Professional Documents
Culture Documents
220/66kV 220kV BHILAD 220/66kV 220kV BHILAD 220kV BUS PT 220kV BUS
220/66kV 220kV 220kV 21.1 DISTANCE PROTECTION RELAY (MAIN-1 PROTECTION)
TRF - 1 (HV) LINE NO. 2 TRF - 2 (HV) LINE NO. 1 TRF - 3 (HV) VAPI LINE TARAPUR LINE
COUPLER BAY
21.2 DISTANCE PROTECTION RELAY (MAIN-2 PROTECTION)
$ 25
CHECK SYNCHRONISING RELAY
2-8LA 2-6LA 2-2LA 2-1LA
BCU BCU (INTEGRATED IN 21.1,21.2, 87L1, 87L2 & BCU)
V 25 V 25
220kV 110V 110V 1 1 1 220kV 110V 110V 1 NO - VOLTAGE RELAY
√3 √3 √3 √3 √3 √3 27
CL-0.2 CL-3P 2 27 59.1 2 2 CL-0.2 CL-3P 2 27 59.1 (1 - ɸ STATIC RELAY FOR 220kV LINE & 3 - ɸ STATIC RELAY FOR 66kV CAP. BANK)
50VA 50VA 2-8LCVT 2-6LCVT 2-2LCVT 50VA 50VA 2-1LCVT
50 LOCAL BREAKER BACKUP PROTECTION
LBB (INTEGRATED IN 21.1, 87L1, 51,67,87T & 87BB)
51 NON DIRECTIONAL O/C PROTECTION RELAY
2-889FES * 2-689FES
* 2-289FES
* 2-189FES
* NON DIRECTIONAL EARTH FAULT PROTECTION
51N
2-889L 2-689L 2-289L 2-189L (INTEGRATED IN 51)
2-889ES-II 2-689ES-II 2-289ES-II 2-189ES-II
55 POWER FACTOR CONTROLLER
FROM P1
BUS-2 PT BCU CORE-1 60N NEUTRAL CURRENT UNBALANCE RELAY
P2 P2 CL-0.5, 15VA, ISF≤5 P2 P2
F2 V2 F1 V1 A ** 1500-1200-600/1-1-1-1A
2-4CT 67 RELAY
DIRECTIONAL OVER CURRENT PROTECTION
50 87BB CORE-5, CL-PS FROM 50 CORE-5, CL-PS
LBB Vk≥1400V,Rct≤12Ω BUS-1 PT CORE-2, CL-PS LBB 87BB Vk≥1400V,Rct≤12Ω
Im≤25mA at Vk Im≤25mA at Vk 67N DIRECTIONAL EARTH FAULT PROTECTION RELAY (INTEGRATED IN 67)
GIS MODULE
50 Im≤25mA at Vk
LBB 51N 51 ** Vk≥1400V,Rct≤12Ω
CORE-4, CL-PS CORE-4, CL-PS
GIS MODULE
GIS MODULE
SPARE Vk≥1400V,Rct≤12Ω SPARE Vk≥1400V,Rct≤12Ω POWER SWINGPROTECTION(INTEGRATED IN 21.1, 21.2, 87L1 & 87L2)
Im≤25mA at Vk Im≤25mA at Vk 68
CORE-3, CL-PS
SPARE Im≤25mA at Vk
CORE-3, CL-PS ** CORE-3, CL-PS AUTO RECLOSING RELAY (INTEGRATED21.1,
IN 21.2, 87L1 & 87L2
)
59.2 68 79 87L2 Vk≥1400V,Rct≤12Ω 59.2 68 79 21.2 79
Vk≥1400V,Rct≤12Ω Vk≥1400V,Rct≤12Ω
FROM Im≤25mA at Vk FROM Im≤25mA at Vk
SELECTED SELECTED
CORE-4, CL-PS 87BB BUS BAR PROTECTION
BUS PT 50 CORE-2, CL-PS 50 87BB BUS PT 50 CORE-2, CL-PS
59.2 68 79 LBB 87L1 Vk≥1400V,Rct≤12Ω ** Im≤25mA at Vk 59.2 68 79 LBB 21.1 Vk≥1400V,Rct≤12Ω
LBB
Im≤25mA at Vk Vk≥1400V,Rct≤12Ω Im≤25mA at Vk
FROM
BCU
220kV 110V 110V 110V 110V FROM
BCU 87T TRANSFORMER DIFFERENTIAL
PROTECTIONRELAY
SELECTED CORE-1 √3 √3 √3 √3 √3 SELECTED CORE-1
BUS PT V MVAR MW A CL-0.5,15VA,ISF≤5
2-6CT
CL-0.5 CL-3P CL-3P CL-3P P2 2-2CT
BUS PT V MVAR MW A CL-0.5,15VA,ISF≤5
1500-1200-600/1-1-1-1-1A
2-8CT
100VA 100VA 100VA 100VA 1500-1200-600/1-1-1-1-1A
2-1CT 87L1 LINE DIFFERENTIAL
PROTECTIONRELAY (MAIN-1 PROTECTION)
PROTECTION
MVARh MWh MVARh MWh
P1 P1 4 3 2-452 P1 P1
METERING PROTECTION 87L2 LINE DIFFERENTIAL
PROTECTIONRELAY (MAIN-2 PROTECTION)
1 2
GIS MODULE
2-852 2-652 2-252 2-152
2-589A PT-I ES OVER FLUXINGPROTECTIONRELAY
99
2-589A PT-I
(INTEGRATED IN87T)
2-889ES-I 2-689ES-I 2-489ES-II 2-489ES-I 2-289ES-I 2-189ES-I
RESTRICTED EARTH FAULT PROTECTION RELAY
2-889B 2-889A 2-689B 2-689A 2-289B 2-289A 2-189B 2-189A 64R
2-589A PT-I FES
* BUS PT-I 2-489B 2-489A (INTEGRATED IN87T FOR 66/11kV STN. TR.)
220kV MAIN BUS-I, OVER VOLTAGE PROTECTION STAGE-1
59.1
3150A, 50KA, 3SEC (INTEGRATED IN21.1, 21.2, 87L1 & 87L2
)
GIS MODULE
2-989B 2-989A 2-789B 2-789A 2-589B PT-II FES
* BUS PT-II 2-389B 2-389A 59 THREE PHASE STATIC OVER VOLTAGE RELAY
2-989ES-I 2-789ES-I 2-389ES-I
2-589B PT-II
A AMMETER
2-589B PT-II ES
2-952 2-752 2-352
1 2 V VOLTMETER
METERING PROTECTION
P1 P1 4 3 P1
MVAR REACTIVE POWER METER
BCU PROTECTION
PF MW A
2-9 CT
2-7CT 220kV 110V 110V 110V 110V 2-3CT
INTEGRATED IN BCU
V MVAR CORE-1,CL-0.5, 15VA,ISF≤5
1500-1200-600/1-1-1-1-1A √3 √3 √3 √3 √3
CL-0.5 CL-3P CL-3P CL-3P
MW ACTIVE POWER METER
MVARh MWh
FROM CORE-2, CL-PS 100VA 100VA 100VA 100VA
SELECTED 67N 67 Vk≥1400V,Rct≤12Ω PF POWER FACTOR METER
BUS PT FROM Im≤25mA at Vk
SELECTED
GIS MODULE
GIS MODULE
GIS MODULE
BUS PT CORE-3, CL-PS
50
99 87T Vk≥1400V,Rct≤12Ω F FREQUENCY METER
LBB Im≤25mA at Vk
FROM LV CT
GIS MODULE
59
BAY GIS MODULE COMPRISING
LA,VT,FES, LINE DISCONNECTOR WITH
*** CORE-3, CL-PS
* * * CORE-3, CL-PS 01
GIS MODULE
GIS MODULE
GIS MODULE
GIS MODULE
TO HV Vk≥950V,Rct≤10Ω ES ,CT(RATIO-1500-1200/1-1-1A)CB,,
FROM SELECTED Vk≥600V,Rct≤6Ω
*
*
Im≤30mA at Vk
BUS PT Im≤25mA at Vk BUS DISCONNECTOR W/O ES & WITH
50
LBB 67N 67 ** CORE-2,CL-5P10,
15VA P1 FROM SELECTED ES.
27 50
LBB 67N 67 *** CORE-2,
CL-5P10,15VA * * BUS PT 50
LBB 67N 67 * CORE-2,CL-5P10,
15VA
CORE-3,
A
BCU
* CL-5P10,15VA
3- Ø 66 KV, 1600 A, 40 KA - 3 SEC,LINE
BCU BCU 6-13CT BCU
6-14CT
*** 6-3CT BAY GIS MODULE COMPRISING
FROM SELECTED
PF V MVAR MW A ** CORE-1,CL-0.5,
15VA,ISF≤5
FROM SELECTED
PF V MVAR MW A CORE-1,
100-50/1-1-1-1A
* 6-11CT
50
LBB 51N 51 * CORE-2,
CL-5P10,15VA
* 6-6CT
FROM SELECTED
PF V MVAR MW A * CORE-1,CL-0.5,
15VA,ISF≤5 02 LA,VT,FES, LINE DISCONNECTOR WITH
BUS PT BUS PT BUS PT
*
MVARh MVAR 200-100/1-1-1A MVARh MWh CL-0.5,15VA,ISF≤5 66kV 110V 110V 110V MVARh MWh 1500-1200/1-1-1-1A ES ,CT RATIO(600-300/1-1-1A) CB,
, BUS
√3 √3 √3 √3
6-7CT DISCONNECTOR W/O ES & WITH ES.
55 P1 P1 P1 CL-0.5 CL-3P CL-3P
CORE-1, P1 P1
50VA 50VA 50VA
*
GIS MODULE
SPARE CL-0.5,15VA,ISF≤5
CT FROM 3 1500-1200/1-1-1A
220/66kV TRF LV 81
6-1452 6-1152 F1 V1 PROTECTION 6-652 6-352
6-1352 1 2 B1
P2 6-752 3- Ø 66 KV, 1600 A, 40 KA - 3 SEC,CAP.
6-889A PT-IES BANK BAY GIS MODULE COMPRISING
6-889A PT-I 6-789ES-II 6-789ES-I
03 LA,VT,FES, LINE DISCONNECTOR WITH
6-1489ES-I 6-1389ES-I 6-1189ES-I 6-689ES-I 6-389ES-I
*
ES ,CT RATIO(200-100/1-1-1A) CB,
, BUS
**
6-889A PT-I FES BUS PT-I
6-1489B 6-1489A 6-1389B 6-1389A 6-1189B 6-1189A
* 6-789B 6-789A 6-689B 6-689A 6-389B 6-389A DISCONNECTOR W/O ES & WITH ES.
*
6-1789B 6-1789A 6-1689B 6-1689A 6-1589B 6-1589A 6-1289B 6-1289A 6-1089B 6-1089A 6-989B 6-989A
6-889B PT-II FES BUS PT-II 6-589B 6-589A 6-489B 6-489A 6-289B 6-289A 6-189B 6-189A (1500-1200/1-1-1-1A),
DISCONNECTOR
6-1789ES-I 6-1689ES-I 6-1589ES-I 6-1289ES-I 6-1089ES-I 6-989ES-I * 6-589ES-I 6-489ES-I 6-289ES-I 6-189ES-I
WITH ES , TR SIDE ES, LA.
6-889B PT-II
6-889B PT-IIES
3- Ø 66 KV, 1600 A, 40 KA - 3 SEC, BUS
6-1752 6-1652 6-1552 6-1252 6-1052 6-952 F2 V2
1 2 81
B2 PROTECTION 6-552 6-452 6-252 6-152 All the Protections & Configurations shown220kV
for TarapurLine, COUPLER BAY GIS MODULE
3
220/66kV TRF - 1, 66kV Line No.1 are applicable to all other 05 COMPRISING, BUS DISCONNECTOR
*
66kV 110V 110V 110V WITH ES- 2NOS., CB & CT WITH RATIO
P1 P1 P1 FROM P1 P1 P1 √3 √3 √3 √3
CL-0.5 CL-3P CL-3P
P1 P1 P1 FROM P1 respective bays. (1500-1200/1-1-1 A).
SELECTED SELECTED
BUS PT BCU 6-12CT 50VA 50VA 50VA BUS PT BCU 6-1CT
CORE-1, CORE-1,
6-17CT 6-16CT 6-15CT * 6-10CT 6-9CT 6-5CT * 6-4CT 6-2CT *
$ isAllapplicable
the Protections & Configurations shown for 220kV Bhilad Line - 2
V MVAR MW A V MVAR MW A
1500-1200/1-1-1A 600-300/1-1-1A 3- Ø, 66 KV, 1600A, 40 KA- 3 SEC,
GIS MODULE
GIS MODULE
CL-0.5,15VA,ISF≤5 CL-0.5,15VA,ISF≤5 STATION TRANSFORMER BAY GIS
GIS MODULE
GIS MODULE
GIS MODULE
GIS MODULE
GIS MODULE
GIS MODULE
GIS MODULE
GIS MODULE
MVARh MWh MVARh MWh
to 220kV Bhilad Line - 1 MODULE COMPRISING ,BUS
CORE-2, CORE-2, 06 DISCONNECTOR W/O ES & WITH ES.,
FROM
50
LBB 67N 67 * CL-5P10,15VA * FROM
50
LBB 67N 67 * CL-5P10,15VA CB, CT RATIO(100-50/1-1-1-1A),
***
# isAllapplicable
the Protections & Configurations shown for 66kV Sarigam Line - 2
SELECTED SELECTED
BUS PT BUS PT
DISCONNECTOR WITH ES , TR SIDE ES,
LA.
SPARE *
CORE-3,
CL-5P10,15VA * SPARE *
CORE-3,
CL-5P10,15VA
to 66kV Sarigam Line - 1
3- Ø 66 KV, 2000 A, 40 KA - 3 SEC,
BUSBAR GIS MODULE COMPRISING,
P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 66KV 110V 110V 110V
*
07 PT RATIO ( √3 / √3 - √3 - √3 )
,FES,BUS DISCONNECTOR WITH ES.
6-1789ES-II 6-1689ES-II 6-1589ES-II 6-1289ES-II 6-1089ES-II 6-989ES-II 6-589ES-II 6-489ES-II 6-289ES-II 6-189ES-II
6-1789L 6-1689L 6-1589L 6-1289L 6-1089L 6-989L 6-589L 6-489L 6-289L 6-189L
TENDER PURPOSE
6-1289FES 6-189FES
* 6-1789FES
* 6-1689FES
* 6-1589FES
* * 6-1089FES
* 6-989FES
* 6-589FES
* 6-489FES
* 6-289FES
* G GUJARAT ENERGY TRANSMISSION CORPN.LTD.
E
MFM 25 66kV 110V 110V 110V MFM 2566kV 110V 110V 110V
T S.P.VIDYUT BHAVAN, RACE COURSE,
6-17PT 6-16PT 6-15PT 6-12PT BCU
√3 √3 √3 √3
CL-0.5 CL-3P CL-3P 6-10PT 6-9PT 6-5PT 6-4PT 6-2PT 6-1PT BCU
√3 √3 √3 √3
CL-0.5 CL-3P CL-3P
C VADODARA - 390 007
27 50VA 50VA 50VA 27 50VA 50VA 50VA O
6-17LA 6-16LA 6-15LA 6-12LA 6-10LA 6-9LA 6-5LA 6-4LA 6-2LA 6-1LA
SIZE:
JE(ENGG.) DE(ENGG.) EE(ENGG.) SE(ENGG.) CE(ENGG.) A0
SCALE: DATE: DRG. NO: SHEET: REV:
1 SLD DRG NO: GETCO / E / 2S-395 / P-002, R0, DTD : 24.08.2018 R0 FIRST PREPARATION
N.T.S. GETCO / E / 1 OF 1 R0
SR NO. REFERENCE REV: DESCRIPTION 28.08.2018 2S-395/ P - 003