Resolved Issues
The following bugs were fixed for this patch release. Please click on
the bug number for a more detailed description of the problem.
I0009887 The 16-pen Trend does not refresh trend and time stamps
properly.
I0019683 The Alarm button does not function when the SPC dataset is
made using the Duplicate button.
I0019946 Quick function call, which has a name more than eight (8)
characters long, causes AE (Assertion Error) and WindowViewer to
freeze.
I0020178 A return to normal entry is not given the Return color, if the
tag was Acknowledged prior to its return to normal.
I0020201 The "dot field" import creates a new tag, when an attempt is
made to import and the dot-field tag is converted to a remote tag.
I0020352 The List Box control has graphical remnants on the top and
left borders.
I0020775 There is invalid data in the Value field when a discrete tag is
used.
I0020781 SPC Dataset is saved without the product name when the
<Enter> key is used.
I0020787 Line Printer for alarm printing limits the flexibility of the
printer's usage.
I0020818 The Tagname button does not work after some Retentive
Memory tags are deleted, and then an attempt is made to modify a
BindList.
Back to Top
Detailed Description
Problem:
DB Load fails at embedded spaces in a tagname's DDE Access. No
space was removed when the dbload was performed.
However, please be aware that the access name with invalid
characters, such as a space, could not be used with the remote tags;
a warning was given when an invalid access name was created.
Back to Top
I0009887 The 16-pen Trend does not refresh trend and time stamps
properly.
Problem:
After the 16-pen Trend has been running for a while, it stops
repainting the trend and time stamps properly. The time stamps
show only the time in seconds, and the start time is not the same for
all tags in the trend.
Back to Top
Problem:
In WindowMaker, if one of the wizards is added to a window from the
Wizard Selection/Buttons menu, then the window is saved, closed,
and reopened, the object is a different size.
Back to Top
Back to Top
Problem:
InTouch is unable to distinguish the keypad characters/symbols -
from . (minus and period).
The two keys are located on either side of the zero, and are nearly
impossible to distinguish unless the system font is set to 200% its
normal size on Windows 2000. The fonts on NT are large, and both
characters/symbols are still not easily identifiable. Setting the system
font to 200% causes major problems for the rest of the system, and
is not a viable workaround.
Back to Top
Problem:
A Script function, that will either give information whether a window
is open or not, or return a list containing the currently open
window(s), is requested.
Parameter Description
======= =======
Example(s):
Syntax: OpenWindowsList();
Remarks: During runtime, a dialog box with the title "Open Windows
List" is displayed, and all the InTouch windows which are open at that
given point are shown in a dialog box.
Back to Top
Problem:
An error is displayed when one of the windows is imported.
Back to Top
Problem:
When the "BindList" under the SQL Access Manager tree node is
clicked on, a Selection Box, which is a pop-up window, is thrown up.
From then on until the dialog box is closed, all the messages are
dispatched to the Selection Box Window Procedure.
When the Selection Box window is closed by selecting the Cancel
button or by clicking on a point other than the Selection Box,
POSTMESSAGE is posted to the Selection Box Window Procedure; this
will destroy the window.
Back to Top
Problem:
When No Alarm is selected, and the following script:
"ErrorNumber=GetPropertyM("ALMOBJ_1.AlarmProv",tag1);" is
executed, it will result in "ErrorNumber=-1" and "Tag1=blank," and
an error in the WWlogger.
The problem is, these errors fill the WWlogger; it is requested that
the logger messages be eliminated since "ErrorNumber=-1" is all that
the Error needs.
Back to Top
Problem:
ptSetTimeAxisToCurrent does not work. There are two problems: the
Start Time is set to current time, and documented parameters do not
exist.
This function should at least use the current span and set the End
Time of the trend to the current time. It does not; it sets the Start
Time to the current time, showing the span, but in the future, where
there is no logged data.
It should also have two parameters. The first is for the trend object
name, and the second being a parameter for its span, either "Current
Span" or a specific Start Time; and then it should use the current
time for the End Time.
Back to Top
Problem:
In Alarm Logger, Output/Configure...-> Message format, each field
can be given a width of the column in the printout. However, "value"
and "limit" fields are not bound by the width settings, no matter what
the width values are. Even with "Remove trailing spaces" unchecked,
the "value" and "limit" fields are still misaligned on the printout,
which causes the rest of the columns after them to also misalign.
Back to Top
Problem:
The X or Y location of a window changes when the Width or Height of
the window is manually reduced.
Back to Top
Back to Top
I0019683 The Alarm button does not function when the SPC dataset is
made using the Duplicate button.
Problem:
When the Alarm button is clicked, SPCPro invokes the SPC Alarm
Selection dialog box only if the alarm set object has already existed,
even if the database has no alarms configured for the current dataset
yet. However, if a dataset is duplicated, no alarm set objects are
created.
Back to Top
Problem:
The SendKeys message is not being executed.
Back to Top
Problem:
When Using InSQL as a Historical provider, there is a problem with
timezones that are GMT +.
InTouch shows the Historical data as being in the past (that is, a
point that was recorded at 20:11 would show in the Historical display
as being recorded at 18:11, if the Time Zone is GMT + 2), while the
data that is logged by InTouch is correct.
Back to Top
Back to Top
I0019946 Quick function call, which has a name more than eight (8)
characters long, causes AE (Assertion Error) and WindowViewer to
freeze.
Problem:
When calling a Quick function that has a name more than eight (8)
characters long, the Assertion Error and WindowViewer freeze.
Back to Top
Problem:
The new behavior was implemented by CR# I0000894 (InTouch 7.0
SP2 Patch 03). There is a functionality change because the new
InTouch version does not have backward compatibility.
The NewShowAt entry in the InTouch.ini file is used to control the
behavior.
In order to allow applications, using the change implemented for CR#
I0000894, to behave in the same manner without any additional
changes, the default for NewShowAt is set to 1.
For those who would like to keep the first window open, it is
necessary to add NewShowAt=0 to this .ini file.
Back to Top
Problem:
Trend Object scans every time it is initialized, and Scooter change
takes a long time to update.
Back to Top
Back to Top
Problem:
Stringfromtime() and StringFromTimeLocal() do not follow the
ControlPanel/RegionalSettings format.
Back to Top
I0020178 A return to normal entry is not given the Return color, if the
tag was Acknowledged prior to its return to normal.
Problem:
When the Alarm Object is configured, there is a color for Ack, Alarm,
and Return. Under any circumstances, the color should represent the
current situation. For instance, whether the tag has been
ackowledged or not, and has now returned to normal, it should be the
color set for "Alarm Return." When the tag is Acknowledged, whether
it has returned to normal or not, it should show the color for "Ack
Alarm."
Back to Top
Problem:
AlarmParetoPlus queries data from the AlarmDurations and
AlarmSummary tables; if there are no records in these two (2) tables,
it will return "No records found" message. If the values of the
EventDuration fields in the AlarmDurations table are equal to zeros, it
will return the error message, "Runtime error 6 Overflow."
Back to Top
Problem:
A new SQL error message, "-1014 The Sql.def file does not exist,"
needs to be added to the already-existing list.
Back to Top
Problem:
If one item in the tree is clicked on, the correct item is selected and
passed through, but the cursor highlight moves to a totaly different
object. This causes confusion for the user; and it makes the object
appear to be broken.
Back to Top
I0020201 The "dot field" import creates a new tag, when an attempt is
made to import and the dot-field tag is converted to a remote tag.
Problem:
The "dot field" import creates a new remote tag that combines the
main tag with the dot-field extensions. The new remote tag
eliminates the "dot field" functionality.
Back to Top
Problem:
The .AlarmEnabled dot-field retentive value is lost if "Update Use
Count" is used on the application.
If "Alarm Enable Retentive" is set and the .AlarmEnabled field of a tag
is disabled or reset, WindowViewer is closed, WindowMaker is run,
and the "Update Use Count" is utilized, the .AlarmEnabled dot field
will go back to "Set" or "Enabled," when WindowViewer is restarted.
Back to Top
Problem:
Error HTSPT/HTSetPenName: "FT701EU Invalid Trend Tag" appears
when dot fields are used in more than one parameter for the
htsetpenname().
Back to Top
Problem:
When the remote references point to a dot field for remote alarm
groups, and if links to remote references are created pointing to a dot
field in remote alarm groups, such as
"AccessName:AlarmGroup1.Alarm" and
"AccessName:AlarmGroup2.Alarm," the error message can be seen
being displayed twice for the second link, as if the feature was
attempting to activate two tags instead of just one.
Back to Top
I0020352 The List Box control has graphical remnants on the top and
left borders.
Problem:
The List Box control has graphical remnants on the top and left
borders.
If a List Box is placed on a window, then you go to runtime and move
the window around, the top and left edges on the List Box do not
redraw correctly. There are graphic artifacts left on the edges.
Back to Top
Problem:
When a window is moved by using the mouse, its X-Y-location
information does not change.
Back to Top
Back to Top
Problem:
Alarm Logger Configuration setting: Cannot set HH:MM:SS and
HH:MM for time format in the Message tab.
Back to Top
I0020775 There is invalid data in the Value field when a discrete tag is
used.
Problem:
When one InTouch application with alarms is created using a discrete
tag, and any value message other than ON & OFF is used, the values
of the "VALUE" field in the Alarm Summary are not correct.
Back to Top
I0020781 SPC Dataset is saved without the product name when the
<Enter> key is used.
Problem:
The SPC Dataset is saved without the product name when the
<Enter> key is used. It is requested that the application give a
warning message, "You must create a Product for this new Dataset
first." before the dataset is saved; and, the SPC Dataset
Configuration must be prevented from closing if no products have
been created for the dataset.
Back to Top
I0020787 Line Printer for alarm printing limits the flexibility of the
printer's usage.
Problem:
The earlier version of Windows operating system, for example: Win
NT, was not supported with plug-and-play devices. The printer used
to be configured as the default printer, to print InTouch alarms,
without the printer-driver software installed. However, now Windows
2000 and Windows XP provide the plug-and-play service. It detects
the printer and the OS installs the printer-driver software, thus
making it incompatible for InTouch alarm printing. According to
Wonderware Tech Note 149, alarms can be printed out through the
network; this method still works, but only with physical-parallel-ports
printer, not with com-port, USB-port, or virtual-port printers.
Back to Top
I0020818 The Tagname button does not work after some Retentive
Memory tags are deleted, and then an attempt is made to modify a
BindList.
Problem:
When some Retentive Memory tags are deleted and an attempt is
then made to modify a BindList, the Tagname button does not work.
Back to Top
Problem:
This problem occurs only on a WinNT 4.0 SP6a computer with
WindowViewer running as a service.
A Dr. Watson error message is generated when WindowViewer is shut
down.
Back to Top
Problem:
When SQLSetParamChar is used to set the parameters of a stored
procedure, to be executed using SQLSetStatement,
SQLPrepareStatement, and SQLExecute, and the stored procedure
that is to be executed is an insert statement, then the data sent to
the procedure becomes bad the second time an SQLSetParamChar is
used.
Back to Top
Problem:
When creating a Memory Real tag with an analog input link that also displays "##.##,"
a value input of 1.595 that is typed in will be shown as 1.59. Most numbers with a
5 (five) as the last digit after the decimal (.) are not rounded up. Only
one number is rounded up, 3.595 rounds up to 3.60.
Back to Top
Problem:
When the computer clock goes to midnight, no new historical log files are created; no
new data is seen in the Trend Object if it is updated, and no errors show in the
WWlogger files either.
Back to Top
Problem:
Data logged at 8:00 A.M. shows a time stamp of 10:00 P.M. in the Historical Trend
Object.
Back to Top