC4
FSB2BC4
LKB2NC4
FSB1YC2
FSB1BC2
FSB1RC2
BCPU(6MD86)
BCPU(6MD86)
BCPU(6MD86)
BCPU(6MD86)
BCPU(6MD86)
LNPL1 1488 1488 1488
FS87T1-R
FS87T2-R
MCB-DCCO1
MCB-DCCO2
FS87T1-Y
FS87T1-B
LK87T1-N
FS87T2-Y
FS87T2-B
LK87T2-N
FSLM2-R
FSLM2-Y
FSLM2-B
LKLM2-N
MCB-BCPU
MCB2-ETH
LKLV-N
FSLV-R
MCB1-ETH
FSLV-Y
FSLV-B
MCB-87T2
1338
MCB-87T1
1338 1338
MCB-86.1
MCB-DC2
MCB-DC1
MCB-LM1
MCB-LM2
MCB-AUX
AMCB
LHMR4 RHMR4
87T1 (7UT86)
87T1 (7UT86)
87T1 (7UT86)
87T1 (7UT86)
87T1 (7UT86)
LH6 (D60.00 mmxW60.00 mm)
LH6 1138 1138 RH6 1138
X:LCC (131-228)
2195
X:CT F (18-20)
X:TR (101-138)
X:LCC (1-130)
X:CT (65-72)
X:LCC
(131-260)X:SP
X:SP
(1-130)X:SP
X:SP
X:CT (1-64)
X:CT
X:CT
65
18 X:TR X:SP
3
133
X:SP
2
X:LCC
133
X:LCC
134
X:SP 134 3 X:LCC
2 X:CT F
X:CT 4 X:SP X:LCC 135
19 X:TR X:SP
66 135 4 X:LCC
X:CT 101 5
X:SP X:SP X:LCC 136
3 X:CT F X:LCC
X:CT X:TR 6 136 5
20 102 X:SP X:SP 137
X:CT 67 X:LCC X:LCC
7 137
4 X:TR 6 138
X:SP X:SP X:LCC
X:CT 103 X:LCC
8 138
X:TR 139
X:CT X:PT1 6
X:TR
X:TR
17
X:SP
X:SP
147
X:SP
X:LCC
15
148
X:LCC
10 110 18 149
X:PT 1 7 X:SP 148 X:LCC X:LCC
X:TR 19 X:SP 16
X:CT 1 X:TR 150
111 X:SP 149 X:LCC X:LCC
11 8 X:SP
20 17 151
X:PT 1 X:TR X:TR X:SP 150
X:LCC X:LCC
X:CT 2 9 112 21 X:SP
X:SP 18 152
12 X:TR 151 X:LCC
X:TR 22 X:SP X:LCC
X:PT 1 10 X:SP 153
113 152 19 X:LCC
X:CT 3 X:TR 23 X:SP
13 26 X:SP 22
MH5
5 X:TR X:SP 157
X:CT X:LCC X:LCC
X:TR 116 27 156
15 X:SP 23 158
X:PT 1 14 X:SP X:LCC X:LCC
X:TR X:TR 28 157
X:CT 6 X:SP 24 159
15 117 X:SP X:LCC X:LCC
16 158
29 25 160
X:PT 1 X:TR X:TR X:SP X:SP X:LCC X:LCC
X:CT
23
X:PT2 X:TR
25
X:TR
126
40
X:SP
41
X:SP
170
X:LCC
37
X:LCC
172
X:SP X:LCC X:LCC
X:TR X:SP
X:PT 2 X:TR 171 38 173
X:CT 26 42 X:LCC
1 127 X:SP X:SP X:LCC
24 X:TR 174
43 172 39 X:LCC
27 X:TR X:SP X:LCC
D D
X:PT 2 X:SP 175
X:CT 128 173 40
2 X:TR 44 X:SP X:LCC
177 X:LCC
31 131 48 X:SP X:LCC
X:SP 180
X:PT 2 178 45 X:LCC
X:CT X:TR X:TR 49 X:SP X:LCC
5 181
28 32 132 X:SP 179 46 X:LCC
X:TR 50 X:SP X:LCC
X:PT 2 X:TR X:SP 182
X:CT 33 180 47 X:LCC
6 133 51 X:SP X:LCC
29 X:TR 183
87T2(RET670)
X:SP 181 48 X:LCC
X:TR
X:PT 2 X:LCC
X:CT
34 11
40
X:TR
X:LV 59
X:SP
X:SP
189 56
X:LCC
191
X:LCC
192
60 X:SP
41 X:LV X:SP 57 X:LCC
X:PT 2 190
X:CT 1 61 X:SP X:LCC 193
12 X:TR X:LCC
35 X:SP 191 58
42 X:LV X:LCC 194
62 X:SP
RVMR4
RVMR3
X:PT 2 X:TR X:LCC
2 X:SP 59
LVMR4
LVMR3
LVMR2
RVMR2
RVMR1
13 43 63
36 X:SP X:LCC
LVMR1
X:LV 60
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) V206 03
X:CT
38
X:PT3 X:TR
46
X:LV
5
66
X:SP
X:SP
196
63
X:LCC
X:LCC
199
67 X:SP X:LCC
X:TR X:LV 64
X:CT X:PT 3 X:SP 197 X:LCC 200
47 6 X:LCC
39 1 68 X:SP 65
X:TR X:SP 201
X:LV 198 X:LCC X:LCC
48 69 X:SP
X:CT X:PT 3 7 66 202
X:TR X:SP 199 X:LCC
40 2 X:SP X:LCC
49 X:LV 70 67
200 203
8 X:LCC X:LCC
X:PT 3 X:TR X:SP X:SP
X:CT 68 204
3 50 X:LV 71 201 X:LCC
41 X:LCC
MH6
X:TR X:LV X:SP X:SP
X:CT X:PT 3 73 209
54 12 76 206 X:LCC X:LCC
44 6
X:TR X:SP X:SP 74 210
X:LV X:LCC
55 77 207 X:LCC
X:CT X:PT 3 13 X:SP 211
X:TR X:SP 75
45 7 78 X:LCC X:LCC
56 X:LV 208
X:SP X:SP 76 212
14 X:LCC X:LCC
HMR1
61 18 X:SP 82
X:LCC X:LCC
49 11 X:TR 85 215
X:LV X:SP 83 219
62 X:SP X:LCC
22 220 X:LCC
52 X:LVPT X:TR 90 224
X:SP 88 X:LCC
1 66 X:SP X:LCC
X:CT X:TR
X:LM 91 221 225
228
3 69 94 224 92
X:LM X:SP X:SP
X:CT X:TR X:LCC
2 95 225
55 X:LVPT 70 X:SP 93
X:SP X:LCC
X:CT
4
X:TR X:LM
3
96
X:SP
226
X:SP
94
X:LCC
X:NIFPS
71 X:NIFPS
56 X:LVPT 97 227 95
X:TR X:LM X:SP 1
5 X:SP X:LCC
72 4 228 X:NIFPS
X:CT 98 96
X:TR X:SP X:SP X:LCC 2
57 X:LVPT X:LM
73 99 229 97 X:NIFPS
6 5 X:SP
X:SP X:LCC 3
X:CT X:TR 230
X:LCC 5
X:CT F (1-17)
59 102 232
X:TR X:LA 100 X:NIFPS
X:SP X:SP
76
X:CT
60
X:CT F X:TR
1
X:LA
103
X:SP
233
X:SP X:LCC
101
6
X:NIFPS
7
77 104 234
2 X:SP X:LCC X:NIFPS
X:CT F X:TR X:SP
235 102 8
1 78 105 X:SP X:LCC
X:CT X:LA X:SP X:NIFPS
61 X:TR 3 236 103
X:CT F 106 X:LCC 9
79 X:SP X:SP X:NIFPS
X:MWT (1-5)
2 X:LA 104
X:TR 107 237 X:LCC 10
X:CT 4 X:SP
E E
X:LCC 4
X:MWT 113 243
X:AC 6
X:CT F
X:TR
85 2 X:SP
114
X:SP
244
111
X:LCC
X:OLTC
5
112
HT
X:TR 117 247
2 X:CT F X:MWT X:SP 115 8
88 X:SP
9 5 248 X:LCC X:OLTC
X:TR
**PS2
118
X:SP X:SP 116 9
X:AC 89 X:LCC X:OLTC
X:CT F 119 249
3 X:TR 117
X:LCC 10
10 X:SP X:SP
X:DC (1-5)
258
MV2
X:CT F X:SP X:SP X:OLTC
MH9
X:TR 130
100
RV4
RV3
RV2
RV1
LV5
LV4
LV3
LV2
0
0 0 0
102
10.00
1000 1000
F
REAR SIDE - LH F
NOTE : Equipment location may change during manufacturing Name Plate Rail
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated V 206R 1 mm. : 10 mm.
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad Internal Layout System for Various Substations V20603
3007687802(T),30071 Sh. 03 of 3
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-V206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Internal Layout
G) <02 ->
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
A A
SI DG EA
Wiring Schematics
B B
C C
Last Used by: z004mx4y
Time: 10:03:30 AM
Date: 11/28/2022
D D
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 01
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
F F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad Cover Sheet System for Various Substations W20601
3007687802(T),30071 Sh. 01 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <- 02>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
PANEL PANEL
SHEET NO. DESCRIPTION DRAWING NUMBER SHEET NO. DESCRIPTION DRAWING NUMBER
A REFERENCE REFERENCE A
Cover Sheet Logic Diagram
01 (3)G719EA-MG9256-02-W206 206R 21 (3)G719EA-MG9256-02-W206 206R
Wiring Schematics Wiring Schematics
List of Documents Logic Diagram
02 (3)G719EA-MG9256-02-W206 206R 22 (3)G719EA-MG9256-02-W206 206R
Wiring Schematics Wiring Schematics
List of Documents Logic Diagram
03 (3)G719EA-MG9256-02-W206 206R 23 (3)G719EA-MG9256-02-W206 206R
Wiring Schematics Wiring Schematics
List of Documents Logic Diagram
04 (3)G719EA-MG9256-02-W206 206R 24 (3)G719EA-MG9256-02-W206 206R
B Wiring Schematics Wiring Schematics B
Legend Logic Diagram
05 (3)G719EA-MG9256-02-W206 206R 25 (3)G719EA-MG9256-02-W206 206R
Wiring Schematics Wiring Schematics
TB LIST Logic Diagram
06 (3)G719EA-MG9256-02-W206 206R 26 (3)G719EA-MG9256-02-W206 206R
Wiring Schematics Wiring Schematics
System Gas Single Line Diagram 220kV Side Logic Diagram
07 (3)G719EA-MG9256-02-W206 206R 27 (3)G719EA-MG9256-02-W206 206R
Wiring Schematics Wiring Schematics
System Gas Single Line Diagram 220kV Side PT SELECTION LOGIC
08 (3)G719EA-MG9256-02-W206 206R 28 (3)G719EA-MG9256-02-W206 206R
Wiring Schematics Wiring Schematics
C C
Last Used by: z004mx4y
F F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad List of Documents System for Various Substations W20602
3007687802(T),30071 Sh. 02 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <01 03>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
PANEL PANEL
SHEET NO. DESCRIPTION DRAWING NUMBER SHEET NO. DESCRIPTION DRAWING NUMBER
A REFERENCE REFERENCE A
Differential Protection BI Circuit-87T1 BCPU Relay BI Circuit
41 (3)G719EA-MG9256-02-W206 206R 61 (3)G719EA-MG9256-02-W206 206R
Wiring Schematics Wiring Schematics
Differential Protection BI Circuit-87T1 BCPU Relay BI Circuit
42 (3)G719EA-MG9256-02-W206 206R 62 (3)G719EA-MG9256-02-W206 206R
Wiring Schematics Wiring Schematics
Differential Protection BI Circuit-87T1 BCPU Relay BI Circuit
43 (3)G719EA-MG9256-02-W206 206R 63 (3)G719EA-MG9256-02-W206 206R
Wiring Schematics Wiring Schematics
Differential Protection BI Circuit-87T1 BCPU Relay BI Circuit
44 (3)G719EA-MG9256-02-W206 206R 64 (3)G719EA-MG9256-02-W206 206R
B Wiring Schematics Wiring Schematics B
Differential Protection BI Circuit-87T1 BCPU Relay BO Circuit
45 (3)G719EA-MG9256-02-W206 206R 65 (3)G719EA-MG9256-02-W206 206R
Wiring Schematics Wiring Schematics
Differential Protection BI Circuit-87T1 BCPU Relay BO Circuit
46 (3)G719EA-MG9256-02-W206 206R 66 (3)G719EA-MG9256-02-W206 206R
Wiring Schematics Wiring Schematics
Differential Protection BO Circuit-87T1 86.1 Trip Relay Circuit
47 (3)G719EA-MG9256-02-W206 206R 67 (3)G719EA-MG9256-02-W206 206R
Wiring Schematics Wiring Schematics
Differential Protection 4-20mA Ckt-87T1 86.2 Trip Relay Circuit
48 (3)G719EA-MG9256-02-W206 206R 68 (3)G719EA-MG9256-02-W206 206R
Wiring Schematics Wiring Schematics
C C
Last Used by: z004mx4y
F F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad List of Documents System for Various Substations W20603
3007687802(T),30071 Sh. 03 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <02 04>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
PANEL PANEL
SHEET NO. DESCRIPTION DRAWING NUMBER SHEET NO. DESCRIPTION DRAWING NUMBER
A REFERENCE REFERENCE A
To NIFPS Distribution CKT Connection Diagram 87T1
81 (3)G719EA-MG9256-02-W206 206R 101 (3)G719EA-MG9256-02-W206 206R
Wiring Schematics Wiring Schematics
Zone Trip Philosophy for CRP Connection Diagram 87T1
82 (3)G719EA-MG9256-02-W206 206R 102 (3)G719EA-MG9256-02-W206 206R
Wiring Schematics Wiring Schematics
SF6 Gas Zone Trip Circuit Connection Diagram 87T1
83 (3)G719EA-MG9256-02-W206 206R 103 (3)G719EA-MG9256-02-W206 206R
Wiring Schematics Wiring Schematics
SF6 Gas Zone Trip Circuit Connection Diagram 87T1
84 (3)G719EA-MG9256-02-W206 206R 104 (3)G719EA-MG9256-02-W206 206R
B Wiring Schematics Wiring Schematics B
SF6 Gas Zone Trip Circuit Connection Diagram 87T1
85 (3)G719EA-MG9256-02-W206 206R 105 (3)G719EA-MG9256-02-W206 206R
Wiring Schematics Wiring Schematics
SF6 Gas Zone Trip Circuit Connection Diagram 87T2
86 (3)G719EA-MG9256-02-W206 206R 106 (3)G719EA-MG9256-02-W206 206R
Wiring Schematics Wiring Schematics
SF6 Gas Zone Trip Circuit Connection Diagram 87T2
87 (3)G719EA-MG9256-02-W206 206R 107 (3)G719EA-MG9256-02-W206 206R
Wiring Schematics Wiring Schematics
SF6 Gas Zone Trip Circuit BI/BO Table
88 (3)G719EA-MG9256-02-W206 206R 108 (3)G719EA-MG9256-02-W206 206R
Wiring Schematics Wiring Schematics
C C
Last Used by: z004mx4y
F F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad List of Documents System for Various Substations W20604
3007687802(T),30071 Sh. 04 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <03 05>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Sheet Version: V 1.1 SYMBOL & DESCRIPTION SYMBOL & DESCRIPTION SYMBOL & DESCRIPTION
A A
L+ L-
HOOTER
POWER SUPPLY
BELL
CIRCUIT BREAKER
-S
ISOLATOR
PUSH BUTTON
B B
CURRENT TRANSFORMER
STABLIZING RESISTOR
SURGE ARRESTER
VARIASTOR
EARTH BAR
C C
Last Used by: z004mx4y
SWITCH CONTACT
WAVE TRAP
Time: 10:05:11 AM
Date: 11/28/2022
SOCKET
FUSE
1S2
1S2
1S2
I II III
LINK
1S2
1S2
1S2
CURRENT TRANSFORMER SECONDARY
DISCONNECTING TERMINAL
D D
CURRENT COIL
OPEARTING/REST COIL
E LATCHED CONTACT-NO E
I> I>
LATCHED CONTACT-NC
MCB
SPACE HEATER
A A
Designation Comment
X:CT TB FOR CT CIRCUIT
X:CT TB FOR CT CIRCUIT
X:MWT TB FOR MWT CIRCUIT
X:AC TB FOR AC CIRCUIT
X:CT F TB FOR RELAY CT SPARE CIRCUIT
A A
MAIN BUS-1 GC-3 GC-3 GC-3 GC-3
GC-13
GC-14
B B
GC-2
GC-2
GC-2
GC-1
GC-1
GC-1
GC-15
GC-16
T15 T25
GC-5
GC-5
GC-5
C C
Last Used by: z004mx4y
Time: 10:06:13 AM
GC-0
GC-0
GC-0
Date: 11/28/2022
GC-6
GC-6
GC-6
D D
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 07
GC-7
GC-7
CopyRight (C) Siemens Limited, India All Rights Reserved.
GC-9
GC-9
GC-7
E E
GC-10
GC-10
GC-12
GC-12
MAIN BUS-2 GC-4 GC-15 GC-13 GC-4 MAIN BUS-2 GC-4 GC-4
GC-01
GC-02
B B
GC-2
GC-2
GC-2
GC-1
GC-1
GC-1
GC-5
GC-5
GC-5
GC-05
GC-06
C C
Last Used by: z004mx4y
Time: 10:06:50 AM
GC-0
GC-0
GC-0
Date: 11/28/2022
FUTURE BAY
GC-6
GC-6
GC-6
GC-00
D D
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 08
GC-7
CopyRight (C) Siemens Limited, India All Rights Reserved.
GC-7
GC-9
E E
GC-10
220kV BUS REACTOR 220kV ICT-3 220kV LINE-2 220kV BUS COUPLER
A A
Q15 Q25
B B
Q1 Q2 Q1 Q2 Q1 Q2
Q63 Q64
T1 T1 T1
T15 T25
C C
Last Used by: z004mx4y
Q0 Q0 Q0
Time: 10:07:31 AM
Date: 11/28/2022
T2 T2 T2
D D
Q52 Q52 Q52
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 09
Q9 Q9 Q9
CopyRight (C) Siemens Limited, India All Rights Reserved.
Q8 T5 Q8 T35 Q8 T5
Q61 Q61 Q61
E E
A A
B B
Q11 Q21 Q1 Q2 Q1 Q2 Q1 Q2
Q52
Q51 Q51 Q51
Q51
T1 T1 T1
P2 P2
C C
Last Used by: z004mx4y
Q0 Q0 Q0
Time: 10:08:18 AM
Date: 11/28/2022
T1 T2
P1 P1
T2 T2 T2
Q0
D D
Q52 Q52 Q52
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 10
Q9 Q9 Q9
CopyRight (C) Siemens Limited, India All Rights Reserved.
Q8 T35 Q8 T5 Q8
Q61 Q61
E E
D
C
CopyRight (C) Siemens Limited, India All Rights Reserved. Last Used by: z004mx4y E-Base Version: 7.1.0.1305
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 11 Date: 11/28/2022 DB Version: SL-V 1.1-08/01/2019
0
A
Time: 10:09:00 AM Sheet Version: V 1.1
Revision
1
1
Remarks
QT Corrected
First Submission
220kV MAIN BUS-1 GC-16 GC-14 GC-3 MAIN BUS-1
Date
GC-15 GC-13 GC-4 MAIN BUS-2
11/25/2022 MJ
Q2 M Q1 M
07/27/2022 NBS
2
2
Version
Name Appr By
Q51 M
MS
Drawn By RVS
M M
Chkd By MMS
Q2 Q1
1
P1
CT-T1 S1
CORE-1
RATIO: 900-600/1A
CLASS: 0.2S S2 GETCO TARIFF METERING
VA 7.5-5
ISF<5
Orig.:
FROM LV SIDE LINE PT CORE-2
(FOR OLTC CONTROL)
GC-2
GC-1
CT-T1
Siemens Ltd.
S1
CORE-2 7UT86 87T1 (7UT86)
T1 RATIO: 1200-800/1A FROM LV SIDE
CLASS: PX S2 Transf. Prot CT CORE-1 Q51 M
3
3
PT CORE-3
CT-T1
CT-T1
P2
Replaces:
VA 7.5-5
P2
ISF<5
P1
CT-T2 S1
4
4
Vkp(V) 1200-800
P2
Replaced by:
Q52
CT-T2 S1
CORE-2
RATIO: 1200-800/1A
CLASS: PX S2
T2 Vkp(V) 1200-800
le @ Vk/2 (mA) 30-40
PE
RATIO: 4000-2000/1A
5
5
Wiring Schematics
GC-8
GC-9
LA
Q52
GC-11
GC-10
M Q9
220/132/33kV,250MVA ICT-3 HV(BAY-206)
6
6
Q8
LA 220kV ICT-3
(BAY-206)
G)
Q61
LCC -D06
D06-T5(VT)
3007687802(T),30071
48372(L),3007688671(
PM130EH LM-2
Load Manger
System for Various Substations
Q62
7
7
ONLY Y-PH PT
Supply of Control & Relay panels and Associated
/12.1
(3)G719EA-MG9256-02-W206
W 206R
8
8
W20611
<10 12>
Unless otherwise specified, wires are PVC 1.5 GY
Sh. 11 of 116
F
E
B
A
D
C
F
E
B
A
D
C
CopyRight (C) Siemens Limited, India All Rights Reserved. Last Used by: z004mx4y E-Base Version: 7.1.0.1305
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 12 Date: 11/28/2022 DB Version: SL-V 1.1-08/01/2019
0
A
Time: 10:09:31 AM Sheet Version: V 1.1
Revision
1
1
Remarks
QT Corrected
/11.7
First Submission
S
ICT HV BUSHING CT
Date
11/25/2022 MJ
07/27/2022 NBS
P1
S1
CT-2
RATIO: 729/2A
2
2
CLASS: 3 HV WTI
Version
Name Appr By
VA:15
S2
P2
MS
Drawn By RVS
Chkd By MMS
1
P1
S1
CT-1
Orig.:
RATIO: 800/1A
CLASS: PS RET670 87T2(RET670)
Vk>1000V
Siemens Ltd.
S2 Main-2Transf. Prot
RCT <=3.5Ohm
P2
Imag<30mA at Vk/2
3
3
Replaces:
Vk> 1000V
RCT <=3.5Ohm S2
P2
Imag<30mA at Vk/2
PT CORE-3
4
4
TRAFO. MB
ICT-3
Replaced by:
250MVA CT-5 CT-4
220/132/33kV RATIO: 1200/1A
YNa0(d)11 RATIO: 800/1A
CLASS: PS CLASS: PS
Vk>1000V Vk>1000V
Rct<=3.5 Ohm Rct <=3.5 Ohm
Imag <30mA at Vk/2 Imag <30mA at Vk/2
P2 P1 P2 P1 PE
S2
S1
S2
S1
5
5
ICT LV BUSHING CT
PE
Wiring Schematics
P2
S2
CT-8
RATIO: 1200/1A
CLASS: PS
Vk>1000V
Rct<=3.5 Ohm S1
P1
Imag<30mA at Vk/2
220/132/33kV,250MVA ICT-3 HV(BAY-206)
6
6
P2
S2
CT-6
RATIO: 1200/1A
CLASS: PS
Vk>1000V
Rct<=3.5 Ohm S1
P1
Imag<30mA at Vk/2
G)
3007687802(T),30071
P2
48372(L),3007688671(
S2
CT-7
RATIO: 1094/2A
CLASS: 3 LV WTI
System for Various Substations
VA:15
7
7
S1
P1
(3)G719EA-MG9256-02-W206
W 206R
TO 132kV LV SIDE
8
8
W20612
<11 13>
Unless otherwise specified, wires are PVC, 1.5mm Sq, GY
Sh. 12 of 116
F
E
B
A
D
C
1 2 3 4 5 6 7 8
Q2 Q1
M M
Q51 M
B LCC -D06
B
-X610
13
14
1S1 24
33
CT-T1
P1
1S1
CLASS: 0.2S
VA 7.5-5 1S3 1S2
ISF<5 1S2 -X610 206R
34
C 1S3 C
Last Used by: z004mx4y
P2
1S3
Time: 10:10:07 AM
31
P2
Date: 11/28/2022
21
11
-X620 X:CT 10 A111
/37.3
11 11
12 A131
/37.3
21 13
2S1 14 A151 7UT86 87T1 (7UT86)
/37.3
31 15 Transf. Prot
CT-T1
P1
2S1
D CLASS: PX D
le @ Vk/2 (mA) 30-40 2S3 2S2
Rct @ 75C (Ohms) 10-5 2S2
A171A
Vkp(V) 1200-800
2S3
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 13
-X620
P2
2S3 16 A175
/37.3
42
P2
17
-P405 18 A171B PE
3 D131
/36.2
26 4
3S1 5 D151
/36.2
E CT-T1
36 6 PM130EH LM-1 E
P1
D171A
RATIO: 900-600/1A
P1
3S1
CLASS: 0.2S
VA 7.5-5 3S3 3S2 7 D171
/36.2
P2
ISF<5 3S2 8
3S3 9 D171B PE
P2
3S3
-X632
P2
45
R-PH
Y-PH
B-PH
DWG:(3)G71770-AD399-S160
SH NO:SA1,SA2&SA3
/14.2
/14.2
/13.2
/13.2
/13.2
R-PH
Y-PH
B-PH
A A
Q0
C171A
RATIO: 1200-800/1A P1 1S1
CLASS: PX
Vkp(V) 1200-800 1S3 1S2
le @ Vk/2 (mA) 30-40 1S2
Rct @ 75C (Ohms) 10-5
1S3
P2
1S3
-X640
P2
C 25 C171 C
Last Used by: z004mx4y
/55.3
42 26
Time: 10:10:49 AM
Date: 11/28/2022
27 C171B PE
-X650
11
14
21
2S1 24
SPARE CORE
31
CT-T2
P1
2S1
CLASS: PX
Vkp(V) 1200-800 2S3 2S2
le @ Vk/2 (mA) 30-40 2S2 -X650
D Rct @ 75C (Ohms) 10-5 34 D
2S3
P2
2S3 200R
33
P2
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 14
23
13
-X660 B671
/W200 /14.6
11
21
CopyRight (C) Siemens Limited, India All Rights Reserved.
3S1
31
CT-T2
P1
3S3 B631
/W200 /14.6
P2
24 B611
/W200 /14.6
14
R-PH
Y-PH
B-PH
/15.2
/15.2
/15.2
DWG: (3)G71770-AD399-S160
SH NO:SA3&SA4
F Note:** Adopted CT Ratio To Be Confirmed By Customer Unless otherwise specified, wires are PVC, 1.5mm Sq, GY F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad CT Distribution Circuit System for Various Substations W20614
3007687802(T),30071 Sh. 14 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <13 15>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
/14.2
/14.2
/14.2
R-PH
Y-PH
B-PH
A A
B B
Q52
Q9
M
C C
Last Used by: z004mx4y
Q8
Time: 10:11:25 AM
Date: 11/28/2022
D D
LA
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 15
Q61
LA
Q61
CopyRight (C) Siemens Limited, India All Rights Reserved.
LA
E Q61 E
R-PH
Y-PH
B-PH
/16.2
/16.2
/16.2
220/66kV ICT-1
/15.2
/15.2
/15.2
A A
R-PH
Y-PH
B-PH
Q62
Q62
Q62
LCC -D06 LCC -D06 LCC -D06
D06-T5(VT) D06-T5(VT) D06-T5(VT)
A
Primary Primary Primary
R-PH Y-PH B-PH
B B
R-PH
Y-PH
B-PH
N
/17.2
/17.2
1n
2n
WDG-1 WDG-2 WDG-3 LCC -D06
D06-T5(VT)
3n
Y-PH Y-PH Y-PH
WDG-4
RATIO: 220000V/√3 / 110/√3 RATIO: 220000V/√3 / 110/√3 RATIO: 220000V/√3 / 110/√3 Y-PH
CLASS: CL.0.2 CLASS: CL.0.2 CLASS: CL.3P RATIO: 220000V/√3 / 110/√3
1a
1a
2a
CLASS: CL.3P
3a
C C
Last Used by: z004mx4y
Time: 10:11:56 AM
Date: 11/28/2022
LCC -D06
D D
206R
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 16
4
X:PT3 X:PT3
8
X:PT3 X:PT3
CopyRight (C) Siemens Limited, India All Rights Reserved.
E231L
E271L
E E
/36.2
/36.2
TO GETCO TARRIF METERING TO LOAD MANAGER-2 CKT SPARE CORE SPARE CORE
/16.2
/16.2
/16.2
A A
R-PH
Y-PH
B-PH
ICT HV BUSHING CT TRAFO. MB
P1
S1 -X
CT-2
XX
RATIO: 729/2A
CLASS: 3
VA:15 WTI
B S2
-X B
XX 206R
30 A231
/49.3
17 31
P1
P1
P1
S1 S1 S1 32 A251
/49.3
CT-1 27 33
RATIO: 800/1A RET670 87T2(RET670)
C C
Last Used by: z004mx4y
CLASS: PS
Vk>1000V Main-2Transf. Prot
Time: 10:12:33 AM
A271A
RCT <=3.5Ohm S2 S2 S2
Date: 11/28/2022
Imag<30mA at Vk/2
P2
P2
P2
-X5
28
34 A271
/49.3
18 35
8
36 A271B PE
-X5
12 S1
D 22
/18.4 D
P1
P1
P1
S1 S1 S1 32
CT-3
RATIO: 1200/1A
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 17
P2
P2
33 S2
/18.4
23
CopyRight (C) Siemens Limited, India All Rights Reserved.
13
D.NO: 2XYN464032C2676
E SH:NO:27&28 E
R-PH
Y-PH
B-PH
/18.2
/18.2
/18.2
/17.2
/17.2
/17.2
R-PH
Y-PH
B-PH
A A
B B
Rct<=3.5 Ohm
Last Used by: z004mx4y
TRAFO. MB
CLASS: PS
CLASS: PS
Vk>1000V
Vk>1000V
ICT-3
Time: 10:13:07 AM
Date: 11/28/2022
250MVA
CT-5
CT-4
220/132/33kV
YNa0(d)11
P2 P1 P2 P1 PE
S2
S1
S2
S1
TRAFO. MB 206R
-X5 -X5
D 43 42 PE 38 37 D
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 18
HV BUSHING CT
S1 X:CT 37 A115A
/17.4 /49.3
38
S2 39 A175A
/17.4
CopyRight (C) Siemens Limited, India All Rights Reserved.
/49.3
40
A175A-1
E 41 A175B-1 PE E
S2
S1
/19.5
LV BUSHING CT /19.5
R-PH
Y-PH
B-PH
/19.2
/19.2
/19.2
D.NO: 2XYN464032C2676
SH:NO:28
TO LV SIDE
/18.2
/18.2
/18.2
R-PH
Y-PH
B-PH
A A
-X5
53 S2
/18.5
63
P2
P2
P2
S2 S2 S2
CT-8 73
RATIO: 1200/1A TO OVER ALL REF PROTECTION
B CLASS: PS B
Vk>1000V -X5
S1 S1 S1 S1
Rct<=3.5 Ohm /18.5
72
P1
P1
P1
Imag<30mA at Vk/2
62 206R
52
A371A-1 50 A371B-1 PE
-X5
48 48 A371A
/49.3
P2
P2
P2
S2 S2 S2 58 49
C CT-6 68 C
Last Used by: z004mx4y
RATIO: 1200/1A
Time: 10:13:39 AM
CLASS: PS
Date: 11/28/2022
Vk>1000V -X5
S1 S1 S1 46 A351A
Rct<=3.5 Ohm /49.3
RET670 87T2(RET670)
67
P1
P1
P1
47
Imag<30mA at Vk/2
Main-2Transf. Prot
44 A331A
/49.3
57 45
X:CT 42 A311A
/49.3
47 43
D D
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 19
P2
-X
CT-7 S2
RATIO: 1094/2A XX
CLASS: 3 LV WTI
VA:15
-X
S1
CopyRight (C) Siemens Limited, India All Rights Reserved.
XX
P1
E E
DWG.NO: 2XYN464032C2676SH
NO:27,28&29
R-PH
Y-PH
B-PH
/20.2
/20.2
/20.2
/19.2
/19.2
/19.2
R-PH
Y-PH
B-PH
A A
-F1/-Q612
-T5/-Q61
LINE VT RATIO:
132kV / 110V / 110V / 110V
B 3 3 3 3 B
WDF-1 50VA/3P
WDF-2 50VA/3P
WDF-3 50VA/0.2
Q8(115-89TE1)
Time: 10:14:20 AM
59
Date: 11/28/2022
PE
102LCC X:CT 58
CORE-1 -X610 42 57 A371
/37.3
A373A
RATIO: 1200-800/1A
P2
P2
P2
CLASS: PS,
Vkp-(600-300) S2 S2 S2 56
Ie at Vk/2-(37. 5to 75mA)..Rct at 75C<(5-2.5)
-X610 31 55 A351
S1 S1 S1 /37.3
54
P1
P1
P1
-X610 21 53 A331
/37.3
52
D D
-X610 11 51 A311
/37.3
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 20
DWG: (3)G71770-AE251-S160
Q0(115-52)
SH:SA1
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
Q1(115-89A) Q2(115-89B)
QZ1(115-89AE)
BUS BAR-II
BUS BAR-I
A A
Time: 10:14:56 AM
Date: 11/28/2022
1.1/1.2/
1 OPEN/CLOSE 1.3 BCPU(6MD85) 06 220kV ICT-3
ISOLATOR Q1
Q1 OPEN/CLOSE
220kV ICT-3 06 BCPU(6MD85) - COMMAND
&
D 220kV ICT-3 06 BCPU(6MD85) KEY LOCAL MODE D
1
220kV ICT-3 06 BCPU(6MD85) KEY REMOTE MODE
SCADA - Q1 OPEN/CLOSE &
220kV ICT-3 06 &
COMMAND
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 21
&
E E
A A
Time: 10:15:20 AM
Date: 11/28/2022
1.4/1.5/
1 OPEN/CLOSE 1.6 BCPU(6MD85) 06 220kV ICT-3
ISOLATOR Q2
Q2 OPEN/CLOSE
220kVICT-3 06 BCPU(6MD85) - COMMAND
&
D 220kV ICT-3 06 BCPU(6MD85) KEY LOCAL MODE D
1
220kV ICT-3 06 BCPU(6MD85) KEY REMOTE MODE
SCADA - Q2 OPEN/CLOSE &
220kV ICT-3 06 &
COMMAND
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 22
&
E E
A A
B Q9 OPEN/CLOSE B
220KV ICT-3 06 BCPU(6MD85) - COMMAND
&
220KV ICT-3 06 BCPU(6MD85) KEY LOCAL MODE
1
220KV ICT-3 06 BCPU(6MD85) KEY REMOTE MODE 1 OPEN/CLOSE 3.5/3.6/3.7 BCPU (7SJ85) 06 220KV ICT-3
SCADA - Q9 OPEN/CLOSE & ISOLATOR Q9
220KV ICT-3 06 &
COMMAND
Time: 10:15:45 AM
Date: 11/28/2022
D D
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 23
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
A A
Time: 10:16:13 AM
Date: 11/28/2022
D D
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 24
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
A A
D D
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 25
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
A A
Time: 10:17:07 AM
Date: 11/28/2022
D D
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 26
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
&
E
REMOTE ON
220KV ICT-3 06 BCPU(6MD85) 1.1 Q1 OPEN + INT
220KV ICT-3 06 BCPU(6MD85) 1.3 Q2 OPEN &
220KV ICT-3 06 BCPU(6MD85) 1.5 Q9 OPEN
&
G
REMOTE OFF
C + INT C
Last Used by: z004mx4y
220KV ICT-3
Date: 11/28/2022
&
Syn check ok
D D
&
1
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 27
CB CLOSE (BAY-06)
1 BCPU (BINARY OUTPUT-3.12)
A
B
CopyRight (C) Siemens Limited, India All Rights Reserved.
&
E E
E
1
C CB TRIP (BAY-06)
& BCPU (BINARY OUTPUT-3.11)
G
&
A A
BINARY RELAY
B DESCRIPTION
OUTPUT NO DESIGNATION BAY NO FEEDER NAME B
FEEDER NAME BAY NO RELAY BINARY DESCRIPTION
DESIGNATION INPUT NO
C C
Last Used by: z004mx4y
Time: 10:17:55 AM
D D
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 28
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
A A
BB PROTN. RELAY-7SS85
TRIP CIRCUIT – TC-1
HV BCPU(7SJ85)
86.1 TRIP RELAY
96 TRIP RELAY
LV TC-1/TC-2
PROTECTION
ANSI CODE
RELAY
87T DIFF.PROTN 87T1(7UT86) X X
C 50/51&50N/51N NON.DIR O/C&E/F PROTN 87T1(7UT86) X X C
Last Used by: z004mx4y
24 OVERFLUXING 87T1(7UT86) X X
Time: 10:18:20 AM
Date: 11/28/2022
A A
B B
C WIRING DIAGRAM C
Last Used by: z004mx4y
Time: 10:18:43 AM
Date: 11/28/2022
D D
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 30
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
XB:AC 1 H1
A A
X:AC 1
XB:AC 2 H2
X:AC 2
TO BCPU
12
14
AMCB
N
1
11
16A
/62.5
I> I>
B B
N
2
H6
H5
CFLS LED
21 22 H7 1 2
/94.4
C C
Last Used by: z004mx4y
Time: 10:19:12 AM
Date: 11/28/2022
HTS TH HT
1 2 H8 1 2 H9 1 2
PS1
1 PS 2
S
D E D
PE EW
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 31
**PS2
1 PS 2
CopyRight (C) Siemens Limited, India All Rights Reserved.
E
E E
PE EW
A A
DCDB-1 MCB-DC1 DCC01
32A
X:DC 1 J101 1 2 J103 111 112 J105
I>
/32.4 /33.1
2 J102 3 4 J104 113 114 J106
I>
/32.4 /33.1
Dc-1 CHANGE OVER
110V DC 11 14 DCC01
DC-1 SUPPLY /52.3
12 To 87T2 121 211 J103A 115 116
/32.4
111 112 J104A 117 118
/32.6
XB:DC 1 113 114 /32.4
/32.6
221 222
B /93.3 SPARE B
2 223 224
115 116
/32.6
117 118
/32.6
225 226
/93.3 SPARE
To 87T2
To 87T1
LCC -D06 227 228
/62.5 TO BCPU
DWG:(3) -X130 X:LCC 1
12
14
12
14
G71770- MCB-DCCO1 MCB-DCCO2
3
1
AD399- -X130 2
S115
11
11
SH:G1 3
10A 10A
/44.5
/52.3
I> I> I> I>
C C
Last Used by: z004mx4y
4
Time: 10:19:48 AM
Date: 11/25/2022
DCC02
/32.4
4 J202 3 4 J204 113 114 J206
I>
D /32.4 /33.1 D
Dc-2 CHANGE OVER
110V DC 11 14 DCC02
DC-2 SUPPLY /44.4
12 To 87T1 121 211
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 32
111 112
/32.6
113 114
/32.6
XB:DC 3 221 222
/93.3 SPARE
223 224
4 115 116
/32.6
CopyRight (C) Siemens Limited, India All Rights Reserved.
117 118
/32.6
225 226
/93.3 SPARE
LCC -D06 227 228
/62.5 TO BCPU
E E
DWG:(3)G7 -X130 X:LCC 3
1770-
5
AD399- -X130 4
S115
SH:G1 7
A A
J105 J105
/32.8
J106 J106
/32.8
To 87T2
To 87T2
To 87T2
To 87T2
To 87T2
To 87T2
To 87T2
DC-1 Supervision Relay
80A
12 21
MCB-AUX
12
14
12
14
12
14
12
14
12
14
12
14
12
14
MCB-87T1 MCB-LM1 MCB1-ETH MCB-86.1 MCB-SP1 MCB-SP2
1
3
11 13
11
11
11
11
11
11
11
4A 6A 10A 4A 4A 4A 6A 28 18
/52.3
/52.3
/52.3
/52.3
/52.3
/52.3
/52.3
B I> I> I> I> I> I> I> I> I> I> I> I> I> I> 16 17 B
/52.3 To 87T2
26 27
K101 2
K102 4
K301 2
K302 4
1ESW 2
2ESW 4
4
/92.3 Spare
U1
U2
U3
U4
K701
K702
K501
K502
2ES-6
/39.4
/39.7
/36.5
/36.5
X:SP 1 2 X:SP 3 4
5
/83.4
/83.7
/67.3
/67.7
7
6
To 87T1
To Load Manager
-
Circuit-1 To Gas Zone Trip To 86.1 SPARE-1 SPARE-2
circuit
C C
Last Used by: z004mx4y
J205
/32.8
J206
/32.8
To 87T1
To 87T1
To 87T1
To 87T1
To 87T1
To 87T1
DC-2 Supervision Relay
80B
12 21
12
14
12
14
12
14
12
14
12
14
12
14
MCB-87T2 MCB-BCPU MCB-LM2 MCB2-ETH MCB-86.2 MCB-SP3
3
1
3
D D
11 13
11
11
11
11
11
11
4A 4A 6A 4A 4A 10A 28 18
/44.4
/44.4
/44.4
/44.5
/44.5
/44.4
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 33
I> I> I> I> I> I> I> I> I> I> I> I> 16 17
/44.4 To 87T1
26 27
2
K601 2
K602 4
4
3ESW /92.3 SPARE
4ESW
U5
U6
K201
K202
K401
K402
K601
K602
K801
K802
CopyRight (C) Siemens Limited, India All Rights Reserved.
2ES-6
X:SP 5 6
1
/51.4
/51.7
/56.3
/56.7
/36.5
/36.5
/68.3
/68.7
3
E E
SPARE-3
+
To Load Manager
-
1E211
X:PT1 1
WINDING-2 (METERING)
A A
XB:PT1 1
1E231
BUS-1 PT
X:PT1 2
XB:PT1 2
1E251
X:PT1 3
XB:PT1 3
1E271
X:PT1 4
XB:PT1 4
1E211
1E231
1E251
1E271
B B
/72.2
/72.2
/72.2
/72.2
To VT Selection Circuit 1E311
X:PT1 5
WINDING-3 (PROTECTION)
XB:PT1 5
1E331
BUS-1 PT
X:PT1 6
XB:PT1 6
1E351
X:PT1 7
XB:PT1 7
C 1E371 C
Last Used by: z004mx4y
X:PT1 8
Time: 10:20:51 AM
XB:PT1 8
Date: 11/28/2022
1E311
1E331
1E351
1E371
/72.2
/72.2
/72.2
/72.2
To VT Selection Circuit
1E411
X:PT1 9
WINDING-4 (PROTECTION)
XB:PT1 9
D D
1E431
BUS-1 PT
X:PT1 10
XB:PT1 10
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 34
1E451
X:PT1 11
XB:PT1 11
1E471
X:PT1 12
XB:PT1 12
CopyRight (C) Siemens Limited, India All Rights Reserved.
1E411
1E431
1E451
1E471
E E
/73.2
/73.2
/73.2
/73.2
To VT Selection Circuit
2E211
A A
X:PT2 1
WINDING-2 (METERING)
XB:PT2 1
2E231
BUS-2 PT
X:PT2 2
XB:PT2 2
2E251
X:PT2 3
XB:PT2 3
2E271
X:PT2 4
XB:PT2 4
2E211
2E231
2E251
2E271
B B
2E311
/72.2
/72.2
/72.2
/72.2
X:PT2 5
WINDING-3 (PROTECTION)
XB:PT2 5
2E331
To VT Selection Circuit
X:PT2 6
BUS-2 PT
XB:PT2 6
2E351
X:PT2 7
XB:PT2 7
2E371
C X:PT2 8 C
Last Used by: z004mx4y
XB:PT2 8
Time: 10:21:36 AM
2E311
2E331
2E351
2E371
Date: 11/28/2022
/72.2
/72.2
/72.2
/72.2
To VT Selection Circuit
2E411
X:PT2 9
WINDING-4 (PROTECTION)
XB:PT2 9
2E431
BUS-2 PT
X:PT2 10
D D
XB:PT2 10
2E451
X:PT2 11
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 35
XB:PT2 11
2E471
X:PT2 12
XB:PT2 12
2E411
2E431
2E451
2E471
CopyRight (C) Siemens Limited, India All Rights Reserved.
/73.2
/73.2
/73.2
/73.2
E To VT Selection Circuit E
Y
CT-T1
D133 2L Shield
E253 V3 Cable S1
RS485 PORT
D151 D151 3S Tx S1
/13.6
Rx S2 S2
B
D171 D171 D153 3L COM S3
/13.6
E273 VN S3
AUX SUPPLY
B L/+ L/- G B
E-BB
EW PE
E213
E233
E253
E273
/72.7
/72.7
/72.7
/72.7
MWT
PT Supply From
Selected Bus PT Core-2
29
28
27
26
25
24
23
22
21
20
~/-
~/+
VT INPUT CT INPUT
AUX
SUPPLY OUTPU OUTPU
C C
Last Used by: z004mx4y
T-2 T-1
+
-
-
Time: 10:22:15 AM
Date: 11/25/2022
8
7
6
5
Shield
S11
S12
S21
S22
Cable
X:MWT 1 2 3 4
K301
K302
D D
/33.2
/33.2
FSLM2-R Load Manger
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 36
Y
Line PT FSLM2-B 2L
Core-2,3&4 X:LM 3 E251L 2 1 E253L V3
RS485 PORT
E B-Ph 2A 3S Tx E
Supply Rx
B
3L COM
LKLM2-N
E271L X:LM 4 E271L 2 1 E273L VN
/16.4
Shield
AUX SUPPLY
L/+ L/- G Cable
E-BB
PE
K601
K602
EW
/33.3
/33.3
1200-800/1A PX
A131
/13.6
/101.1
CORE-2
CT-T1
A151 A151 1A5 *I P 1.3 1A6
/13.6
/101.1
A175 A175
/13.6
B B
A311 A311 1B1 *I P 1.5 1B2
/20.5
/101.1
1200-800/1A PS,
A331 A331
/20.5
/101.1
CORE-1
102LCC
A351 A351 1B5 *I P 1.7 1B6
/20.5
/101.1
A371 A371
/20.5
C C
Last Used by: z004mx4y
Time: 10:22:46 AM
Date: 11/28/2022
8 /102.1
12 /102.1
A871A
E E
PE EW X:CT F 13
A A
87T1 (7UT86) 87T1 (7UT86)
E-BB PE
PE EW 1PE
FS87T1-R V 4.1
E313 2 1 E315 4A1 4A2 /101.1
/72.7
2A /103.1 E-BB PE
PE EW 3PE
FS87T1-Y V 4.2
E333 2 1 E335 4A3 4A4 /102.1
SEL. BUS VT /72.7
2A /103.1
CORE-3 E-BB PE
PE EW 3PE
FS87T1-B V 4.3
E353 2 1 E355 4A5 4A6 /102.1
B /72.7 B
2A /103.1 E-BB PE
PE EW 4PE
LK87T1-N
E373 2 1 E375 /103.1
/72.7
E-BB PE
PE EW 4PE
/103.1
E-BB PE
PE EW 5PE
E313
E333
E353
E373
/104.1
E-BB PE
PE 5PE
/50.3
/50.3
/50.3
/50.3
EW
/104.1
C C
Last Used by: z004mx4y
E-BB PE
TO 87T2 CKT PE EW 6PE
Time: 10:23:25 AM
E-BB PE
PE EW 6PE
-X711 FSLV-R V 4.4
X:LVPT 1 E811 2 1 E813 4A7 4A8 /105.1
11 2A /103.1
FSLV-Y
-X711 X:LVPT 2 E831 2 1 E833 4A11 V 4.5 4A12
FROM LV SIDE
21 2A /103.1
CORE-1
FSLV-B
-X711 X:LVPT 3 E851 2 1 E853 4A13 V 4.6 4A14
31 2A /103.1
D D
-X711 LKLV-N
X:LVPT 4 E871 2 1 E873
41
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 38
OLTC OPERATION
DWG: (3)G71770-AE251-S161-B
SH:SB1
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
4C3 V 4.8 4C4
/103.1
/33.1
/33.2
87T1 (7UT86)
K101
K102
PS
A A
K101 2B1 2B2
+ - Power Supply
X:TR 1 /102.1
-X4.1 BI 2.1
6 2K103 2B12 Fan-3 Thermal
154 /102.1 Overload Alarm
-X4.1 BI 2.2
7 2K105 2B14 Fan-4 Thermal
155 /102.1 Overload Alarm
-X4.1 BI 2.3
8 2K107 2B13 2B11 Fan-5 Thermal
156 /102.1 Overload Alarm
C C
Last Used by: z004mx4y
-X4.1 BI 3.1
9 3K103 3C13 3D1 Fan-6 Thermal
Time: 10:24:11 AM
157
-X4.1 BI 3.2
10 3K105 3C14 3D2 Fan-7 Thermal
158 /102.1 Overload Alarm
-X4.1 BI 3.3
11 3K107 3D5 3D3 Fan-8 Thermal
159 /102.1 Overload Alarm
-X4.1 BI 3.4
12 3K109 3D6 3D4 Fan-9 Thermal
160 /102.1 Overload Alarm
D -X4.1 BI 3.5 D
13 3K111 3D7 3D9 Fan-10 Thermal
161 /102.1 Overload Alarm
-X4.1 BI 3.6
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 39
-X4.1 BI 3.7
15 3K115 3D13 3D11 Fan-12 Thermal
163 /102.1 Overload Alarm
BI 3.8
CopyRight (C) Siemens Limited, India All Rights Reserved.
-X4.1 BI 4.1
E 17 4K103 4C13 4D1 Pump-2 Thermal E
165 /103.1 Overload Alarm
-X4.1 BI 4.2
18 4K105 4C14 4D2 Pump-3 Thermal
166 /103.1 Overload Alarm
-X4.1 BI 4.3
19 4K107 4D5 4D3 Pump-4 Thermal
167 /103.1 Overload Alarm
K102
E-BB PE
K101
DWG.NO:2XYN464032C2676
PE EW 1PE
SH.NO:22
/101.1
/40.7
PE-Pin
/40.4
/39.4
/39.7
87T1 (7UT86)
K101
K102
A A
X:TR 20
/104.1
Date: 11/28/2022
186 187
BI 5.6
31 5K113 5A8
SPARE
/104.1
D BI 5.7 D
32 5K115 5A9
SPARE
/104.1
BI 5.8
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 40
33 5K117 5A10
SPARE
/104.1 5A5
5A6
5.COM 1-8 /104.1
K101A
CopyRight (C) Siemens Limited, India All Rights Reserved.
/41.1
E E
K102
K101
DWG.NO:2XYN464032C2676
SH.NO:22
/41.6
/41.4
/40.4
/40.7
87T1 (7UT86)
/40.2
K101
K102
A A
K101A
-X4.1 -X4.1 BI 5.9
X:TR 34 5K119 5C1
FAN 1 TO 6 ON
206 207 /104.1
-X4.1 BI 5.10
35 5K121 5C2
FAN 7 TO 12 ON
208 /104.1
-X4.1
BI 5.11
209 X:SP 7 X:SP 8 5K127 5C3
SPARE
B /104.1 B
-X4.1
BI 5.12
210 X:SP 9 5K129 5C4
SPARE
/104.1
-X4.1
211 BI 5.13
X:SP 10 5K131 5C7
-X4.1 SPARE
/104.1
212 BI 5.14
X:SP 11 5K133 5C8
-X4.1 SPARE
/104.1
213
C C
Last Used by: z004mx4y
-X4.1
Time: 10:26:01 AM
Date: 11/28/2022
214
-X4.1
215
-X4.1
216
-X4.1
217
D -X4.1 D
218
-X4.1
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 41
219
-X4.1 BI 5.15
36 5K123 5C9
PUMP 1 TO 4 ON
220 /104.1
CopyRight (C) Siemens Limited, India All Rights Reserved.
-X4.1
221
E -X4.1 E
222
-X4.1 BI 5.16
37 5K125 5C10 COOLER AND OLTC
223 /104.1 SUPPLY ON
5C5
K101A
5C6
/104.1
K102
5.COM 9-16
/42.2
K101
DWG.NO:2XYN464032C2676
SH.NO:24
/42.7
/42.3
/41.1
/41.4
/41.6
87T1 (7UT86)
K101A
K101
K102
A A
-X4.1 BI 5.17
X:TR 38 5K135 5D1
Stand-By Fan On
224 /104.1
-X4.1 BI 5.18
39 5K137 5D2
Stand-By Pump On
225 /104.1
-X4.1 BI 5.19
40 5K139 5D3
Control Supply On
226 /104.1
-X4.1 BI 5.20
41 5K141 5D4
Control Switch Manual
B 229 /104.1 B
-X4.1 BI 5.21
42 5K143 5D7
Control Switch Auto
230 /104.1
-X4.1 BI 5.22
43 5K145 5D8
Control switch Remote
231 /104.1
X:TR 46
Buchholz CB Trip-1
11 12 /104.1
Time: 10:26:52 AM
5D5
Date: 11/28/2022
5D6
5.COM 17-24 /104.1
-X4.1 -X4.1 BI 5.25
47 5K151 5E1
PRV_1 TRIP -1
15 16 /104.1
5.COM 25-32
DWG NO :2XYN464032C2676
K101
K102
SH:30&31
/43.2
/43.3
/43.7
F Unless otherwise specified, wires are PVC, 1.5mm Sq, GY F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad Differential Protection BI Circuit-87T1 System for Various Substations W20642
3007687802(T),30071 Sh. 42 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <41 43>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
/42.2
/42.3
/42.7
87T1 (7UT86)
K101B
K101
K102
A A
BI 5.38
60 5K177 5G8
SPARE
/104.1
BI 5.40
62 5K181 5G10
SPARE
Time: 10:27:50 AM
/104.1 5G5
Date: 11/28/2022
5G6
5.COM 33-40 /104.1
-X4.1 -X4.1 BI 5.41
63 5K183 5H1
PRV-CB-3_TRIP-1
61 62 /104.1
BI 5.42
64 5K185 5H2
SPARE
/104.1
DWG NO :2XYN464032C2676
K101
K102
SH:31 TO 33
/44.1
/44.3
/44.7
F Unless otherwise specified, wires are PVC, 1.5mm Sq, GY F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad Differential Protection BI Circuit-87T1 System for Various Substations W20643
3007687802(T),30071 Sh. 43 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <42 44>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
/43.2
/43.3
/43.7
87T1 (7UT86)
K101B
K101
K102
A A
-X4.1 -X4.1 BI 6.1
X:TR 71 6K103 6A1
OSR-3_Trip-2
87 88 /105.1
-X4.1 -X4.1 BI 6.2
72 6K105 6A2
RPRR Cable Box-1_Trip
89 90 /105.1
-X4.1 -X4.1 BI 6.3
73 6K107 6A3
RPRR Cable Box-2_Trip
91 92 /105.1
-X4.1 -X4.1 BI 6.4
74 6K109 6A4
RPRR Cable Box-3_Trip
93 94 /105.1
BI 6.5
6K111 6A7
CRP DC-2 Fail
/105.1
B MCB-DC2 MCB2-ETH MCB-DCCO1 B
11 14 11 14 11 14
/32.3 12 /33.4 12 /32.5 12
To 87T2
MCB-BCPU MCB-87T2 MCB-86.2
11 14 11 14 11 14
/33.2 12 /33.1 12 /33.5 12
K2 BI 6.6
24 25 6K113 6A8 SF6 ZONE INTER TRIP
/89.4 /105.1 (BELOW CB )
C C
Last Used by: z004mx4y
BI 6.7
Time: 10:28:44 AM
BI 6.10
** ** 117 6K121 6C2 FOT LIVE CONTACT
D /105.1 D
BI 6.11
** ** 118 6K123 6C3 BREATHER ERROR
/105.1
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 44
BI 6.12
** ** 119 6K125 6C4 BREATHER HEATER ON
/105.1
BI 6.13
X:SP 12 15 6K127 6C7
SPARE
CopyRight (C) Siemens Limited, India All Rights Reserved.
/105.1
K101B
BI 6.14
16 6K129 6C8
SPARE
E /105.1 E
/45.2
13
BI 6.15
17 6K131 6C9
SPARE
/105.1
BI 6.16
14 18 6K133 6C10
SPARE
/105.1 6C5
DWG.NO:2XYN464032C2676
SH.NO:33,35 6C6
K101
K102
6.COM 9-16 /105.1
/45.4
/45.6
F NOTE:** TB IDENTIFIED AT SITE Unless otherwise specified, wires are PVC, 1.5mm Sq, GY F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad Differential Protection BI Circuit-87T1 System for Various Substations W20644
3007687802(T),30071 Sh. 44 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <43 45>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
/44.1
/44.3
/44.7
87T1 (7UT86)
K101B
K101
K102
A A
-X4.1 -X4.1 BI 6.17
X:TR 77 6K135 6D1
MOLG-OLTC_LOL
45 46 /105.1
SH.NO:32&33 /105.1
Time: 10:29:46 AM
6.COM 17-24
Date: 11/28/2022
OLTC MB.
TB-1 43 X:OLTC 1
5 6K157 6E4
TC STUCK UP
25 26 /105.1
BI 6.30
CopyRight (C) Siemens Limited, India All Rights Reserved.
K101
K102
/46.2
/46.4
/46.6
DRG NO:2XYN464034C2676
SHT NO: 02
F Unless otherwise specified, wires are PVC, 1.5mm Sq, GY F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad Differential Protection BI Circuit-87T1 System for Various Substations W20645
3007687802(T),30071 Sh. 45 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <44 46>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
/45.2
/45.4
/45.6
SHT NO: 02 87T1 (7UT86)
A A
K101A
K101
K102
TB-1 TB-1 BI 6.33
X:OLTC 10 6K167 6G1
AC SUPPLY FAIL / PHASE REVERSE
46 47 /105.1
TB-1
B 21 B
LCC (BAY-115)
X:LV 1
-X -X BI 6.39
5 6K179 6G9
132KV SIDE BKR CLOSE
XX XX /105.1
132KV B/C BKR CLOSE
-X -X BI 6.40
6 6K181 6G10
132KV B/C BKR CLOSE
XX XX /105.1
6G5
NOTE: XX- TB NUMBERS TO BE IDENTIFIED AT SITE 6.COM 33-40 6G6
/105.1
BI 6.41
X:SP 19 X:SP 20 6K183 6H1
SPARE
/105.1
D D
BI 6.42
X:SP 21 6K185 6H2
SPARE
/105.1
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 46
BI 6.43
X:SP 22 6K187 6H3
SPARE
/105.1
BI 6.44
X:SP 23 6K189 6H4
SPARE
/105.1
BI 6.45
X:SP 24 6K191 6H7
SPARE
/105.1
E E
BI 6.46
X:SP 25 6K193 6H8
SPARE
/105.1
BI 6.47
X:SP 26 6K195 6H9
SPARE
/105.1
BI 6.48
X:SP 27 6K197 6H10
SPARE
/105.1 6H5
6H6
6.COM 41-48 /105.1
A A
87T1 (7UT86)
BO 2.2
K905N 2B5 2B8 K907N TO NIFPS
/81.4 /81.4
C /102.1 2B6 DIFF.PROTN.TRIP C
Last Used by: z004mx4y
Time: 10:31:17 AM
Date: 11/28/2022
/103.1
BO 3.6
3C7 3C10 N424 OLTC TAP LOWER
/78.6
/103.1 3C8 CMD
E E
TRAFO. MB
A A
87T1 (7UT86)
SHIELD CABLE
7 85 F CH1
-X4 X:TR S61 ANAI-CA-EL 2F1 2F2
TAP POSITION INDICATION /102.1
(4-20mA) -X4 8 X:TR 86 S62
-X XX X:TR 93
B B
EW
HV WTI TEMP 19 87 F CH2
-X4 X:TR S63 ANAI-CA-EL2F3 2F4
(4-20mA) /102.1
-X4 20 X:TR 88 S64
-X XX X:TR 94
C C
Last Used by: z004mx4y
Time: 10:31:57 AM
Date: 11/28/2022
-X XX X:TR 95
D D
-X4 30 X:TR 91 S67 ANAI-CA-EL 2F7 F CH4 2F8
/102.1
OIL TEMP
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 48
PE
E E-BB E
87T2(RET670)
A A
A101 (I)-1
A211 A211 X401:1• X401:2
/17.6
/106.1
A102 (I)-1
A231 A231 X401:3• X401:4
1200-800/1A PX
/17.6
/106.1
CORE-1
CT-T2
A103 (I)-1
A251 A251 X401:5• X401:6
/17.6
/106.1
A271 A271
/17.6
B B
A104 (I)-1
A311A A311A X401:7• X401:8
/19.7
/106.1
A371A
A105 (I)-1
1200/1A PS A331A A331A X401:9• X401:10
/19.7
/106.1
CT-6
A106 (I)-1
A351A A351A •
X401:11 X401:12
/19.7
/106.1
A371A A371A
/19.7
C C
Last Used by: z004mx4y
Time: 10:32:52 AM
Date: 11/28/2022
/106.1
0-1000Ω/200W
400V RMS/1A
2
SD1
1
A175A A175A
/18.8
D D
A108 (I)-1
X:CT F 14 A411A •
X401:15 X401:16
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 49
/106.1
X:CT F 15 A471A
CopyRight (C) Siemens Limited, India All Rights Reserved.
A109 (I)-1
X:CT F 16 A611A •
X401:17 X401:18
/106.1
E E
X:CT F 17 A671A
A A
206R
87T2(RET670)
B B
FS87T2-R A110 (I OR U)-1
E313 2 1 E313A •
X401:19 X401:20
/38.4
2A /106.1
FS87T2-Y A111 (I OR U)-1
SEL. BUS VT
E333 2 1 E333A •
X401:21 X401:22
CORE-3
/38.4
2A /106.1
FS87T2-B A112 (I OR U)-1
E353 2 1 E353A •
X401:23 X401:24
/38.4
2A /106.1
LK87T2-N
E373 2 1 E373A
/38.4
C C
Last Used by: z004mx4y
E-BB
Time: 10:33:35 AM
Date: 11/28/2022
PE EW PE
/106.1
PE-Pin
D D
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 50
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
/33.1
/33.2
87T2(RET670)
K201
K202
A A
K201 X11:4 X11:5
+ - Power Supply
X:TR 97 /106.1
/106.1
Date: 11/25/2022
232 233
BI15
CopyRight (C) Siemens Limited, India All Rights Reserved.
K202
K201
/52.7
DWG.NO:2XYN464032C2676
/52.4
SH.NO:22,23,30,31&32
F Unless otherwise specified, wires are PVC, 1.5mm Sq, GY F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad Differential Protection BI Circuit-87T2 System for Various Substations W20651
3007687802(T),30071 Sh. 51 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <50 52>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
206R
DB Version: SL-V 1.1-08/01/2019
E-Base Version: 7.1.0.1305
/51.4
/51.7
87T2(RET670)
K201
K202
A A
K2 BI19
22 23 K229 X51:5 X51:6
SF6 ZONE TRIP INTER TRIP
/89.4 /106.1
80A BI20
16 17 K231 X51:7 X51:8
DC-1-Fail
/33.7 /106.1
MCB-87T1
11 14
BI21
/33.1 12 33 K233 X51:9 X51:10
SPARE
/106.1
MCB1-ETH
11 14
BI22
/33.4 12 X:SP 30 34 K235 X51:11 X51:12
SPARE
/106.1
B MCB-AUX B
11 14
BI23
/33.3 12 35 K237 X51:13 X51:14
SPARE
/106.1
MCB-LM1
11 14
/33.2 12
MCB-DC1
11 14
/32.3 12
BI24
43 K239 X51:15 X51:16
MCB-DCCO2 SPARE
11 14 /106.1
/32.6 12
BI25
To 87T1 32 K241 X52:1 X52:2
MCB-86.1 SPARE
C 11 14 /106.1 C
Last Used by: z004mx4y
/33.5 12
Time: 10:35:22 AM
Date: 11/28/2022
MCB-SP2
11 14
/33.7 12
BI27
40 K245 X52:5 X52:6
SPARE
/106.1
D BI28 D
41 K247 X52:7 X52:8
SPARE
/106.1
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 52
BI29
X:SP 31 36 K249 X52:9 X52:10
SPARE
/106.1
CopyRight (C) Siemens Limited, India All Rights Reserved.
BI30
37 K251 X52:11 X52:12
SPARE
/106.1
E E
BI31
38 K253 X52:13 X52:14
SPARE
/106.1
BI32
39 K255 X52:15 X52:16
SPARE
/106.1
87T2(RET670)
SHIELD CABLE
A A
MI:01
X:SP 44 S71 XA:7 XA:8
Spare
X:SP 45 S72
X:SP 46
A371B
MI:02
X:SP 47 S73 XA:9 XA:10
Spare
B B
X:SP 48 S74
X:SP 49
A371B
MI:03
X:SP 50 S75 XA:11 XA:12
Spare
X:SP 51 S76
C C
Last Used by: z004mx4y
Time: 10:36:13 AM
X:SP 52
Date: 11/28/2022
MI:04
X:SP 53 S77 XA:13 XA:14
Spare
X:SP 54 S78
X:SP 55
D D
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 53
MI:05
X:SP 56 S79 XA:15 XA:16
Spare
X:SP 57 S80
X:SP 58
CopyRight (C) Siemens Limited, India All Rights Reserved.
E MI:06
E
X:SP 59 S81 XA:17 XA:18
Spare
X:SP 60 S82
X:SP 61
PE
E-BB
87T2(RET670) 87T2(RET670)
A BO17 X42:7 A
U78 X:SP 78 SPARE
BO1 X41:1 U64 X:SP 64 /107.1
SPARE
/107.1
1K101 X42:8 BO18 X42:9 1K103A
/79.6 /79.6 TO LBB INITIATION
K501 X41:2 BO2 X41:3 K511A /107.1
/67.3 /67.4 TO 86.1 TRIP RELAY
/107.1
BO19X42:10 U79 X:SP 79 SPARE
BO3 X41:4 U65 X:SP 65 /107.1
SPARE
/107.1
X:SP 73 U73 X42:11 BO20X42:12 U77 X:SP 77
SPARE
K801 X41:5 BO4 X41:6 K801C /107.1
/68.3 /68.4 TO 86.2 TRIP RELAY
/107.1
B BO21X42:13 X:SP 80 SPARE B
U80
BO5 X41:7 U66 X:SP 66 /107.1
SPARE
/107.1
X:SP 74 U74 X42:14 BO22X42:15 U81 X:SP 81
SPARE
1L101 X41:8 BO6 X41:9 1L103 /107.1
/78.4 /78.4 TO ANNUN. BC PANEL TRIP ALARAM
/107.1
1L101 X41:11 BO8 X41:12 1L105 X:SP 75 U75 X42:17 BO24X42:18 U83 X:SP 83 SPARE
/78.4 /78.4 TO ANNUN. BC PANEL NON TRIP ALARAM
/107.1 /107.1
C C
Last Used by: z004mx4y
/107.1
Date: 11/28/2022
D BO13 X42:1 D
U70 X:SP 70
SPARE
/107.1
E E
A A
C111 1A1 *I P 1A1 1A2
/14.6
/96.1
1200-800/1A PX
/14.6
/96.1
CORE-1
CT-T2
C151 1A5 *I P 1A3 1A6
/14.6
/96.1
C173
C171 1A7 *I P 1A4 1A8
/14.6
/96.1
B B
RU
1 R1 2
3 R2 4
5 R3 6
FSBCPU-R V 1.1
E413 2 1 E415 1B1 1B2
/73.7
C 2A /96.1 C
Last Used by: z004mx4y
Supply FromCore-4
FSBCPU-Y
Selected Bus PT
V 1.2
Time: 10:38:02 AM
/73.7 1B4
2A /96.1
FSBCPU-B V 1.3
E453 2 1 E455 1B5 1B6
/73.7
2A /96.1
LKBCPU-N
E473 2 1 E475
/73.7
D D
7 R4 8
115R
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 55
FROM LV SIDE PT
CORE-3
-X731 LKBCPU-LV
6 E731 2 1 E735
E 41 E
DWG: (3)G71770-AE251-S161-B
SH:SB1
/33.2
/33.2
BCPU(6MD86)
K401
K402
A A
LCC -D06 PS
K401 2B1 2B2
-X203 X:LCC 5 + - Power Supply
/96.1
Date: 11/28/2022
12
K402
E-BB PE
K401
PE EW 1PE
/96.1
/57.3
/57.7
DWG NO: (3)G71770-AD399-S141
PE-Pin
/57.1
SH:NO:QB1&QB2
/56.1
/56.3
/56.7
BCPU(6MD86)
K401
K401
K402
A -X08 -X203 BI 3.7 A
X:LCC 24 3K415 3B1 3A13
HIGH SPEED ESW Q8 CLOSE
12 22 /97.1
BI 3.11
B -X61L1 -X203 28 3K423 3B9 3B7 B
ISOLATING LINK Q62 OPEN
5 26 /97.1
-X203 BI 4.1
30 4K403 4A1
SELECTOR SWITCH IN REMOTE
28 /98.1
-X203 BI 4.2
31 4K405 4A2
SELECTOR SWITCH IN LOCAL
29 /98.1
C C
Last Used by: z004mx4y
-X203 BI 4.3
32 4K407 4A3
MASTER INTERLOCK OVERRIDE
Time: 10:39:51 AM
/98.1
Date: 11/28/2022
30
GC09
DWG NO: (3)G71770-AD399-S141
.A BI 4.4
SH:NO:QB2 17 18 4K409 4A4
-X501 GC-09 GD1 GAS ZONE TRIP
23 /86.6 /98.1
1
-X501 BI 4.5
33 4K411 4A7
HAND CRANK COVER OPEN
5 /98.1
-X501 BI 4.6
34 4K413 4A8
GENERAL LOCKOUT SF6
6 /98.1
D D
-X501 BI 4.7
35 4K415 4A9
MOTOR PROTECTION
7 /98.1
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 57
-X501 BI 4.8
36 4K417 4A10
CB LOSS OF SF6 POLE A
8 /98.1 4A5
4.COM 1-8 4A6
/98.1
-X501 BI 4.9
37 4K419 4C1
CB LOSS OF SF6 POLE B
CopyRight (C) Siemens Limited, India All Rights Reserved.
9 /98.1
-X501 BI 4.10
38 4K421 4C2
CB LOSS OF SF6 POLE C
E 10 /98.1 E
-X501 BI 4.11
39 4K423 4C3
MOTOR RUNNING TIME SUPERVISION
11 /98.1
-X501 BI 4.12
40 4K425 4C4
POLE DISCREPANCY TRIPPING
12 /98.1
K401A
K401
K402
/58.7
DWG NO: (3)G71770-AD399-S152
/58.1
/59.1
/58.4
/58.7
SH:NO:RB1
F Unless otherwise specified, wires are PVC 1.5 GY F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad BCPU Relay BI Circuit System for Various Substations W20657
3007687802(T),30071 Sh. 57 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <56 58>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
LCC -D06 206R
DB Version: SL-V 1.1-08/01/2019
E-Base Version: 7.1.0.1305
/57.1
/57.3
/57.7
/57.7
K401A
K401
K402
A A
-X501 BI 4.13
X:LCC 41 4K427 4C7 GAS COMP. 01 (Q1 POLE A)
13 /98.1 LOSS OF SF6
-X501 BI 4.14
X:LCC 42 4K429 4C8 GAS COMP. 01 (Q1 POLE A)
14 /98.1 MIN. SF6 DENSITY
-X501 BI 4.15
X:LCC 43 4K431 4C9 GAS COMP. 01 (Q1 POLE B)
15 /98.1 LOSS OF SF6
-X501 BI 4.16
X:LCC 44 4K433 4C10 GAS COMP. 01 (Q1 POLE B)
B 16 /98.1 4C5 MIN. SF6 DENSITY B
4.COM 9-16 4C6
/98.1
-X501 BI 4.17
X:LCC 45 4K435 4D1 GAS COMP. 01 (Q1 POLE C)
17 /98.1 LOSS OF SF6
-X501 BI 4.18
X:LCC 46 4K437 4D2 GAS COMP. 01 (Q1 POLE C)
18 /98.1 MIN. SF6 DENSITY
-X501 BI 4.19
X:LCC 47 4K439 4D3 GAS COMP. 02 (Q2 POLE A)
19 /98.1 LOSS OF SF6
-X501 BI 4.20
C X:LCC 48 4K441 4D4 GAS COMP. 02 (Q2 POLE A) C
Last Used by: z004mx4y
-X501 BI 4.21
X:LCC 49 4K443 4D7
ALARM SIGNALLING VOLTAGE MCB OPERATED
21 /98.1
-X501 BI 4.22
X:LCC 50 4K445 4D8
LIVE CONTACT-H501
22 /98.1
-X501 BI 4.23
X:LCC 51 4K447 4D9 GAS COMP. 02 (Q2 POLE B)
23 /98.1 LOSS OF SF6
-X501 BI 4.24
X:LCC 52 4K449 4D10 GAS COMP. 02 (Q2 POLE B)
D /98.1 MIN. SF6 DENSITY D
24 4D5
4.COM 17-24 4D6
/98.1
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 58
-X501 BI 4.25
X:LCC 53 4K451 4E1 GAS COMP. 02 (Q2 POLE C)
25 /98.1 LOSS OF SF6
-X501 BI 4.26
X:LCC 54 4K453 4E2 GAS COMP. 02 (Q2 POLE C)
26 /98.1 MIN. SF6 DENSITY
CopyRight (C) Siemens Limited, India All Rights Reserved.
-X501 BI 4.27
X:LCC 55 4K455 4E3 GAS COMP. 03 (BB1)
27 /98.1 LOSS OF SF6
E E
-X501 BI 4.28
X:LCC 56 4K457 4E4 GAS COMP. 03 (BB1)
28 /98.1 MIN. SF6 DENSITY
/59.7
K401
K402
DWG,NO:- G71770-AD399-S152
SH:NO:RB1&RB2
/59.4
/59.7
F Unless otherwise specified, wires are PVC, 1.5mm Sq, GY F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad BCPU Relay BI Circuit System for Various Substations W20658
3007687802(T),30071 Sh. 58 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <57 59>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
LCC -D06 206R
DB Version: SL-V 1.1-08/01/2019
E-Base Version: 7.1.0.1305
/57.1
/58.7
/58.4
/58.7
K401A
A A
K401
K402
-X501 BI 4.29
X:LCC 57 4K459 4E7 GAS COMP. 04 (BB2)
29 /98.1 LOSS OF SF6
-X501 BI 4.30
X:LCC 58 4K461 4E8 GAS COMP. 04 (BB2)
30 /98.1 MIN. SF6 DENSITY
-X501 BI 4.31
X:LCC 59 4K463 4E9 GAS COMP. 05 (T1 POLE A)
31 /98.1 LOSS OF SF6
-X501 BI 4.32
X:LCC 60 4K465 4E10 GAS COMP. 05 (T1 POLE A)
B 32 /98.1 4E5 MIN. SF6 DENSITY B
4.COM 25-32 4E6
-X501 BI 4.33
X:LCC 61 4K467 4G1 /98.1 GAS COMP. 05 (T1 POLE B)
33 /98.1 LOSS OF SF6
-X501 BI 4.34
X:LCC 62 4K469 4G2 GAS COMP. 05 (T1 POLE B)
34 /98.1 MIN. SF6 DENSITY
-X501 BI 4.35
X:LCC 63 4K471 4G3 GAS COMP. 05 (T1 POLE C)
35 /98.1 LOSS OF SF6
-X501 BI 4.36
X:LCC 64 4K473 4G4 GAS COMP. 05 (T1 POLE C)
/98.1 MIN. SF6 DENSITY
C 36 C
Last Used by: z004mx4y
Time: 10:41:34 AM
Date: 11/28/2022
-X501 BI 4.37
X:LCC 65 4K475 4G7 GAS COMP. 06 (T2 POLE A)
37 /98.1 LOSS OF SF6
-X501 BI 4.38
X:LCC 66 4K477 4G8 GAS COMP. 06 (T2 POLE A)
38 /98.1 MIN. SF6 DENSITY
DWG,NO:- G71770-AD399-S152
SH:NO:RB2
-X502 X:LCC 67
1 BI 4.39
-X502 X:LCC 68 4K479 4G9 GAS COMP. 06 (T2 POLE B)
D /98.1 LOSS OF SF6 D
5
-X502 BI 4.40
X:LCC 69 4K481 4G10 GAS COMP. 06 (T2 POLE B)
/98.1 MIN. SF6 DENSITY
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 59
6 4G5
4.COM 33-40 4G6
-X502 BI 4.41
X:LCC 70 4K483 4H1 /98.1 GAS COMP. 06 (T2 POLE C)
7 /98.1 LOSS OF SF6
-X502 BI 4.42
X:LCC 71 4K485 4H2 GAS COMP. 06 (T2 POLE C)
CopyRight (C) Siemens Limited, India All Rights Reserved.
-X502 BI 4.43
X:LCC 72 4K487 4H3 GAS COMP. 07 (IC POLE A)
E 9 /98.1 LOSS OF SF6 E
-X502 BI 4.44
X:LCC 73 4K489 4H4 GAS COMP. 07 (IC POLE A)
10 /98.1 MIN. SF6 DENSITY
K401B
K401
K402
DWG,NO:- G71770-AD399-S152
/60.1
/60.7
SH:NO:RB3
/60.4
/60.7
F Unless otherwise specified, wires are PVC, 1.5mm Sq, GY F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad BCPU Relay BI Circuit System for Various Substations W20659
3007687802(T),30071 Sh. 59 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <58 60>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
LCC -D06 206R
DB Version: SL-V 1.1-08/01/2019
E-Base Version: 7.1.0.1305
/59.1
/59.4
/59.7
/59.7
K401B
K401
K402
A A
-X502 BI 4.45
X:LCC 74 4K491 4H7 GAS COMP. 07 (IC POLE B)
11 /98.1 LOSS OF SF6
-X502 BI 4.46
X:LCC 75 4K493 4H8 GAS COMP. 07 (IC POLE B)
12 /98.1 MIN. SF6 DENSITY
-X502 BI 4.47
X:LCC 76 4K495 4H9 GAS COMP. 07 (IC POLE C)
13 /98.1 LOSS OF SF6
-X502 BI 4.48
X:LCC 77 4K497 4H10 GAS COMP. 07 (IC POLE C)
B 14 /98.1 MIN. SF6 DENSITY B
4H5
4.COM 41-48 4H6
/98.1
K3 BI 5.1
14 15 5K403 5A1
BB Z1 OPTD DUE TO GAS ZONE TRIP(DR)
/90.6 /99.1
K4 BI 5.2
14 15 5K405 5A2
BB Z2 OPTD DUE TO GAS ZONE TRIP(DR)
/91.6 /99.1
GC10 BI 5.3
17 .A 18 5K407 5A3
GC-10 GAS ZONE TRIP
/86.6 /99.1
C C
Last Used by: z004mx4y
-X502 BI 5.4
X:LCC 78 5K409 5A4 GAS COMP. 08 (T5 POLE B)
Time: 10:42:25 AM
15
-X502 BI 5.5
X:LCC 79 5K411 5A7 GAS COMP. 08 (T5 POLE B)
16 /99.1 MIN. SF6 DENSITY
K1 BI 5.6
16 17 5K413 5A8
GAS ZONE TRIP 86A/86B
/89.4 /99.1
K2 BI 5.7
16 17 5K415 5A9
SF6 ZONE TRIP INTER TRIP (DR)
/89.4 /99.1
D -X502 BI 5.8 D
X:LCC 80 5K417 5A10 GAS COMP. 09 (F1 POLE A)
17 /99.1 LOSS OF SF6
5.COM 1-8 5A5
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 60
5A6
-X502 BI 5.9
X:LCC 81 5K419 5C1 /99.1 GAS COMP. 09 (F1 POLE A)
18 /99.1 MIN. SF6 DENSITY
-X502 BI 5.10
X:LCC 82 5K421 5C2 GAS COMP. 09 (F1 POLE B)
19 /99.1 LOSS OF SF6
CopyRight (C) Siemens Limited, India All Rights Reserved.
-X502 BI 5.11
X:LCC 83 5K423 5C3 GAS COMP. 09 (F1 POLE B)
20 /99.1 MIN. SF6 DENSITY
E E
-X502 BI 5.12
X:LCC 84 5K425 5C4
LIVE CONTACT-H502
21 /99.1
K401B
/61.1
K401
K402
DWG,NO:- G71770-AD399-S152
SH:NO:RB2&RB3
/61.4
/61.7
F Unless otherwise specified, wires are PVC, 1.5mm Sq, GY F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad BCPU Relay BI Circuit System for Various Substations W20660
3007687802(T),30071 Sh. 60 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <59 61>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
LCC -D06 206R
DB Version: SL-V 1.1-08/01/2019
E-Base Version: 7.1.0.1305
/60.1
/60.4
/60.7
K401B
A A
K401
K402
-X502 BI 5.13
X:LCC 85 5K429 5C7 GAS COMP. 09 (F1 POLE C)
22 /99.1 LOSS OF SF6
-X502 BI 5.14
X:LCC 86 5K431 5C8 GAS COMP. 09 (F1 POLE C)
23 /99.1 MIN. SF6 DENSITY
-X502 BI 5.15
X:LCC 87 5K433 5C9 GAS COMP. 10 (BD_L1)
24 /99.1 LOSS OF SF6
-X502 BI 5.16
X:LCC 88 5K435 5C10 GAS COMP. 10 (BD_L1)
B 25 /99.1 5C5 MIN. SF6 DENSITY B
5.COM 9-16 5C6
/99.1
-X502 BI 5.17
X:LCC 89 5K437 5D1 GAS COMP. 10 (BD_L2)
26 /99.1 LOSS OF SF6
-X502 BI 5.18
X:LCC 90 5K439 5D2 GAS COMP. 10 (BD_L2)
27 /99.1 MIN. SF6 DENSITY
-X502 BI 5.19
X:LCC 91 5K441 5D3 GAS COMP. 10 (BD_L3)
28 /99.1 LOSS OF SF6
-X502 BI 5.20
C X:LCC 92 5K443 5D4 GAS COMP. 10 (BD_L3) C
Last Used by: z004mx4y
-X502 BI 5.21
X:LCC 93 5K445 5D7 GAS COMP. 11 (Z2_L1)
30 /99.1 LOSS OF SF6
-X502 BI 5.22
X:LCC 94 5K447 5D8 GAS COMP. 11 (Z2_L1)
31 /99.1 MIN. SF6 DENSITY
-X502 BI 5.23
X:LCC 95 5K449 5D9 GAS COMP. 11 (Z2_L2)
32 /99.1 LOSS OF SF6
-X502 BI 5.24
X:LCC 96 5K451 5D10 GAS COMP. 11 (Z2_L2)
D /99.1 MIN. SF6 DENSITY D
33
5D5
5.COM 17-24
5D6
/99.1
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 61
-X502 BI 5.25
X:LCC 97 5K453 5E1 GAS COMP. 11 (Z2_L3)
34 /99.1 LOSS OF SF6
-X502 BI 5.26
X:LCC 98 5K455 5E2 GAS COMP. 11 (Z2_L3)
35 /99.1 MIN. SF6 DENSITY
CopyRight (C) Siemens Limited, India All Rights Reserved.
GC03
.A BI 5.27
17 18 5K457 5E3
GC-03 BB1 GAS ZONE TRIP DR
/85.6 /99.1
E GC04 E
.A BI 5.28
17 18 5K459 5E4
GC-04 BB2 GAS ZONE TRIP DR
/86.6 /99.1
K401
K402
/62.7
DWG,NO:- G71770-AD399-S152
SH:NO:RB4
/62.4
/62.7
F Unless otherwise specified, wires are PVC 1.5 GY F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad BCPU Relay BI Circuit System for Various Substations W20661
3007687802(T),30071 Sh. 61 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <60 62>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
LCC -D06 206R
DB Version: SL-V 1.1-08/01/2019
E-Base Version: 7.1.0.1305
/61.4
BCPU(6MD86)
/61.7
/61.7
K401
K402
A -X504 A
X:LCC 99
1
GC13
.A BI 5.29
17 18 5K461 5E7
GC-13 BB2 GAS ZONE TRIP DR
/87.5 /99.1
-X504 BI 5.30
X:LCC 100 5K463 5E8
VT MCB TRIPPED
7 /99.1
BI 5.32
B -X504 X:LCC 101 5K467 5E10 CRP AC MCB FAIL / LCC AC FAIL B
8 /99.1 5E5 AC MCB TRIP
-X504 AMCB 5.COM 25-32 5E6
11 14
6 /31.4 12 /99.1
-X504 BI 5.33
X:LCC 102 5K469 5G1 DC MCB TRIPPED
9 /99.1 DC-1 / DC-2 FAIL
-X504 BI 5.34
X:LCC 103 5K471 5G2
SPARE
10 /99.1
-X504 BI 5.35
X:LCC 104 5K473 5G3
LIVE CONTACT-H503
21 /99.1
C C
Last Used by: z004mx4y
/67.5 /99.1
Date: 11/28/2022
86.2 BI 5.37
113 114 5K477 5G7
86.2 TRIP RELAY OPTD.
/68.5 /99.1
200R BI 5.38
DCC02
227 228 5K479 5G8 DCC02
6K401 XB:BB6 18 /32.4 /99.1 DE-ENERGIZED
/W200 /34.7
BI 5.39
65K481 XB:BB6 19 5K481 5G9
/W200 /34.7 96 TRIP RELAY OPTD.
/99.1
D D
FROM B/B PANEL 96 OPTD GC12
.A BI 5.40
17 18 5K483 5G10
GC-12 GD2 GAS ZONE TRIP
/99.1
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 62
/87.5 5G5
5.COM 33-40 5G6
/99.1
95.1 BI 5.41
16 17 5K485 5H1
86.1 RELAY UNHEALTHY
100R /67.3 /99.1
95.2 BI 5.42
CopyRight (C) Siemens Limited, India All Rights Reserved.
K402
/63.7
/63.3
/63.7
F Unless otherwise specified, wires are PVC, 1.5mm Sq, GY F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad BCPU Relay BI Circuit System for Various Substations W20662
3007687802(T),30071 Sh. 62 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <61 63>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
206R
DB Version: SL-V 1.1-08/01/2019
E-Base Version: 7.1.0.1305
/62.4
/62.7
BCPU(6MD86)
/62.7
K401
K402
A A
CS52
7
TNC BI 5.45
13 14 5K493 5H7
-X503 CB CLOSE COMMAND
X:LCC 105 /94.6 /99.1
1 BI 5.46
-X503 X:LCC 106 5K495 5H8 PSD 02
2 /99.1 BY PASS
-X503 BI 5.47
X:LCC 107 5K497 5H9 PSD 02 DEVICE
3 /99.1 IN SERVICE
-X503 BI 5.48
X:LCC 108 5K499 5H10 PSD 02
B 4 /99.1 5H5 CB VOLTAGE ERROR B
5.COM 41-48 5H6
/99.1
-X503 BI 6.1
X:LCC 109 6K403 6A1 PSD 02
5 /100.1 SYNC DATA ERROR
-X503 BI 6.2
X:LCC 110 6K405 6A2 PSD 02
6 /100.1 SYNC OPERATION FAILED
-X503 BI 6.3
X:LCC 111 6K407 6A3 PSD 02
7 /100.1 DEVICE OK
-X503 BI 6.4
C X:LCC 112 6K409 6A4 C
Last Used by: z004mx4y
GC01
DWG,NO:- G71770-AD399-S151
.B BI 6.5
SH:NO:RA11 23 24 6K411 6A7
GC-01 Q1 GAS ZONE TRIP DR
/83.5 /100.1
GC02
.B BI 6.6
23 24 6K413 6A8
GC-02 Q2 GAS ZONE TRIP DR
/83.5 /100.1
GC05
.A BI 6.7
17 18 6K415 6A9
GC-05 T1CT GAS ZONE TRIP DR
/83.5 /100.1
GC00 BI 6.8
D D
23 .B 24 6K417 6A10
GC-00 Q0 GAS ZONE TRIP DR
/84.5 /100.1 6A5
6A6
6.COM BI 1-8 /100.1
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 63
GC06 BI 6.9
17 .A 18 6K419 6C1
GC-06 T2CT GAS ZONE TRIP DR
/84.5 /100.1
GC07
.A BI 6.10
17 18 6K421 6C2
GC-07 Q9 GAS ZONE TRIP DR
CopyRight (C) Siemens Limited, India All Rights Reserved.
/84.5 /100.1
GC08
.A BI 6.11
17 18 6K423 6C3
GC-08 LPT GAS ZONE TRIP DR
E /85.6 /100.1 E
GC11
.A BI 6.12
17 18 6K425 6C4
GC-11 LA GAS ZONE TRIP DR
/85.6 /100.1
K401
/64.7
K402
/64.3
/64.7
F Unless otherwise specified, wires are PVC, 1.5mm Sq, GY F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad BCPU Relay BI Circuit System for Various Substations W20663
3007687802(T),30071 Sh. 63 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <62 64>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
206R
DB Version: SL-V 1.1-08/01/2019
E-Base Version: 7.1.0.1305
/63.3
/63.7
BCPU(6MD86)
/63.7
BCPU(6MD86)
K401
K402
A E-BB PE A
PE EW 1PE
/96.1
195-R BI 6.13
26 27 6K427 6C7
E-BB PE TC-1 R-PH FAULTY
PE EW 3PE /76.4 /100.1
/97.1
195-Y BI 6.14
E-BB PE 26 27 6K429 6C8
TC-1 Y-PH FAULTY
PE EW 3PE /76.4 /100.1
/97.1
195-B BI 6.15
26 27 6K431 6C9
E-BB PE TC-1 B-PH FAULTY
PE EW 4PE /76.4 /100.1
/98.1
295-R BI 6.16
E-BB PE 26 27 6K433 6C10
TC-2 R-PH FAULTY
B PE EW 4PE /77.4 /100.1 6C5 B
/98.1 6.COM BI 9-16 6C6
/100.1
E-BB PE
PE EW 5PE
/99.1
E-BB PE
PE EW 5PE
/99.1
E-BB PE
PE EW 6PE
/100.1
E-BB PE
C PE EW 6PE C
Last Used by: z004mx4y
295-Y BI 6.17
/100.1 26 27 6K435 6D1
TC-2 Y-PH FAULTY
Time: 10:45:25 AM
/77.4 /100.1
Date: 11/28/2022
295-B BI 6.18
26 27 6K437 6D2
TC-2 B-PH FAULTY
/77.4 /100.1
GC14
.A BI 6.19
17 18 6K439 6D3
GC-14 BB1 GAS ZONE TRIP DR
/87.5 /100.1
GC15
.A BI 6.20
17 18 6K441 6D4
GC-15 BB2 GAS ZONE TRIP DR
LCC -D06 /88.5 /100.1
GC16
D .A BI 6.21 D
** X:LA 1 17 18 6K443 6D7
GC-16 BB1 GAS ZONE TRIP DR
/88.5 /100.1
BI 6.22
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 64
BI 6.23
** X:LA 3 6K447 6D9
LA COUNTER - YPH
/100.1
BI 6.24
CopyRight (C) Siemens Limited, India All Rights Reserved.
K402
/69.2
/69.6
NOTE: ** TERMINALS TO BE IDENTIFIED AT SITE
F Unless otherwise specified, wires are PVC, 1.5mm Sq, GY F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad BCPU Relay BI Circuit System for Various Substations W20664
3007687802(T),30071 Sh. 64 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <63 65>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
/74.3
6E6 KC302 6H5
/74.3
Time: 10:46:04 AM
/100.1 6H6
Date: 11/28/2022
D BO 6.12 6G4 D
KC343 K401 1B13 BO 1.3 1B14 K413 VT SELECTION(WDG-02)
/75.4 HIGH SPEED ESW Q8 CLOSE(+VE) /70.2 /70.3
KC301
/100.1 /96.1
K415 VT SELECTION(WDG-02)
BO 6.13 6G7 /70.3
U84 X:SP 84 /96.1
SPARE
/100.1
1C6 BO 1.5 1C3 K417 VT SELECTION(WDG-03)
BO 6.14 6G8 /70.3
U85 X:SP 85 /96.1
SPARE
/100.1
CopyRight (C) Siemens Limited, India All Rights Reserved.
A A
BCPU(6MD86)
SPARE
/97.1
Time: 10:46:40 AM
Date: 11/28/2022
/97.1
/97.1
E E
A A
/33.5
/33.5
Trip Relay
K501
K502
87T1 (7UT86) 86.1
K501 K511A K511A 121 K502A
/47.4 /47.5 O 122
K511B 111
11
12
13
14
RU.86.1
B K511C 211 8X47Ω/5W B
87T2(RET670) R 212
K501 K511A
21
22
23
24
RXTMA
/54.2 /54.3
113 114
/62.5 TO BCPU BI CKT.
115 116
/80.4 TO LV CB TC-1
117 118
/80.4 TO LV CB CLOSING CKT
BCPU(6MD86) 221 222
/92.3 SPARE
K501 K511A 223 224
/66.4 /66.5 /80.4 TO LV CB TC-2
225 226
/92.3 SPARE
227 228
K1 /74.4 TO CB CLOSING CKT
X:SP 104 12 13 317 318
/76.4 TO CB TC-1 CKT
/89.4 315 316
/76.4 TO CB TC-1 CKT.
FUTURE TRIP 313 314
/76.4 TO CB TC-1 CKT.
C X:SP 105 311 312 C
Last Used by: z004mx4y
425 426
Date: 11/28/2022
D D
DRG NO:3005963698
SHT NO: W102 45 86.1 Supvn relay
95.1
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 67
12 21
11 13
28 18
16 17
/62.5 To BCPU BI
CopyRight (C) Siemens Limited, India All Rights Reserved.
26 27
/92.6 Spare
E E
A A
/33.5
/33.5
Trip Relay
K801
K802
87T1 (7UT86) 86.2
K801 K801C K801C 121 K802A
/47.4 /47.5 O 122
K821B 111
87T2(RET670)
11
12
13
14
K801 K801C K821C 211 RU.86.2
/54.2 /54.3 R 212
8X47Ω/5W
21
22
23
24
113 114 RXTMA
B /62.5 TO BCPU BI CKT. B
BCPU(6MD86) 115 116
/80.4 TO LV CB TC-1
X:SP 106 K801 K801C 117 118
/66.4 /66.5 /80.4 TO LV CB CLOSING CKT
221 222
/92.3 SPARE
FUTURE TRIP 223 224
/80.4 TO LV CB TC-2
X:SP 107 225 226
/92.3 SPARE
227 228
/74.5 TO CB CLOSING CKT
317 318
K1 /76.4 TO CB TC-1 CKT
14 15 315 316
/76.4 TO CB TC-1 CKT.
/89.4 313 314
/76.4 TO CB TC-1 CKT.
311 312
/77.4 TO CB TC-2 CKT.
427 428
PB86.2 /77.4 TO CB TC-2 CKT.
16 26 425 426
/77.4 TO CB TC-2 CKT.
C /94.5 423 424 C
Last Used by: z004mx4y
BCPU(6MD86)
K801 K821C
/66.4 /66.5
115R
X:HV 4 X:LV 11
X:HV 5 X:LV 12
11 13
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 68
28 18
16 17
/62.5 To BCPU BI
26 27
/92.6 Spare
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
/64.3
/64.7
K401
A A
K402
CS52
3
TNC
5 6
/94.6
52A
BCPU(6MD86)
.A
K401 K425 K425 11 12
/66.4 /66.5
13 14
B /74.4 To CB Open Circuit(+VE) B
15 16
/74.4 To CB Open Circuit(-VE)
17 18
.B
21 22
23 24
/92.3 Spare
25 26
/92.3 Spare
27 28
/92.3 Spare
52B
C C
Last Used by: z004mx4y
.A
Time: 10:48:28 AM
/66.4 /66.5 11 12
13 14
/74.4 To CB Close Ckt(+VE)
15 16
/74.4 To CB Close Ckt (-VE)
17 18
To BB Panel
.B
21 22
23 24
/92.3 Spare
25 26
D /92.3 Spare D
27 28
/92.3 Spare
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 69
K401
K402
/70.2
/70.7
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
/69.2
/69.6
BCPU(6MD86)
A Voltage Selection Relay A
K401
K402
75.1
K401 K413 K413 112
/65.5 /65.6 O 111
211
113 213
/72.3 Bus-2 VT Selection
114 214
/72.3 Bus-1 VT Selection
115 215
/72.3 Bus-2 VT Selection
116 216
/72.3 Bus-1 VT Selection
117 217
/72.3 Bus-2 VT Selection
118 218
B /72.3 Bus-1 VT Selection B
127 227
/72.3 Bus-1 VT Selection
126 226
/72.3 Bus-2 VT Selection
125 225
/92.6 SPARE
123 223
121 221
128 228
/92.6 SPARE
124 224
122 222
C C
Last Used by: z004mx4y
Time: 10:48:59 AM
Date: 11/28/2022
115 215
/72.3 Bus-2 VT Selection
116 216
/72.3 Bus-1 VT Selection
117 217
/72.3 Bus-2 VT Selection
118 218
/72.3 Bus-1 VT Selection
127 227
/72.3 Bus-1 VT Selection
126 226
/72.3 Bus-2 VT Selection
CopyRight (C) Siemens Limited, India All Rights Reserved.
125 225
/92.6 SPARE
123 223
121 221
E 128 228 E
/92.6 SPARE
124 224
122 222
K401
K402
/71.2
/71.7
F Unless otherwise specified, wires are PVC 1.5 GY F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad PT Selection Circuit System for Various Substations W20670
3007687802(T),30071 Sh. 70 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <69 71>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
/70.7
A A
/70.2
K402
K401
BCPU(6MD86)
Voltage Selection Relay
75.3
K401 K421 K421 112
/65.5 /65.6 O 111
211
122 222
Time: 10:49:29 AM
Date: 11/28/2022
D D
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 71
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
FSB1RC2 75.1
1E211 2 1 1E213 114 214 E213 E213
A /34.4 /36.2 A
2A /70.4
To Load Manager
Supply Core-2
FSB1YC2 75.1
Metering
BUS-1 PT
1E231 2 1 1E233 116 216 E233 E233
/34.4 /70.4 /36.2
2A
FSB1BC2 75.1
1E251 2 1 1E253 118 218 E253 E253
/34.4 /70.4 /36.2
2A
LKB1NC2 75.1
1E271 2 1 1E273 127 227 E273 E273
/34.4 /70.4 /36.2
B FSB2RC2 75.1 B
2E211 2 1 2E213 113 213
/35.4 /70.4
2A
FSB2YC2 75.1
2E231 2 1 2E233 115 215
Supply Core-2
/35.4
Metering
/70.4
BUS-2 PT
2A
FSB2BC2 75.1
2E251 2 1 2E253 117 217
/35.4 /70.4
2A
LKB2NC2 75.1
2E271 2 1 2E273 126 226
/35.4 /70.4
C C
Last Used by: z004mx4y
FSB1RC3 75.2
Time: 10:50:00 AM
2A
Protection
FSB1YC3 75.2
BUS-1 PT
TO 87T1
/34.6 /70.4 /38.4
2A
FSB1BC3 75.2
1E351 2 1 1E353 118 218 E353 E353
/34.6 /70.4 /38.4
2A
LKB1NC3 75.2
1E371 2 1 1E373 127 227 E373 E373
/34.6 /70.4 /38.4
D D
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 72
FSB2RC3 75.2
2E311 2 1 2E313 113 213
/35.5
2A /70.4
Supply Core-3
FSB2YC3 75.2
Protection
/35.6
2A /70.4
FSB2BC3 75.2
2E351 2 1 2E353 117 217
CopyRight (C) Siemens Limited, India All Rights Reserved.
/35.6
2A /70.4
LKB2NC3 75.2
2E371 2 1 2E373 126 226
/35.6
/70.4
E E
206R
A A
FSB1RC4 75.3
1E411 2 1 1E413 114 214 E413
/34.4 /71.4 /55.3
2A
Supply Core-4
FSB1YC4 75.3
Protection
BUS-1 PT
To BCPU
B /34.4 /71.4 /55.3 B
2A
FSB1BC4 75.3
1E451 2 1 1E453 118 218 E453
/34.4 /71.4 /55.3
2A
LKB1NC4 75.3
1E471 2 1 1E473 127 227 E473
/34.4 /71.4 /55.3
FSB2RC4 75.3
2E411 2 1 2E413 113 213
/35.4 /71.4
2A
FSB2YC4 75.3
Supply Core-4
Protection
BUS-2 PT
/35.4 /71.4
2A
FSB2BC4 75.3
Time: 10:50:34 AM
/35.4 /71.4
2A
LKB2NC4 75.3
2E471 2 1 2E473 126 226
/35.4 /71.4
D D
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 73
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
KC305A-1
KC307 Open(-Ve)
/69.5 9
52B
15 .A 16 KC309 118 -X201
115R Close(-Ve)
/69.5 10
B X:HV 6 X:LV 19 B
BCPU(6MD86)
C C
Last Used by: z004mx4y
14
ISO Q2
KC319 KC319 123 -X201
/65.3 Close
15
20
ESW Q52
KC331 KC331 129 -X201
/65.3 Close
E 21 E
A A
BCPU(6MD86)
Time: 10:51:33 AM
/65.6 Open/Close(-Ve)
28
D D
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 75
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
6K7 7
/W200 /34.7
28 18
Time: 10:52:06 AM
16 17
Date: 11/28/2022
/92.6 SPARE
26 27
/64.5 TO BCPU
Supervision Relay
195-Y -X321
12 21 K15 142
30
K25 145 -X321
11 13 TC-1 PRE CLOSE SUPVN (Y-PH)
31
28 18
16 17
/92.6 SPARE
26 27
D /64.5 TO BCPU D
Supervision Relay
195-B -X321
12 21 K17 143
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 76
32
K27 146 -X321
11 13 TC-1 PRE CLOSE SUPVN (B-PH)
33
28 18
16 17
/92.6 SPARE
26 27
/64.5 TO BCPU
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
DWG NO:(3)G71770-AD399-S121
SH:MB2
F Unless otherwise specified, wires are PVC, 1.5mm Sq, GY F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad CB TC1 CIRCUIT System for Various Substations W20676
3007687802(T),30071 Sh. 76 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <75 77>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
6K55 10
/W200 /34.7
6K57 11
/W200 /34.7
Supervision Relay
295-R -X322
12 21 K63 151
12
K73 154 -X322
C 11 13 C
Last Used by: z004mx4y
28 18
Date: 11/28/2022
16 17
/92.6 SPARE
26 27
/64.5 TO BCPU
Supervision Relay
295-Y -X322
12 21 K65 152
14
K75 155 -X322
11 13 TC-2 PRE CLOSE SUPVN (Y-PH)
15
28 18
16 17
D /92.6 SPARE D
26 27
/64.5 TO BCPU
Supervision Relay
295-B -X322
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 77
12 21 K67 153
16
K77 156 -X322
11 13 TC-2 PRE CLOSE SUPVN (B-PH)
17
28 18
16 17
/92.6 SPARE
CopyRight (C) Siemens Limited, India All Rights Reserved.
26 27
/64.5 TO BCPU
E E
DWG NO:(3)G71770-AD399-S121
SH:NO:MB3
F Unless otherwise specified, wires are PVC, 1.5mm Sq, GY F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad CB TC-2 CIRCUIT System for Various Substations W20677
3007687802(T),30071 Sh. 77 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <76 78>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
OLTC MB.
BCPU(6MD86)
To Annu. B/C Panel 6L103 2 XB:BC6 1L103 1L103 1L101
/W204/53.2 /65.6 /65.5
Trip Alarm
13 X:OLTC TB-1 11 COMMON
87T1 (7UT86)
1L103 1L101 87T1 (7UT86)
/47.5 /47.4
BCPU(6MD86)
To Annu. B/C Panel Non 6L105 3 XB:BC6 1L105 1L105 1L101
/W204/53.2 /65.6 /65.5
Trip Alarm
/47.4 /47.5
1L105 1L101
/54.3 /54.2
Time: 10:53:21 AM
Date: 11/28/2022
87T1 (7UT86)
DRG NO:2XYN464034C2676
To Annu. B/C Panel 6L107 4 XB:BC6 1L107 1L107 1L101 SHT NO: 02
/W204/53.2 /47.5 /47.4
OLTC non trip alarm
BCPU(6MD86)
LC
2B9 2B10
To Annu. B/C Panel 6L109 5 XB:BC6 1L109 2B7 /97.1
D Relay Un Healthy /W204/53.2 D
87T1 (7UT86)
LC
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 78
2B9 2B10
2B7 /102.1
87T2(RET670)
X11:1 X11:2
CopyRight (C) Siemens Limited, India All Rights Reserved.
X11:3 /106.1
E E
2ES-6
8
6L111 6 XB:BC6 1L111 9
To Annu. B/C Panel /W204/53.2
10
Ethernet Switch Unhealthy Failsafe
200R 206R
A A
+VE
87T1 (7UT86)
B B
87T2(RET670)
1K103A 1K101
/54.6 /54.5
86.1
/W200 /21.3 6K105 3 XB:BB6 1K105A 424 423
LBB START /67.5
86.2
424 423
/68.5
C C
Last Used by: z004mx4y
Time: 10:53:52 AM
205R
Date: 11/28/2022
XB:ZZ 1 K1101
XB:ZZ 2
BUSBAR ZONE-1 TRIP
XB:ZZ 3
BUSBAR ZONE-2 TRIP
K1155
K1153
D D
BUSBAR ZONE-1 TRIP
K3
12 13
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 79
/90.6
E E
14 K2 15
/89.4
BCPU(6MD86)
K101-HV K111A-HV
B /66.4 /66.5 B
6K101BB XB:BB6 14
/W200 /34.7
6K103BB 15
/W200 /34.7
86.1 86.2
6K109BB XB:BB6 20 117 118 K103AHV 117 118 K103BHV X:LV 15 X:HV 8
/W200 /34.7 COMMON
/67.5 /68.5
C C
Last Used by: z004mx4y
Time: 10:54:21 AM
86.1
223 224 18 X:HV 2 TRIP TO LV TC-2
D /67.5 D
/68.5
K2
12 13
/89.4
BCPU(6MD86)
CopyRight (C) Siemens Limited, India All Rights Reserved.
K401-HV K401C-HV
/66.4 /66.5
E E
6K105BB XB:BB6 16
/W200 /34.7
6K107BB 17 K401C-HV
/W200 /34.7
A A
206R NIFPS
87T2(RET670)
K905N K907N
/54.2 /54.3
/47.4 /47.5
87T2(RET670)
K911N K913N
/54.2 /54.3
PRV OPERATED
87T1 (7UT86)
D D
K915N K917N K917N X:NIFPS 8 TS1 19
/47.4 /47.5
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 81
87T2(RET670)
K915N K917N
/54.2 /54.3
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
GC-2
GC-1
SF6 Stage-2 Low, GC.07-Q9 Trip 132kV Side
Grp-A & Grp-B Intertrip To ICT
Q51 M
SF6 Stage-2 Low, GC.08-T35 Trip 132kV Side
Grp-A & Grp-B Intertrip To ICT
P1
SF6 Stage-2 Low, GC.09-F1 Trip 132kV Side
GC-5
CT-T1
Grp-A & Grp-B Intertrip To ICT
P2
SF6 Stage-2 Low, GC.10-BD Trip 132kV Side
C C
Last Used by: z004mx4y
GC-0
Q0
P1
GC-6
CT-T2
P2
SF6 Stage-2 Low, GC.04-BB2 Trip BB Zone-2
Q52
D D
SF6 Stage-2 Low, GC.13-BB2 Trip BB Zone-2
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 82
GC-7
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
GC-8
GC-9
LA
GC-10
GC-11
GC-12
220kV ICT-3
F (BAY-203) Unless otherwise specified, wires are PVC, 1.5mm Sq, GY F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad Zone Trip Philosophy for CRP System for Various Substations W20682
3007687802(T),30071 Sh. 82 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <81 83>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
/33.3
/33.3
K701
K702
A A
X:LCC 157
GC01
.A
X99 X99 158 K706
GC01 R_PH TRIP 11 12
81 253
13 14
X99 X99 /89.2 TO ZONE INTER-TRIP
GC01 Y_PH TRIP 15 16
/90.4 TO BUSBAR ZONE-1 TRIP
82 256 17 18
B /91.5 TO BUSBAR ZONE-2 TRIP B
X99 X99 .B
GC01 B_PH TRIP
83 259 21 22
23 24
/63.5 TO BCPU CIRCUIT
25 26
/92.6 SPARE
27 28
GC02
.A
X99 X99 159 K707
GC02 R_PH TRIP 11 12
C 84 262 C
Last Used by: z004mx4y
13 14
/89.2 TO ZONE INTER-TRIP
Time: 10:55:44 AM
X99 X99 15 16
Date: 11/28/2022
23 24
/63.5 TO BCPU CIRCUIT
25 26
/92.6 SPARE
27 28
D D
GC05
.A
X99 X99 160 K708 11 12
GC05 R_PH TRIP
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 83
87 271
13 14
X99 X99 /89.2 TO ZONE TRIP 86-A/B
15 16
GC05 Y_PH TRIP /89.2 TO ZONE INTER-TRIP
88 274 17 18
/63.5 TO BCPU CIRCUIT
X99 X99 .B
CopyRight (C) Siemens Limited, India All Rights Reserved.
23 24
/90.4 TO BUSBAR ZONE-1 TRIP
E 25 26 E
/91.5 TO BUSBAR ZONE-2 TRIP
27 28
/93.3 SPARE
K701
/84.2
K701
K702
/89.2
/84.7
Refer Drawing No:(3)G71770-AD399-S150-B
Page:RC2,RC3
/83.1
/83.7
K701
A A
K702
GC00
.A
X99 X99 X:LCC 161 K709
GC00 TRIP 11 12
113 114
13 14
/89.2 TO ZONE INTER-TRIP
15 16
/90.4 TO BUSBAR ZONE-1 TRIP
17 18
/91.5 TO BUSBAR ZONE-2 TRIP
.B
21 22
B 23 24 B
/63.5 TO BCPU CIRCUIT
25 26
/93.3 SPARE
27 28
GC06
.A
X99 X99 162 K710
GC06 R_PH TRIP 11 12
90 280
13 14
X99 X99 /89.2 TO ZONE TRIP 86-A/B
15 16
GC06 Y_PH TRIP /89.2 TO ZONE INTER-TRIP
91 283 17 18
/63.5 TO BCPU CIRCUIT
C C
Last Used by: z004mx4y
X99 X99 .B
GC06 B_PH TRIP
Time: 10:56:23 AM
164 K711
Date: 11/28/2022
92 286 21 22
23 24
/93.3 SPARE
25 26
27 28
GC07
.A
X99 X99 163 K712 11 12
GC07 R_PH TRIP
93 289
13 14
D X99 X99 /89.2 TO ZONE TRIP 86-A/B D
15 16
GC07 Y_PH TRIP /89.2 TO ZONE INTER-TRIP
94 292 17 18
/63.5 TO BCPU CIRCUIT
X99 X99
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 84
.B
GC07 B_PH TRIP
95 295 165 K713 21 22
23 24
/93.3 SPARE
25 26
27 28
CopyRight (C) Siemens Limited, India All Rights Reserved.
K701
K702
E E
/85.2
/85.8
Refer Drawing No:(3)G71770-AD399-S150-B
Page:RC4,RC5
/84.2
/84.7
A A
K701
K702
GC08
.A
X99 X99 X:LCC 166 K714
GC08 TRIP 11 12
96 298
13 14
/89.2 TO ZONE TRIP 86-A/B
15 16
/89.2 TO ZONE INTER-TRIP
17 18
/63.5 TO BCPU CIRCUIT
.B
X:LCC 169 K715 21 22
B B
23 24
/93.3 SPARE
25 26
27 28
GC11
.A
X99 X99 167 K716
GC11 R_PH TRIP 11 12
110 326
13 14
X99 X99 /89.2 TO ZONE TRIP 86-A/B
15 16
GC11 Y_PH TRIP /89.2 TO ZONE INTER-TRIP
C 111 327 17 18 C
Last Used by: z004mx4y
X99 X99 .B
Date: 11/28/2022
23 24
/93.3 SPARE
25 26
27 28
GC03
.A
X99 X99 168 K718 11 12
GC03 BB TRIP
102 316
D D
13 14
/89.2 TO ZONE INTER-TRIP
15 16
/90.4 TO BUSBAR ZONE-1 TRIP
17 18
/61.5 TO BCPU CIRCUIT
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 85
.B
171 K719 21 22
23 24
/93.3 SPARE
25 26
CopyRight (C) Siemens Limited, India All Rights Reserved.
27 28
K701
K702
E E
/86.2
/86.7
Refer Drawing No:(3)G71770-AD399-S150-B
Page:RC6,RC7
/85.8
/85.2
K702
K701
A A
GC04
.A
X99 X99 X:LCC 172 K720
GC04 BB TRIP 11 12
103 319
13 14
/89.2 TO ZONE INTER-TRIP
15 16
/91.5 TO BUSBAR ZONE-2 TRIP
17 18
/61.5 TO BCPU CIRCUIT
.B
175 K721 21 22
B 23 24 B
/93.3 SPARE
25 26
27 28
GC09
.A
X99 X99 173 K722
GC09 R_PH TRIP 11 12
104 320
13 14
X99 X99 /89.4 TO ZONE INTER-TRIP
15 16
GC09 Y_PH TRIP /89.2 TO ZONE TRIP 86-A/B
C 105 321 17 18 C
Last Used by: z004mx4y
X99 X99 .B
Date: 11/28/2022
23 24
/93.3 SPARE
25 26
27 28
GC10
.A
X99 X99 174 K724 11 12
GC10 R_PH TRIP
107 323
D D
13 14
X99 X99 /89.4 TO ZONE INTER-TRIP
15 16
GC10 Y_PH TRIP /89.2 TO ZONE TRIP 86-A/B
108 324 17 18
/60.5 TO BCPU CIRCUIT
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 86
X99 X99 .B
GC10 B_PH TRIP
109 325 177 K725 21 22
23 24
/93.5 SPARE
25 26
CopyRight (C) Siemens Limited, India All Rights Reserved.
27 28
K701
E E
/87.2
K702
/87.7
Refer Drawing No:(3)G71770-AD399-S150-B
Page:RC7,RC8
A A
/86.2
/86.7
K701
K702
GC12
.A
X99 X99 178 K726 11 12
329 GC12 R_PH TRIP 120
13 14
X99 X99 /89.2 TO ZONE TRIP 86-A/B
15 16
B GC12 Y_PH TRIP /89.4 TO ZONE INTER-TRIP B
330 121 17 18
/62.5 TO BCPU CIRCUIT
X99 X99 .B
GC12 B_PH TRIP
331 122 179 K727 21 22
23 24
/93.5 SPARE
25 26
27 28
GC13
.A
** ** 180 K728 11 12
GC13 R_PH TRIP
C C
Last Used by: z004mx4y
13 14
/89.4 TO ZONE INTER-TRIP
Time: 10:58:23 AM
** ** 15 16
Date: 11/28/2022
** ** .B
GC13 B_PH TRIP
181 K729 21 22
23 24
/93.5 SPARE
25 26
27 28
D D
GC14
.A
** **
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 87
182 K730 11 12
GC14 R_PH TRIP
13 14
/89.4 TO ZONE INTER-TRIP
** ** /90.4
15 16
TO BUSBAR ZONE-1 TRIP
GC14 Y_PH TRIP
17 18
/64.5 TO BCPU CIRCUIT
CopyRight (C) Siemens Limited, India All Rights Reserved.
E 23 24 E
/93.5 SPARE
25 26
K701
27 28
K702
/88.2
/88.7
Refer Drawing No:(3)G71770-AD399-S150-B
Page:RC8
/87.2
/87.7
A A
K701
K702
GC15
.A
** ** X:LCC 184 K732 11 12
GC15 R_PH TRIP
13 14
/89.4 TO ZONE INTER-TRIP
** ** /91.5
15 16
TO BUSBAR ZONE-2 TRIP
B GC15 Y_PH TRIP B
17 18
/64.5 TO BCPU CIRCUIT
** ** .B
GC15 B_PH TRIP
185 K733 21 22
23 24
/93.5 SPARE
25 26
27 28
C C
Last Used by: z004mx4y
Time: 10:59:10 AM
Date: 11/28/2022
GC16
.A
** ** 186 K734 11 12
GC16 R_PH TRIP
13 14
/89.4 TO ZONE INTER-TRIP
** ** /90.4
15 16
TO BUSBAR ZONE-1 TRIP
GC16 Y_PH TRIP
17 18
/64.5 TO BCPU CIRCUIT
** ** .B
GC16 B_PH TRIP
187 K735 21 22
D D
23 24
/93.5 SPARE
25 26
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 88
27 28
CopyRight (C) Siemens Limited, India All Rights Reserved.
K702
E E
/89.6
NOTE:** TB NUMBERS TO BE IDENTIFIED AT SITE
/83.4
/88.7
K701
K702
A A
GC10
15 .A 16
/86.6 SF6 ZONE TRIP 86-A/B
GC05 K1
13 .A 14 K736 11 21
/83.5
GC06 12 13
/67.3 TO GR-A TRIP
13 .A 14 14 15
/68.4 TO GR-B TRIP
/84.5 16 17
/60.5 TO BCPU
GC07 22 23
/93.3 SPARE
13 .A 14 24 25
/84.5 26 27
B GC08 B
13 .A 14
/85.6
GC11
13 .A 14
/85.6
GC09
15 .A 16
/86.6
GC12
13 .A 14
/87.5
C C
Last Used by: z004mx4y
TO ZONE INTER-TRIP
GC01 K2
Time: 10:59:52 AM
13 .A 14 K737
Date: 11/28/2022
11 21
/83.5
GC02 12 13
/80.4 LV TC-2 TRIP
13 .A 14 14 15
/80.4 LV TC-1 TRIP
/83.5 16 17
/60.5 TO BCPU
GC05 22 23
/52.5 TO 87T2
15 .A 16 24 25
/44.4 TO 87T1
/83.5 26 27
/93.3 SPARE
GC00
13 .A 14
/84.5 GC09
D D
GC06 13 .A 14
15 .A 16 /86.6
/84.5 GC10
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 89
GC07 13 .A 14
15 .A 16 /86.6
/84.5 GC12
GC08 15 .A 16
15 .A 16 /87.5
/85.6 GC13
CopyRight (C) Siemens Limited, India All Rights Reserved.
GC11 13 .A 14
15 .A 16 /87.5
/85.6 GC14
E GC03 13 .A 14 E
13 .A 14 /87.5
/85.6 GC15
GC04 13 .A 14
13 .A 14 /88.5
/86.6 GC16
13 .A 14
/88.5
K701
K702
/90.4
/90.7
/89.2
/89.6
A A
K701
K702
BUSBAR ZONE-1 TRIP
GC03 K3
15 .A 16 K739 11 21
/85.6
GC01
12 13
.A /79.6 TO B/B PANEL
15 16 14 15
/60.5 TO BCPU
/83.5 16 17
/93.3 SPARE
GC14 22 23
.A /92.6 SPARE
15 16 24 25
B /87.5 26 27 B
GC16
.A
15 16
/88.5
GC05
23 .B 24
/83.5
C GC00 C
Last Used by: z004mx4y
15 .A 16
Time: 11:00:27 AM
/84.5
Date: 11/28/2022
GC02
15 .A 16
/83.5
Q1 ISOL CLOSE
P1 P2 56 189
D D
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 90
K702
/91.4
/91.8
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
A A
/90.4
/90.7
K701
K702
BUSBAR ZONE-2 TRIP
GC02 K4
17 .A 18 K740 11 21
/83.5
GC04 12 13
.A /79.6 TO B/B PANEL
15 16 14 15
/60.5 TO BCPU
/86.6 16 17
/93.3 SPARE
GC13 22 23
.A /92.6 SPARE
15 16 24 25
B /87.5 26 27 B
GC15
15 .A 16
/88.5
GC01
17 .A 18
/83.5
GC05
C 25 .B 26 C
Last Used by: z004mx4y
/83.5
Time: 11:00:57 AM
GC00
Date: 11/28/2022
17 .A 18
/84.5
Q2 ISOL CLOSE
P1 P2 88 191
D D
DRG NO: (3)G71770-AD399-S1-B
SHT NO:QD3
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 91
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
A 95.1 A
X:SP 136 U136 26 27 U137 X:SP 137
/67.3
86.1
X:SP 108 U108 225 226 U109 X:SP 109
95.2
/67.5 X:SP 138 U138 26 27 U139 X:SP 139
/68.3
86.1 75.1
X:SP 110 U110 221 222 U111 X:SP 111 X:SP 140 U140 125 225 U141 X:SP 141
/67.5 /70.4
86.2 75.1
X:SP 112 U112 225 226 U113 X:SP 113 X:SP 142 U142 128 228 U143 X:SP 143
/68.5 /70.4
B 75.2 B
X:SP 144 U144 125 225 U145 X:SP 145
86.2
X:SP 114 U114 221 222 U115 X:SP 115 /70.4
/68.5
75.2
X:SP 146 U146 128 228 U147 X:SP 147
80A
X:SP 116 U116 26 27 U117 X:SP 117 /70.4
/33.7
75.3
X:SP 148 U148 125 225 U149 X:SP 149
80B
X:SP 118 U118 26 27 U119 X:SP 119 /71.4
/33.7
75.3
X:SP 150 U150 128 228 U151 X:SP 151
CS52 /71.4
1
TNC 195-R
C X:SP 120 U120 U121 121 X:SP 152 U152 16 17 U153 X:SP 153 C
Last Used by: z004mx4y
1 2
/94.6 /76.4
Time: 11:01:47 AM
CS52
Date: 11/28/2022
195-Y
6 X:SP 154 U154 16 17 U155 X:SP 155
122 U122 TNC U123 123 /76.4
X:SP 11 12 X:SP
/94.6
195-B
X:SP 156 U156 16 17 U157 X:SP 157
52B /76.4
.B
X:SP 124 U124 27 28 U125 X:SP 125
295-R
/69.5 X:SP 158 U158 16 17 U159 X:SP 159
52B /77.4
.B
X:SP 126 U126 25 26 U127 X:SP 127
295-Y
/69.5 X:SP 160 U160 16 17 U161 X:SP 161
D 52B /77.4 D
.B
X:SP 128 U128 23 24 U129 X:SP 129
295-B
/69.5 X:SP 162 U162 16 17 U163 X:SP 163
52A
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 92
/77.4
.B
X:SP 130 U130 23 24 U131 X:SP 131
K3
/69.5 X:SP 164 U164 22 23 U165 X:SP 165
52A /90.6
.B
X:SP 132 U132 25 26 U133 X:SP 133
/69.5
K4
CopyRight (C) Siemens Limited, India All Rights Reserved.
52A
X:SP 166 U166 22 23 U167 X:SP 167
.B
X:SP 134 U134 27 28 U135 X:SP 135 /91.6
/69.5
E GC01 E
.B
X:SP 168 U168 25 26 U169 X:SP 169
/83.5
GC02
.B
X:SP 170 U170 25 26 U171 X:SP 171
/83.5
GC05 GC10
.B .B
X:SP 172 U172 27 28 U173 X:SP 173 X:SP 206 U206 23 24 U207 X:SP 207
A A
/83.5 /86.6
GC00 GC12
.B .B
X:SP 174 U174 25 26 U175 X:SP 175 X:SP 208 U208 23 24 U209 X:SP 209
/84.5 /87.5
GC06 GC13
.B .B
X:SP 176 U176 23 24 U177 X:SP 177 X:SP 210 U210 23 24 U211 X:SP 211
/84.5 /87.5
GC07 GC14
.B .B
X:SP 178 U178 23 24 U179 X:SP 179 X:SP 212 U212 23 24 U213 X:SP 213
B /84.5 /87.5 B
GC08 GC15
.B .B
X:SP 180 U180 23 24 U181 X:SP 181 X:SP 214 U214 23 24 U215 X:SP 215
/85.6 /88.5
GC11
.B GC16
X:SP 182 U182 23 24 U183 X:SP 183
.B
/85.6 X:SP 216 U216 23 24 U217 X:SP 217
/88.5
GC03
X:SP 184 U184 23 .B 24 U185 X:SP 185
/85.6
C GC04 C
Last Used by: z004mx4y
/86.6
Date: 11/28/2022
D K4 D
X:SP 194 U194 16 17 U195 X:SP 195
/91.6
DCC01
X:SP 198 U198 225 226 U199 X:SP 199
/32.4
CopyRight (C) Siemens Limited, India All Rights Reserved.
GC09
.B
X:SP 204 U204 23 24 U205 X:SP 205
/86.6
A A
B 206R B
CS52
TNC
CFLS PB86.1 1 2
/92.3
13 14 15 25
3 4
21 22 16 26 /62.5
/31.4 /67.3
17 27 5 6
/69.3
18 28
7 8
C C
Last Used by: z004mx4y
9 10
Time: 11:03:22 AM
PB86.2
Date: 11/28/2022
11 12
15 25 /92.3
16 26 13 14
/68.4 /63.5
17 27
15 16
18 28
17 18
19 20
D D
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 94
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
A A
C C
Last Used by: z004mx4y
Time: 11:03:49 AM
Date: 11/28/2022
D D
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 95
87T2(RET670)
PRODUCT CODE LONG :
CopyRight (C) Siemens Limited, India All Rights Reserved.
RET670*2.2-F00X00-A00001030300000010-B00000000000000000000000000-
C330033330013003322102000000-D33322010-T0000-E033300-F3-S0-G322-H03000000222-K00000000-
E L1100-M03100330-P000000000000000000-B1X0-CE-CB-B-B3B6-CD1AD1RX-KXXXXXXXXXXXXX E
B B
1PE
1PE
1PE
BCPU(6MD86) /56.7 /64.3
1IL
*
*
C C
Last Used by: z004mx4y
Time: 11:04:21 AM
Date: 11/28/2022
1A1
1A2
1A3
1A4
1A5
1A6
1A7
1A8
BCPU(6MD86) /55.6 /55.6 /55.6 /55.6
1UL
1B1
1B2
1B3
1B4
1B5
1B6
1B7
1B8
*
1BI
1C13
1C14
1D10
1D13
1D11
1D14
1D12
1D1
1D2
1D5
1D3
1D6
1D4
1D7
1D9
1D8
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
1C1
1C4
1C6
1C8
1B10
1B12
1B13
1C10
1BO
F
1B11 F
1B14 F
F
1C2
1C3
1C7
1B9
A A
Pin CB202
LC
Ethernet
+
-
2PS
2B7
2B9
2B10
2B2
2B1
E CH1 E CH2 G H J K
B BCPU(6MD86) /56.7 /78.4 B
BI 2.1 BI 2.2 BI 2.3
*
2BI 2B12
2B14
2B13
2B11
BCPU(6MD86) /56.7 /56.7 /56.7
BO 2.1 BO 2.2
C C
Last Used by: z004mx4y
2B4
2B6
2B8
2BO
Time: 11:05:12 AM
Date: 11/28/2022
S
2B3
2B5
D D
3PE
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 97
3PE
3PE
BI 3.1 BI 3.2 BI 3.3 BI 3.4 BI 3.5 BI 3.6 BI 3.7 BI 3.8 BI 3.9 BI 3.10 BI 3.11 BI 3.12
CopyRight (C) Siemens Limited, India All Rights Reserved.
*
3BI
E E
3A11
3A10
3A12
3A13
3A14
3B10
3A1
3A3
3A2
3A4
3A7
3A5
3A8
3A6
3A9
3B1
3B2
3B3
3B5
3B4
3B6
3B9
3B7
3B8
BCPU(6MD86) /56.7 /56.7 /56.7 /56.7 /56.7 /56.7 /57.7 /57.7 /57.7 /57.7 /57.7 /57.7
BO 3.1 BO 3.2 BO 3.3 BO 3.4 BO 3.5 BO 3.6 BO 3.7 BO 3.8 BO 3.9 BO 3.10 BO 3.11 BO 3.12 BO 3.13 BO 3.14 BO 3.15 BO 3.16
3C2
3C4
3C6
3C8
3D2
3D4
3D6
3D8
3B12
3B14
3C10
3C12
3C14
3D10
3D12
3D14
3BO
3B11 S
3B13 S
3C11 S
3C13 S
3D11 S
3D13 S
3C1
3C3
3C5
3C7
3C9
3D1
3D3
3D5
3D7
3D9
BCPU(6MD86) /65.6 /66.4 /66.4 /66.4 /66.4 /66.4 /66.4 /66.4 /66.4 /66.4 /66.4 /66.4 /66.4 /66.4 /66.4 /66.4
F Unless otherwise specified, wires are PVC 1.5 GY F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad Connection Diagram BCPU System for Various Substations W20697
3007687802(T),30071 Sh. 97 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <96 98>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Designation : Input and Output Module IO230
DB Version: SL-V 1.1-08/01/2019
E-Base Version: 7.1.0.1305
A A
4PE
4PE
4PE
BCPU(6MD86) /64.3 /64.3
+
4BI 1-8
B B
4A10
4A1
4A2
4A3
4A4
4A7
4A8
4A9
4A5
4A6
BCPU(6MD86) /57.7 /57.7 /57.7 /57.7 /57.7 /57.7 /57.7 /57.7 /57.7
4BI 9-16
4C10
4C1
4C2
4C3
4C4
4C7
4C8
4C9
4C5
4C6
C C
Last Used by: z004mx4y
BCPU(6MD86) /57.7 /57.7 /57.7 /57.7 /58.7 /58.7 /58.7 /58.7 /58.7
Time: 11:06:06 AM
Date: 11/28/2022
+
4BI 17-24
4D10
4D1
4D2
4D3
4D4
4D7
4D8
4D9
4D5
4D6
BCPU(6MD86) /58.7 /58.7 /58.7 /58.7 /58.7 /58.7 /58.7 /58.7 /58.7
+
4BI 25-32
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 98
4E10
4E1
4E2
4E3
4E4
4E7
4E8
4E9
4E5
4E6
BCPU(6MD86) /58.7 /58.7 /58.7 /58.7 /59.7 /59.7 /59.7 /59.7 /59.7
4BI 33-40
E E
4G10
4G1
4G2
4G3
4G4
4G7
4G8
4G9
4G5
4G6
BCPU(6MD86) /59.7 /59.7 /59.7 /59.7 /59.7 /59.7 /59.7 /59.7 /59.7
4BI 41-48
4H10
4H1
4H2
4H3
4H4
4H7
4H8
4H9
4H5
4H6
BCPU(6MD86) /59.7 /59.7 /59.7 /59.7 /60.6 /60.6 /60.6 /60.6 /60.7
F Unless otherwise specified, wires are PVC, 1.5mm Sq, GY F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad Connection Diagram BCPU System for Various Substations W20698
3007687802(T),30071 Sh. 98 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <97 99>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Designation : Input and Output Module IO230
DB Version: SL-V 1.1-08/01/2019
E-Base Version: 7.1.0.1305
A A
5PE
5PE
5PE
BCPU(6MD86) /64.3 /64.3
+
5BI 1-8
B B
5A10
5A1
5A2
5A3
5A4
5A7
5A8
5A9
5A5
5A6
BCPU(6MD86) /60.6 /60.6 /60.6 /60.6 /60.6 /60.6 /60.6 /60.6 /60.7
5BI 9-16
5C10
5C1
5C2
5C3
5C4
5C7
5C8
5C9
5C5
5C6
C C
Last Used by: z004mx4y
BCPU(6MD86) /60.6 /60.6 /60.6 /60.6 /61.7 /61.7 /61.7 /61.7 /61.7
Time: 11:06:55 AM
Date: 11/28/2022
+
5BI 17-24
5D10
5D1
5D2
5D3
5D4
5D7
5D8
5D9
5D5
5D6
BCPU(6MD86) /61.7 /61.7 /61.7 /61.7 /61.7 /61.7 /61.7 /61.7 /61.7
+
5BI 25-32
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 99
5E10
5E1
5E2
5E3
5E4
5E7
5E8
5E9
5E5
5E6
BCPU(6MD86) /61.7 /61.7 /61.7 /61.7 /62.7 /62.7 /62.7 /62.7 /62.7
5BI 33-40
E E
5G10
5G1
5G2
5G3
5G4
5G7
5G8
5G9
5G5
5G6
BCPU(6MD86) /62.7 /62.7 /62.7 /62.7 /62.7 /62.7 /62.7 /62.7 /62.7
5BI 41-48
5H10
5H1
5H2
5H3
5H4
5H7
5H8
5H9
5H5
5H6
BCPU(6MD86) /62.7 /62.7 /62.7 /62.7 /63.7 /63.7 /63.7 /63.7 /63.7
F Unless otherwise specified, wires are PVC, 1.5mm Sq, GY F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad Connection Diagram BCPU System for Various Substations W20699
3007687802(T),30071 Sh. 99 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <98 100>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Designation : Input and Output Module IO231
DB Version: SL-V 1.1-08/01/2019
E-Base Version: 7.1.0.1305
A A
6PE
6PE
6PE
BCPU(6MD86) /64.3 /64.3
6A10
6A1
6A2
6A3
6A4
6A7
6A8
6A9
6A5
6A6
BCPU(6MD86) /63.7 /63.7 /63.7 /63.7 /63.7 /63.7 /63.7 /63.7 /63.7
6C10
6C1
6C2
6C3
6C4
6C7
6C8
6C9
6C5
6C6
C C
Last Used by: z004mx4y
BCPU(6MD86) /63.7 /63.7 /63.7 /63.7 /64.7 /64.7 /64.7 /64.7 /64.7
Time: 11:07:45 AM
Date: 11/28/2022
6D10
6D1
6D2
6D3
6D4
6D7
6D8
6D9
6D5
6D6
BCPU(6MD86) /64.7 /64.7 /64.7 /64.7 /64.7 /64.7 /64.7 /64.7 /64.7
6E10 S
6E1
6E2
6E3
6E4
6E7
6E8
6E9
6E5
6E6
BCPU(6MD86) /65.2 /65.2 /65.2 /65.2 /65.2 /65.2 /65.2 /65.2 /65.2
E E
6G1 S
6G2 S
6G3 S
6G4 S
6G7 S
6G8 S
6G9 S
6G10 S
6G5
6G6
BCPU(6MD86) /65.2 /65.2 /65.2 /65.2 /65.2 /65.2 /65.2 /65.2 /65.2
6H10 S
6H1
6H2
6H3
6H4
6H7
6H8
6H9
6H5
6H6
BCPU(6MD86) /65.6 /65.6 /65.6 /65.6 /65.6 /65.6 /65.6 /65.6 /65.6
F Unless otherwise specified, wires are PVC, 1.5mm Sq, GY F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad Connection Diagram BCPU System for Various Substations W206100
3007687802(T),30071 Sh. 100 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <99 101>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Designation : Case Size: 1/1 19", 12xI, 8xV, 119 BI, 12 BO, 1 Live Status, 32 LED, Flush Mounting Technical Specifications
DB Version: SL-V 1.1-08/01/2019
E-Base Version: 7.1.0.1305
B B
1PE
1PE
1PE
87T1 (7UT86) /39.7 /38.8
1IL
*
*
C C
Last Used by: z004mx4y
Time: 11:08:26 AM
Date: 11/28/2022
1A1
1A2
1A3
1A4
1A5
1A6
1A7
1A8
1B1
1B2
1B3
1B4
1B5
1B6
1B7
1B8
87T1 (7UT86) /37.5 /37.5 /37.5 /37.5 /37.5 /37.5 /37.5 /37.5
1BI *
1D13
1D11
1D10
1D14
1D12
1D9
1D1
1D3
1D5
1D7
1BO
F
F
1D2
1D4
1D6
1D8
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
A A
Pin CB202
LC F CH1 F CH2 F CH3 F CH4
Ethernet
+
-
2PS
2B7
2B9
2B10
2B2
2B1
2F1
2F2
2F3
2F4
2F5
2F6
2F7
2F8
E CH1 E CH2 G H J K
B 87T1 (7UT86) /39.7 /78.4 /48.6 /48.6 /48.6 /48.6 B
BI 2.1 BI 2.2 BI 2.3
*
2BI 2B12
2B14
2B13
2B11
87T1 (7UT86) /39.7 /39.7 /39.7
BO 2.1 BO 2.2
C C
Last Used by: z004mx4y
2B4
2B6
2B8
2BO
Time: 11:09:05 AM
Date: 11/28/2022
S
2B3
2B5
D D
3PE
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 102
3PE
3PE
3IL
*
E E
3A1
3A2
3A3
3A4
3A5
3A6
3A7
3A8
3BI
3C13
3C14
3D10
3D13
3D11
3D14
3D12
3D1
3D2
3D5
3D3
3D6
3D4
3D7
3D9
3D8
87T1 (7UT86) /39.7 /39.7 /39.7 /39.7 /39.7 /39.7 /39.7 /39.7
F Unless otherwise specified, wires are PVC 1.5 GY F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad Connection Diagram 87T1 System for Various Substations W206102
3007687802(T),30071 Sh. 102 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <101 103>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
3C1
3C4
3C6
3C8
3B10
3B12
3B13
3C10
3BO
A A
3B11 F
3B14 F
F
3C2
3C3
3C7
3B9
87T1 (7UT86) /47.4 /47.4 /47.4 /47.4 /47.4 /47.4
Designation : Input and Output Module IO211
4:IO211 Type : Part of 7UT86
Manufacturer : Siemens
Add. Info. 1 : 8 x Voltage Transformer
87T1 (7UT86) Add. Info. 2 : 8 x Binary Inputs DC 24 - 250V
4PE
B B
4PE
4PE
87T1 (7UT86) /38.8 /38.8
*
4BI
4C13
4C14
4D10
4D13
4D11
4D14
4D12
4D1
4D2
4D5
4D3
4D6
4D4
4D7
4D9
4D8
C C
Last Used by: z004mx4y
87T1 (7UT86) /39.7 /39.7 /39.7 /40.7 /40.7 /40.7 /40.7 /40.7
Time: 11:09:52 AM
Date: 11/28/2022
4UL
4A11
4A12
4A13
4A14
4C1
4C2
4C3
4C4
4A1
4A2
4A3
4A4
4A5
4A6
4A7
4A8
87T1 (7UT86) /38.6 /38.6 /38.6 /38.6 /38.6 /38.6 /38.6 /38.6
D D
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 103
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
A A
5PE
5PE
5PE
87T1 (7UT86) /38.8 /38.8
+
5BI 1-8
B B
5A10
5A1
5A2
5A3
5A4
5A7
5A8
5A9
5A5
5A6
87T1 (7UT86) /40.7 /40.7 /40.7 /40.7 /40.7 /40.7 /40.7 /40.7 /40.7
5BI 9-16
5C10
5C1
5C2
5C3
5C4
5C7
5C8
5C9
5C5
5C6
C C
Last Used by: z004mx4y
87T1 (7UT86) /41.6 /41.6 /41.6 /41.6 /41.6 /41.6 /41.6 /41.6 /41.6
Time: 11:10:37 AM
Date: 11/28/2022
+
5BI 17-24
5D10
5D1
5D2
5D3
5D4
5D7
5D8
5D9
5D5
5D6
87T1 (7UT86) /42.6 /42.6 /42.6 /42.6 /42.6 /42.6 /42.6 /42.6 /42.7
+
5BI 25-32
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 104
5E10
5E1
5E2
5E3
5E4
5E7
5E8
5E9
5E5
5E6
87T1 (7UT86) /42.6 /42.6 /42.6 /42.6 /42.6 /42.6 /42.6 /42.6 /42.7
5BI 33-40
E E
5G10
5G1
5G2
5G3
5G4
5G7
5G8
5G9
5G5
5G6
87T1 (7UT86) /43.6 /43.6 /43.6 /43.6 /43.6 /43.6 /43.6 /43.6 /43.7
5BI 41-48
5H10
5H1
5H2
5H3
5H4
5H7
5H8
5H9
5H5
5H6
87T1 (7UT86) /43.6 /43.6 /43.6 /43.6 /43.6 /43.6 /43.6 /43.6 /43.7
F Unless otherwise specified, wires are PVC, 1.5mm Sq, GY F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad Connection Diagram 87T1 System for Various Substations W206104
3007687802(T),30071 Sh. 104 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <103 105>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Designation : Input and Output Module IO230
DB Version: SL-V 1.1-08/01/2019
E-Base Version: 7.1.0.1305
A A
6PE
6PE
6PE
87T1 (7UT86) /38.8 /38.8
+
6BI 1-8
B B
6A10
6A1
6A2
6A3
6A4
6A7
6A8
6A9
6A5
6A6
87T1 (7UT86) /44.6 /44.6 /44.6 /44.6 /44.6 /44.6 /44.6 /44.6 /44.7
6BI 9-16
6C10
6C1
6C2
6C3
6C4
6C7
6C8
6C9
6C5
6C6
C C
Last Used by: z004mx4y
87T1 (7UT86) /44.6 /44.6 /44.6 /44.6 /44.6 /44.6 /44.6 /44.6 /44.7
Time: 11:11:26 AM
Date: 11/28/2022
+
6BI 17-24
6D10
6D1
6D2
6D3
6D4
6D7
6D8
6D9
6D5
6D6
87T1 (7UT86) /45.6 /45.6 /45.6 /45.6 /45.6 /45.6 /45.6 /45.6 /45.6
+
6BI 25-32
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 105
6E10
6E1
6E2
6E3
6E4
6E7
6E8
6E9
6E5
6E6
87T1 (7UT86) /45.6 /45.6 /45.6 /45.6 /45.6 /45.6 /45.6 /45.6 /45.6
6BI 33-40
E E
6G10
6G1
6G2
6G3
6G4
6G7
6G8
6G9
6G5
6G6
87T1 (7UT86) /46.6 /46.6 /46.6 /46.6 /46.6 /46.6 /46.6 /46.6 /46.6
6BI 41-48
6H10
6H1
6H2
6H3
6H4
6H7
6H8
6H9
6H5
6H6
87T1 (7UT86) /46.6 /46.6 /46.6 /46.6 /46.6 /46.6 /46.6 /46.6 /46.6
F Unless otherwise specified, wires are PVC, 1.5mm Sq, GY F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad Connection Diagram 87T1 System for Various Substations W206105
3007687802(T),30071 Sh. 105 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <104 106>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Designation : Case Size: 3/4 19", 9xI, 3xV, 32 BI, 24 BO, 1 Watchdog Contact, 15 LED, Flush Mounting Technical Specifications:
DB Version: SL-V 1.1-08/01/2019
E-Base Version: 7.1.0.1305
Time Synchronization
System Interface
B B
-
X11:4
X11:5
X11:3
X11:1
X11:2
PE
B
/51.7 /50.6 /78.4
A101 (I)-1 A102 (I)-1 A103 (I)-1 A104 (I)-1 A105 (I)-1 A106 (I)-1 A107 (I)-1 A108 (I)-1 A109 (I)-1
Current Inputs
•
•
X401:14
X401:10
X401:12
X401:13
X401:15
X401:16
X401:17
X401:18
X401:11
X401:4
X401:2
X401:3
X401:5
X401:6
X401:7
X401:8
X401:9
X401:1
C C
Last Used by: z004mx4y
Time: 11:12:12 AM
87T2(RET670) /49.5 /49.5 /49.5 /49.5 /49.5 /49.5 /49.5 /49.5 /49.5
Date: 11/28/2022
Voltage Inputs
•
•
X401:24
X401:20
X401:22
X401:23
X401:19
X401:21
D BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 BI14 BI15 BI16 D
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 106
Input 1-16
X32:14
X32:10
X32:12
X32:13
X32:15
X32:16
X31:14
X32:11
X31:10
X31:12
X31:13
X31:15
X31:16
X32:4
X31:11
X32:2
X32:3
X32:5
X32:6
X32:7
X32:8
X32:9
X31:4
X32:1
X31:2
X31:3
X31:5
X31:6
X31:7
X31:8
X31:9
X31:1
87T2(RET670) /51.7 /51.7 /51.7 /51.7 /51.7 /51.7 /51.7 /51.7 /51.7 /51.7 /51.7 /51.7 /51.7 /51.7 /51.7 /51.7
CopyRight (C) Siemens Limited, India All Rights Reserved.
BI17 BI18 BI19 BI20 BI21 BI22 BI23 BI24 BI25 BI26 BI27 BI28 BI29 BI30 BI31 BI32
Input 17-32
E E
X52:14
X52:10
X52:12
X52:13
X52:15
X52:16
X51:14
X52:11
X51:10
X51:12
X51:13
X51:15
X51:16
X52:4
X51:11
X52:2
X52:3
X52:5
X52:6
X52:7
X52:8
X52:9
X51:4
X52:1
X51:2
X51:3
X51:5
X51:6
X51:7
X51:8
X51:9
X51:1
87T2(RET670) /51.7 /51.7 /52.7 /52.7 /52.7 /52.7 /52.7 /52.7 /52.7 /52.7 /52.7 /52.7 /52.7 /52.7 /52.7 /52.7
A A
BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12
Output 1-12
X41:14
X41:10
X41:12
X41:13
X41:15
X41:16
X41:18
X41:17
X41:11
X41:4
X41:3
X41:2
X41:6
X41:5
X41:7
X41:9
X41:8
X41:1
B B
87T2(RET670) /54.2 /54.3 /54.2 /54.3 /54.2 /54.3 /54.2 /54.3 /54.2 /54.3 /54.2 /54.3
BO13 BO14 BO15 BO16 BO17 BO18 BO19 BO20 BO21 BO22 BO23 BO24
Output 13-24
X42:14
X42:10
X42:12
X42:13
X42:15
X42:16
X42:18
X42:17
X42:11
X42:4
X42:3
X42:2
X42:6
X42:5
X42:7
X42:9
X42:8
X42:1
87T2(RET670) /54.2 /54.3 /54.2 /54.3 /54.5 /54.5 /54.5 /54.5 /54.5 /54.5 /54.5 /54.5
C C
Last Used by: z004mx4y
Time: 11:12:51 AM
Date: 11/28/2022
D D
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 107
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
87T1 (7UT86) BI 3.2 /W206/39.7 87T1 (7UT86) BI 5.6 /W206/40.7 87T1 (7UT86) BI 5.26 /W206/42.6
Date: 11/28/2022
Overload Alarm
E E
Pump-3 Thermal SPARE Oil Flow Indicator-4_Trip-2
87T1 (7UT86) BI 4.2 /W206/39.7 87T1 (7UT86) BI 5.14 /W206/41.6 87T1 (7UT86) BI 5.34 /W206/43.6
Overload Alarm
F F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad BI/BO Table System for Various Substations W206108
3007687802(T),30071 Sh. 108 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <107 109>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
BREATHER ERROR
PRV-CB-2_Trip-1 CONTROL SUPPLY FAIL
87T1 (7UT86) BI 5.39 /W206/43.6 87T1 (7UT86) BI 6.11 /W206/44.6 87T1 (7UT86) BI 6.31 /W206/45.6
BREATHER HEATER ON
SPARE DM MOTOR TRIP / SUPPLY OFF
87T1 (7UT86) BI 5.40 /W206/43.6 87T1 (7UT86) BI 6.12 /W206/44.6 87T1 (7UT86) BI 6.32 /W206/45.6
87T1 (7UT86) BI 5.46 /W206/43.6 87T1 (7UT86) BI 6.18 /W206/45.6 87T1 (7UT86) BI 6.38 /W206/46.6
Date: 11/28/2022
D D
RPRR Cable Box-1_Trip PRV-OLTC-3_Trip-1 SPARE
87T1 (7UT86) BI 6.2 /W206/44.6 87T1 (7UT86) BI 6.22 /W206/45.6 87T1 (7UT86) BI 6.42 /W206/46.6
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 109
E E
SF6 ZONE INTER TRIP LOWER LIMIT REACHED SPARE
87T1 (7UT86) BI 6.6 /W206/44.6 87T1 (7UT86) BI 6.26 /W206/45.6 87T1 (7UT86) BI 6.46 /W206/46.6
(BELOW CB )
F F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad BI/BO Table System for Various Substations W206109
3007687802(T),30071 Sh. 109 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <108 110>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Design. BI/BO Comments Sheet Ref. Design. BI/BO Comments Sheet Ref. Design. BI/BO Comments Sheet Ref.
A A
To ANN BC Panel
87T1 (7UT86) BO 2.1 /W206/47.4
OLTC Non Trip Alram
B B
TO NIFPS
87T1 (7UT86) BO 2.2 /W206/47.4
DIFF.PROTN.TRIP
TO NIFPS
87T1 (7UT86) BO 3.1 /W206/47.4
BUCHHOLZ TRIP
TO NIFPS
87T1 (7UT86) BO 3.2 /W206/47.4
PRV TRIP
LBB INITIATION
87T1 (7UT86) BO 3.3 /W206/47.4
C C
Last Used by: z004mx4y
D D
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 110
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
F F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad BI/BO Table System for Various Substations W206110
3007687802(T),30071 Sh. 110 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <109 111>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
D D
PRV_2 TRIP -2 Spare Spare
87T2(RET670) BI13 /W206/51.7 87T2(RET670) BO1 /W206/54.2 87T2(RET670) BO21 /W206/54.5
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 111
E E
PRV-CB-2_Trip-2 Spare Spare
87T2(RET670) BI17 /W206/51.7 87T2(RET670) BO5 /W206/54.2 87T2(RET670) MI:01 /W206/53.5
F F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad BI/BO Table System for Various Substations W206111
3007687802(T),30071 Sh. 111 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <110 112>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Spare
87T2(RET670) MI:05 /W206/53.5
Spare
87T2(RET670) MI:06 /W206/53.5
B B
C C
Last Used by: z004mx4y
Time: 11:14:53 AM
Date: 11/28/2022
D D
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 112
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
F F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad BI/BO Table System for Various Substations W206112
3007687802(T),30071 Sh. 112 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <111 113>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
CIRCUIT BREAKER Q0 B-PH OPEN Isolating Link Q61 Close Gas Comp. 01 (Q1 pole C)
BCPU(6MD86) BI 1.1 /W206/56.7 BCPU(6MD86) BI 3.10 /W206/57.7 BCPU(6MD86) BI 4.18 /W206/58.7
Min. SF6 density
CIRCUIT BREAKER Q0 B-PH CLOSE Isolating Link Q62 Open Gas Comp. 02 (Q2 pole A)
BCPU(6MD86) BI 1.2 /W206/56.7 BCPU(6MD86) BI 3.11 /W206/57.7 BCPU(6MD86) BI 4.19 /W206/58.7
Loss of SF6
CIRCUIT BREAKER Q0 Y-PH OPEN Isolating Link Q62 Close Gas Comp. 02 (Q2 pole A)
BCPU(6MD86) BI 1.3 /W206/56.7 BCPU(6MD86) BI 3.12 /W206/57.7 BCPU(6MD86) BI 4.20 /W206/58.7
Min. SF6 density
CIRCUIT BREAKER Q0 Y-PH CLOSE Selector Switch In Remote Alarm Signalling Voltage MCB Operated
BCPU(6MD86) BI 1.4 /W206/56.7 BCPU(6MD86) BI 4.1 /W206/57.7 BCPU(6MD86) BI 4.21 /W206/58.7
B B
CIRCUIT BREAKER Q0 R-PH OPEN Selector Switch In Local Live Contact-H501
BCPU(6MD86) BI 1.5 /W206/56.7 BCPU(6MD86) BI 4.2 /W206/57.7 BCPU(6MD86) BI 4.22 /W206/58.7
CIRCUIT BREAKER Q0 R-PH CLOSE Master Interlock Override Gas Comp. 02 (Q2 pole B)
BCPU(6MD86) BI 1.6 /W206/56.7 BCPU(6MD86) BI 4.3 /W206/57.7 BCPU(6MD86) BI 4.23 /W206/58.7
Loss of SF6
BB DISCONNECTOR Q1 OPEN GC-09 GD1 GAS ZONE TRIP Gas Comp. 02 (Q2 pole B)
BCPU(6MD86) BI 1.7 /W206/56.7 BCPU(6MD86) BI 4.4 /W206/57.7 BCPU(6MD86) BI 4.24 /W206/58.7
Min. SF6 density
BB DISCONNECTOR Q1 CLOSE Hand Crank Cover Open Gas Comp. 02 (Q2 pole C)
BCPU(6MD86) BI 1.8 /W206/56.7 BCPU(6MD86) BI 4.5 /W206/57.7 BCPU(6MD86) BI 4.25 /W206/58.7
Loss of SF6
C C
Last Used by: z004mx4y
MAINTENANCE ESW Q51 OPEN CB loss of SF6 Pole A Gas Comp. 03 (BB1)
BCPU(6MD86) BI 2.3 /W206/56.7 BCPU(6MD86) BI 4.8 /W206/57.7 BCPU(6MD86) BI 4.28 /W206/58.7
Min. SF6 density
MAINTENANCE ESW Q51 CLOSE CB loss of SF6 Pole B Gas Comp. 04 (BB2)
BCPU(6MD86) BI 3.1 /W206/56.7 BCPU(6MD86) BI 4.9 /W206/57.7 BCPU(6MD86) BI 4.29 /W206/59.7
Loss of SF6
D D
MAINTENANCE ESW Q52 OPEN CB loss of SF6 Pole C Gas Comp. 04 (BB2)
BCPU(6MD86) BI 3.2 /W206/56.7 BCPU(6MD86) BI 4.10 /W206/57.7 BCPU(6MD86) BI 4.30 /W206/59.7
Min. SF6 density
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 113
MAINTENANCE ESW Q52 CLOSE Motor Running Time Supervision Gas Comp. 05 (T1 pole A)
BCPU(6MD86) BI 3.3 /W206/56.7 BCPU(6MD86) BI 4.11 /W206/57.7 BCPU(6MD86) BI 4.31 /W206/59.7
Loss of SF6
LINE DISCONNECTOR Q9 OPEN Pole Discrepancy Tripping Gas Comp. 05 (T1 pole A)
BCPU(6MD86) BI 3.4 /W206/56.7 BCPU(6MD86) BI 4.12 /W206/57.7 BCPU(6MD86) BI 4.32 /W206/59.7
Min. SF6 density
CopyRight (C) Siemens Limited, India All Rights Reserved.
LINE DISCONNECTOR Q9 CLOSE Gas Comp. 01 (Q1 pole A) Gas Comp. 05 (T1 pole B)
BCPU(6MD86) BI 3.5 /W206/56.7 BCPU(6MD86) BI 4.13 /W206/58.7 BCPU(6MD86) BI 4.33 /W206/59.7
Loss of SF6 Loss of SF6
E E
HIGH SPEED ESW Q8 OPEN Gas Comp. 01 (Q1 pole A) Gas Comp. 05 (T1 pole B)
BCPU(6MD86) BI 3.6 /W206/56.7 BCPU(6MD86) BI 4.14 /W206/58.7 BCPU(6MD86) BI 4.34 /W206/59.7
Min. SF6 density Min. SF6 density
HIGH SPEED ESW Q8 CLOSE Gas Comp. 01 (Q1 pole B) Gas Comp. 05 (T1 pole C)
BCPU(6MD86) BI 3.7 /W206/57.7 BCPU(6MD86) BI 4.15 /W206/58.7 BCPU(6MD86) BI 4.35 /W206/59.7
Loss of SF6 Loss of SF6
Circuit Breaker Q0 CB Spring Charged Gas Comp. 01 (Q1 pole B) Gas Comp. 05 (T1 pole C)
BCPU(6MD86) BI 3.8 /W206/57.7 BCPU(6MD86) BI 4.16 /W206/58.7 BCPU(6MD86) BI 4.36 /W206/59.7
Min. SF6 density Min. SF6 density
Isolating Link Q61 Open Gas Comp. 01 (Q1 pole C) Gas Comp. 06 (T2 pole A)
BCPU(6MD86) BI 3.9 /W206/57.7 BCPU(6MD86) BI 4.17 /W206/58.7 BCPU(6MD86) BI 4.37 /W206/59.7
Loss of SF6 Loss of SF6
F F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad BI/BO Table System for Various Substations W206113
3007687802(T),30071 Sh. 113 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <112 114>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Design. BI/BO Comments Sheet Ref. Design. BI/BO Comments Sheet Ref. Design. BI/BO Comments Sheet Ref.
A A
Gas Comp. 06 (T2 pole A) Gas Comp. 09 (F1 pole B) VT MCB tripped
BCPU(6MD86) BI 4.38 /W206/59.7 BCPU(6MD86) BI 5.10 /W206/60.6 BCPU(6MD86) BI 5.30 /W206/62.7
Min. SF6 density Loss of SF6
Gas Comp. 06 (T2 pole B) Live Contact-H502 CRP AC MCB FAIL / LCC AC FAIL
BCPU(6MD86) BI 4.40 /W206/59.7 BCPU(6MD86) BI 5.12 /W206/60.6 BCPU(6MD86) BI 5.32 /W206/62.7
Min. SF6 density AC MCB TRIP
Gas Comp. 06 (T2 pole C) Gas Comp. 09 (F1 pole C) DC MCB tripped
BCPU(6MD86) BI 4.41 /W206/59.7 BCPU(6MD86) BI 5.13 /W206/61.7 BCPU(6MD86) BI 5.33 /W206/62.7
Loss of SF6 Loss of SF6 DC-1 / DC-2 Fail
B B
Gas Comp. 06 (T2 pole C) Gas Comp. 09 (F1 pole C) SPARE
BCPU(6MD86) BI 4.42 /W206/59.7 BCPU(6MD86) BI 5.14 /W206/61.7 BCPU(6MD86) BI 5.34 /W206/62.7
Min. SF6 density Min. SF6 density
Gas Comp. 07 (IC pole A) Gas comp. 10 (BD_L1) 86.1 TRIP RELAY OPTD.
BCPU(6MD86) BI 4.44 /W206/59.7 BCPU(6MD86) BI 5.16 /W206/61.7 BCPU(6MD86) BI 5.36 /W206/62.7
Min. SF6 density Min. SF6 density
Gas Comp. 07 (IC pole B) Gas comp. 10 (BD_L2) 86.2 TRIP RELAY OPTD.
BCPU(6MD86) BI 4.45 /W206/60.6 BCPU(6MD86) BI 5.17 /W206/61.7 BCPU(6MD86) BI 5.37 /W206/62.7
Loss of SF6 Loss of SF6
C C
Last Used by: z004mx4y
Gas Comp. 07 (IC pole C) Gas comp. 10 (BD_L3) 96 TRIP RELAY OPTD.
BCPU(6MD86) BI 4.47 /W206/60.6 BCPU(6MD86) BI 5.19 /W206/61.7 BCPU(6MD86) BI 5.39 /W206/62.7
Loss of SF6 Loss of SF6
Gas Comp. 07 (IC pole C) Gas comp. 10 (BD_L3) GC-12 GD2 GAS ZONE TRIP
BCPU(6MD86) BI 4.48 /W206/60.6 BCPU(6MD86) BI 5.20 /W206/61.7 BCPU(6MD86) BI 5.40 /W206/62.7
Min. SF6 density Min. SF6 density
BB Z1 OPTD DUE TO GAS ZONE TRIP(DR) Gas comp. 11 (Z2_L1) 86.1 RELAY UNHEALTHY
BCPU(6MD86) BI 5.1 /W206/60.6 BCPU(6MD86) BI 5.21 /W206/61.7 BCPU(6MD86) BI 5.41 /W206/62.7
Loss of SF6
D D
BB Z2 OPTD DUE TO GAS ZONE TRIP(DR) Gas comp. 11 (Z2_L1) 86.2 RELAY UNHEALTHY
BCPU(6MD86) BI 5.2 /W206/60.6 BCPU(6MD86) BI 5.22 /W206/61.7 BCPU(6MD86) BI 5.42 /W206/62.7
Min. SF6 density
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 114
E E
GAS ZONE TRIP 86A/86B Gas comp. 11 (Z2_L3) PSD 02
BCPU(6MD86) BI 5.6 /W206/60.6 BCPU(6MD86) BI 5.26 /W206/61.7 BCPU(6MD86) BI 5.46 /W206/63.7
Min. SF6 density By Pass
SF6 ZONE TRIP INTER TRIP (DR) GC-03 BB1 GAS ZONE TRIP DR PSD 02 device
BCPU(6MD86) BI 5.7 /W206/60.6 BCPU(6MD86) BI 5.27 /W206/61.7 BCPU(6MD86) BI 5.47 /W206/63.7
In Service
Gas Comp. 09 (F1 pole A) GC-04 BB2 GAS ZONE TRIP DR PSD 02
BCPU(6MD86) BI 5.8 /W206/60.6 BCPU(6MD86) BI 5.28 /W206/61.7 BCPU(6MD86) BI 5.48 /W206/63.7
Loss of SF6 CB Voltage Error
Gas Comp. 09 (F1 pole A) GC-13 BB2 GAS ZONE TRIP DR PSD 02
BCPU(6MD86) BI 5.9 /W206/60.6 BCPU(6MD86) BI 5.29 /W206/62.7 BCPU(6MD86) BI 6.1 /W206/63.7
Min. SF6 density Sync Data Error
F F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad BI/BO Table System for Various Substations W206114
3007687802(T),30071 Sh. 114 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <113 115>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
E E
TC-2 B-PH FAULTY SPARE LINE DISCONNECTOR Q9 CLOSE(+VE)
BCPU(6MD86) BI 6.18 /W206/64.7 BCPU(6MD86) BO 3.6 /W206/66.4 BCPU(6MD86) BO 6.10 /W206/65.2
GC-14 BB1 GAS ZONE TRIP DR SPARE HIGH SPEED ESW Q8 OPEN(+VE)
BCPU(6MD86) BI 6.19 /W206/64.7 BCPU(6MD86) BO 3.7 /W206/66.4 BCPU(6MD86) BO 6.11 /W206/65.2
GC-15 BB2 GAS ZONE TRIP DR SPARE HIGH SPEED ESW Q8 CLOSE(+VE)
BCPU(6MD86) BI 6.20 /W206/64.7 BCPU(6MD86) BO 3.8 /W206/66.4 BCPU(6MD86) BO 6.12 /W206/65.2
F F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad BI/BO Table System for Various Substations W206115
3007687802(T),30071 Sh. 115 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <114 116>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
SPARE
BCPU(6MD86) BO 6.14 /W206/65.2
SPARE
BCPU(6MD86) BO 6.15 /W206/65.2
SPARE
BCPU(6MD86) BO 6.16 /W206/65.2
BB DISCONNECTOR Q1 OPEN/CLOSE(-VE)
BCPU(6MD86) BO 6.17 /W206/65.6
B B
BB DISCONNECTOR Q2 OPEN/CLOSE(-VE)
BCPU(6MD86) BO 6.18 /W206/65.6
SPARE
BCPU(6MD86) BO 6.23 /W206/65.6
SPARE
BCPU(6MD86) BO 6.24 /W206/65.6
D D
220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) W206 116
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
F F
Version 1 220kV Thaltej Substation 220/132/33kV,250MVA ICT-3 HV(BAY-206) Supply of Control & Relay panels and Associated W 206R
A QT Corrected 11/25/2022 MJ Drawn By RVS Torrent Power Ltd, Ahmedabad BI/BO Table System for Various Substations W206116
3007687802(T),30071 Sh. 116 of 116
0 First Submission 07/27/2022 NBS Chkd By MMS Siemens Ltd.
48372(L),3007688671( (3)G719EA-MG9256-02-W206
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics
G) <115 ->
1 2 3 4 5 6 7 8