Table reading:
lter × 1s
1) Define multiple: ----------------------
lpn
2) Fix line according to Ipn primary current and its multiple.
3) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
If such point should fall within the white area, a larger CT type
should be used: ARM7 - ARM8.
Dimensions (mm)
type ARM6/N1-N2
Weight kg 22
86 50 43 M 12
P1
175
200
GROUPE SCHNEIDER
52
P2
408
400
370
362
225
N°4 holes
23
Ø 11
260
5
122 102
M6 screw type
secondary and earthing terminals
224
Table reading:
lter × 1s
1) Define multiple: ----------------------
lpn
2) Fix line according to Ipn primary current and its multiple.
3) A TA is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
If such point should fall within the grey area, choose a smaller TA type:
ARM6
If such point should fall within the white area, a larger TA type
should be used: ARM8.
Dimensions (mm)
type ARM7/N1-N2-N3
Weight kg 30
86 50 43 M 12
P1
GROUPE SCHNEIDER
175
200
52
GROUPE SCHNEIDER
P2
408
400
370
362
260
157 150
M6 screw type
secondary and earthing terminals
307
Table reading:
lter × 1s
1) Define multiple: ----------------------
lpn
2) Fix line according to Ipn primary current and its multiple.
3) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
If such point should fall within the grey area, choose a smaller CT type:
ARM1 - ARM2 - ARM3 - ARM4 for Um 6 24 kV;
ARM6 - ARM7 for Um = 36 kV.
Dimensions (mm)
type ARM8/N1-N2-N3
Weight kg 35
86 50 43 M 12
GROUPE SCHNEIDER
P1
175
200
249
52
GROUPE SCHNEIDER
P2
408
400
370
362
23
Ø 11
260
152 150
M6 screw type
secondary and earthing terminals
302
1000
1200
1250
1500
1600
1800
2000
2500
1000-500
1500-750
2000-1000
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
Dimensions (mm)
type ARM9/N1-N2-N3
Weight kg 35
Ipn Ipn
800 ÷ 1600 A 1800 ÷ 2500 A
362
200
P2
175
P1
40
23
45
5
70
120
184
157 150 M6 screw type 225 N°4 holes 70
secondary and earthing terminals Ø 11
260 70
307
1000
1200
1500
2000
3000
4000
5000
2000-1000
3000-1500
4000-2000
5000-2500
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
Dimensions (mm)
type ARO1a/N1-N2-N3 and ARO1b/N1-N2-N3
Weight kg 27
L
Ø
175
200
P1 P2
369
230
23
GROUPE SCHNEIDER
225
5
N°4 holes
Ø 11
260
# type ARO1a/N1-N2-N3
L = 238 mm Ø = 110 mm M6 screw type secondary
# type ARO1b/N1-N2-N3 and earthing terminals
L = 248 mm Ø = 130 mm Connection between primary
and shielding (lenght 300 mm)
1000
1200
1500
2000
3000
4000
2000-1000
3000-1500
4000-2000
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
Dimensions (mm)
type ARO2/N1-N2-N3
Weight kg 32 248
110
175
200
P1 P2
420
280
GROUPE SCHNEIDER
Ø 11
5
260
ARF1/N1 - ARF1/N2
* * *
100 100-200
* * * *
150 150-300
** ** ** ** *
200 200-4
300 300-600
400 400-800
600 600-1200
800 800-1600
1000 1000-2000
1250
1500
2000
2500
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
* cl. 1 Fs≤15 ** cl. 0.5 Fs≤15
3) In case of double (DR) CT, rated outputs are guaranteed on low ratio and are
doubled on high ratio.
Dimensions (mm)
type ARF1/N1-N2
Weight kg 8
85
25
100
M6 secondary
terminals
140
170
198
GROUPE SCHNEIDER
7
P1
170
N°4 slot
198 Ø 9 x 11
130
229
50 50-100
*
100 100-200
* * * *
150 150-300
** ** ** ** *
200 200-400
300 300-600
400 400-800
600 600-1200
800 800-1600
1000 1000-2000
1250
1500
2000
2500
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
* cl. 1 Fs≤15 ** cl. 0.5 Fs≤15
If such point should fall within the grey area, choose a smaller CT type:
ARF1.
3) In case of double ratio (DR) CT, rated outputs are guaranteed on low ratio and
are doubled on high ratio.
Dimensions (mm)
type ARF2/N1-N2-N3
Weight kg 12
85
25
150
M6 secondary
7
140
170
198
terminals
GROUPE SCHNEIDER
P1
130
229
ARF3/N1
alternatively
lpn measuring sec. protection sec
primary class 0.5 class 5P
rated Fs = 10 Fl = 10
current (A) VA VA
SR DR 2.5 5 7.5 10 15 20 30 50 2.5 5 7.5 10 15 20 30 50
50 100-50
* * *
100 200-100
* * * *
150 300-150
** ** ** **
200 400-200
300 600-300
400 800-400
600 1200-600
800 1600-800
1000 2000-1000
1200
1500
2000
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
* cl. 1 Fs≤15 ** cl. 0.5 Fs≤15
3) In case of double ratio (DR) CT, rated outputs are guaranteed on low ratio and
are doubled on high ratio.
Dimensions (mm)
type ARF3/N1
Weight kg 7
105
30
S2
S1 S3
100
M6 secondary P1
terminals
198
GROUPE SCHNEIDER
83
113
ARF4/N1 - ARF4/N2
50 100-50
100 200-100
150 300-150
200 400-200
300 600-300
400 800-400
600 1200-600
800 1600-800
1000 2000-1000
1250 2500-1250
1500
2000
2500
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
* cl. 1 Fs≤15 ** cl. 0.5 Fs≤15 *** cl. 10P
3) In case of double ratio (DR) CT, rated outputs are guaranteed on low ratio and
are doubled on high ratio.
Dimensions (mm)
type ARF4/N1-N2
Weight kg 14
105
25
100
M6 secondary
terminals
140
200
238
GROUPE SCHNEIDER
7
P1
200
238 N°4 slot
Ø 9 x 11
152
271