Post type with Current transformers

Wound primary ARM6/N1 - ARM6/N2

# Max reference voltage for insulation: 36 kV Selection table


# Isn secondary rated current: 1 or 5 A n°. of secondaries per CT 1 2
# Ipn primary rated current: see page 7 standard types ARM6/N1 ARM6/N2
# Iter short circuit thermal current (expressed as a
multiple of Ipn): 100 ÷ 1000
# Idin short circuit dynamic current: 2.5 Iter
# SR = Single Ratio
DR = Double Ratio with changeover on primary
1st measuring sec.
class 0.5
Fs = 10
VA
"Iter" lpn alternatively 5 7.5 10 15 20 20 30 30 30 30 30
multiple primary measuring sec. protection sec. 2nd protection secondary
of lpn rated class 0.5 class 5P class 5P
Max current (A) Fs = 10 Fl = 10 Fl = 10
60 kAx1s VA VA VA
SR DR 7.5 10 15 20 30 50 5 7.5 10 15 20 30 50 5 5 5 7.5 5 10 10 15 20 30 50
5÷ 6-3 ÷
100
800 800-400
20 ÷ 40-20 ÷
160
300 600-300
20 ÷ 40-20 ÷
200
300 600-300
15 ÷ 30-15 ÷
250
200 400-200
10 ÷ 20-10 ÷
320
150 300-150
5÷ 10-5 ÷
400
100 200-100
5÷ 10-5 ÷
500
100 200-100
5÷ 10-5 ÷
630
75 150-75
5÷ 10-5 ÷
800
50 100-50
5÷ 10-5 ÷
1000
50 100-50

Table reading:
lter × 1s
1) Define multiple: ----------------------
lpn
2) Fix line according to Ipn primary current and its multiple.
3) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
If such point should fall within the white area, a larger CT type
should be used: ARM7 - ARM8.

Dimensions (mm)
type ARM6/N1-N2
Weight kg 22

86 50 43 M 12
P1

175
200

GROUPE SCHNEIDER
52
P2
408
400

370
362

225
N°4 holes
23

Ø 11
260
5

122 102
M6 screw type
secondary and earthing terminals
224

AMTED300031EN_020_029. Gamme Schneider Electric


fm/20
Post type with Current transformers
0

Wound primary ARM7/N1 - ARM7/N2 - ARM7/N3

# Max reference voltage for insulation: 36 kV Selection table


# Isn secondary rated current: 1 or 5 A
n°. of secondaries per CT 1 2 3
# Ipn primary rated current: see page 7
standard types ARM7/N1 ARM7/N2 ARM7/N3
# Iter short circuit thermal current (expressed as a
multiple of Ipn): 100 ÷ 1200 1st meas. sec.
# Idin short circuit dynamic current: 2.5 Iter class 0.5
# SR = Single Ratio Fs = 10
DR = Double Ratio with changeover on primary VA
5 10 15 20 30
st
1 measuring sec. nd
2 prot.sec.
class 0.5 class 5P
Fs = 10 Fl = 10
VA VA
"Iter" lpn alternatively 5 7.5 10 15 20 20 30 30 30 30 30 5 5 7.5 10 15
multiple primary measuring sec. protection sec. 2nd protection secondary 3rd prot. sec.
of lpn rated class 0.5 class 5P class 5P class 5P
max current (A) Fs = 10 Fl = 10 Fl = 10 Fl = 15
60 kAx1s VA VA VA VA
SR DR 7.5 10 15 20 30 50 5 7.5 10 15 20 30 50 5 5 5 7.5 5 10 10 15 20 30 50 5 5 7.5 10 15
5÷ 6-3 ÷
100
800 800-400
20 ÷ 40-20 ÷
160
300 600-300
20 ÷ 40-20 ÷
200
300 600-300
15 ÷ 30-15 ÷
250
200 400-200
10 ÷ 20-10 ÷
320
150 300-150
5÷ 10-5 ÷
400
100 200-100
5÷ 10-5 ÷
500
100 200-100
5÷ 10-5 ÷
630
75 150-75
5÷ 10-5 ÷
800
50 100-50
5÷ 10-5 ÷
1000
50 100-50
5÷ 10-5 ÷
1200 50 100-50

Table reading:
lter × 1s
1) Define multiple: ----------------------
lpn
2) Fix line according to Ipn primary current and its multiple.
3) A TA is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
If such point should fall within the grey area, choose a smaller TA type:
ARM6
If such point should fall within the white area, a larger TA type
should be used: ARM8.

Dimensions (mm)
type ARM7/N1-N2-N3
Weight kg 30

86 50 43 M 12
P1

GROUPE SCHNEIDER
175
200
52
GROUPE SCHNEIDER

P2
408
400

370
362

225 N°4 holes


Ø 11
23

260

157 150
M6 screw type
secondary and earthing terminals
307

Schneider Electric Gamme AMTED300031EN_020_029.


fm/21
Post type with Current transformers
0

Wound primary ARM8/N1 - ARM8/N2 - ARM8/N3

# Max reference voltage for insulation: Selection table


Um 7.2 - 12 - 17.5 - 24 - 36 kV
n°. of secondaries per CT 1 2 3
# Isn secondary rated current: 1 or 5 A
standard types ARM8/N1 ARM8/N2 ARM8/N3
# Ipn primary rated current: see page 7
# Iter short circuit thermal current (expressed as a 1st meas. sec.
multiple of Ipn): 100 ÷ 1200 class 0.5
# Idin short circuit dynamic current: 2.5 Iter Fs = 10
# SR = Single Ratio VA
DR = Double Ratio with changeover on primary 5 10 15 20 30
st
1 measuring sec. nd
2 prot.sec.
class 0.5 class 5P
Fs = 10 Fl = 10
VA VA
"Iter" lpn alternatively 5 7.5 10 15 20 20 30 30 30 30 30 5 5 7.5 10 15
multiple primary measuring sec. protection sec. nd
2 protection secondary rd
3 prot. sec.
of lpn rated class 0.5 class 5P class 5P class 5P
max current (A) Fs = 10 Fl = 10 Fl = 10 Fl = 15
60 kAx1s VA VA VA VA
SR DR 7.5 10 15 20 30 50 5 7.5 10 15 20 30 50 5 5 5 7.5 5 10 10 15 20 30 50 5 5 7.5 10 15
5÷ 6-3 ÷
100
800 800-400
20 ÷ 40-20 ÷
160
300 600-300
20 ÷ 40-20 ÷
200
300 600-300
15 ÷ 30-15 ÷
250
200 400-200
10 ÷ 20-10 ÷
320
150 300-150
5÷ 10-5 ÷
400
100 200-100
5÷ 10-5 ÷
500
100 200-100
5÷ 10-5 ÷
630
75 150-75
5÷ 10-5 ÷
800 50 100-50
5÷ 10-5 ÷
1000 50 100-50
5÷ 10-5 ÷
1200 50 100-50

Table reading:
lter × 1s
1) Define multiple: ----------------------
lpn
2) Fix line according to Ipn primary current and its multiple.
3) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
If such point should fall within the grey area, choose a smaller CT type:
ARM1 - ARM2 - ARM3 - ARM4 for Um 6 24 kV;
ARM6 - ARM7 for Um = 36 kV.

Dimensions (mm)
type ARM8/N1-N2-N3
Weight kg 35

86 50 43 M 12

GROUPE SCHNEIDER
P1

175
200
249
52
GROUPE SCHNEIDER

P2
408
400

370
362
23

225 N°4 holes


5

Ø 11
260

152 150
M6 screw type
secondary and earthing terminals
302

AMTED300031EN_020_029. Gamme Schneider Electric


fm/22
Post type with Current transformers
0

bar primary ARM9/N1 - ARM9/N2 - ARM9/N3

# Max reference voltage for insulation: 36 kV Selection table


# Isn secondary rated current: 1 or 5 A
n°. of secondaries per CT 1 2 3
# Ipn primary rated current: see selection table
standard types ARM9/N1 ARM9/N2 ARM9/N3
# Iter short circuit thermal current: 60 kA x 1s
# Idin short circuit dynamic current: 2.5 Iter 1st meas. sec.
# SR = Single Ratio class 0.5
DR = Double Ratio with changeover on secondary Fs = 10
VA
5 10 15 20 30
st
1 measuring sec. nd
2 prot.sec.
class 0.5 class 5P
Fs = 10 Fl = 10
VA VA
alternatively 5 7.5 10 15 20 20 30 30 30 30 30 5 5 7.5 10 15
lpn measuring sec. protection sec. nd
2 protection secondary rd
3 prot. sec.
primary class 0.5 class 5P class 5P class 5P
rated Fs = 10 Fl = 10 Fl = 10 Fl = 15
current (A) VA VA VA VA
SR DR 7.5 10 15 20 30 50 5 7.5 10 15 20 30 50 5 5 5 7.5 5 10 10 15 20 30 50 5 5 7.5 10 15

1000

1200

1250

1500

1600

1800

2000

2500

1000-500

1500-750

2000-1000

Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.

Dimensions (mm)
type ARM9/N1-N2-N3
Weight kg 35

M 12 x 23 DETAILS OF PRIMARY BARS


GROUPE SCHNEIDER

Ipn Ipn
800 ÷ 1600 A 1800 ÷ 2500 A
362

200
P2

175
P1

40
23

45
5

70

120
184
157 150 M6 screw type 225 N°4 holes 70
secondary and earthing terminals Ø 11
260 70
307

Schneider Electric Gamme AMTED300031EN_020_029.


fm/23
Support type Current transformers
0

without primary ARO1a/N1 - ARO1a/N2 - ARO1a/N3


ARO1b/N1 - ARO1b/N2 - ARO1b/N3

# Max reference voltage for insulation: Selection table


7.2 - 12 - 17.5 kV
n°. of secondaries per CT 1 2 3
# Isn secondary rated current: 1 or 5 A
standard types ARO1a/N1 ARO1a/N2 ARO1a/N3
# Ipn primary rated current: see selection table ARO1b/N1 ARO1b/N2 ARO1b/N3
# Iter short circuit thermal current: 60 kA x 1s 1st meas. sec.
# Idin short circuit dynamic current: 2.5 Iter class 0.5
# SR = Single Ratio Fs = 10
DR = Double Ratio with changeover on secondary VA
5 10 15 20 30
st
1 measuring sec. nd
2 prot.sec.
class 0.5 class 5P
Fs = 10 Fl = 10
VA VA
alternatively 5 7.5 10 15 20 20 30 30 30 30 30 5 10 15 20 30
lpn measuring sec. protection sec. nd
2 protection secondary rd
3 prot. sec.
primary class 0.5 class 5P class 5P class 5P
rated Fs = 10 Fl = 10 Fl = 10 Fl = 15
current (A) VA VA VA VA
SR DR 7.5 10 15 20 30 50 5 7.5 10 15 20 30 50 5 5 5 7.5 5 10 10 15 20 30 50 5 5 7.5 10 15

1000

1200

1500

2000

3000

4000

5000

2000-1000

3000-1500

4000-2000

5000-2500

Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.

Dimensions (mm)
type ARO1a/N1-N2-N3 and ARO1b/N1-N2-N3
Weight kg 27
L

Ø
175
200

P1 P2
369
230
23

GROUPE SCHNEIDER

225
5

N°4 holes
Ø 11
260

# type ARO1a/N1-N2-N3
L = 238 mm Ø = 110 mm M6 screw type secondary
# type ARO1b/N1-N2-N3 and earthing terminals
L = 248 mm Ø = 130 mm Connection between primary
and shielding (lenght 300 mm)

AMTED300031EN_020_029. Gamme Schneider Electric


fm/24
Support type Current transformer
0

without primary ARO2/N1 - ARO2/N2 - ARO2/N3

# Max reference voltage for insulation: 24 - 36 kV Selection table


# Isn secondary rated current: 1 or 5 A
# Ipn primary rated current: see selection table n°. of secondaries per CT 1 2 3
# Iter short circuit thermal current: 60 kA x 1s standard types ARO2/N1 ARO2/N2 ARO2/N3
# Idin short circuit dynamic current: 2.5 Iter
1st meas. sec.
# SR = Single Ratio class 0.5
DR = Double Ratio with changeover on secondary Fs = 10
VA
5 10 15 20 30
1st measuring sec. 2nd prot.sec.
class 0.5 class 5P
Fs = 10 Fl = 10
VA VA
alternatively 5 7.5 10 15 20 20 30 30 30 30 30 5 5 7.5 10 15
lpn measuring sec. protection sec. 2nd protection secondary 3rd prot. sec.
primary class 0.5 class 5P class 5P class 5P
rated Fs = 10 Fl = 10 Fl = 10 Fl = 15
current (A) VA VA VA VA
SR DR 7.5 10 15 20 30 50 5 7.5 10 15 20 30 50 5 5 5 7.5 5 10 10 15 20 30 50 5 5 7.5 10 15

1000

1200

1500

2000

3000

4000

2000-1000

3000-1500

4000-2000

Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.

Dimensions (mm)
type ARO2/N1-N2-N3
Weight kg 32 248

110
175
200

P1 P2
420
280

225 N°4 holes


23

GROUPE SCHNEIDER

Ø 11
5

260

M6 screw type secondary


and earthing terminals

connection between primary


and shielding (lenght 300 mm)

Schneider Electric Gamme AMTED300031EN_020_029.


fm/25
Toroidal type Current transformers
0

ARF1/N1 - ARF1/N2

# Max reference voltage for insulation: 0.72 kV Selection table


# Isn secondary rated current: 1 or 5 A
n°. of secondaries per CT 1 2
# Ipn primary rated current: see selection table
standard types ARF1/N1 ARF1/N2
# Iter short circuit thermal current: 60 kA x 1s
# Idin short circuit dynamic current: 2.5 Iter
# SR = Single Ratio
DR = Double Ratio with changeover on secondary
1st measuring sec.
class 0.5
Fs = 10
VA
alternatively 5 7.5 10 15 20 20 30 30 30
lpn measuring sec. protection sec 2nd protection secondary
primary class 0.5 class 5P class 5P
rated Fs = 10 Fl = 10 Fl = 10
current (A) VA VA VA
SR DR 2.5 5 7.5 10 15 20 30 50 2.5 5 7.5 10 15 20 30 50 5 5 5 7.5 10 10 15 20 20
*
50 50-100

* * *
100 100-200

* * * *
150 150-300

** ** ** ** *
200 200-4

300 300-600

400 400-800

600 600-1200

800 800-1600

1000 1000-2000

1250

1500

2000

2500

Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
* cl. 1 Fs≤15 ** cl. 0.5 Fs≤15
3) In case of double (DR) CT, rated outputs are guaranteed on low ratio and are
doubled on high ratio.

Dimensions (mm)
type ARF1/N1-N2
Weight kg 8

85
25

100

M6 secondary
terminals
140

170
198
GROUPE SCHNEIDER
7

P1

170
N°4 slot
198 Ø 9 x 11
130
229

AMTED300031EN_020_029. Gamme Schneider Electric


fm/26
Toroidal type Current transformers
0

ARF2/N1 - ARF2/N2 - ARF2/N3

# Max reference voltage for insulation: 0.72 kV Selection table


# Isn secondary rated current: 1 or 5 A
n°. of secondaries per CT 1 2 3
# Ipn primary rated current: see selection table
standard types ARF2/N1 ARF2/N2 ARF2/N3
# Iter short circuit thermal current: 60 kA x 1s
# Idin short circuit dynamic current: 2.5 Iter 1st meas. sec.
# SR = Single Ratio class 0.5
DR = Double Ratio with changeover on secondary Fs = 10
VA
5 10 15 20 30
1st measuring sec. 2nd prof. sec.
class 0.5 class 5P
Fs = 10 Fl = 10
VA VA
alternatively 5 7.5 10 15 20 20 30 30 30 5 5 7.5 10 15
lpn measuring sec. protection sec nd rd
2 protection secondary 3 prot. sec.
primary class 0.5 class 5P class 5P class 5P
rated Fs = 10 Fl = 10 Fl = 10 Fl = 15
current (A) VA VA VA VA
SR DR 2.5 5 7.5 10 15 20 30 50 2.5 5 7.5 10 15 20 30 50 5 5 5 7.5 10 10 15 20 20 5 10 10 15 20

50 50-100

*
100 100-200

* * * *
150 150-300

** ** ** ** *
200 200-400

300 300-600

400 400-800

600 600-1200

800 800-1600

1000 1000-2000

1250

1500

2000

2500

Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
* cl. 1 Fs≤15 ** cl. 0.5 Fs≤15
If such point should fall within the grey area, choose a smaller CT type:
ARF1.
3) In case of double ratio (DR) CT, rated outputs are guaranteed on low ratio and
are doubled on high ratio.

Dimensions (mm)
type ARF2/N1-N2-N3
Weight kg 12

85
25

150

M6 secondary
7

140

170
198

terminals
GROUPE SCHNEIDER

P1

170 N°4 slot


198 Ø 9 x 11

130
229

Schneider Electric Gamme AMTED300031EN_020_029.


fm/27
Toroidal type Current transformers
0

ARF3/N1

# Max reference voltage for insulation: 0.72 kV Selection table


# Isn secondary rated current: 1 or 5 A n°. of secondaries per CT 1
# Ipn primary rated current: see selection table standard types ARF3/N1
# Iter short circuit thermal current : 60 kA x 1s
# Idin short circuit dynamic current: 2.5 Iter
# SR = Single Ratio
DR = Double Ratio with changeover on secondary

alternatively
lpn measuring sec. protection sec
primary class 0.5 class 5P
rated Fs = 10 Fl = 10
current (A) VA VA
SR DR 2.5 5 7.5 10 15 20 30 50 2.5 5 7.5 10 15 20 30 50

50 100-50

* * *
100 200-100

* * * *
150 300-150

** ** ** **
200 400-200

300 600-300

400 800-400

600 1200-600

800 1600-800

1000 2000-1000

1200

1500

2000

Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
* cl. 1 Fs≤15 ** cl. 0.5 Fs≤15
3) In case of double ratio (DR) CT, rated outputs are guaranteed on low ratio and
are doubled on high ratio.

Dimensions (mm)
type ARF3/N1
Weight kg 7

105
30

S2
S1 S3
100

M6 secondary P1

terminals
198
GROUPE SCHNEIDER
83

113

AMTED300031EN_020_029. Gamme Schneider Electric


fm/28
Toroidal type Current transformers
0

ARF4/N1 - ARF4/N2

# Max reference voltage for insulation: 0.72 kV Selection table


# Isn secondary rated current: 1 or 5 A
n°. of secondaries per CT 1 2
# Ipn primary rated current: see selection table
standard types ARF4/N1 ARF4/N2
# Iter short circuit thermal current : 60 kA x 1s
# Idin short circuit dynamic current: 2.5 Iter
# SR = Single Ratio
DR = Double Ratio with changeover on secondary

1st measuring sec.


class 0.5
Fs = 10
VA
alternatively 5 7.5 10 15 15 20 30 20 30 30 30
lpn measuring sec. protection sec 2nd protection secondary
primary class 0.5 class 5P class 5P
rated Fs = 10 Fl = 10 Fl = 10
current (A) VA VA VA
SR DR 2.5 5 7.5 10 15 20 30 50 2.5 5 7.5 10 15 20 30 50 5 5 5 7.5 10 10 15 20 20 30 50

50 100-50

100 200-100

150 300-150

200 400-200

300 600-300

400 800-400

600 1200-600

800 1600-800

1000 2000-1000

1250 2500-1250

1500

2000

2500

Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
* cl. 1 Fs≤15 ** cl. 0.5 Fs≤15 *** cl. 10P
3) In case of double ratio (DR) CT, rated outputs are guaranteed on low ratio and
are doubled on high ratio.

Dimensions (mm)
type ARF4/N1-N2
Weight kg 14

105
25

100

M6 secondary
terminals
140

200
238
GROUPE SCHNEIDER
7

P1

200
238 N°4 slot
Ø 9 x 11
152
271

Schneider Electric Gamme AMTED300031EN_020_029.